SLP1-MIB
This is the MIB module for the SecureLinx Power Manager.
Main OID:
slp1.1.3.6.1.4.1.244.1.9.1
92
Objects
Active
Status
2
Dependencies
Imported Objects
Objects
92 total| Object Name |
|---|
lantronix OBJECT IDENTIFIER .1.3.6.1.4.1.244 |
products OBJECT IDENTIFIER .1.3.6.1.4.1.244.1 |
slp OBJECT IDENTIFIER .1.3.6.1.4.1.244.1.9 |
slp1This is the MIB module for the SecureLinx Power Manager. MODULE-IDENTITY .1.3.6.1.4.1.244.1.9.1 |
slp1SystemGroup OBJECT IDENTIFIER .1.3.6.1.4.1.244.1.9.1.1 |
slp1SystemVersionThe firmware version of the system.ro DisplayString .1.3.6.1.4.1.244.1.9.1.1.1 |
slp1SystemNICSerialNumberThe serial number of the network interface card in the system.ro DisplayString .1.3.6.1.4.1.244.1.9.1.1.2 |
slp1SystemLocationThe location of the system.rw DisplayString .1.3.6.1.4.1.244.1.9.1.1.3 |
slp1SystemTowerCountThe number of towers in the system.ro INTEGER .1.3.6.1.4.1.244.1.9.1.1.4 |
slp1SystemEnvMonCountThe number of environmental monitors in the system.ro INTEGER .1.3.6.1.4.1.244.1.9.1.1.5 |
slp1SystemTables OBJECT IDENTIFIER .1.3.6.1.4.1.244.1.9.1.2 |
slp1TowerTableA table of towers. SEQUENCE OF Slp1TowerEntry .1.3.6.1.4.1.244.1.9.1.2.1 |
slp1TowerEntryRow definition for the tower table. Slp1TowerEntry .1.3.6.1.4.1.244.1.9.1.2.1.1 |
slp1TowerIndexIndex for the tower table. INTEGER .1.3.6.1.4.1.244.1.9.1.2.1.1.1 |
slp1TowerIDThe ID of the tower.ro DisplayString .1.3.6.1.4.1.244.1.9.1.2.1.1.2 |
slp1TowerNameThe name of the tower.rw DisplayString .1.3.6.1.4.1.244.1.9.1.2.1.1.3 |
slp1TowerStatusThe operational status of the tower.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.1.1.4 |
slp1TowerInfeedCountThe number of input feeds on the tower.ro INTEGER .1.3.6.1.4.1.244.1.9.1.2.1.1.5 |
slp1InfeedTableA table of input feeds. SEQUENCE OF Slp1InfeedEntry .1.3.6.1.4.1.244.1.9.1.2.2 |
slp1InfeedEntryRow definition for the input feed table. Slp1InfeedEntry .1.3.6.1.4.1.244.1.9.1.2.2.1 |
slp1InfeedIndexIndex for the input feed table. INTEGER .1.3.6.1.4.1.244.1.9.1.2.2.1.1 |
slp1InfeedIDThe ID of the input feed.ro DisplayString .1.3.6.1.4.1.244.1.9.1.2.2.1.2 |
slp1InfeedNameThe name of the input feed.rw DisplayString .1.3.6.1.4.1.244.1.9.1.2.2.1.3 |
slp1InfeedCapabilitiesThe capabilities of the input feed.ro Bits .1.3.6.1.4.1.244.1.9.1.2.2.1.4 |
slp1InfeedStatusThe status of the input feed. If the slp1InfeedCapabilities 'onSense' bit is TRUE, then all of the states are supported and indicate the sensed state of the input feed. If the slp1InfeedCapabilities 'onSense' bit is FALSE, then only the 'on' and 'noComm' states are supported, and 'on' indicates a derived state, not a sensed state.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.2.1.5 |
slp1InfeedLoadStatusThe status of the load measured on the input feed. If the slp1InfeedCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the slp1InfeedCapabilities 'loadSense' bit is FALSE, then only the 'normal' and 'noComm' states are supported.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.2.1.6 |
slp1InfeedLoadValueThe load measured on the input feed. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured.ro INTEGER(-1..25500) UNITS "hundredth Amps" .1.3.6.1.4.1.244.1.9.1.2.2.1.7 |
slp1InfeedLoadHighThreshThe load high threshold value of the input feed in Amps.rw INTEGER .1.3.6.1.4.1.244.1.9.1.2.2.1.8 |
slp1InfeedOutletCountThe number of outlets on the input feed.ro INTEGER .1.3.6.1.4.1.244.1.9.1.2.2.1.9 |
slp1OutletTableA table of outlets. SEQUENCE OF Slp1OutletEntry .1.3.6.1.4.1.244.1.9.1.2.3 |
slp1OutletEntryRow definition for the outlet table. Slp1OutletEntry .1.3.6.1.4.1.244.1.9.1.2.3.1 |
slp1OutletIndexIndex for the outlet table. INTEGER .1.3.6.1.4.1.244.1.9.1.2.3.1.1 |
slp1OutletIDThe ID of the outlet.ro DisplayString .1.3.6.1.4.1.244.1.9.1.2.3.1.2 |
slp1OutletNameThe name of the outlet.rw DisplayString .1.3.6.1.4.1.244.1.9.1.2.3.1.3 |
slp1OutletCapabilitiesThe capabilities of the outlet.ro Bits .1.3.6.1.4.1.244.1.9.1.2.3.1.4 |
slp1OutletStatusThe status of the outlet. If the slp1OutletCapabilities 'onSense' bit is TRUE, then all of the states are supported and indicate the sensed state of the outlet. If the slp1OutletCapabilities 'onSense' bit is FALSE, then only the 'off', 'on', and 'noComm' states are supported, and 'off' and 'on' indicate a derived state, not a sensed state.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.3.1.5 |
