Home/Catalog/SOCOMECUPS-MIB-v2

SOCOMECUPS-MIB-v2

Detailed view of the defined objects, syntax rules, and hierarchical paths.

490
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

490 total
Object Name
socomecSicon
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555
RFC1155-SMI
Unknown
.1.3.6.1.4.1.4555
product
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1
pduAgent
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1
iPDU
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20
ipduObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1
ipduIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.1
ipduIdentManufacturerThe name of manufacturer.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.1.1
ipduIdentModelThe Model designation of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.1.2
ipduIdentAgentSoftwareVersionThe firmware version of the device.ro
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.1.3
ipduIdentNameA description of this device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.1.4
ipduAgent
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2
ipduAgentConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2.1
ipduAgentMibVersionThe Mib Version implemented on this device.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.2.1.1
ipduAgentLog
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2.1.4
pduAgentDataLogIntervalThe interval of the updation of the data log. The value is in secondsrw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.2.1.4.1
ipduAgentControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2.1.5
ipduAgentControlDefaultReset all parameters of the agent to default value.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.1.5.1
ipduAgentControlRestartRestart the agent.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.1.5.2
ipduAgentTrap
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2.1.6
ipduAgentTrapRetryCountThe count of repeat traps send to NMS before trap acknowledgement received.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.2.1.6.1
ipduAgentTrapRetryTimeThe time interval in seconds between retry traps sned to NMS.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.2.1.6.2
ipduAgentTrapAckSignatureThe signature of trap acknowledgement.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.2.1.6.3
ipduAgentTrapsReceiversTableA list of managers to send traps to. The number of entries is given by the value of agentConfigNumTrapReceivers
SEQUENCE OF IpduAgentTrapsReceiversEntry
.1.3.6.1.4.1.4555.1.1.20.1.2.1.7
ipduAgentTrapsReceiversEntryThe managers to send traps to.
IpduAgentTrapsReceiversEntry
.1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1
trapsIndexThe index to a trap receiver entry.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.1
trapsReceiverAddrThe IP address of the manager to send a trap to.rw
IpAddress
.1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.2
receiverCommunityStringThe community name to use in the trap when sent to the manager.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.3
receiverNmsTypeThe trap group that NMS desired.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.4
receiverSeverityLevelThe severity level of traps to be received by this manager.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.5
receiverDescriptionDescription of trap receiversrw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.6
ipduAgentAccessControlTableA list of managers which can access the device with private community string.
SEQUENCE OF IpduAgentAccessControlEntry
.1.3.6.1.4.1.4555.1.1.20.1.2.1.8
ipduAgentAccessControlEntryThe managers.
IpduAgentAccessControlEntry
.1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1
accessIndexThe index to a access control entry.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1.1
accessControlAddrThe IP address of the manager to access the device.rw
IpAddress
.1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1.2
accessControlModeAccess type, only read/Write access type can change parameter of the device.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1.3
ipduAgentTime
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2.2
ipduAgentTimeDateThe date in agent, format is (dd/mm/yyyy)rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.2.2.1
ipduAgentTimeTimeThe time in agent, format is (hh:mm:ss)rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.2.2.2
ipduAgentTimerFromNtpEnable or disable the agent to synchronize date/time with NTP server.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.2.3
ipduAgentNtpIpAddressThe ip address of NTP server.rw
IpAddress
.1.3.6.1.4.1.4555.1.1.20.1.2.2.4
ipduAgentNtpTimeZoneTime Zone to use when synchronize with NTP server.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.2.5
ipduAgentDayLightSavingEnable/disable the Day Light Saving when synchronize with NTP server.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.2.6
ipduAgentNetwork
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2.3
ipduAgentNetworkIp
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2.3.1
ipduAgentNetworkIpAdressThe ip address that NMS can identify the managed device.rw
IpAddress
.1.3.6.1.4.1.4555.1.1.20.1.2.3.1.1
ipduAgentNetworkIpGatewayThe default gateway that allow device managed through routers.rw
IpAddress
.1.3.6.1.4.1.4555.1.1.20.1.2.3.1.2
ipduAgentNetworkIpSubnetInternet address subnet maskrw
IpAddress
.1.3.6.1.4.1.4555.1.1.20.1.2.3.1.3
ipduAgentNetworkDhcpControlEnable/disable DHCP protocolrw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.3.2
ipduAgentNetworkPingControlEnable/disable to response to PING request.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.3.3
ipduAgentNetworkTftpControlEnable/disable TFTP protocolrw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.3.4
ipduAgentNetworkTelnet
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2.3.5
ipduAgentTelnetControlEnable/disable Telnet protocol.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.3.5.1
ipduAgentTelnetPortThe TCP port for telnetrw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.2.3.5.2
ipduAgentNetworkHttp
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2.3.6
ipduAgentHttpControlEnable/disable HTTP protocol.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.3.6.1
ipduAgentHttpPortThe TCP port for HTTP.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.2.3.6.2
ipduAgentNetworkSnmp
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.2.3.7
ipduAgentSnmpControlEnable/disable SNMP protocol.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.2.3.7.1
ipduAgentSnmpPortThe UDP port for SNMP.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.2.3.7.2
ipduDevice
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.3
ipduDeviceInlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.3.1
ipduDeviceInletNumberThe inlet number on this device.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.1
ipduDeviceInletConfigTableA list of inlet on this device.
