The `companyMIB` module facilitates the monitoring and management of Uninterruptible Power Supply (UPS) hardware via SNMP, exposing critical telemetry such as battery status, input/output voltage, load percentage, and remaining runtime.

The MIB module to describe UPS
Main OID:
companyMIB.1.3.6.1.4.1.21111
328
Objects
Active
Status
5
Dependencies

Imported Objects

Objects

328 total
Object Name
companyMIBThe MIB module to describe UPS
MODULE-IDENTITY
.1.3.6.1.4.1.21111
products
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1
ups
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1
upsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.1
upsIdManufacturerThe name of the UPS manufacturer.ro
DisplayString
.1.3.6.1.4.1.21111.1.1.1.1
upsIdProtocolThe UPS Protocol id.ro
Enumeration
.1.3.6.1.4.1.21111.1.1.1.2
upsIdModelNameThe UPS Model designation.ro
DisplayString
.1.3.6.1.4.1.21111.1.1.1.3
upsIdSerialNumberThe UPS serial no.ro
DisplayString
.1.3.6.1.4.1.21111.1.1.1.4
upsIdNameA string identifying the UPS. This object should be set by the administrator.rw
DisplayString
.1.3.6.1.4.1.21111.1.1.1.5
upsIdFWVersionMain CPU firmware version.ro
DisplayString
.1.3.6.1.4.1.21111.1.1.1.6
upsIdUPSTypeUPS type.ro
Enumeration
.1.3.6.1.4.1.21111.1.1.1.7
upsRating
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.2
upsRatinVoltageThe rating input voltage of UPSro
NonNegativeInteger UNITS "0.1 Volt DC"
.1.3.6.1.4.1.21111.1.1.2.1
upsRatoutVoltageThe rating output voltage of UPSro
NonNegativeInteger UNITS "0.1 Volt DC"
.1.3.6.1.4.1.21111.1.1.2.2
upsRatoutFrequencyThe rating output frequency of UPSro
NonNegativeInteger UNITS "0.1 HZ"
.1.3.6.1.4.1.21111.1.1.2.3
upsRatoutCurrentThe rating output current of UPSro
NonNegativeInteger UNITS "0.1 Amp DC"
.1.3.6.1.4.1.21111.1.1.2.4
upsRatoutApparentPowerThe rating output apparent power of UPSro
NonNegativeInteger UNITS "0.1 VA"
.1.3.6.1.4.1.21111.1.1.2.5
upsRatoutTruePowerThe rating output true power of UPSro
NonNegativeInteger UNITS "0.1 Wt"
.1.3.6.1.4.1.21111.1.1.2.6
upsRatBatVoltageThe rating battery voltage of UPSro
NonNegativeInteger UNITS "0.1 vol"
.1.3.6.1.4.1.21111.1.1.2.7
upsBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.3
upsBatStatusThe indication of the status in the UPS system's batteries.ro
Enumeration
.1.3.6.1.4.1.21111.1.1.3.1
upsBatSecondsOnBatteryIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. -1 shall be returned if the unit is not on battery power.ro
INTEGER UNITS "seconds"
.1.3.6.1.4.1.21111.1.1.3.2
upsBatEstMinutesRemainingAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.ro
INTEGER UNITS "minutes"
.1.3.6.1.4.1.21111.1.1.3.3
upsBatEstChargeRemainingAn estimate of the battery charge remaining expressed as a percent of full charge.ro
INTEGER
.1.3.6.1.4.1.21111.1.1.3.4
upsBatPBatVoltageThe magnitude of the present Positive battery voltage.ro
NonNegativeInteger UNITS "0.1 Volt DC"
.1.3.6.1.4.1.21111.1.1.3.5
upsBatNBatVoltageThe magnitude of the present negative battery voltage.ro
NonNegativeInteger UNITS "0.1 Volt DC"
.1.3.6.1.4.1.21111.1.1.3.6
upsBatPBatCurrentThe positive battery present current.ro
INTEGER UNITS "0.1 Amp DC"
.1.3.6.1.4.1.21111.1.1.3.7
upsBatNBatCurrentThe present negative battery current.ro
INTEGER UNITS "0.1 Amp DC"
.1.3.6.1.4.1.21111.1.1.3.8
upsBatPBatChargCurrentThe Positive battery charging current.ro
INTEGER UNITS "0.1 Amp DC"
.1.3.6.1.4.1.21111.1.1.3.9
upsBatNBatchargCurrentThe present negative battery charging current.ro
INTEGER UNITS "0.1 Amp DC"
.1.3.6.1.4.1.21111.1.1.3.10