slp1OutletLoadStatusThe status of the load measured on the outlet. If the slp1OutletCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the slp1OutletCapabilities 'loadSense' bit is FALSE, then only the 'normal' and 'noComm' states are supported.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.3.1.6 |
slp1OutletLoadValueThe load measured on the outlet. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured.ro INTEGER(-1..25500) UNITS "hundredth Amps" .1.3.6.1.4.1.244.1.9.1.2.3.1.7 |
slp1OutletLoadLowThreshThe load low threshold value of the outlet in Amps.rw INTEGER .1.3.6.1.4.1.244.1.9.1.2.3.1.8 |
slp1OutletLoadHighThreshThe load high threshold value of the outlet in Amps.rw INTEGER .1.3.6.1.4.1.244.1.9.1.2.3.1.9 |
slp1OutletControlStateThe control state of the outlet. The supported states are dependent upon the slp1OutletCapabilities 'powerControl' and 'shutdown' bits, as well as the supported features of the firmware version.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.3.1.10 |
slp1OutletControlActionAn action to change the control state of the outlet. If the slp1OutletCapabilities 'powerControl' bit is TRUE, then the 'on', 'off', and 'reboot' actions can be used to change the control state of the outlet. If the slp1OutletCapabilities 'powerControl' bit is FALSE, then the actions have no effect.rw Enumeration .1.3.6.1.4.1.244.1.9.1.2.3.1.11 |
slp1EnvMonTableA table of environmental monitors. SEQUENCE OF Slp1EnvMonEntry .1.3.6.1.4.1.244.1.9.1.2.4 |
slp1EnvMonEntryRow definition for the environmental monitor table. Slp1EnvMonEntry .1.3.6.1.4.1.244.1.9.1.2.4.1 |
slp1EnvMonIndexIndex for the environmental monitor table. INTEGER .1.3.6.1.4.1.244.1.9.1.2.4.1.1 |
slp1EnvMonIDThe ID of the environmental monitor.ro DisplayString .1.3.6.1.4.1.244.1.9.1.2.4.1.2 |
slp1EnvMonNameThe name of the environmental monitor.rw DisplayString .1.3.6.1.4.1.244.1.9.1.2.4.1.3 |
slp1EnvMonStatusThe operational status of the environmental monitor.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.4.1.4 |
slp1EnvMonWaterSensorNameThe name of the water sensor.rw DisplayString .1.3.6.1.4.1.244.1.9.1.2.4.1.5 |
slp1EnvMonWaterSensorStatusThe status of the water sensor.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.4.1.6 |
slp1EnvMonADCNameThe name of the analog-to-digital converter.rw DisplayString .1.3.6.1.4.1.244.1.9.1.2.4.1.7 |
slp1EnvMonADCStatusThe status of the analog-to-digital converter.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.4.1.8 |
slp1EnvMonADCCountThe 8-bit count value from the analog-to-digital converter. A non-negative value indicates the digital value retrieved from the ADC. A negative value indicates that a digital value was not able to be retrieved.ro INTEGER(-1..255) .1.3.6.1.4.1.244.1.9.1.2.4.1.9 |
slp1EnvMonADCLowThreshThe 8-bit count low threshold value of the analog-to-digital converter.rw INTEGER .1.3.6.1.4.1.244.1.9.1.2.4.1.10 |
slp1EnvMonADCHighThreshThe 8-bit count high threshold value of the analog-to-digital converter.rw INTEGER .1.3.6.1.4.1.244.1.9.1.2.4.1.11 |
slp1EnvMonTempHumidSensorCountThe number of temperature/humidity sensors on the environmental monitor.ro INTEGER .1.3.6.1.4.1.244.1.9.1.2.4.1.12 |
slp1EnvMonContactClosureCountThe number of contact closures on the environmental monitor.ro INTEGER .1.3.6.1.4.1.244.1.9.1.2.4.1.13 |
slp1TempHumidSensorTableA table of temperature/humidity sensors. SEQUENCE OF Slp1TempHumidSensorEntry .1.3.6.1.4.1.244.1.9.1.2.5 |
slp1TempHumidSensorEntryRow definition for the temperature/humidity sensor table. Slp1TempHumidSensorEntry .1.3.6.1.4.1.244.1.9.1.2.5.1 |
slp1TempHumidSensorIndexIndex for the temperature/humidity sensor table. INTEGER .1.3.6.1.4.1.244.1.9.1.2.5.1.1 |
slp1TempHumidSensorIDThe ID of the temperature/humidity sensor.ro DisplayString .1.3.6.1.4.1.244.1.9.1.2.5.1.2 |
slp1TempHumidSensorNameThe name of the temperature/humidity sensor.rw DisplayString .1.3.6.1.4.1.244.1.9.1.2.5.1.3 |
slp1TempHumidSensorStatusThe operational status of the temperature/humidity sensor.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.5.1.4 |
slp1TempHumidSensorTempStatusThe status of the temperature sensor.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.5.1.5 |