SEQUENCE OF IpduDeviceInletConfigEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2
ipduDeviceInletConfigEntryThe inlet number of device.
IpduDeviceInletConfigEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1
inletConfigIndexThe index to a access inlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.1
inletConfigDescA Description of inlet of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.2
inletConfigVoltageHighThe Inlet high voltage threshold, in volts.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.3
inletConfigVoltageHighActionReaction of the device when inlet voltage higher than set point.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.4
inletConfigVoltageLowThe Inlet low voltage threshold, in volts.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.5
inletConfigVoltageLowActionReaction of the device when inlet voltage lower than set point.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.6
inletConfigCurrentHighThe Inlet low voltage threshold, in 0.1 amps.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.7
inletConfigCurrentHighActionReaction of the device when inlet current higher than set point.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.8
inletConfigFrequencyHighThe Inlet high frequency threshold, in hz.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.9
inletConfigfrequencyHighActionReaction of the device when inlet frequency higher than set point.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.10
inletConfigFrequencyLowThe Inlet low frequency threshold, in hz.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.11
inletConfigfrequencyLowActionReaction of the device when inlet frequency lower than set point.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.12
ipduDeviceInletStatusTableA list of inlet on this device.
SEQUENCE OF IpduDeviceInletStatusEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.1.3
ipduDeviceInletStatusEntryThe inlet number of device.
IpduDeviceInletStatusEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1
inletStatusIndexThe index to a access inlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.1
inletStatusVoltageThe Inlet Voltage in 0.1 voltsro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.2
inletStatusCurrentThe Inlet Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.3
inletStatusFrequencyThe Inlet Frequency in 0.1 Hzro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.4
inletStatusKwattThe Inlet Kwatt in 0.1 KW/Hro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.5
inletStatusWHThe Inlet Kwatt in 0.1 W/Hro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.6
inletWattResetReset inlet kw.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.1.4
ipduDeviceOutlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.3.2
ipduDeviceOutletNumberThe outlet number on this device.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.1
ipduDeviceOutletConfigTableA list of outlet on this device.
SEQUENCE OF IpduDeviceOutletConfigEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.2.2
ipduDeviceOutletConfigEntryThe inlet number of device.
IpduDeviceOutletConfigEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1
outletConfigIndexThe index to a access inlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.1
outletConfigDescA Description of outlet of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.2
outletConfigLocationLocation of device connectted to this outlet.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.3
outletConfigOnDelayThe delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.4
outletConfigOffDelayThe delay time before turn off tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.5
outletConfigCurrentHighThe outlet high current threshold, in amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.6
outletConfigCurrentHighActionReaction of the device when outlet current higher than set point.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.7
ipduDeviceOutletStatusTableA list of outlet on this device.
SEQUENCE OF IpduDeviceOutletStatusEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.2.3
ipduDeviceOutletStatusEntryThe outlet number of device.
IpduDeviceOutletStatusEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1
outletStatusIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.1
outletStatusStatusOutlet statero
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.2
outletStatusCurrentThe outlet Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.3
outletStatusKwattThe outlet Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.4
outletStatusWHThe outlet Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.5
outletStatusStateTimeTime in seconds since the outlet changed to current state.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.6
outletStatusTimeToGoRemain time the outlet state will be changed by agent, in secondsro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.7
ipduDeviceOutletControlTableA list of outlet on this device.
SEQUENCE OF IpduDeviceOutletControlEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.2.4
ipduDeviceOutletControlEntryThe outlet number of device.
IpduDeviceOutletControlEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.2.4.1
outletControlIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.2.4.1.1
outletControlControlSet to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.2.4.1.2
ipduDeviceOutletControlAllSet to control all outlets perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.2.5
ipduDeviceOutletWattResetReset outlet kw.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.2.6
ipduDeviceCcOut
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.3.3
ipduDeviceCcOutNumberThe contact closure output number on this device.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.3.1
ipduDeviceCcOutConfigTableA list of contact closure output on this device.
SEQUENCE OF IpduDeviceCcOutConfigEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.3.2
ipduDeviceCcOutConfigEntryThe CC number of device.
IpduDeviceCcOutConfigEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1
ccOutConfigIndexThe index to access contact closure output configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.1
ccOutConfigDescA Description of a contact closure output of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.2
ccOutConfigEventActionEnable/disble the contact closure output to react to events.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.3
ccOutConfigCloseDelayThe delay time in seconds when the contact closure output set to close.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.4
ccOutConfigOpenDelayThe delay time in seconds when the contact closure output set to open.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.5
ipduDeviceCcOutStatusTableA list of contact closure output on this device.