upsBatPBatDischargCurrentThe present positive battery discharging current.ro
INTEGER UNITS "0.1 Amp DC"
.1.3.6.1.4.1.21111.1.1.3.11
upsBatNBatDischargCurrentThe present negative battery discharging current.ro
INTEGER UNITS "0.1 Amp DC"
.1.3.6.1.4.1.21111.1.1.3.12
upsBatTemperatureThe ambient temperature at or near the UPS Battery casing.ro
INTEGER UNITS "degrees 0.1 Centigrade"
.1.3.6.1.4.1.21111.1.1.3.13
upsBatNumberInSeriesThe number of battery in series.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.21111.1.1.3.14
upsBatNumberInParallelThe number of battery in Parallel.ro
PositiveInteger (UPS-MIB)
.1.3.6.1.4.1.21111.1.1.3.15
upsBatPBatDischargCurrent2The present positive battery pipe2 discharging current.ro
INTEGER UNITS "0.1 Amp DC"
.1.3.6.1.4.1.21111.1.1.3.16
upsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.4
upsInLineBadsA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.ro
NonNegativeInteger (UPS-MIB)
.1.3.6.1.4.1.21111.1.1.4.1
upsInTtlApparentPowerTotal input apparent power .ro
NonNegativeInteger UNITS "0.1VA"
.1.3.6.1.4.1.21111.1.1.4.2
upsInTtlTruePowerTotal input active(true) power .ro
NonNegativeInteger UNITS "0.1WT"
.1.3.6.1.4.1.21111.1.1.4.3
upsInNumLinesThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.ro
NonNegativeInteger (UPS-MIB)
.1.3.6.1.4.1.21111.1.1.4.4
upsInTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.
SEQUENCE OF UpsInEntry
.1.3.6.1.4.1.21111.1.1.4.5
upsInEntryAn entry containing information applicable to a particular input line.
UpsInEntry
.1.3.6.1.4.1.21111.1.1.4.5.1
upsInLineIndexThe number of output linesro
INTEGER
.1.3.6.1.4.1.21111.1.1.4.5.1.1
upsInFrequencyThe present input frequency.ro
NonNegativeInteger UNITS "0.1 Hertz"
.1.3.6.1.4.1.21111.1.1.4.5.1.2
upsInVoltageThe input utility line voltage .ro
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.4.5.1.3
upsInCurrentThe magnitude of the present input currentro
INTEGER UNITS "0.1Amp"
.1.3.6.1.4.1.21111.1.1.4.5.1.4
upsInApparentPowerThe magnitude of the present input Apparent power.ro
NonNegativeInteger UNITS "0.1VA"
.1.3.6.1.4.1.21111.1.1.4.5.1.5
upsInTruePowerThe magnitude of the present input true power.ro
NonNegativeInteger UNITS "0.1Watts"
.1.3.6.1.4.1.21111.1.1.4.5.1.6
upsInPowerFactorInput true power/apparent power factorro
NonNegativeInteger UNITS "0.01"
.1.3.6.1.4.1.21111.1.1.4.5.1.7
upsInLineVoltageThe input utility line voltage . if upsInLineIndex =1, upsInLineVoltage = Line voltage of RS phase; if upsInLineIndex =2, upsInLineVoltage = Line voltage of ST phase; if upsInLineIndex =3, upsInLineVoltage = Line voltage of TR phase.ro
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.4.5.1.8
upsInTtlVoltageThe input utility line tatol voltage .ro
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.4.6
upsInTtlCurrentThe input utility line tatol current.ro
INTEGER UNITS "0.1 A"
.1.3.6.1.4.1.21111.1.1.4.7
upsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.5
upsOutSourceThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.==UPS standby modero
Enumeration
.1.3.6.1.4.1.21111.1.1.5.1
upsOutTtlApparentPowerTotal output apparent power .ro
NonNegativeInteger UNITS "0.1VA"
.1.3.6.1.4.1.21111.1.1.5.3
upsOutTtlTruePowerTotal output active(true) power .ro
NonNegativeInteger UNITS "0.1Watts"
.1.3.6.1.4.1.21111.1.1.5.4
upsOutTtlPercentLoadThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.ro
INTEGER
.1.3.6.1.4.1.21111.1.1.5.5
upsOutNumLinesThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.ro
INTEGER
.1.3.6.1.4.1.21111.1.1.5.6
upsOutTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.
