SDEVICE-MIB
This MIB describes the functions of the Schleifenbauer device family.
Main OID:
schleifenbauer.1.3.6.1.4.1.31034
103
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
103 total| Object Name |
|---|
schleifenbauerThis MIB describes the functions of the Schleifenbauer device family. MODULE-IDENTITY .1.3.6.1.4.1.31034 |
device0 OBJECT IDENTIFIER .1.3.6.1.4.1.31034.2 |
identification OBJECT IDENTIFIER .1.3.6.1.4.1.31034.2.3 |
spdmVersionData model version, currently 1.10ro Integer32 .1.3.6.1.4.1.31034.2.3.1 |
firmwareVersionThe units firmware revision number.ro Integer32 .1.3.6.1.4.1.31034.2.3.2 |
buildNumberDate and time of latest build of the firmware.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.3.3 |
salesOrderNumberSP sales order number.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.3.4 |
productIdSP product id.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.3.5 |
serialNumberSP serial number.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.3.6 |
hardwareAddressHardware serial number; cannot be changed. Can be used as backup unit address. format as 3 unsigned ints separated by dashes: int - int - intro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.3.7 |
macAddressThe ethernet interfaces unique hardware address.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.3.8 |
unitAddressUser defined address; this will be used for addressing the unit.rw Integer32 .1.3.6.1.4.1.31034.2.3.9 |
deviceNameUser configurable device name or identifier.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.3.10 |
deviceLocationUser configurable device location identifier.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.3.11 |
vanityTagCharacters to be displayed as vanity tekst in display.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.3.12 |
configuration OBJECT IDENTIFIER .1.3.6.1.4.1.31034.2.4 |
noPhasesEither zero, one or three for no input metering, single or three phase systemro Integer32 .1.3.6.1.4.1.31034.2.4.1 |
noOutletsTotalTotal number of outlets, even hardwired without switch/measure modules.ro Integer32 .1.3.6.1.4.1.31034.2.4.2 |
noSwitchedOutletsNumber of switched outlets. If outlet numbering is non-contiguous: the highest outlet number.ro Integer32 .1.3.6.1.4.1.31034.2.4.3 |
noMeasuredOutletsNumber of measured outlets. If outlet numbering is non-contiguous: the highest outlet number.ro Integer32 .1.3.6.1.4.1.31034.2.4.4 |
noSensorsThe number of external, digital environmental sensors: 0 for none, 1 to 16 depending on number of reported sensorsro Integer32 .1.3.6.1.4.1.31034.2.4.5 |
maximumLoadMaximum rated load of device per phase, usually either 16 or 32 A.ro Integer32 .1.3.6.1.4.1.31034.2.4.6 |
systemstatus OBJECT IDENTIFIER .1.3.6.1.4.1.31034.2.5 |
deviceStatusCodeReturns an internal status or error code. 0 = OK, 16 = watchdog timer caused reset, 128 = slave module was reset, 144 = both previous.ro Integer32 .1.3.6.1.4.1.31034.2.5.1 |
temperatureAlertAn alert has been raised due to temperature exceeding treshhold; 0= no alert; 1= internal unit temp, 2= external sensor.ro Integer32 .1.3.6.1.4.1.31034.2.5.2 |
inputCurrentAlertAn alert has been raised due to current exceeding treshhold; 0=no alert; 1-3 for input phase.ro Integer32 .1.3.6.1.4.1.31034.2.5.3 |
outputCurrentAlertAn alert has been raised due to current exceeding treshhold; 0=no alert; 1-48 for outlet.ro Integer32 .1.3.6.1.4.1.31034.2.5.4 |