SEQUENCE OF IpduDeviceCcOutStatusEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.3.3
ipduDeviceCcOutStatusEntryThe CC number of device.
IpduDeviceCcOutStatusEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1
ccOutStatusIndexThe index to access contact closure output configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1.1
ccOutStatusStatusState of a contact closure output of device.ro
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1.2
ccOutStatusTimeOnStateTime in seconds since the contact closure output changed to current state.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1.3
ipduDeviceCcOutControlTableA list of contact closure output on this device.
SEQUENCE OF IpduDeviceCcOutControlEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.3.4
ipduDeviceCcOutControlEntryThe outlet number of device.
IpduDeviceCcOutControlEntry
.1.3.6.1.4.1.4555.1.1.20.1.3.3.4.1
ccOutControlIndexThe index to a access contact closure output configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.3.3.4.1.1
ccOutControlControlSet to control the contact closure output perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.3.3.4.1.2
ipduSlave
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.4
ipduSlaveState
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.4.1
ipduSlaveStateTableA list of outlet on this device.
SEQUENCE OF IpduSlaveStateEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.1.1
ipduSlaveStateEntryThe outlet number of device.
IpduSlaveStateEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.1.1.1
slaveStateIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.1.1.1.1
slaveStateControl01Set to control the outlet perform action as requested to slave outlet Aro
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.1.1.1.2
ipduSlaveInlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.4.2
ipduSlaveInletStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1
ipduDeviceSlaveInletStatusTableA list of inlet on this device.
SEQUENCE OF IpduDeviceSlaveInletStatusEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1
ipduDeviceSlaveInletStatusEntryThe inlet number of device.
IpduDeviceSlaveInletStatusEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1
inletSlaveStatusIndexThe index to a access inlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.1
inletSlaveStatusVoltageThe Inlet Voltage in 0.1 voltsro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.2
inletSlaveStatusCurrentThe Inlet Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.3
inletSlaveStatusFrequencyThe Inlet Frequency in 0.1 Hzro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.4
inletSlaveStatusKwattThe Inlet Kwatt in 0.001 KW/Hro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.5
inletSlaveStatusWHThe Inlet Kwatt in 0.001 KW/Hro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.6
inletSlaveStatusVoltage2The Inlet Voltage in 0.1 voltsro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.7
inletSlaveStatusCurrent2The Inlet Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.8
inletSlaveStatusFrequency2The Inlet Frequency in 0.1 Hzro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.9
inletSlaveStatusKwatt2The Inlet Kwatt in 0.001 KW/Hro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.10
inletSlaveStatusWH2The Inlet Kwatt in 0.001 KW/Hro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.11
ipduSlaveInletConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.2
ipduDeviceslaveInletConfigTableA list of inlet on this device.
SEQUENCE OF IpduDeviceslaveInletConfigEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1
ipduDeviceslaveInletConfigEntryThe inlet number of device.
IpduDeviceslaveInletConfigEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1
slaveInletConfigIndexThe index to a access inlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.1
slaveInletConfigVoltageHighThe Inlet high voltage threshold, in volts.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.2
slaveInletConfigVoltageLowThe Inlet low voltage threshold, in volts.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.3
slaveInlet2ConfigVoltageHighThe Inlet 2 high voltage threshold, in volts.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.4
slaveInlet2ConfigVoltageLowThe Inlet low voltage threshold, in volts.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.5
ipduSlaveOutlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.4.3
ipduSlaveOutletConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1
ipduSlaveDeviceOutletNameTableA list of outlet on this device.
SEQUENCE OF IpduSlaveDeviceOutletNameEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1
ipduSlaveDeviceOutletNameEntryThe outlet number of device.
IpduSlaveDeviceOutletNameEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1
slaveOutletNameIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.1
slaveOutletName01A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.2
slaveOutletName02A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.3
slaveOutletName03A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.4
slaveOutletName04A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.5
slaveOutletName05A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.6
slaveOutletName06A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.7
slaveOutletName07A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.8
slaveOutletName08A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.9
slaveOutletName09A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.10
slaveOutletName10A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.11
slaveOutletName11A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.12
slaveOutletName12A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.13
ipduSlaveDeviceOutletLocationTableA list of outlet on this device.
SEQUENCE OF IpduSlaveDeviceOutletLocationEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2
ipduSlaveDeviceOutletLocationEntryThe outlet number of device.
IpduSlaveDeviceOutletLocationEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1
slaveOutletLocationIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.1
slaveOutletLocation01A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.2
slaveOutletLocation02A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.3
slaveOutletLocation03A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.4
slaveOutletLocation04A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.5
slaveOutletLocation05A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.6
slaveOutletLocation06A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.7
slaveOutletLocation07A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.8
slaveOutletLocation08A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.9
slaveOutletLocation09A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.10
slaveOutletLocation10A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.11
slaveOutletLocation11A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.12
slaveOutletLocation12A Description of a outlet name of device.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.13
ipduSlaveDeviceOutletOnTimeTableA list of outlet on this device.
