SNMP-UPS-MIB
Detailed view of the defined objects, syntax rules, and hierarchical paths.
75
Objects
Active
Status
2
Dependencies
Imported Objects
Objects
75 total| Object Name |
|---|
mgmt OBJECT IDENTIFIER .1.1.3.6.1.4.1.42359.2.2.1.2.3.1.3.6.6.1.3.6.1.1.1.1.3.6.1.4.1.42359.2.2.1.2.3.1.3.6.6.1.3.6.1.1.2.2 |
RFC1155-SMI Unknown .1.1.3.6.1.4.1.42359.2.2.1.2.3.1.3.6.6.1.3.6.1.1.1.1.3.6.1.4.1.42359.2.2.1.2.3.1.3.6.6.1.3.6.1.1.2.2 |
mib-2 OBJECT IDENTIFIER .1.1.3.6.1.4.1.42359.2.2.1.2.3.1.3.6.6.1.3.6.1.1.1.1.3.6.1.4.1.42359.2.2.1.2.3.1.3.6.6.1.3.6.1.1.2.2.1 |
directory OBJECT IDENTIFIER .1.3.6.1.1 |
experimental OBJECT IDENTIFIER .1.3.6.1.3 |
univPowerSupply OBJECT IDENTIFIER .1.3.6.1.3.9999 |
ident OBJECT IDENTIFIER .1.3.6.1.3.9999.1 |
identDescrThe UPS description. This should include the
vendor name, model number and software revision.ro OCTET STRING .1.3.6.1.3.9999.1.1 |
identSpecificA reference to MIB definitions
specific to the particular UPS being
managed. If this information is not
present, its value should be set to
the OBJECT IDENTIFIER { 0 0 }, which
is a syntactically valid object
identifier, and any conformant
implementation of ASN.1 and BER must
be able to generate and recognize this
value.ro OBJECT IDENTIFIER .1.3.6.1.3.9999.1.2 |
battery OBJECT IDENTIFIER .1.3.6.1.3.9999.2 |
batTimeRemainingThe estimated time to battery charge
depletion. (Unit of measure: Minute)ro INTEGER .1.3.6.1.3.9999.2.1 |
batTemperatureThe battery temperature. (Unit of
measure: Degree, Centigrade)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.2.2 |
batVoltageThe current battery voltage. (Unit of
measure: volt)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.2.3 |
batChargeCurrentThe current battery charging current.
(Unit of measure: Amp/10)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.2.4 |
batDischargeCurrentThe current battery discharging current.
(Unit of measure: Amp/10)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.2.5 |
batCapacityThe current battery capacity in percentage
of total available.ro INTEGER .1.3.6.1.3.9999.2.6 |
input OBJECT IDENTIFIER .1.3.6.1.3.9999.3 |
inputFrequencyThe current input frequency. (Unit of
measure: mHz)ro INTEGER (-2147483647..2147483647) .1.3.6.1.3.9999.3.1 |
inputBrownOutsThe number of brown-out conditions since the
agent started.ro Counter .1.3.6.1.3.9999.3.2 |
inputBlackOutsThe number of black-out conditions since the
agent started.ro Counter .1.3.6.1.3.9999.3.3 |
inputTransientsThe number of transient (sag and surge)
conditions since the agent started.ro Counter .1.3.6.1.3.9999.3.4 |
inputNumPhasesThe number of input phases utilized in this
device. This entry indicates the number of rows
in the input table.ro Enumeration .1.3.6.1.3.9999.3.5 |
inputTable SEQUENCE OF InputEntry .1.3.6.1.3.9999.3.6 |
inputEntry InputEntry .1.3.6.1.3.9999.3.6.1 |
inputPhaseThe input phase.ro INTEGER .1.3.6.1.3.9999.3.6.1.1 |
inputVoltageThe input voltage. (Unit of measure: Volt)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.3.6.1.2 |
inputCurrentThe input current. (Unit of measure: Amp/10)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.3.6.1.3 |
inputVAThe input volt-amps.ro INTEGER (-32768..32767) .1.3.6.1.3.9999.3.6.1.4 |
inputWattsThe input power. (Unit of measure: Watt)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.3.6.1.5 |
output OBJECT IDENTIFIER .1.3.6.1.3.9999.4 |
outputFrequencyMeasured in mHz.ro INTEGER (-2147483647..2147483647) .1.3.6.1.3.9999.4.1 |
outputInverterTempThe temperature of the inverter. (Unit of
measure: degree, Centigrade)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.4.2 |
outputControllerTempThe temperature of the controller. (Unit of
measure: degree, Centigrade)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.4.3 |
outputNumPhasesThe number of output phases utilized in this
device. This entry indicates the number of rows in
the output table.ro Enumeration .1.3.6.1.3.9999.4.4 |
outputTable SEQUENCE OF OutputEntry .1.3.6.1.3.9999.4.5 |
outputEntry OutputEntry .1.3.6.1.3.9999.4.5.1 |
outputPhaseThe output phase.ro INTEGER .1.3.6.1.3.9999.4.5.1.1 |
outputVoltageThe output voltage. (Unit of measure: Volt)ro INTEGER (-2147483647..2147483647) .1.3.6.1.3.9999.4.5.1.2 |
outputCurrentThe output current. (Unit of measure: Amp/10)ro INTEGER (-2147483647..2147483647) .1.3.6.1.3.9999.4.5.1.3 |
outputVAThe output volt-amps.ro INTEGER (-32768..32767) .1.3.6.1.3.9999.4.5.1.4 |
outputWattsThe output power. (Unit of measure: Watt)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.4.5.1.5 |
bypass OBJECT IDENTIFIER .1.3.6.1.3.9999.5 |
