Objects
Active
Status
5
Dependencies

Imported Objects

Objects

259 total
Object Name
socomecSicon
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555
RFC1155-SMI
INTEGER
.1.3.6.1.4.1.4555
software
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1
network
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1
netvision
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1
upsObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1
upsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.1
upsIdentModelThe UPS Model designation.ro
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.1.1
upsIdentUPSFirmwareVersionThe UPS firmware version.ro
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.1.2
upsIdentAgentSoftwareVersionThe UPS Net Vision software version.ro
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.1.3
upsIdentUpsSerialNumberThe UPS serial no.ro
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.1.4
upsBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.2
upsBatteryStatusThe present battery statusro
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.2.1
upsSecondsOnBatteryIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. -1 shall be returned if the unit is not on battery power.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.2.2
upsEstimatedMinutesRemainingAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.2.3
upsEstimatedChargeRemainingAn estimate of the battery charge remaining expressed as a percent of full charge.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.2.4
upsBatteryVoltageThe magnitude of the present battery voltage in 0.1 Volt DC.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.2.5
upsBatteryTemperatureThe ambient temperature at or near the UPS Battery casing.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.2.6
upsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.3
upsInputNumLinesThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.3.1
upsInputFrequencyThe current input frequency to the UPS system in 0.1 HZ.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.3.2
upsInputTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.
SEQUENCE OF UpsInputEntry
.1.3.6.1.4.1.4555.1.1.1.1.3.3
upsInputEntryAn entry containing information applicable to a particular input line.
UpsInputEntry
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1
upsInputLineIndexro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1.1
upsInputVoltageThe input utility line voltage in 0.1 volts.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1.2
upsInputCurrentThe magnitude of the present input current in 0.1 A.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3
upsInputVoltageMaxThe maximum utility line voltage in 0.1 VAC for last 1 minute.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1.4
upsInputVoltageMinThe minimum utility line voltage in 0.1 VAC for last 1 minute.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5
upsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.4
upsOutputSourceThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.ro
INTEGER SYNTAX INTEGER { unknown(1), onInverter(2), onMains(3), ecoMode(4), onBypass(5), standby(6), onMaintenanceBypass(7), upsOff(8), normalMode(9) }
.1.3.6.1.4.1.4555.1.1.1.1.4.1
upsOutputFrequencyThe current output frequency of the UPS system in 0.1 of HZ.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.4.2
upsOutputNumLinesThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.4.3
upsOutputTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.
SEQUENCE OF UpsOutputEntry
.1.3.6.1.4.1.4555.1.1.1.1.4.4
upsOutputEntryAn entry containing information applicable to a particular output line.
UpsOutputEntry
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1
upsOutputLineIndexThe output line identifier.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1.1
upsOutputVoltageThe output voltage of the UPS system in 0.1 volts.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2
upsOutputCurrentThe output current of the UPS system in 0.1 Amps.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3
upsOutputPercentLoadThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4
upsOutputKvaOutput KVA.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1.5
upsBypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.5
upsBypassFrequencyThe present bypass frequency.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.5.1
upsBypassNumLinesThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.5.2
upsBypassTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
SEQUENCE OF UpsBypassEntry
.1.3.6.1.4.1.4555.1.1.1.1.5.3
upsBypassEntryAn entry containing information applicable to a particular bypass input.
UpsBypassEntry
.1.3.6.1.4.1.4555.1.1.1.1.5.3.1
upsBypassLineIndexThe bypass line identifier.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.5.3.1.1
upsBypassVoltageThe present bypass voltage.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2
upsBypassCurrentThe present bypass current.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3
upsAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.6
upsAlarmsPresentThe present number of active alarm conditions.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.1
upsAlarmTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.
SEQUENCE OF UpsAlarmEntry
.1.3.6.1.4.1.4555.1.1.1.1.6.2
upsAlarmEntryAn entry containing information applicable to a particular alarm.