SEQUENCE OF IpduSlaveDeviceOutletOnTimeEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3
ipduSlaveDeviceOutletOnTimeEntryThe outlet number of device.
IpduSlaveDeviceOutletOnTimeEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1
slaveOutletOnTimeIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.1
slaveOutletOnTime01The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.2
slaveOutletOnTime02The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.3
slaveOutletOnTime03The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.4
slaveOutletOnTime04The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.5
slaveOutletOnTime05The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.6
slaveOutletOnTime06The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.7
slaveOutletOnTime07The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.8
slaveOutletOnTime08The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.9
slaveOutletOnTime09The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.10
slaveOutletOnTime10The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.11
slaveOutletOnTime11The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.12
slaveOutletOnTime12The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.13
ipduSlaveDeviceOutletOffTimeTableA list of outlet on this device.
SEQUENCE OF IpduSlaveDeviceOutletOffTimeEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4
ipduSlaveDeviceOutletOffTimeEntryThe outlet number of device.
IpduSlaveDeviceOutletOffTimeEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1
slaveOutletOffTimeIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.1
slaveOutletOffTime01The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.2
slaveOutletOffTime02The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.3
slaveOutletOffTime03The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.4
slaveOutletOffTime04The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.5
slaveOutletOffTime05The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.6
slaveOutletOffTime06The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.7
slaveOutletOffTime07The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.8
slaveOutletOffTime08The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.9
slaveOutletOffTime09The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.10
slaveOutletOffTime10The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.11
slaveOutletOffTime11The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.12
slaveOutletOffTime12The delay time before turn on tis outlet, in seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.13
ipduSlaveDeviceOutletCurrThTableA list of outlet on this device.
SEQUENCE OF IpduSlaveDeviceOutletCurrThEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5
ipduSlaveDeviceOutletCurrThEntryThe outlet number of device.
IpduSlaveDeviceOutletCurrThEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1
slaveOutletCurrThIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.1
slaveOutletCurrTh01The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.2
slaveOutletCurrTh02The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.3
slaveOutletCurrTh03The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.4
slaveOutletCurrTh04The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.5
slaveOutletCurrTh05The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.6
slaveOutletCurrTh06The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.7
slaveOutletCurrTh07The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.8
slaveOutletCurrTh08The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.9
slaveOutletCurrTh09The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.10
slaveOutletCurrTh10The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.11
slaveOutletCurrTh11The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.12
slaveOutletCurrTh12The Outlet Current Threshold ,in 0.1 Amp.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.13
ipduSlaveOutletStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2
ipduSlaveDeviceOutletCurrentTableA list of outlet on this device.
SEQUENCE OF IpduSlaveDeviceOutletCurrentEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1
ipduSlaveDeviceOutletCurrentEntryThe outlet number of device.
IpduSlaveDeviceOutletCurrentEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1
slaveOutletCurrentIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.1
slaveOutletCurrent01The outlet A Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.2
slaveOutletCurrent02The outlet B Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.3
slaveOutletCurrent03The outlet C Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.4
slaveOutletCurrent04The outlet D Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.5
slaveOutletCurrent05The outlet E Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.6
slaveOutletCurrent06The outlet F Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.7
slaveOutletCurrent07The outlet G Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.8
slaveOutletCurrent08The outlet H Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.9
slaveOutletCurrent09The outlet I Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.10
slaveOutletCurrent10The outlet J Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.11
slaveOutletCurrent11The outlet K Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.12
slaveOutletCurrent12The outlet L Current in 0.001 Amp.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.13
ipduSlaveDeviceOutletWattTableA list of outlet on this device.
SEQUENCE OF IpduSlaveDeviceOutletWattEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2
ipduSlaveDeviceOutletWattEntryThe outlet number of device.
IpduSlaveDeviceOutletWattEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1
slaveOutletWattIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.1
slaveOutletWatt01The outlet A Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.2
slaveOutletWatt02The outlet B Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.3
slaveOutletWatt03The outlet C Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.4
slaveOutletWatt04The outlet D Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.5
slaveOutletWatt05The outlet E Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.6
slaveOutletWatt06The outlet F Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.7
slaveOutletWatt07The outlet G Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.8
slaveOutletWatt08The outlet H Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.9
slaveOutletWatt09The outlet I Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.10
slaveOutletWatt10The outlet J Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.11
slaveOutletWatt11The outlet K Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.12
slaveOutletWatt12The outlet L Watt in 0.1 W/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.13
ipduSlaveDeviceOutletKwattTableA list of outlet on this device.
SEQUENCE OF IpduSlaveDeviceOutletKwattEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3
ipduSlaveDeviceOutletKwattEntryThe outlet number of device.
IpduSlaveDeviceOutletKwattEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1
slaveOutletKwattIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.1
slaveOutletKwatt01The outlet A Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.2
slaveOutletKwatt02The outlet B Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.3
slaveOutletKwatt03The outlet C Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.4
slaveOutletKwatt04The outlet D Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.5
slaveOutletKwatt05The outlet E Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.6
slaveOutletKwatt06The outlet F Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.7
slaveOutletKwatt07The outlet G Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.8
slaveOutletKwatt08The outlet H Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.9
slaveOutletKwatt09The outlet I Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.10
slaveOutletKwatt10The outlet J Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.11
slaveOutletKwatt11The outlet K Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.12
slaveOutletKwatt12The outlet L Kwatt in 0.001 KW/H.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.13
ipduSlaveOutletAction
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3
ipduSlaveDeviceOutletActionTableA list of outlet on this device.
SEQUENCE OF IpduSlaveDeviceOutletActionEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1
ipduSlaveDeviceOutletActionEntryThe outlet number of device.
IpduSlaveDeviceOutletActionEntry
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1
slaveOutletActionIndexThe index to a access outlet configuration table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.1
slaveOutletAction01Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.2
slaveOutletAction02Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.3
slaveOutletAction03Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.4
slaveOutletAction04Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.5
slaveOutletAction05Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.6
slaveOutletAction06Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.7
slaveOutletAction07Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.8
slaveOutletAction08Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.9
slaveOutletAction09Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.10
slaveOutletAction10Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.11
slaveOutletAction11Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.12
slaveOutletAction12Set to control the outlet perform action as requested.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.13
ipduEnv
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.5
ipduEnvEmd
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.5.1
ipduEnvEmdStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.1
ipduEnvEmdStatusEmdTypeEMD Type.ro
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.1.1
ipduEnvEmdStatusTemperatureEMD Temperature in 0.1 degree C.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.1.2
ipduEnvEmdStatusHumidityEMD Humidity in 0.1%.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.1.3
ipduEnvEmdStatusAlarm1EMD Alarm-1 state.ro
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.1.4
ipduEnvEmdStatusAlarm2EMD Alarm-2 state.ro
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.1.5
ipduEnvEmdConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2
ipduEnvEmdConfigEmdPresenceConfigure the EMD presence by auto-detect or not exist (disabled).rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.1
ipduEnvEmdConfigEmdNameThe name of Emd.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.2
ipduEnvEmdConfigTemp
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3
ipduEnvEmdConfigTempNameThe name of EMD Temperature sensor.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.1
ipduEnvEmdConfigTempHighSetPointEMD Temperature set point high, alarm will active when temperature over this value, in degree C.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.2
ipduEnvEmdConfigTempHighStatusEnabled/disabled the high setpoint be applied or notrw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.3
ipduEnvEmdConfigTempLowSetPointEMD Temperature set point high, alarm will active when temperature under this value, in degree C.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.4
ipduEnvEmdConfigTempLowStatusEnabled/disabled the low setpoint be applied or notrw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.5
ipduEnvEmdConfigTempOffsetOffset of temperature in degree C to adjust EMD temperature measurement.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.6
ipduEnvEmdConfigHumi
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4
ipduEnvEmdConfigHumiNameThe name of EMD Humidity.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.1
ipduEnvEmdConfigHumiHighSetPointEMD humidity set point high, alarm will active when humidity over this value, in %.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.2
ipduEnvEmdConfigHumiHighStatusEnabled/disabled the high setpoint be applied or notrw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.3
ipduEnvEmdConfigHumiLowSetPointEMD humidity set point low, alarm will active when humidity under this value, in %.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.4
ipduEnvEmdConfigHumiLowStatusEnabled/disabled the high setpoint be applied or notrw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.5
ipduEnvEmdConfigHumiOffsetEmd Hum Offset;rw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.6
ipduEnvEmdConfigAlarm1
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.5
ipduEnvEmdConfigAlarm1NameThe name of EMD Alarm-1.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.5.1
ipduEnvEmdConfigAlarm1TypeEMD Alarm-1 typerw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.5.2
ipduEnvEmdConfigAlarm2
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.6
ipduEnvEmdConfigAlarm2NameThe name of EMD Alarm-2.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.6.1
ipduEnvEmdConfigAlarm2TypeEMD Alarm-2 typerw
Enumeration
.1.3.6.1.4.1.4555.1.1.20.1.5.1.2.6.2
ipduTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.20.2
ipduInletVoltageTooHighCRITICAL: The input voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.1
ipduInletVoltageNotTooHighWARNING: The input voltage return from over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.2