bypassFrequencyThe bypass frequency. (Unit of measure: mHz)ro INTEGER (-2147483647..2147483647) .1.3.6.1.3.9999.5.1 |
bypassNumPhasesThe number of bypass phases utilized in this
device. This entry indicates the number of rows in
the input table.ro Enumeration .1.3.6.1.3.9999.5.2 |
bypassTable SEQUENCE OF BypassEntry .1.3.6.1.3.9999.5.3 |
bypassEntry BypassEntry .1.3.6.1.3.9999.5.3.1 |
bypassPhaseThe bypass phase.ro INTEGER .1.3.6.1.3.9999.5.3.1.1 |
bypassVoltageThe bypass voltage. (Unit of measure: Volt)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.5.3.1.2 |
bypassCurrentThe bypass current. (Unit of measure: Amp/10)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.5.3.1.3 |
status OBJECT IDENTIFIER .1.3.6.1.3.9999.6 |
statSummaryA summary of non-critical conditions. Each of the
enumerated values are added to compute the value
of this object.ro Enumeration .1.3.6.1.3.9999.6.1 |
alarm OBJECT IDENTIFIER .1.3.6.1.3.9999.7 |
alarmSummaryA summary of critical conditions. Each of the
enumerated values are added to compute the value
of this object.ro Enumeration .1.3.6.1.3.9999.7.1 |
test OBJECT IDENTIFIER .1.3.6.1.3.9999.8 |
testBatterySetting this variable to 'start' will initiate
the battery test. Setting this variable to 'abort'
will stop the battery test if the test is in-
progress, otherwise it has no effect. Reading this
variable will return zero. If 'testBatteryStatus'
is remain in the failure state.rw Enumeration .1.3.6.1.3.9999.8.1 |
testBatteryStatusThe status of the battery test.ro Enumeration .1.3.6.1.3.9999.8.2 |
testDiagSetting this variable to 'start' will initiate
the diagnostics test. Setting this variable to
'abort' will stop the diagnostics test if the test
is in-progress, otherwise it has no effect.
Reading this variable will return zero.rw Enumeration .1.3.6.1.3.9999.8.3 |
testDiagStatusThe status of the diagnostics test.ro Enumeration .1.3.6.1.3.9999.8.4 |
testIndicatorsSetting this variable to 'start' will initiate
the indicators test. Setting this variable to
'abort' will stop the indicators test if the test
is in-progress, otherwise it has no effect.
Reading this variable will return zero.rw Enumeration .1.3.6.1.3.9999.8.5 |
testIndicatorsStatusThe status of the indicators test. Note: this
test requires
physical verification to be useful.ro Enumeration .1.3.6.1.3.9999.8.6 |
schedule OBJECT IDENTIFIER .1.3.6.1.3.9999.9 |
schedOutputOffDelaySetting this object will stop the output after
the indicated number of TimeTicks. Setting this
object to -1 will abort any shutdown sequence. The
output will restart in the number of TimeTicks
indicated by 'schedOutputOnDelay' unless it is
equal to -1. In the later case, the output will
remain inactive. This object will be set to -1
when the device is initialized on power-up or
restart.rw TimeTicks (SNMPv2-SMI) .1.3.6.1.3.9999.9.1 |
schedOutputOnDelayThe length of time to delay before coming on-
line. If this value is -1 the output will remain
off. This object will be set to -1 when the
device is initialized on power-up or restart.rw TimeTicks (SNMPv2-SMI) .1.3.6.1.3.9999.9.2 |
schedSystemShutdownSetting this object to 'true' will shutdown the
device.rw Enumeration .1.3.6.1.3.9999.9.3 |
schedUnixShutdownSetting this device to 'true' will cause unix
shutdown traps to be issued at a system-dependent
rate, or until this object is set to false.rw Enumeration .1.3.6.1.3.9999.9.4 |
config OBJECT IDENTIFIER .1.3.6.1.3.9999.10 |
configOutputVoltageThe nominal output voltage. (Unit of measure:
volt)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.10.1 |
configInputVoltageThe nominal input voltage. (Unit of measure:
volt)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.10.2 |
configOutputFreqThe nominal output frequency. (Unit of measure:
mHz)ro INTEGER (-2147483647..2147483647) .1.3.6.1.3.9999.10.3 |
configInputFreqThe nominal input frequency. (Unit of measure:
mHz)ro INTEGER (-2147483647..2147483647) .1.3.6.1.3.9999.10.4 |
configNominalBatTimeThe nominal battery time. (Unit of measure:
minute)ro INTEGER (-32768..32767) .1.3.6.1.3.9999.10.5 |
configAudioStatusThe status of the audio alarm. 'Off' indicates
the alarm will not sound, while the 'squelch'
value indicates the alarm has sounded and
squelched. A squelched audio status will return to
the previous state ('on' or 'off') when the alarm
stops sounding.rw Enumeration .1.3.6.1.3.9999.10.6 |
configAutoRestartSetting this object to 'on' will cause the device
to restart after a shutdown.rw Enumeration .1.3.6.1.3.9999.10.7 |
private OBJECT IDENTIFIER .1.3.6.1.4 |
enterprises OBJECT IDENTIFIER .1.3.6.1.4.1 |