SEQUENCE OF UpsOutEntry
.1.3.6.1.4.1.21111.1.1.5.7
upsOutEntryAn entry containing information applicable to a particular output line.
UpsOutEntry
.1.3.6.1.4.1.21111.1.1.5.7.1
upsOutLineIndexThe output line identifier.ro
INTEGER
.1.3.6.1.4.1.21111.1.1.5.7.1.1
upsOutVoltageThe output voltage of the UPS system.ro
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.5.7.1.2
upsOutCurrentThe output current of the UPS systemro
INTEGER UNITS "0.1 Amp"
.1.3.6.1.4.1.21111.1.1.5.7.1.3
upsOutApparentPowerThe present output apparent power.ro
NonNegativeInteger UNITS "0.1VA"
.1.3.6.1.4.1.21111.1.1.5.7.1.4
upsOutTruePowerThe present output true power.ro
NonNegativeInteger UNITS "0.1Watts"
.1.3.6.1.4.1.21111.1.1.5.7.1.5
upsOutPowerFactorOutput true power/apparent power factorro
NonNegativeInteger UNITS "0.01"
.1.3.6.1.4.1.21111.1.1.5.7.1.6
upsOutPercentLoadThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.ro
INTEGER
.1.3.6.1.4.1.21111.1.1.5.7.1.7
upsOutLineVoltageThe output line voltage of the UPS system. if upsOutLineIndex =1, upsOutLineVoltage = Line voltage of RS phase; if upsOutLineIndex =2, upsOutLineVoltage = Line voltage of ST phase; if upsOutLineIndex =3, upsOutLineVoltage = Line voltage of TR phase.ro
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.5.7.1.8
upsOutFrequencyThe present output frequency.ro
NonNegativeInteger UNITS "0.1Hertz"
.1.3.6.1.4.1.21111.1.1.5.7.1.9
upsOutTtlVoltageTotal output voltage .ro
INTEGER UNITS "0.1vot"
.1.3.6.1.4.1.21111.1.1.5.8
upsOutTtlCurrentTotal output current.ro
INTEGER UNITS "0.1A"
.1.3.6.1.4.1.21111.1.1.5.9
upsOutStatusFor HVDC device. char status[4]; status[0]status[1]:00, no output1; 01, line output1; 02, bat output1 status[2]status[3]:00, no output2; 01, line output2; 02, bat output2ro
DisplayString
.1.3.6.1.4.1.21111.1.1.5.10
upsOutSource2For HVDC(protocol:P12) machine. The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.==UPS standby modero
Enumeration
.1.3.6.1.4.1.21111.1.1.5.11
upsBypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.6
upsByFrequencyThe present bypass frequency.ro
INTEGER UNITS "0.1 Hertz"
.1.3.6.1.4.1.21111.1.1.6.1
upsByNumLinesThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.ro
INTEGER
.1.3.6.1.4.1.21111.1.1.6.2
upsByTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
SEQUENCE OF UpsByEntry
.1.3.6.1.4.1.21111.1.1.6.3
upsByEntryAn entry containing information applicable to a particular bypass input.