ipduInletVoltageTooLowCRITICAL: The input voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.3
ipduInletVoltageNotTooLowWARNING: The input voltage return from under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.4
ipduInletCurrentTooHighCRITICAL: The input current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.5
ipduInletCurrentNotTooHighWARNING: The input current return from over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.6
ipduInletFrequencyTooHighCRITICAL: The input frequency over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.7
ipduInletFrequencyNotTooHighWARNING: The input frequency return from over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.8
ipduInletFrequencyTooLowCRITICAL: The input frequency under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.9
ipduInletFrequencyNotTooLowWARNING: The input frequency return from under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.10
ipduInlet2VoltageTooHighCRITICAL: The input2 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.11
ipduInlet2VoltageNotTooHighWARNING: The input2 voltage return from over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.12
ipduInlet2VoltageTooLowCRITICAL: The input2 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.13
ipduInlet2VoltageNotTooLowWARNING: The input2 voltage return from under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.14
ipduInlet2CurrentTooHighCRITICAL: The input2 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.15
ipduInlet2CurrentNotTooHighWARNING: The input2 current return from over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.16
ipduInlet2FrequencyTooHighCRITICAL: The input2 frequency over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.17
ipduInlet2FrequencyNotTooHighWARNING: The input2 frequency return from over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.18
ipduInlet2FrequencyTooLowCRITICAL: The input2 frequency under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.19
ipduInlet2FrequencyNotTooLowWARNING: The input2 frequency return from under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.20
ipduOutletCurrentTooHighCRITICAL: The output current of outlet over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.21
ipduOutletCurrentNotTooHighWARNING: The output current of outlet return from over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.22
ipduOutletStateChangedINFORMATION: The outlet state had changed from on to off, or from off to on.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.23
ipduEmdTemperatureNotHighINFORMATION: emd Temperature Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.24
ipduEmdTemperatureTooHighWARNING: emd Temperature Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.25
ipduEmdTemperatureNotLowINFORMATION: emd Temperature Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.26
ipduEmdTemperatureTooLowWARNING: emd Temperature Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.27
ipduEmdHumidityNotHighINFORMATION: emd Humidity Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.28
ipduEmdHumidityTooHighWARNING: emd Humidity Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.29
ipduEmdHumidityNotLowINFORMATION: emd Humidity Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.30
ipduEmdHumidityTooLowWARNING: emd Humidity Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.31
ipduEmdAlarm1NormalINFORMATION: emd Alarm1 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.32
ipduEmdAlarm1ActiveWARNING: emd Alarm1 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.33
ipduEmdAlarm2NormalINFORMATION: emd Alarm2 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.34
ipduEmdAlarm2ActiveWARNING: emd Alarm2 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.35
ipduSlave01Inlet01OverHighCRITICAL: The Slave01 input01 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.36
ipduSlave01Inlet01NotOverHighCRITICAL: The Slave01 input01 voltage Not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.37
ipduSlave01Inlet02OverHighCRITICAL: The Slave01 input02 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.38
ipduSlave01Inlet02NotOverHighCRITICAL: The Slave01 input02 voltage Not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.39
ipduSlave01Inlet01UnderLowCRITICAL: The Slave01 input01 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.40
ipduSlave01Inlet01NotUnderLowCRITICAL: The Slave01 input01 voltage Not under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.41
ipduSlave01Inlet02UnderLowCRITICAL: The Slave01 input02 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.42
ipduSlave01Inlet02NotUnderLowCRITICAL: The Slave01 input02 voltage Not under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.43
ipduSlave01Inlet01CurrentOverThCRITICAL: The Slave01 input01 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.44
ipduSlave01Inlet01NotCurrentOverThCRITICAL: The Slave01 input01 current not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.45
ipduSlave01Inlet02CurrentOverThCRITICAL: The Slave01 input02 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.46
ipduSlave01Inlet02NotCurrentOverThCRITICAL: The Slave01 input02 current not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.47
ipduSlave01EmdTemperatureNotHighINFORMATION: The Slave01 emd Temperature Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.48
ipduSlave01EmdTemperatureTooHighWARNING: The Slave01 emd Temperature Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.49
ipduSlave01EmdTemperatureNotLowINFORMATION: The Slave01 emd Temperature Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.50
ipduSlave01EmdTemperatureTooLowWARNING: The Slave01 emd Temperature Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.51
ipduSlave01EmdHumidityNotHighINFORMATION: The Slave01 emd Humidity Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.52
ipduSlave01EmdHumidityTooHighWARNING: The Slave01 emd Humidity Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.53
ipduSlave01EmdHumidityNotLowINFORMATION: The Slave01 emd Humidity Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.54
ipduSlave01EmdHumidityTooLowWARNING: The Slave01 emd Humidity Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.55
ipduSlave01EmdAlarm1NormalINFORMATION: The Slave01 emd Alarm1 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.56