UpsAlarmEntry
.1.3.6.1.4.1.4555.1.1.1.1.6.2.1
upsAlarmIdA unique identifier for an alarm condition. This value must remain constant.ro
PositiveInteger
.1.3.6.1.4.1.4555.1.1.1.1.6.2.1.1
upsAlarmDescrA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.4555.1.1.1.1.6.2.1.2
upsAlarmTimeThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.4555.1.1.1.1.6.2.1.3
upsAlarmExtDesExtra description.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.4555.1.1.1.1.6.2.1.4
upsWellKnownAlarms
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.6.3
upsAlarmBatteryBadOne or more batteries have been determined to require replacement.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.1
upsAlarmOnBatteryThe UPS is drawing power from the batteries.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.2
upsAlarmLowBatteryThe remaining battery run-time is less than or equal to upsConfigLowBattTime.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.3
upsAlarmDepletedBatteryThe UPS will be unable to sustain the present load when and if the utility power is lost.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.4
upsAlarmTempBadA temperature is out of tolerance.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.5
upsAlarmInputBadAn input condition is out of tolerance.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.6
upsAlarmOutputBadAn output condition (other than OutputOverload) is out of tolerance.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.7
upsAlarmOutputOverloadThe output load exceeds the UPS output capacity.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.8
upsAlarmOnBypassThe Bypass is presently engaged on the UPS.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.9
upsAlarmBypassBadThe Bypass is out of tolerance.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.10
upsAlarmOutputOffAsRequestedThe UPS has shutdown as requested, i.e., the output is off.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.11
upsAlarmUpsOffAsRequestedThe entire UPS has shutdown as commanded.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.12
upsAlarmChargerFailedAn uncorrected problem has been detected within the UPS charger subsystem.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.13
upsAlarmUpsOutputOffThe output of the UPS is in the off state.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.14
upsAlarmUpsSystemOffThe UPS system is in the off state.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.15
upsAlarmFanFailureThe failure of one or more fans in the UPS has been detected.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.16
upsAlarmFuseFailureThe failure of one or more fuses has been detected.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.17
upsAlarmGeneralFaultA general fault in the UPS has been detected.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.18
upsAlarmDiagnosticTestFailedThe result of the last diagnostic test indicates a failure.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.19
upsAlarmCommunicationLostA problem has been encountered in the communications between the agent and the UPS.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.20
upsAlarmAwaitingPowerThe UPS output is off and the UPS is awaiting the return of input power.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.21
upsAlarmShutdownPendingA upsShutdownAfterDelay countdown is underway.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.22
upsAlarmShutdownImminentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.23
upsAlarmTestInProgressA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-TYPE macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-TYPE.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.24
upsAlarmPowerSupplyFaultDigital power supply fault.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.25
upsAlarmAuxMainFailAuxiliary mains out of tolerance.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.26
upsAlarmManualBypassCloseManual By-pass closedro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.27
upsAlarmShortCircuitShort Circuit on UPS output.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.28
upsAlarmBatteryChargerFailureBattery charger failure.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.29
upsAlarmInverterOverCurrentInverter Over-current.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.30
upsAlarmInverterDistorsionExcessive Inverter Distorsion.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.31
upsAlarmPrechargeVoltageFailPrecharge voltage out of tolerance.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.32
upsAlarmBoostTooLowBoost output voltage too low.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.33
upsAlarmBoostTooHighBoost output voltage too high.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.34
upsAlarmBatteryTooHighBattery voltage too high.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.35
upsAlarmImproperConditionImproper condition of usero
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.36
upsAlarmOverloadTimeoutOverload timeout blocking Inverter.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.37
upsAlarmControlSystemFailureMicroprocessor control system failurero
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.38
upsAlarmDataCorruptedConfiguration data map corrupted.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.39