slp1TempHumidSensorTempValueThe temperature measured by the sensor. A non-negative value indicates the measured temperature in tenths of degrees Celsius. A negative value indicates that a temperature value was not able to be measured.ro INTEGER(-1..1235) UNITS "tenth degrees Celsius" .1.3.6.1.4.1.244.1.9.1.2.5.1.6 |
slp1TempHumidSensorTempLowThreshThe temperature low threshold value of the sensor in degrees Celsius.rw INTEGER .1.3.6.1.4.1.244.1.9.1.2.5.1.7 |
slp1TempHumidSensorTempHighThreshThe temperature high threshold value of the sensor in degrees Celsius.rw INTEGER .1.3.6.1.4.1.244.1.9.1.2.5.1.8 |
slp1TempHumidSensorHumidStatusThe status of the humidity sensor.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.5.1.9 |
slp1TempHumidSensorHumidValueThe humidity measured by the sensor. A non-negative value indicates the measured humidity in percentage relative humidity. A negative value indicates that a humidity value was not able to be measured.ro INTEGER(-1..100) UNITS "percentage relative humidity" .1.3.6.1.4.1.244.1.9.1.2.5.1.10 |
slp1TempHumidSensorHumidLowThreshThe humidity low threshold value of the sensor in percentage relative humidity.rw INTEGER .1.3.6.1.4.1.244.1.9.1.2.5.1.11 |
slp1TempHumidSensorHumidHighThreshThe humidity low threshold value of the sensor in percentage relative humidity.rw INTEGER .1.3.6.1.4.1.244.1.9.1.2.5.1.12 |
slp1ContactClosureTableA table of contact closures. SEQUENCE OF Slp1ContactClosureEntry .1.3.6.1.4.1.244.1.9.1.2.6 |
slp1ContactClosureEntryRow definition for the contact closure table. Slp1ContactClosureEntry .1.3.6.1.4.1.244.1.9.1.2.6.1 |
slp1ContactClosureIndexIndex for the contact closure table. INTEGER .1.3.6.1.4.1.244.1.9.1.2.6.1.1 |
slp1ContactClosureIDThe ID of the contact closure.ro DisplayString .1.3.6.1.4.1.244.1.9.1.2.6.1.2 |
slp1ContactClosureNameThe name of the contact closure.rw DisplayString .1.3.6.1.4.1.244.1.9.1.2.6.1.3 |
slp1ContactClosureStatusThe status of the contact closure.ro Enumeration .1.3.6.1.4.1.244.1.9.1.2.6.1.4 |
slp1Traps OBJECT IDENTIFIER .1.3.6.1.4.1.244.1.9.1.100 |
slp1Events OBJECT IDENTIFIER .1.3.6.1.4.1.244.1.9.1.100.0 |
slp1TowerStatusEventTower status event. If enabled, this trap is sent when the slp1TowerStatus indicates an error state ('noComm'). This trap is repeated periodically while the slp1TowerStatus remains in an error state. If the slp1TowerStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error slp1TowerStatus, and then stops being repeated. While the slp1TowerStatus indicates an error state, all status and load traps are suppressed for input feeds and outlets on the tower. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.1 |
slp1InfeedStatusEventInput feed status event. If enabled, this trap is sent when the slp1InfeedStatus indicates an error state ('offError', 'onError', or 'noComm'). This trap is repeated periodically while the slp1InfeedStatus remains in an error state. If the slp1InfeedStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error slp1InfeedStatus, and then stops being repeated. While the slp1InfeedStatus indicates an error state, load traps are suppressed for the input feed, and, if the slp1InfeedCapabilities 'failSafe' bit is FALSE, all status and load traps are suppressed for outlets on the input feed. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.2 |
slp1InfeedLoadEventInput feed load event. If enabled, this trap is sent when the slp1InfeedLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the slp1InfeedLoadStatus remains in an error state. If the slp1InfeedLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error slp1InfeedLoadStatus, and then stops being repeated. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.3 |
slp1OutletStatusEventOutlet status event. If enabled, this trap is sent when the slp1OutletStatus indicates an error state ('offError', 'onError', or 'noComm'). This trap is repeated periodically while the slp1OutletStatus remains in an error state. If the slp1OutletStatus returns to a non-error state ('off' or 'on'), this trap is sent once more with the non-error slp1OutletStatus, and then stops being repeated. While the slp1OutletStatus indicates an error state, load traps are suppressed for the outlet. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.4 |