ipduSlave01EmdAlarm1ActiveWARNING: The Slave01 emd Alarm1 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.57
ipduSlave01EmdAlarm2NormalINFORMATION: The Slave01 emd Alarm2 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.58
ipduSlave01EmdAlarm2ActiveWARNING: The Slave01 emd Alarm2 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.59
ipduSlave01OutletCurrentOverThWARNING: The Slave01 Outlet Current over threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.60
ipduSlave02Inlet01OverHighCRITICAL: The Slave02 input01 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.61
ipduSlave02Inlet01NotOverHighCRITICAL: The Slave02 input01 voltage Not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.62
ipduSlave02Inlet02OverHighCRITICAL: The Slave02 input02 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.63
ipduSlave02Inlet02NotOverHighCRITICAL: The Slave02 input02 voltage Not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.64
ipduSlave02Inlet01UnderLowCRITICAL: The Slave02 input01 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.65
ipduSlave02Inlet01NotUnderLowCRITICAL: The Slave02 input01 voltage Not under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.66
ipduSlave02Inlet02UnderLowCRITICAL: The Slave02 input02 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.67
ipduSlave02Inlet02NotUnderLowCRITICAL: The Slave02 input02 voltage Not under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.68
ipduSlave02Inlet01CurrentOverThCRITICAL: The Slave02 input01 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.69
ipduSlave02Inlet01NotCurrentOverThCRITICAL: The Slave02 input01 current not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.70
ipduSlave02Inlet02CurrentOverThCRITICAL: The Slave02 input02 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.71
ipduSlave02Inlet02NotCurrentOverThCRITICAL: The Slave02 input02 current not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.72
ipduSlave02EmdTemperatureNotHighINFORMATION: The Slave02 emd Temperature Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.73
ipduSlave02EmdTemperatureTooHighWARNING: The Slave02 emd Temperature Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.74
ipduSlave02EmdTemperatureNotLowINFORMATION: The Slave02 emd Temperature Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.75
ipduSlave02EmdTemperatureTooLowWARNING: The Slave02 emd Temperature Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.76
ipduSlave02EmdHumidityNotHighINFORMATION: The Slave02 emd Humidity Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.77
ipduSlave02EmdHumidityTooHighWARNING: The Slave02 emd Humidity Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.78
ipduSlave02EmdHumidityNotLowINFORMATION: The Slave02 emd Humidity Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.79
ipduSlave02EmdHumidityTooLowWARNING: The Slave02 emd Humidity Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.80
ipduSlave02EmdAlarm1NormalINFORMATION: The Slave02 emd Alarm1 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.81
ipduSlave02EmdAlarm1ActiveWARNING: The Slave02 emd Alarm1 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.82
ipduSlave02EmdAlarm2NormalINFORMATION: The Slave02 emd Alarm2 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.83
ipduSlave02EmdAlarm2ActiveWARNING: The Slave02 emd Alarm2 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.84
ipduSlave02OutletCurrentOverThWARNING: The Slave02 Outlet Current over threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.85
ipduSlave03Inlet01OverHighCRITICAL: The Slave03 input01 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.86
ipduSlave03Inlet01NotOverHighCRITICAL: The Slave03 input01 voltage Not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.87
ipduSlave03Inlet02OverHighCRITICAL: The Slave03 input02 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.88
ipduSlave03Inlet02NotOverHighCRITICAL: The Slave03 input02 voltage Not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.89
ipduSlave03Inlet01UnderLowCRITICAL: The Slave03 input01 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.90
ipduSlave03Inlet01NotUnderLowCRITICAL: The Slave03 input01 voltage Not under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.91
ipduSlave03Inlet02UnderLowCRITICAL: The Slave03 input02 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.92
ipduSlave03Inlet02NotUnderLowCRITICAL: The Slave03 input02 voltage Not under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.93
ipduSlave03Inlet01CurrentOverThCRITICAL: The Slave03 input01 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.94
ipduSlave03Inlet01NotCurrentOverThCRITICAL: The Slave03 input01 current not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.95
ipduSlave03Inlet02CurrentOverThCRITICAL: The Slave03 input02 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.96
ipduSlave03Inlet02NotCurrentOverThCRITICAL: The Slave03 input02 current not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.97
ipduSlave03EmdTemperatureNotHighINFORMATION: The Slave03 emd Temperature Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.98
ipduSlave03EmdTemperatureTooHighWARNING: The Slave03 emd Temperature Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.99
ipduSlave03EmdTemperatureNotLowINFORMATION: The Slave03 emd Temperature Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.100
ipduSlave03EmdTemperatureTooLowWARNING: The Slave03 emd Temperature Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.101
ipduSlave03EmdHumidityNotHighINFORMATION: The Slave03 emd Humidity Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.102
ipduSlave03EmdHumidityTooHighWARNING: The Slave03 emd Humidity Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.103
ipduSlave03EmdHumidityNotLowINFORMATION: The Slave03 emd Humidity Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.104
ipduSlave03EmdHumidityTooLowWARNING: The Slave03 emd Humidity Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.105
ipduSlave03EmdAlarm1NormalINFORMATION: The Slave03 emd Alarm1 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.106
ipduSlave03EmdAlarm1ActiveWARNING: The Slave03 emd Alarm1 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.107
ipduSlave03EmdAlarm2NormalINFORMATION: The Slave03 emd Alarm2 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.108
ipduSlave03EmdAlarm2ActiveWARNING: The Slave03 emd Alarm2 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.109