upsAlarmPllFaultPll fault.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.40
upsAlarmInputGeneralAlarmInput mains general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.41
upsAlarmRectifierGeneralAlarmRectifier general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.42
upsAlarmBoostGeneralAlarmBoost general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.43
upsAlarmInverterGeneralAlarmInverter general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.44
upsAlarmBatteryGeneralAlarmBettery charger general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.45
upsAlarmOutputOverOutput voltage over limit.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.46
upsAlarmOutputUnderOutput voltage under limit.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.47
upsAlarmBypassGeneralAlarmBypass charger general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.48
upsAlarmStopForOverloadStop for overload.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.49
upsAlarmImminentStopUPS imminent stopro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.50
upsAlarmModule1AlarmModule 1 in parallel general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.51
upsAlarmModule2AlarmModule 2 in parallel general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.52
upsAlarmModule3AlarmModule 3 in parallel general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.53
upsAlarmModule4AlarmModule 4 in parallel general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.54
upsAlarmModule5AlarmModule 5 in parallel general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.55
upsAlarmModule6AlarmModule 6 in parallel general alarm.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.56
upsAlarmExternalAlarm1External Alarm 1.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.57
upsAlarmExternalAlarm2External Alarm 2.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.58
upsAlarmExternalAlarm3External Alarm 3.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.59
upsAlarmExternalAlarm4External Alarm 4.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.60
upsAlarmEServiceE-Service General Alarmro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.61
upsAlarmRedundancyLostRedundancy lostro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.62
upsAlarmPeriodicServiceCheckPeriodic service check up.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.63
upsAlarmAllTransferDisabledAutomatic and manual transfer disabledro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.64
upsAlarmAutoTransferDisabledAutomatic transfer disabledro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.65
upsAlarmBatteryRoomBattery room alarmro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.66
upsAlarmManualBypassManual bypass alarmro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.67
upsAlarmBatteryDischargedBattery Dischargedro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.68
upsAlarmInsufficientResourcesInsufficient resourcesro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.69
upsAlarmOptionalBoardsOptional boards general alarmro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.70
upsAlarmRectifierFaultRectifier faultro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.71
upsAlarmBoostFaultBoost faultro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.72
upsAlarmInverterFaultInverter faultro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.73
upsAlarmParallelModuleFaultParallel module faultro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.74
upsAlarmGenSetGeneralGen-set general alarmro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.75
upsAlarmGenSetFaultGen-set faultro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.76
upsAlarmEmergencyStopActiveEmergency stop activero
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.77
upsAlarmBatteryCircuitOpenBattery circuit openro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.78
upsAlarmFansFailureFans failurero
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.79
upsAlarmPhaseRotationFaultPhase rotation faultro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.80
upsAlarmA62A62.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.81
upsAlarmA63A63.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.6.3.82
upsTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.7
upsTestIdThe test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of test, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. Tests in progress may be aborted by setting this variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has bee run, in which case the well known value upsTestNoTestsInitiated is returned.rw
INTEGER SYNTAX OBJECT IDENTIFIER --
.1.3.6.1.4.1.4555.1.1.1.1.7.1
upsTestSpinLockA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: try_again: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lock_value = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lock_value, upsTestId = requested_test) if (error_index == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto try_again } if (error_index == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lock_value + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.rw
INTEGER SYNTAX TestAndIncr --
.1.3.6.1.4.1.4555.1.1.1.1.7.2
upsTestResultsSummaryThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.ro
INTEGER SYNTAX INTEGER { notActive(1), inProgress(2), byPass(3), failed(4) }
.1.3.6.1.4.1.4555.1.1.1.1.7.3
upsTestResultsDetailAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.4555.1.1.1.1.7.4
upsTestStartTimeThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.ro
INTEGER SYNTAX TimeStamp
.1.3.6.1.4.1.4555.1.1.1.1.7.5
upsTestElapsedTimeThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.ro
INTEGER SYNTAX TimeInterval
.1.3.6.1.4.1.4555.1.1.1.1.7.6
upsWellKnownTests
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.7.7
upsTestNoTestsInitiatedNo tests have been initiated and no test is in progress.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.7.7.1
upsTestAbortTestInProgressThe test in progress is to be aborted / the test in progress was aborted.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.7.7.2
upsTestGeneralSystemsTestThe manufacturer's standard test of UPS device systems.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.7.7.3
upsTestQuickBatteryTestA test that is sufficient to determine if the battery needs replacement.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.7.7.4
upsDeepBatteryCalibrationThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.7.7.5
upsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.8
upsControlStatusControlThis object Control UPS statusrw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.8.1
upsShutdownDelayThis object set the delay time (in seconds) to turn UPS off after Net Vision broadcast shutdown request to connected clientsrw
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.8.2
upsTurnOffAfterShutdownThis object enable/disable UPS turn off function after shutdown process completerw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.8.3
upsControlShutdownParametersTableTable which describes the parametes for shutdown process when shutdown event occurs
SEQUENCE OF ShutdownParametersEntry
.1.3.6.1.4.1.4555.1.1.1.1.8.4
shutdownParametersEntry
ShutdownParametersEntry
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1
upsControlEventDescrThe shutdown event identificationro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.1
upsControlEventStatusStatus of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.2
upsControlDelayThe Delay after the occurance of the curresponding shutdown event that Net Vision should issue shutdown request to connected clients. For WeeklyScheduledShutdown and SpecialScheduledShutdown, this is the time before the configured Shutdowntime when Net Vision will start sending the warning message to the connected clients. The value is in units of minutes.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.3
upsControlFirstWarningThe delay after the occurance of the curresponding shutdown event that the Net Vision will start sending the warning message to the connected clients. The value is in units of secondsrw
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.4
upsControlWarningIntervalThe frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.5
upsControlSeverityShutdown daemon severity.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.6
upsControlWeeklyScheduleTableThe table to schedule shutting down the ups by weekly.
SEQUENCE OF UpsControlWeeklyScheduleEntry
.1.3.6.1.4.1.4555.1.1.1.1.8.5
upsControlWeeklyScheduleEntryThe entries for each day.
UpsControlWeeklyScheduleEntry
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1
upsControlWeeklyIndexThe index of scheduled events.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1.1
upsControlWeeklyShutdownDayThe weekday on which the UPS should shut down.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1.2
upsControlWeeklyShutdownTimeThe time that the process of shutting down the UPS will be initiated in hh:mm:ss format.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1.3
upsControlWeeklyRestartDayThe weekday on which the UPS should restartrw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1.4
upsControlWeeklyRestartTimeThe time the UPS will restart in hh:mm:ss format.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1.5
upsControlSpecialScheduleTableThe table to schedule shutting down the ups.
SEQUENCE OF UpsControlSpecialScheduleEntry
.1.3.6.1.4.1.4555.1.1.1.1.8.6
upsControlSpecialScheduleEntryThe entries for each day.
UpsControlSpecialScheduleEntry
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1
upsControlSpecialIndexThe index of scheduled events.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1.1
upsControlSpecialShutdownDayThe date on which the UPS should shut down in dd/mm/yyyy format.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1.2
upsControlSpecialShutdownTimeThe time that the process of shutting down the UPS will be initiated in hh:mm:ss formatrw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1.3
upsControlSpecialRestartDayThe date on which the UPS should restart in dd/mm/yyyy formatrw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1.4
upsControlSpecialRestartTimeThe time the UPS will restart in hh:mm:ss format.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1.5
upsControlEcoModeScheduleTableThe table to schedule enable/disable ups eco/mode by weekly.
SEQUENCE OF UpsControlEcoModeScheduleEntry
.1.3.6.1.4.1.4555.1.1.1.1.8.7
upsControlEcoModeScheduleEntryThe entries for each day.