inputVoltageAlertAn alert has been raised due to a voltage dip; 0=no alert; 1-3 for input phase.ro Integer32 .1.3.6.1.4.1.31034.2.5.5 |
oCurrentDropAlertAn alert has been raised due to the current of a measured outlet suddenly dropping to near zero, possibly indicating a blown fuse; 0=no alert; 1-48 for outlet.ro Integer32 .1.3.6.1.4.1.31034.2.5.6 |
iCurrentDropAlertAn alert has been raised due to the current of a measured input suddenly dropping to near zero, possibly indicating a blown fuse; 0=no alert; 1-3 for phase.ro Integer32 .1.3.6.1.4.1.31034.2.5.7 |
reset OBJECT IDENTIFIER .1.3.6.1.4.1.31034.2.6 |
rebootDeviceWarm reboot/reset of device; note: this will have no effect on outlet status!rw Integer32 .1.3.6.1.4.1.31034.2.6.1 |
resetAlertsReset all alert signals.rw Integer32 .1.3.6.1.4.1.31034.2.6.2 |
zeroInputKWhSubtotalReset of input kWh subtotal counters to zero.rw Integer32 .1.3.6.1.4.1.31034.2.6.3 |
zeroOutKWhSubtotalReset of outlet kWh subtotal counter to zero.rw Integer32 .1.3.6.1.4.1.31034.2.6.4 |
resetPeakValuesReset all peak values to zero, as well input as output metering, voltages dips, current peaks and temperatures.rw Integer32 .1.3.6.1.4.1.31034.2.6.5 |
settings OBJECT IDENTIFIER .1.3.6.1.4.1.31034.2.7 |
general OBJECT IDENTIFIER .1.3.6.1.4.1.31034.2.7.1 |
peakDurationA current peak should last at least [stpkdr] MilliSeconds before an alert is raised; max about a minute.rw MilliSeconds .1.3.6.1.4.1.31034.2.7.1.4 |
fixedOutletDelayMinimal delay between two successive relay switches in milliseconds. Minimal delay is 100 ms. Will always be respected!rw MilliSeconds .1.3.6.1.4.1.31034.2.7.1.5 |
powerSaverModeSet backlight on time in seconds; 0 keeps display always on. Note that keeping the backlight on may decrease luminosity over time. Setting this to other values than 10, 60, 120 or 240 is incompatible with the gateway!rw Seconds .1.3.6.1.4.1.31034.2.7.1.6 |
outletPowerupModeBehaviour of outlet on power-up: 0=off; 1=same state as at power down; 2=same state, but delayed by individual delay timer.rw Integer32 .1.3.6.1.4.1.31034.2.7.1.7 |
maximumTemperatureAn alert should be generated whenever the temperature of the first connected T sensor is above this value. Zero means disabled.rw Integer32 .1.3.6.1.4.1.31034.2.7.1.8 |
displayOrientation0 no display; display off; 1 vertical, display on top; 2 vertical, upside down; 3 horizontal, display at left; 4 horizontal, display at rightrw Integer32 .1.3.6.1.4.1.31034.2.7.1.9 |
localAlertResetAllow alerts to be reset locally on device by pushing one of the buttons. [replaces dipDuration]rw Integer32 .1.3.6.1.4.1.31034.2.7.1.10 |
currentDropDetectionEnables the current drop detection function. 0 = always off (default), 1 = input (s) only, 2 = output(s) only, 3 = both inputs and outputs.rw Integer32 .1.3.6.1.4.1.31034.2.7.1.11 |
wirelessDisplayPowerControls the transit power of the wireless display transciever (if installed). Set to zero to completely disable the module.rw Integer32 .1.3.6.1.4.1.31034.2.7.1.12 |
inputmeasuresTableThis table contains all measures related to the measured inputs of the DEVICE. Note: either 1 or 3 channels, depending on number of phases measured. SEQUENCE OF InputmeasuresEntry .1.3.6.1.4.1.31034.2.8 |
inputmeasuresEntryThe record containing the registers for the channel selected by channelIndex. InputmeasuresEntry .1.3.6.1.4.1.31034.2.8.1 |