ipduSlave03OutletCurrentOverThWARNING: The Slave03 Outlet Current over threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.110
ipduSlave04Inlet01OverHighCRITICAL: The Slave04 input01 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.111
ipduSlave04Inlet01NotOverHighCRITICAL: The Slave04 input01 voltage Not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.112
ipduSlave04Inlet02OverHighCRITICAL: The Slave04 input02 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.113
ipduSlave04Inlet02NotOverHighCRITICAL: The Slave04 input02 voltage Not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.114
ipduSlave04Inlet01UnderLowCRITICAL: The Slave04 input01 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.115
ipduSlave04Inlet01NotUnderLowCRITICAL: The Slave04 input01 voltage Not under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.116
ipduSlave04Inlet02UnderLowCRITICAL: The Slave04 input02 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.117
ipduSlave04Inlet02NotUnderLowCRITICAL: The Slave04 input02 voltage Not under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.118
ipduSlave04Inlet01CurrentOverThCRITICAL: The Slave04 input01 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.119
ipduSlave04Inlet01NotCurrentOverThCRITICAL: The Slave04 input01 current not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.120
ipduSlave04Inlet02CurrentOverThCRITICAL: The Slave04 input02 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.121
ipduSlave04Inlet02NotCurrentOverThCRITICAL: The Slave04 input02 current not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.122
ipduSlave04EmdTemperatureNotHighINFORMATION: The Slave04 emd Temperature Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.123
ipduSlave04EmdTemperatureTooHighWARNING: The Slave04 emd Temperature Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.124
ipduSlave04EmdTemperatureNotLowINFORMATION: The Slave04 emd Temperature Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.125
ipduSlave04EmdTemperatureTooLowWARNING: The Slave04 emd Temperature Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.126
ipduSlave04EmdHumidityNotHighINFORMATION: The Slave04 emd Humidity Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.127
ipduSlave04EmdHumidityTooHighWARNING: The Slave04 emd Humidity Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.128
ipduSlave04EmdHumidityNotLowINFORMATION: The Slave04 emd Humidity Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.129
ipduSlave04EmdHumidityTooLowWARNING: The Slave04 emd Humidity Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.130
ipduSlave04EmdAlarm1NormalINFORMATION: The Slave04 emd Alarm1 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.131
ipduSlave04EmdAlarm1ActiveWARNING: The Slave04 emd Alarm1 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.132
ipduSlave04EmdAlarm2NormalINFORMATION: The Slave04 emd Alarm2 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.133
ipduSlave04EmdAlarm2ActiveWARNING: The Slave04 emd Alarm2 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.134
ipduSlave04OutletCurrentOverThWARNING: The Slave04 Outlet Current over threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.135
ipduSlave05Inlet01OverHighCRITICAL: The Slave05 input01 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.136
ipduSlave05Inlet01NotOverHighCRITICAL: The Slave05 input01 voltage Not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.137
ipduSlave05Inlet02OverHighCRITICAL: The Slave05 input02 voltage over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.138
ipduSlave05Inlet02NotOverHighCRITICAL: The Slave05 input02 voltage Not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.139
ipduSlave05Inlet01UnderLowCRITICAL: The Slave05 input01 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.140
ipduSlave05Inlet01NotUnderLowCRITICAL: The Slave05 input01 voltage Not under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.141
ipduSlave05Inlet02UnderLowCRITICAL: The Slave05 input02 voltage under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.142
ipduSlave05Inlet02NotUnderLowCRITICAL: The Slave05 input02 voltage Not under low threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.143
ipduSlave05Inlet01CurrentOverThCRITICAL: The Slave05 input01 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.144
ipduSlave05Inlet01NotCurrentOverThCRITICAL: The Slave05 input01 current not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.145
ipduSlave05Inlet02CurrentOverThCRITICAL: The Slave05 input02 current over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.146
ipduSlave05Inlet02NotCurrentOverThCRITICAL: The Slave05 input02 current not over high threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.147
ipduSlave05EmdTemperatureNotHighINFORMATION: The Slave05 emd Temperature Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.148
ipduSlave05EmdTemperatureTooHighWARNING: The Slave05 emd Temperature Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.149
ipduSlave05EmdTemperatureNotLowINFORMATION: The Slave05 emd Temperature Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.150
ipduSlave05EmdTemperatureTooLowWARNING: The Slave05 emd Temperature Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.151
ipduSlave05EmdHumidityNotHighINFORMATION: The Slave05 emd Humidity Not High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.152
ipduSlave05EmdHumidityTooHighWARNING: The Slave05 emd Humidity Too High.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.153
ipduSlave05EmdHumidityNotLowINFORMATION: The Slave05 emd Humidity Not Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.154
ipduSlave05EmdHumidityTooLowWARNING: The Slave05 emd Humidity Too Low.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.155
ipduSlave05EmdAlarm1NormalINFORMATION: The Slave05 emd Alarm1 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.156
ipduSlave05EmdAlarm1ActiveWARNING: The Slave05 emd Alarm1 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.157
ipduSlave05EmdAlarm2NormalINFORMATION: The Slave05 emd Alarm2 Normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.158
ipduSlave05EmdAlarm2ActiveWARNING: The Slave05 emd Alarm2 Active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.159
ipduSlave05OutletCurrentOverThWARNING: The Slave05 Outlet Current over threshold.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.20.2.0.160