UpsByEntry
.1.3.6.1.4.1.21111.1.1.6.3.1
upsByLineIndexThe bypass line identifier.ro
INTEGER
.1.3.6.1.4.1.21111.1.1.6.3.1.1
upsByVoltageThe present bypass voltage.ro
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.6.3.1.2
upsByCurrentThe present bypass current.ro
INTEGER UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.21111.1.1.6.3.1.3
upsByPowerThe present true power conveyed by the bypass.ro
NonNegativeInteger UNITS "0.1Watts"
.1.3.6.1.4.1.21111.1.1.6.3.1.4
upsByLineVoltageThe present bypass line voltage. if upsByLineIndex=1,upsByLineVoltage=Line voltage of RS phase; if upsByLineIndex=2,upsByLineVoltage=Line voltage of ST phase; if upsByLineIndex=3,upsByLineVoltage=Line voltage of TR phase.ro
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.6.3.1.5
upsTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.7
upsTstBatteryTestThis object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsTestBatteryTestTime.rw
Enumeration
.1.3.6.1.4.1.21111.1.1.7.1
upsTstBatteryTestResultThe results of the current or last UPS diagnostics test performed. The values for donePassed(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.ro
Enumeration
.1.3.6.1.4.1.21111.1.1.7.2
upsTstBatteryTestStartTimeThe value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestBatteryTestResult is noTestsInitiated(6), upsTestStartTime has the value 01/01/1970 00:00:00. format is (MM/DD/YYYY hh:mm:ss)ro
DisplayString
.1.3.6.1.4.1.21111.1.1.7.3
upsTstBatterySettingTimeThe object specify the test time for battery test, the unit is secondsrw
INTEGER
.1.3.6.1.4.1.21111.1.1.7.4
upsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.8
upsCtlShutdownDelayThe delay in seconds the UPS remains on after being told to turn off. if value=-2 cancel shutdown, if value=-1 donothing, value=0 shutdown ups immediatelyrw
INTEGER (-2..2147483648) UNITS "seconds"
.1.3.6.1.4.1.21111.1.1.8.1
upsCtlSleepTimeThe time in minutes for the UPS to go to sleep when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 0 - 9999 minutes in one minute increments. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.rw
INTEGER (-1..2147483648) UNITS "minutes"
.1.3.6.1.4.1.21111.1.1.8.2
upsCtlStartupAfterDelaySetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. -1 mean not startup. must set upsCtlStartupAfterDelay before upsCtlShutdownDelay , the value must larger than 59 if the value not equal -1rw
INTEGER (-1..2147483648) UNITS "seconds"
.1.3.6.1.4.1.21111.1.1.8.3
upsCtlbuzzerSetting this object to 'on' or 'off' to enable or disable buzzerrw
Enumeration
.1.3.6.1.4.1.21111.1.1.8.4
upsCtlRemoteControlUPSSetting this object to turn 'on' or 'off' UPSrw
Enumeration
.1.3.6.1.4.1.21111.1.1.8.5
upsCtloutletPoweronSetting this object to 1 means 1st outlet,2 means 2nd outlet , immediately processrw
INTEGER
.1.3.6.1.4.1.21111.1.1.8.6
upsCtloutletPoweroffSetting this object to 1 means 1st outlet, 2 means 2nd outlet , immediately processrw
INTEGER
.1.3.6.1.4.1.21111.1.1.8.7
upsCtlOutlet1Powerofftimesetting this object to -1 means this control not effect, 0 means immediately process, >0 means wait times unit is minutes use in battery moderw
INTEGER (-1..999)
.1.3.6.1.4.1.21111.1.1.8.8
upsCtlOutlet2Powerofftimesetting this object to -1 means this control not effect, 0 means immediately process , >0 means wait times unit is minutes .use in battery moderw
INTEGER (-1..999)
.1.3.6.1.4.1.21111.1.1.8.9
upsCtlResetConfigurereset all configure para to default.rw
Enumeration
.1.3.6.1.4.1.21111.1.1.8.10
agentConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.9
agentConfigDatetimeThe datetime in agent, format is (MM/DD/YYYY hh:mm:ss)rw
DisplayString
.1.3.6.1.4.1.21111.1.1.9.1
commConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.10
commBaudRateThe UPS communicate baudraterw
Enumeration
.1.3.6.1.4.1.21111.1.1.10.1
commDatabitsThe UPS communicate data bitsrw
INTEGER
.1.3.6.1.4.1.21111.1.1.10.2
commStopbitsThe UPS communicate stop bitsrw
INTEGER
.1.3.6.1.4.1.21111.1.1.10.3
commParityThe UPS communicate Parityrw
Enumeration
.1.3.6.1.4.1.21111.1.1.10.4
commTimeoutThe UPS communicate timeoutrw
INTEGER
.1.3.6.1.4.1.21111.1.1.10.5
upsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.11
upsCfgAlarmbypassSetting this object enable /disable alarm bypass moderw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.1
upsCfgAlarmbatterySetting this object enable/disable alarm battery moderw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.2
upsCfgAutoRebootSetting this object enable/disable auto rebootrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.3
upsCfgBypasswhenupsoffSetting this object start/stop bypass when ups offrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.4
upsCfgBatterDDPSetting this object to enable/disable battery deep-discharge protectionrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.5
upsCfgConvertermodeSetting this object to enable/disable converter moderw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.6
upsCfgECOmodeSetting this object to enable/disable ECO moderw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.7
upsCfgAdvanceECOmodeSetting this object to enable/disable advance ECO moderw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.8
upsCfgGreenPowerFunctionSetting this object to enable/disable green power functionrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.9
upsCfgBatteryOSCSetting this object to enable/disable battery open status checkrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.10
