Home/Catalog/AISLCANALOG-MIB

AISLCANALOG-MIB

AI MIB Summary

The AISLCANALOG-MIB facilitates SNMP-based monitoring of Analog Input Line Cards (SLCs) to track real-time analog signal states, voltage levels, and channel status. This module enables systems administrators to detect input anomalies and manage hardware health for analog telemetry endpoints within industrial or telecommunications infrastructure.

MIB module for SLCs with analog input points.
Main OID:
aiSLCAnalog.1.3.6.1.4.1.539.28
50
Objects
Active
Status
2
Dependencies

Imported Objects

Objects

50 total
Object Name
aii
OBJECT IDENTIFIER
.1.3.6.1.4.1.539
aiSLCAnalogMIB module for SLCs with analog input points.
MODULE-IDENTITY
.1.3.6.1.4.1.539.28
aiSLCAnalogInputTableTable of analog inputs points indexed by point number. Includes description, configuration and status information.
SEQUENCE OF AISLCAnalogInputEntry
.1.3.6.1.4.1.539.28.1
aiSLCAnalogInputEntryEntry of aiSLCAnalogInputTable.
AISLCAnalogInputEntry
.1.3.6.1.4.1.539.28.1.1
aislcainPointNumberInput point number to which this table row applies.ro
PositiveInteger
.1.3.6.1.4.1.539.28.1.1.1
aislcainScanningEnabledEnable or disable scanning of the input.rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.2
aislcainDescriptionTextual description of the point. Maximum length is 80 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.3
aislcainTrapEnableEnable or disable alarm traps.rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.4
aislcainNormalStateTrapIf enabled, transitions from an alarm state to the normal state will generate an SNMP trap or TL1 message.rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.5
aislcainHighAlarmSeveritySeverity of the point's alarm state, or notReported(5) if the point does not generate an alarm.rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.6
aislcainHighAlarmStateTextTextual description of the point's alarm state. Maximum length is 80 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.7
aislcainLowAlarmSeveritySeverity of the point's alarm state, or notReported(5) if the point does not generate an alarm.rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.8
aislcainLowAlarmStateTextTextual description of the point's alarm state. Maximum length is 80 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.9
aislcainNormalStateTextTextual description of the point's normal state. Maximum length is 80 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.10
aislcainUserUnitsThe user-defined units for this input (e.g. degC, degF, etc.).rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.11
aislcainMinInputmAThe current in mA corresponding to the minimum input in user-defined units.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.12
aislcainMinInputuuThe minimum value in user-defined units corresponding to the minimum input in mA.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.13
aislcainMaxInputmAThe current in mA corresponding to the maximum input in user-defined units.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.14
aislcainMaxInputuuThe maximum value in user-defined units corresponding to the maximum input in mA.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.15
aislcainHighLimitScanIf enabled, the high limit threshold will be checked when the input is scanned.rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.16
aislcainHighAlarmThresholduuThe high alarm level in user-defined units.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.17
aislcainHighAlarmThresholdIntervaluuThe high alarm level threshold interval in user-defined units. When the high alarm is active, each time the input rises another interval higher, a new alarm is sent.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.18
aislcainHighAlarmMinPeriodThe minimum number of seconds the input(s) should be energized when the input exceeds the high alarm threshold.rw
INTEGER
.1.3.6.1.4.1.539.28.1.1.19
aislcainHighAlarmHysteresisuuThe amount by which the input must drop below the High Alarm Threshold before the High Alarm will be cleared.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.20
aislcainLowLimitScanIf enabled, the low limit threshold will be checked when the input is scanned.rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.21
aislcainLowAlarmThresholduuThe low alarm level in user-defined units.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.22
aislcainLowAlarmThresholdIntervaluuThe low alarm level threshold interval in user-defined units. When the low alarm is active, each time the input drops another interval lower, a new alarm is sent.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.23
aislcainLowAlarmMinPeriodThe minimum number of seconds the input(s) should be energized when the input falls below the low alarm threshold.rw
INTEGER
.1.3.6.1.4.1.539.28.1.1.24
aislcainLowAlarmHysteresisuuThe amount by which the input must rise above the Low Alarm Threshold before the Low Alarm will be cleared.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.25
aislcainCurrentValueuuThe current input value in user-defined units.ro
DisplayString
.1.3.6.1.4.1.539.28.1.1.26
aislcainCurrentValuemAThe current input value in mA.ro
DisplayString
.1.3.6.1.4.1.539.28.1.1.27
aislcainLastChangeTimeTextural representation of the time of the most recent output change. 24-hour format YYYY-MM-DD HH:MM:SS.ro
DisplayString
.1.3.6.1.4.1.539.28.1.1.28
aislcaintl1AccessIDUnique TL1 access identifier for this point. Maximum length is 22 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.29
aislcaintl1ProvisionedEnable TL1 management of this point.rw
TruthValue (SNMPv2-TC)
.1.3.6.1.4.1.539.28.1.1.30
aislcaintl1AccessIDTypeIdentifies the point as either an equipment(1) alarm condition or an environmental(2) alarm.rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.31
aislcaintl1HighAlarmTypeString indicating the type of alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 10 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.32
aislcaintl1HighAlarmMessageTextual description of the alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 40 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.33
aislcaintl1LowAlarmTypeString indicating the type of alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 10 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.34
aislcaintl1LowAlarmMessageTextual description of the alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 40 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.35
aislcaintl1HighAlarmNotificationCodeSeverity of the point's alarm state.rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.36
aislcaintl1HighAlarmServiceAffectingIndicates whether or not the alarm affects the functioning of the equipment. This is only meaningful when aislcaintl1AccessIDType is equipment(1).rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.37
aislcaintl1HighAlarmConditionTypeString indicating the type of alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 20 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.38
aislcaintl1HighAlarmConditionDescTextual description of the alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 64 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.39
aislcaintl1LowAlarmNotificationCodeSeverity of the point's alarm state.rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.40
aislcaintl1LowAlarmServiceAffectingIndicates whether or not the alarm affects the functioning of the equipment. This is only meaningful when aislcaintl1AccessIDType is equipment(1).rw
Enumeration
.1.3.6.1.4.1.539.28.1.1.41
aislcaintl1LowAlarmConditionTypeString indicating the type of alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 20 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.42
aislcaintl1LowAlarmConditionDescTextual description of the alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 64 characters.rw
DisplayString
.1.3.6.1.4.1.539.28.1.1.43
aislcainAnalogStatusThe current alarm status of the analog input.ro
Enumeration
.1.3.6.1.4.1.539.28.1.1.44
aislcainCurrentStateTextTextual description of the point's current state. This is either aislcainNormalStateText or aislcainAlarmStateText.ro
DisplayString
.1.3.6.1.4.1.539.28.1.1.45
aislcainAnalogAlarmStateThe point's current alarm state, or normal(5).ro
Enumeration
.1.3.6.1.4.1.539.28.1.1.46
AISLCANALOG-MIB - SNMP MIB Reference | MIBs Explorer