UpsControlEcoModeScheduleEntry
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1
upsControlEcoModeIndexThe index of scheduled events.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1.1
upsControlEcoModeStartDayThe weekday on which the UPS Eco/Mode should enable.rw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1.2
upsControlEcoModeStartTimeThe time that the UPS Eco/Mode will be enabled, in hh:mm:ss format.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1.3
upsControlEcoModeEndDayThe weekday on which the UPS Eco/Mode should disablerw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1.4
upsControlEcoModeEndTimeThe time the UPS Eco/Mode will disabled, in hh:mm:ss format.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1.5
upsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.9
upsConfigInputVoltageThe magnitude of the nominal input voltage.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.9.1
upsConfigInputFreqThe nominal input frequency.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.9.2
upsConfigOutputVoltageThe magnitude of the nominal output voltage.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.9.3
upsConfigOutputFreqThe nominal output frequency.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.9.4
upsDevicesTableThe devices powered by UPS and registered to Net Vision
SEQUENCE OF UpsDevicesEntry
.1.3.6.1.4.1.4555.1.1.1.1.9.5
upsDevicesEntryThe devices protected by Net Vision
UpsDevicesEntry
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1
indexOfDeviceThe index of the device that is plugged into the UPS.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.1
addrOfDeviceThe ip address of the device.ro
IpAddress
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.2
nameOfDeviceThe name/description of the device plugged into the UPS.ro
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.3
timeOfConnectionThe that device registered to Net Visionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.4
statusOfConnectionstatusro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.5
severityOfConnectionseverityro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.6
upsAgent
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.10
upsAgentIpaddressThe ip address that NMS can identify the managed devicerw
IpAddress
.1.3.6.1.4.1.4555.1.1.1.1.10.1
upsAgentGatewayThe default gateway that allow device managed through routersrw
IpAddress
.1.3.6.1.4.1.4555.1.1.1.1.10.2
upsAgentSubnetMaskInternet address subnet maskrw
IpAddress
.1.3.6.1.4.1.4555.1.1.1.1.10.3
upsAgentDateThe date in agent, format is (dd/mm/yyyy)rw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.10.4
upsAgentTimeThe time in agent, format is (hh:mm:ss)rw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.10.5
upsAgentNtpTimeServerrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.4555.1.1.1.1.10.6
upsAgentNtpTimeZonerw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.7
upsAgentHistoryLogFrequencyThe frequency of the updation of the history log. The value is in secondsrw
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.10.8
upsAgentExtHistoryLogFrequencyThe ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which is determined by this object.rw
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.10.9
upsAgentPollRateThe frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second)rw
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.10.10
upsAgentBaudRateThe serial port communication speed (2400/9600 allowed).rw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.11
upsAgentDhcpStatusEnable or disable DHCP-BootP capabilityrw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.12
upsAgentTelnetStatusEnable or disable telnet accessrw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.13
upsAgentTftpStatusEnable or disable network upgrade capabilityrw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.14
upsAgentResetToDefaultReset all parameters of Net Vision to default valuerw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.15
upsAgentRestartRestart Net Visionrw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.16
upsAgentClearAgentLogClear agent log datarw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.17
upsAgentClearEventLogClear event log datarw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.18
upsAgentClearExtHistoryLogClear extented history log datarw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.19
upsAgentClearHistoryLogClear history log datarw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.20
upsAgentTrapsReceiversTableA list of managers to send traps to. The number of entries is given by the value of upsAgentNumTrapReceivers
SEQUENCE OF UpsAgentTrapsReceiversEntry
.1.3.6.1.4.1.4555.1.1.1.1.10.21
upsAgentTrapsReceiversEntryThe managers to send traps to.