upsCfgAllowShort3timesSetting this object to enable/disable short 3 timesrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.11
upsCfgColdstartSetting this object to cold start upsrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.12
upsCfgBypassNotAllowedSetting this object to enable/disable bypass moderw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.13
upsCfgBatterylowprotectSetting this object to enable/disable battery low protectrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.14
upsCfgP1progoutletcontrolSetting this object to enable/disable p1 programmable outlet control (battery mode)rw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.15
upsCfgP2progoutletcontrolSetting this object to enable/disable p2 programmable outlet control (battery mode)rw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.16
upsCfgInverterShortClearSetting this object to enable/disable Inverter short clear functionrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.17
upsCfgSitefaildetectionSetting this object to enable/disable site fail detectionrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.18
upsCfgBatNumInParallelBattery numbers in parallel (battery numbers setting)rw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.19
upsCfgBatNumInSeriesBattery numbers in series (battery numbers setting)rw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.20
upsCfgBypassmaxvoltageBypass mode max voltagerw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.21
upsCfgBypassminvoltageBypass mode min voltagerw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.22
upsCfgBypassmaxfrequencyBypass mode max frequency ,for 50 HZ (510..600) for 60HZ (610..700)rw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.23
upsCfgBypassminfrequencyBypass mode min frequency, for 50HZ (400..490) for 60Hz (500..590)rw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.24
upsCfgECOmaxvoltageECO mode max voltagerw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.25
upsCfgECOminvoltageECO mode min voltagerw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.26
upsCfgFreeRunMaxFrequencyFree run mode max frequencyrw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.27
upsCfgFreeRunMinFrequencyFree run mode min frequencyrw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.28
upsCfgEPOStatusGet EPO status,configured by mamualro
Enumeration
.1.3.6.1.4.1.21111.1.1.11.29
upsCfgQSK1StatusGet QSK 1 statusro
Enumeration
.1.3.6.1.4.1.21111.1.1.11.30
upsCfgQSK2StatusGet QSK 2 statusro
Enumeration
.1.3.6.1.4.1.21111.1.1.11.31
upsCfgQSKT1DelaytimeGet QSKT 1 time delayro
INTEGER
.1.3.6.1.4.1.21111.1.1.11.32
upsCfgQSKT2DelaytimeGet QSKT 2 time delayro
INTEGER
.1.3.6.1.4.1.21111.1.1.11.33
upsCfgConstantPhaseAnglesetting this object to Enable/disable Constant Phase Angle functionrw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.34
upsCfgInPhaseAngleGet input phase anglero
Enumeration
.1.3.6.1.4.1.21111.1.1.11.35
upsCfgOutPhaseAngleSet output phase anglerw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.36
upsCfgLimiRunOnBatModeEnable/disable limited runtime on battery moderw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.37
upsCfgChargingCurrentSet charging current to battery .ro
INTEGER UNITS "0.1 Amp DC"
.1.3.6.1.4.1.21111.1.1.11.38
upsCfgBatSeftCheckVoltBatTest until battery voltage lower than <nnn>rw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.39
upsCfgOverChargVoltset over charging voltage to per batteryrw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.40
upsCfgBattUnderVoltset battery under voltage of setting value.value is a number ranging from 200V to 240Vrw
INTEGER
.1.3.6.1.4.1.21111.1.1.11.41
upsCfgBattLowVoltset battery low voltage of setting value.it is 10 to 40V high than battery under voltage. it is 10 to 40V high than battery under voltage.default 20. it means that the battery low point is battery under add 20. for example, if the battery under voltage is 210V, the battry low point voltage is 230V.rw
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.11.42
upsCfgIn1VoltHLossset input1 voltage high loss point.rw
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.11.43
upsCfgIn1VoltLLossset input1 voltage low loss point.rw
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.11.44
upsCfgIn2VoltHLossset input2 voltage high loss point.rw
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.11.45
upsCfgIn2VoltLLossset input2 voltage low loss point.rw
INTEGER UNITS "0.1 Volts"
.1.3.6.1.4.1.21111.1.1.11.46
upsCfgBatteryTurnOnEnable/disable battery turn on.rw
Enumeration
.1.3.6.1.4.1.21111.1.1.11.47
upsTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.12
cmpACFailureAC failure
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.1
cmpFanFailureFan failure
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.2
cmpUPSFailureUPS failure
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.3
cmpChargerFailureCharger failure
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.4
cmpOverloadFailureOverload failure
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.5
cmpOvertempFailureOver temperature fault.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.6
cmpInvertershortcircuitedInverter short-circuited
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.7
cmpbatteryfusebeingocBattery fuse being open-dcircuited failure
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.8