slp1OutletLoadEventOutlet load event. If enabled, this trap is sent when the slp1OutletLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm'). This trap is repeated periodically while the slp1OutletLoadStatus remains in an error state. If the slp1OutletLoadStatus returns to a non-error state ('normal' or 'notOn'), this trap is sent once more with the non-error slp1OutletLoadStatus, and then stops being repeated. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.5 |
slp1OutletChangeEventOutlet on/off change event. If enabled, this trap is sent when the slp1OutletStatus changes from any 'on' state ('on', 'onWait' or 'onError') to any 'off' state ('off', 'offWait' or 'offError'), and vice-versa. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.6 |
slp1EnvMonStatusEventEnvironmental monitor status event. If enabled, this trap is sent when the slp1EnvMonStatus indicates an error state ('noComm'). This trap is repeated periodically while the slp1EnvMonStatus remains in an error state. If the slp1EnvMonStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error slp1EnvMonStatus, and then stops being repeated. While the slp1EnvMonStatus indicates an error state, all status traps are suppressed for the water sensor, ADC, temperature/humudity sensors, and contact closures on the environmental monitor. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.7 |
slp1EnvMonWaterSensorEventEnvironmental monitor water sensor event. If enabled, this trap is sent when the slp1EnvMonWaterSensorStatus indicates an error state ('alarm'). This trap is repeated periodically while the slp1EnvMonWaterSensorStatus remains in an error state. If the slp1EnvMonWaterSensorStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error slp1EnvMonWaterSensorStatus, and then stops being repeated. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.8 |
slp1EnvMonADCEventEnvironmental monitor analog-to-digital converter event. If enabled, this trap is sent when the slp1EnvMonADCStatus indicates an error state ('countLow' or 'countHigh'). This trap is repeated periodically while the slp1EnvMonADCStatus remains in an error state. If the slp1EnvMonADCStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error slp1EnvMonADCStatus, and then stops being repeated. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.9 |
slp1TempHumidSensorStatusEventTemperature/humidity sensor status event. If enabled, this trap is sent when the slp1TempHumidSensorStatus indicates an error state ('lost'). This trap is repeated periodically while the slp1TempHumidSensorStatus remains in an error state. If the slp1TempHumidSensorStatus returns to a non-error state ('found'), this trap is sent once more with the non-error slp1TempHumidSensorStatus, and then stops being repeated. While the slp1TempHumidSensorStatus indicates an error state, all temperature and humidity status traps are suppressed for the temperature/humudity sensor. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.10 |
slp1TempHumidSensorTempEventTemperature/humidity sensor temperature event. If enabled, this trap is sent when the slp1TempHumidSensorTempStatus indicates an error state ('tempLow' or 'tempHigh'). This trap is repeated periodically while the slp1TempHumidSensorTempStatus remains in an error state. If the slp1TempHumidSensorTempStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error slp1TempHumidSensorTempStatus, and then stops being repeated. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.11 |
slp1TempHumidSensorHumidEventTemperature/humidity sensor humidity event. If enabled, this trap is sent when the slp1TempHumidSensorHumidStatus indicates an error state ('humidLow' or 'humidHigh'). This trap is repeated periodically while the slp1TempHumidSensorHumidStatus remains in an error state. If the slp1TempHumidSensorHumidStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error slp1TempHumidSensorHumidStatus, and then stops being repeated. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.12 |
slp1ContactClosureEventContact closure event. If enabled, this trap is sent when the slp1ContactClosureStatus indicates an error state ('alarm'). This trap is repeated periodically while the slp1ContactClosureStatus remains in an error state. If the slp1ContactClosureStatus returns to a non-error state ('normal'), this trap is sent once more with the non-error slp1ContactClosureStatus, and then stops being repeated. NOTIFICATION-TYPE .1.3.6.1.4.1.244.1.9.1.100.0.13 |