channelIndex6The channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1. Integer32 .1.3.6.1.4.1.31034.2.8.1.1 |
kWhTotalIEither the only phase in a single phase measurement; or one of the three phases in a multiphase measurement.ro KiloWattHour .1.3.6.1.4.1.31034.2.8.1.2 |
kWhSubtotalIkWh subtotal register of the only phase in a single phase measurement; or one of three phases in a multiphase measurement. Reset to zero with [rsimks].ro KiloWattHour .1.3.6.1.4.1.31034.2.8.1.3 |
powerFactorIThe effective power factor in percent.ro DeciPowerFactor .1.3.6.1.4.1.31034.2.8.1.4 |
actualCurrentIActual apparent, RMS current.ro DeciAmps .1.3.6.1.4.1.31034.2.8.1.5 |
peakCurrentIPeak apparent, RMS current; highest value since last reset of the alerts.ro DeciAmps .1.3.6.1.4.1.31034.2.8.1.6 |
actualVoltageIThe actual voltage.ro DeciVolts .1.3.6.1.4.1.31034.2.8.1.7 |
minVoltageIRMS voltage dip; lowest value since reset of alerts.ro DeciVolts .1.3.6.1.4.1.31034.2.8.1.8 |
powerVAIPower value calculated, not in data model of device.ro Integer32 .1.3.6.1.4.1.31034.2.8.1.9 |
powerWattIPower value calculated by the gateway, not in data model of device.ro Integer32 .1.3.6.1.4.1.31034.2.8.1.10 |
maxInletAmpsMaximum current per input phase in A; should last at least [stpkdr] MilliSeconds before triggering an alert.rw DeciAmps .1.3.6.1.4.1.31034.2.8.1.11 |
inputCTratioThe multiplier to use in case of use of /5 current transformers. Defaults to 1.rw Integer32 .1.3.6.1.4.1.31034.2.8.1.12 |
inputNameUser configurable naming of inputs or phases. Useful if channels are used to measure branches..rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.8.1.13 |
outletsTableThis table contains the customer specific settings, determining toutlestablehe behaviour of the DEVICE. SEQUENCE OF OutletsEntry .1.3.6.1.4.1.31034.2.9 |
outletsEntryThe record containing the registers forthe channel selected by channelIndex. OutletsEntry .1.3.6.1.4.1.31034.2.9.1 |
channelIndex4The channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1. Integer32 .1.3.6.1.4.1.31034.2.9.1.1 |
outletNameUser configurable naming of individual outlets. Useful to distinguish outlets based on customer or device name.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.9.1.2 |
outputmeasuresTableThis table contains all measures related to the measured outputs of the DEVICE. Note: up to 48 channels, depending on number of measured outlets. SEQUENCE OF OutputmeasuresEntry .1.3.6.1.4.1.31034.2.10 |
outputmeasuresEntryThe record containing the registers for the channel selected by channelIndex. OutputmeasuresEntry .1.3.6.1.4.1.31034.2.10.1 |
channelIndex7The channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1. Integer32 .1.3.6.1.4.1.31034.2.10.1.1 |
kWhTotalOTotal kWh of selected output.ro KiloWattHour .1.3.6.1.4.1.31034.2.10.1.2 |
kWhSubtotalOkWh subtotal register of selected output. Reset to zero with [rsomks].ro KiloWattHour .1.3.6.1.4.1.31034.2.10.1.3 |
powerFactorOPower factor of output.ro DeciPowerFactor .1.3.6.1.4.1.31034.2.10.1.4 |
actualCurrentOActual apparent, RMS current.ro DeciAmps .1.3.6.1.4.1.31034.2.10.1.5 |
peakCurrentOPeak apparent, RMS current; highest value since last reset of alerts.ro DeciAmps .1.3.6.1.4.1.31034.2.10.1.6 |
actualVoltageOActual voltage on output.ro DeciVolts .1.3.6.1.4.1.31034.2.10.1.7 |
maxOutletAmpsMaximum current per outlet in A; should last at least [stpkdr] MilliSeconds before triggering an alert.rw DeciAmps .1.3.6.1.4.1.31034.2.10.1.8 |