cmpLowbatteryThe UPS has returned from a low battery condition.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.9
cmpSysgotoshutdownSystem is going to shutdown
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.10
cmpSitefaultSite fault
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.11
cmpPhasesequenceincorrectPhase sequence incorrect
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.12
cmpPhasesequenceincorrectbypassPhase sequence incorrect in bypass
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.13
cmpFanalarmFan alarm.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.14
cmpEPOenabledEPO enabled
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.15
cmpUnabletotrunonUPSUnalbe to turn on UPS
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.16
cmpOvertemperaturealarmOver temperature alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.17
cmpInputfrequnstablebypassInput frequency unstable in bypass
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.18
cmpChargeralarmCharger alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.19
cmpL1inputfusenotworkL1 input fuse not working
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.20
cmpNeutralnotConnectedNeutral not connected
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.21
cmpL2inputfusenotworkL2 input fuse not working
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.22
cmpL3inputfusenotworkL3 input fuse not working
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.23
cmpPositivePFCabnormalL1Positive PFC abnormal in L1
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.24
cmpNegativePFCabnormalL1Negative PFC abnormal in L1
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.25
cmpPositivePFCabnormalL2Positive PFC abnormal in L2
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.26
cmpNegativePFCabnormalL2Negative PFC abnormal in L2
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.27
cmpPositivePFCabnormalL3Positive PFC abnormal in L3
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.28
cmpNegativePFCabnormalL3Negative PFC abnormal in L3
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.29
cmpBusvoltagenotwdsBus voltage not within default setting
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.30
cmpBusvoltageovermaxvalueBus voltage over maxinum value
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.31
cmpBusvoltagebelowminvalueBus voltage below mininum value
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.32
cmpBusvoltagediffoutofrangeBus voltage differences out fo acceptable range
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.33
cmpBusvoltageofsloperatetoofastBus voltage of slope rate drops too fast
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.34
cmpOvercurrentinPFCIIWARNING:Over current in PFC input inductor.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.35
cmpInvertervoloutofrangeInverter voltage not within default setting.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.36
cmpInvertervolovermaxvalueInverter voltage over maximum value.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.37
cmpInvertervolbelowminvalueInverter voltage below minimum value.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.38
cmpBatteryoppositelyconnectedBattery oppositely connected.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.39
cmpL2phaseshortcicuitedL2Phase inverter short-cicuited.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.40
cmpL3phaseshortcicuitedL3Phase inverter short-cicuited.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.41
cmpL1L2invertershortcicuitedL1L2Inverter short-cicuited.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.42
cmpL2L3invertershortcicuitedL2L3Inverter short-cicuited.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.43
cmpL3L1invertershortcicuitedL3L1Inverter short-cicuited.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.44
cmpL1negativepoweroutofrangeL1 inverter negative powere out of acceptable range.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.45
cmpL2negativepoweroutofrangeL2 inverter negative powere out of acceptable range.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.46
cmpL3negativepoweroutofrangeL3 inverter negative powere out of acceptable range.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.47
cmpBatterySCRshortcircuitedBattery SCR short-circuited.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.48
cmpLineSCRshortcircuitedLine SCR short-circuited.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.49
cmpInverterrelayopenfaultInverter relay open fault.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.50
cmpInverterrelayshortcircuitedInverter relay short-circuited.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.51
cmpInoutwiresoppositelyconnectedInput and output wires oppositely connected.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.52
cmpabnormalcanbuscommunicationAbnormal in CAN-bus communication.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.53
cmpcommfailurebcupsboardCommunication failure between cpus in control board.Or DSP and MCU communication error
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.54
cmpabnormalsyncsignalcircuitAbnomal in synchronous signal circuit.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.55
cmpabnormalsyncpulsesignalcircuitAbnomal in synchronous pulse signal circuit.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.56
cmpcurrent3punbalancedetectedWarning for a three-phase input current unbalance detected.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.57