UpsAgentTrapsReceiversEntry
.1.3.6.1.4.1.4555.1.1.1.1.10.21.1
trapsIndexThe index to a trap receiver entry.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.10.21.1.1
trapsReceiverAddrThe IP address of the manager to send a trap to.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.4555.1.1.1.1.10.21.1.2
receiverCommunityStringThe community name to use in the trap when sent to the manager.rw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.10.21.1.3
receiverDescriptionDescription of trap receiversrw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.10.21.1.4
upsAgentAccessControlTableA list of managers which can access Net Vision with private community string.
SEQUENCE OF UpsAgentAccessControlEntry
.1.3.6.1.4.1.4555.1.1.1.1.10.22
upsAgentAccessControlEntryThe managers.
UpsAgentAccessControlEntry
.1.3.6.1.4.1.4555.1.1.1.1.10.22.1
accessIndexThe index to a access control entry.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.10.22.1.1
accessControlAddrThe IP address of the manager to access Net Visionrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.4555.1.1.1.1.10.22.1.2
accessCommunityStringThe community name to use in the manager when access Net Visionrw
DisplayString
.1.3.6.1.4.1.4555.1.1.1.1.10.22.1.3
accessControlModeAccess type, only read-Write access type can change parameter of Net Visionrw
Enumeration
.1.3.6.1.4.1.4555.1.1.1.1.10.22.1.4
upsAgentMibVersionThe version of MIB spec.ro
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.10.23
upsAgentTrapStringThis OID allows traps to be sent with an octet string argument that my not be defined in the. A get of this OID will return error or NULL string.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.4555.1.1.1.1.10.50
emdStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.1.11
emdSatatusTemperatureThe measurement of EMD temperature, in 0.1 degreero
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.11.1
emdSatatusHumidityThe measurement of EMD humidity, in 0.1 degreero
INTEGER
.1.3.6.1.4.1.4555.1.1.1.1.11.2
upsTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.4555.1.1.1.2
upsTrapOnBatteryThe UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on battery.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.1
upsTrapTestCompletedThis trap is sent upon completion of a UPS diagnostic test.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.2
upsTrapAlarmEntryAddedThis trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for upsAlarmOnBattery and upsAlarmTestInProgress.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.3
upsTrapAlarmEntryRemovedThis trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for upsAlarmTestInProgress.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.4
upsTrapUpsNormalINFORMATION: The UPS status is normal.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.5
upsTrapUpsBattTestFailedSEVERE: UPS failed the last test of battery.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.6
upsTrapOnBatteryPowerWARNING: The UPS has switched to battery backup power.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.7
upsTrapBatteryLowSEVERE: Battery is near to be discharged.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.8
upsTrapPowerRestoredINFORMATION: Input power has been restored.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.9
upsTrapImminentStopSEVERE: The UPS is near to switch off the output power.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.10
upsTrapTurnedOffWARNING: The UPS has been turned off by the management station.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.11
upsTrapOverTemperatureSEVERE: The UPS has sensed a temperature greater than its limit.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.12
upsTrapOverloadSEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.13
upsTrapOnMainsSEVERE: The UPS output is on mains.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.14
upsTrapRedoundancyLostSEVERE: Redoundancy is lost.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.15
upsTrapEmdTempLowSEVERE: EMD Sensor detected low temperature.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.16
upsTrapEmdTempHighSEVERE: EMD Sensor detected high temperature.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.17
upsTrapEmdHumidityLowSEVERE: EMD Sensor detected low humidity.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.18
upsTrapEmdHumidityHighSEVERE: EMD Sensor detected high humidity.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.19
upsTrapEmdFirstInputActiveSEVERE: The <customized string_1> input is active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.20
upsTrapEmdFirstInputRestoredINFORMATION: The <customized string_1> input is restored.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.21
upsTrapEmdSecondInputActiveSEVERE: The <customized string_2> input is active.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.22
upsTrapEmdSecondInputRestoredINFORMATION: The <customized string_2> input is restored.
TRAP-TYPE
.1.3.6.1.4.1.4555.1.1.1.2.0.23
SOCOMECUPS-MIB - SNMP MIB Reference | MIBs Explorer