outputCTratioThe multiplier to use in case of use of /5 current transformers. Defaults to 1.rw Integer32 .1.3.6.1.4.1.31034.2.10.1.9 |
switchedoutletsTableThis table contains the current status of switchable DEVICE's. SEQUENCE OF SwitchedoutletsEntry .1.3.6.1.4.1.31034.2.11 |
switchedoutletsEntryThe record containing the registers for the channel selected by channelIndex. SwitchedoutletsEntry .1.3.6.1.4.1.31034.2.11.1 |
channelIndex5The channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1. Integer32 .1.3.6.1.4.1.31034.2.11.1.1 |
currentStateThe actual state of the outlet relays. The hardware will contain max 48 outlets. Writing is only effective after setting [swounl].rw Integer32 .1.3.6.1.4.1.31034.2.11.1.2 |
scheduledA one indicates pending activity; the switch delay has not yet expired.ro Integer32 .1.3.6.1.4.1.31034.2.11.1.3 |
unlockSetting the value to one will release the safety for this outlet for a couple seconds; switching and rebooting are then temporarily enabled.rw Integer32 .1.3.6.1.4.1.31034.2.11.1.4 |
individualOutletDelayDelay before an individual outlet switches on at power-up in Seconds.rw Seconds .1.3.6.1.4.1.31034.2.11.1.5 |
sensorTableThis table contains the environmental measurements. As well internal temperature as external temperature probes. SEQUENCE OF SensorEntry .1.3.6.1.4.1.31034.2.12 |
sensorEntryThe record containing the registers for the channel selected by channelIndex. SensorEntry .1.3.6.1.4.1.31034.2.12.1 |
channelIndex8The channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1. Integer32 .1.3.6.1.4.1.31034.2.12.1.1 |
sensorTypeType of connected sensor, either T, H or I for respectively Temperature (C), Humidity (%) or dry switch contactro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.12.1.2 |
sensorValueValue of connected sensorro DeciValue .1.3.6.1.4.1.31034.2.12.1.3 |
sensorNameUser definable name for sensors.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.31034.2.12.1.4 |
conformance OBJECT IDENTIFIER .1.3.6.1.4.1.31034.99 |
compliances OBJECT IDENTIFIER .1.3.6.1.4.1.31034.99.1 |
complianceThe requirements for conformance to the SPGW-MIB. Unknown .1.3.6.1.4.1.31034.99.1.1 |
groups OBJECT IDENTIFIER .1.3.6.1.4.1.31034.99.2 |
identificationGroupA collection of objects providing identification information about the device. Unknown .1.3.6.1.4.1.31034.99.2.1 |
configurationGroupA collection of objects providing configuration information about the device. Unknown .1.3.6.1.4.1.31034.99.2.2 |
systemStatusGroupA collection of objects providing status information about the device. Unknown .1.3.6.1.4.1.31034.99.2.3 |
resetGroupGroups resettable attributes op the device. Unknown .1.3.6.1.4.1.31034.99.2.4 |
settingsGroupA collection of objects providing the actual settings about the device. Unknown .1.3.6.1.4.1.31034.99.2.5 |
switchedOutletsGroupA collection of objects providing the actual outlet status of the device. Unknown .1.3.6.1.4.1.31034.99.2.6 |
inputMeasuresGroupA collection of objects providing the actual input measurements of the device. Unknown .1.3.6.1.4.1.31034.99.2.7 |
outputMeasuresGroupA collection of objects providing the actual output measurements of the device. Unknown .1.3.6.1.4.1.31034.99.2.8 |
sensorsGroupA collection of objects providing the actual environmental measurements of the device. Unknown .1.3.6.1.4.1.31034.99.2.9 |