cmpbatteryselftestfailureBattery self-test failure.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.58
cmpintercurrentunbalanceInverter inter-current unbalance.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.59
cmpbatterydisconnectedBattery disconnected.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.60
cmpabnormalhostsignalcircuitAbnormal in host signal circuit.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.61
cmpbatteryoverchargedBettery overcharged.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.62
cmpbatteryvoltoohighBettery voltage is too high.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.63
cmpbatteryvoltoolowBettery voltage is too low.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.64
cmpfemaleconnectornotconnwellFemale connector of parallel cable not connected well.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.65
cmpmaleconnectornotconnwellMale connector of parallel cable not connected well.
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.66
cmplockingbypassA3COW30MLocking inbypass mode after 3 consecutive overloads within 30 minutes
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.67
cmpparallelcabledisconnectedParallel cable disconnected
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.68
cmpsyncpulsecircuitfaultSynchronous pulse signal circuit fault
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.69
cmpsyncsignalcircuitfaltSynchronous signal circuit fault
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.70
cmphostsignalcircuitfaultHost signal circuit fault
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.71
cmpcanbuscommunicationfaultCan-bus communication fault
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.72
cmplowlosspointforvolinACmodeLow loss point for voltage in ac mode not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.73
cmphighlosspointforvolinACmodeHigh loss point for voltage in ac mode not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.74
cmplowlosspointforfreqinACmodeLow loss point for frequency in ac mode not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.75
cmphighlosspointforfreqinACmodeHigh loss point for frequency in ac mode not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.76
cmplowlosspointforvolinbypassmodeLow loss point for voltage in bypass mode not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.77
cmphighlosspointforvolinbypassmodeHigh loss point for voltage in bypass mode not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.78
cmplowlosspointforfreqinbypassmodeLow loss point for frequency in bypass mode not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.79
cmphighlosspointforfreqinbypassmodeHigh loss point for frequency in bypass mode not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.80
cmploadunbalancedLoad unbalanced
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.81
cmpoverloadalarmOverload alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.82
cmpparallelnotconnectedwellParallel cable not connected well
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.83
cmpcommunicationlostCommunication lost
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.84
cmpbatteryconnnotsonsistentBattery connection not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.85
cmpconverternotconsisstentConverter setting not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.86
cmpbypassnotallownotconsistentBypass not allowed setting not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.87
cmpACconnnotconsistentAC connection not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.88
cmpinput3pcurrentunbalanceWarning for three-phase ac input current unbalance
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.89
cmpbypassconnnotconsistentBypass connection not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.90
cmpbatteryprotectionnotconsistentBattery protection setting not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.91
cmpbatterydetectionnotconsistentBattery detection setting not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.92
cmpupsmodeltypesnotconsistentUPS model types not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.93
cmpbypassnotconsistentBypass setting not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.94
cmpcapacitynotconsistentCapacity of upss not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.95
cmpautorestartnotconsistentAuto restart setting not consistent in parallel systems
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.96
cmpBatteryReplaceBattery need to be replace
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.97
cmpACNormalAC normal
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.100
cmpOutputBadAlarmOutput bad alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.103
cmpBypassBadAlarmBypass bad alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.104
cmpOutputOffAlarmOutput off alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.105
cmpUPSShutAlarmUPS shutdown alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.106
cmpSystemOffAlarmSystem off alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.107
cmpFuseFailureAlarmFuse failure alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.108
cmpGenFailureAlarmGeneral failure alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.109
cmpAwaitPowerAlarmAwaiting power alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.110
cmpShutPendingAlarmShutdown pending alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.111
cmpBatDepletedBattery depleted
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.112
cmpUnknowStatusBattery unknow status
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.113
cmpOutputOnOutput on
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.114
cmpTurntobypassUps turn to bypass mode
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.115
cmpTurntobatteryUps turn to battery mode
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.116
cmpOutBoosterTurn to booster
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.117
cmpOutReducerTurn to reducer
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.118
cmpOutBattestTurn to battery test mode
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.119
cmpOtherSourceOther source
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.120
cmpBatfailureBattery failure
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.121
cmpBatTestDonePassedBattery test passed
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.122
cmpBatTestDoneWarningBattery test done warning
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.123
cmpBatTestDoneAbortedBattery test done Aborted
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.124
cmpBatteryNormalBattery normal
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.125
cmpBatteryDischargingBattery Discharging
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.126
cmpP1cutoffprealarmP1 cut off pre-alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.127
cmpInputPhaseErrorWarning for input phase error for LV 6-10K UPS
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.128
cmpMaintainSwitchOpenalarmWarning for maintain switch open
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.129
cmpEMDChAbnormal1EMD Channels 1 Abnormal
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.130
cmpEMDChAbnormal2EMD Channels 2 Abnormal
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.131
cmpEMDChAbnormal3EMD Channels 3 Abnormal
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.132
cmpEMDChAbnormal4EMD Channels 4 Abnormal
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.133
cmpEMDChAbnormal5EMD Channels 5 Abnormal: smoke alarm
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.134
cmpEMDChAbnormal6EMD Channels 6 Abnormal
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.135
cmpEMDChAbnormal7EMD Channels 7 Abnormal
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.136
cmpEMDChAbnormal8EMD Channels 8 Abnormal
TRAP-TYPE
.1.3.6.1.4.1.21111.1.1.12.0.137
trapleafnodev103The share trap-node for send all traps,snmpcard V1-03 and later use this trap-node char trap[16]; trap[0]: trap[0]=1,fault trap ; trap[0]=0,warn trap
DisplayString
.1.3.6.1.4.1.21111.1.1.12.998
trapleafnodev1v2The share trap-node for send all traps
INTEGER
.1.3.6.1.4.1.21111.1.1.12.999
extend
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.1.13
extendWorkTemperatureThe temperature of work environmentro
INTEGER (-2200..2200) UNITS "degrees 0.1 Centigrade"
.1.3.6.1.4.1.21111.1.1.13.1
extendWorkhumidityThe humidity of work environmentro
INTEGER
.1.3.6.1.4.1.21111.1.1.13.2
extendSmokeScopeThe smokeScope of work environmentro
INTEGER
.1.3.6.1.4.1.21111.1.1.13.3
extendEMDAlarm1Environment detector alarm 1ro
Enumeration
.1.3.6.1.4.1.21111.1.1.13.4
extendEMDAlarm2Environment detector alarm 2ro
Enumeration
.1.3.6.1.4.1.21111.1.1.13.5
extendEMDAlarm3Environment detector alarm 3ro
Enumeration
.1.3.6.1.4.1.21111.1.1.13.6
extendEMDAlarm4Environment detector alarm 4ro
Enumeration
.1.3.6.1.4.1.21111.1.1.13.7
inverter
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2
solarIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.1
solarRating
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.2
solarBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.3
solarGrid
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.4
solarACOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.5
solarPV
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.6
solarEnergy
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.7
solarTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.8
solarDefValue
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.9
solarFaultInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.10
solarControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.11
solarAgentConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.12
solarCommConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.13
solarConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.14
solarTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.15
solarExtend
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.2.16
charger
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.3
ATS
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.4
ATSIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.4.1
ATSRating
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.4.2
ATSInformation
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.4.3
ATSControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.4.4
ATSAgentConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.4.5
ATSCommConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.4.6
ATSConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.4.7
ATSTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.4.8
ATSExtend
OBJECT IDENTIFIER
.1.3.6.1.4.1.21111.1.4.9