Standard SNMP MIB module defining data structures for SCTE-HMS-PS-MIB.
61
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
61 total| Object Name |
|---|
IMPORTSNumber of power supply connected to this NE.ro INTEGER ( 0..8 ) .1.3.6.1.4.1.5591.1.4.1 |
psDeviceTableTable containing information about the individual
power supplies being monitored SEQUENCE OF PsDeviceEntry .1.3.6.1.4.1.5591.1.4.2 |
psDeviceEntryList of information about each power supply being monitored. PsDeviceEntry .1.3.6.1.4.1.5591.1.4.2.1 |
psDeviceAddressIndex into the psDeviceTable.Address of this device on the RS-485 pathro INTEGER ( 1..8 ) .1.3.6.1.4.1.5591.1.4.2.1.1 |
psProtocolVersionVersion of the SCTE HMS protocol implemented in the monitored
equipment. The 'Protocol Version' implementation will comply
with the defined protocol in the SCTE 25-3 (formerly HMS 022) document with the
corresponding revision number.
Example: A power supply implementing all commands and responses defined in
SCTE 25-3 (formerly HMS 022) would return a value of 10 (decimal) in this field,
reflecting major revision 1, minor revision 0.
Any number returned that is less than 10 reflects a version of the SCTE 25-3 specification
that had not yet been approved by SCTE.ro INTEGER ( 1..254 ) .1.3.6.1.4.1.5591.1.4.2.1.2 |
psSoftwareVersionThe content of this field is vendor specific. The intent is to provide
a text representation of the power supply or generator system software
version. Any printable ASCII characters can be included in this field.
NULL (0x00) characters are non-printable and are used to fill any unused
locations following the text dataro DisplayString .1.3.6.1.4.1.5591.1.4.2.1.3 |
psDeviceIdThe content of this field is vendor specific. The intent is to provide
manufacturer and/or product specific ASCII text information that will
propagate to the manager's console verbatim. The following special
characters are defined in association with this field:'\' Used to cause
a new line on the console display. Example: 'ALPHA\XM2 9015'
would appear at the monitoring station as :
ALPHA
XM2 9015ro OCTET STRING .1.3.6.1.4.1.5591.1.4.2.1.4 |
psBatteriesCurrent number of batteries per battery string.ro INTEGER ( 0..8 ) .1.3.6.1.4.1.5591.1.4.2.1.5 |
psBatteryStringsCurrent number of battery strings.ro INTEGER ( 0..2 ) .1.3.6.1.4.1.5591.1.4.2.1.6 |
psTempSensorsNumber of Battery temperature sensors.ro INTEGER ( 0..2 ) .1.3.6.1.4.1.5591.1.4.2.1.7 |
psOutputsNumber of power supply outputs.ro INTEGER ( 1..5 ) .1.3.6.1.4.1.5591.1.4.2.1.8 |
psBatteryCurrentSupportBit Map that defines if battery current is measured in this installation.
Bit set means this particular string supports this measurement.
Bits Addresses
0 Not used
1 1 String 1 has battery current support
2 2 String 2 has battery current support
3 3 String 3 has battery current support
4 4 String 4 has battery current support
. . ....................................
. . ....................................
. . ....................................
n n String n has battery current supportro INTEGER .1.3.6.1.4.1.5591.1.4.2.1.9 |
psFloatCurrentSupportBit Map that defines if float current is measured in this installation.
Bit set means this particular string supports this measurement.
Bits Addresses
0 Not used
1 1 String 1 has float current support
2 2 String 2 has float current support
3 3 String 3 has float current support
4 4 String 4 has float current support
. . ..................................
. . ..................................
. . ..................................
n n String n has float current supportro INTEGER .1.3.6.1.4.1.5591.1.4.2.1.10 |
psOutputVoltageSupportDefines if power supply supports monitoring of output voltage
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.11 |
psInputVoltageSupportDefines if power supply supports monitoring of input or line voltage
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported - value in psInputVoltagePresence.
3 = Field is supported - analog representation. value in psInputVoltage.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.12 |
psPowerSupplyTestDefines if power supply supports the remote test feature:
1 = Function not supported.
2 - Function is supported.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.13 |
psMajorAlarmSupportDefines if the power supply supports the major alarm indicator:
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.14 |
psMinorAlarmSupportDefines if the power supply supports the minor alarm indicator:
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.15 |
psTamperSupportDefines if the enclosure door switch is installed in this location:
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.16 |
psBatteryVoltageSupportDefines the if batteries or string voltage are available:
1 = No battery voltage monitoring is available.
2 = Only full string battery voltage is available.
3 = Both individual battery and full string voltages are available.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.17 |
psOutputPowerSupportDefines if the output power measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.18 |
psOutputFrequencySupportDefines if the output frequency measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.19 |
psInputCurrentSupportDefines if the input current measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.20 |
psInputPowerSupportDefines if the input power measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.21 |
psOutputVoltagePower supply output voltage in 1/100 Volts units.
This RMS value is common for all outputs in a multiple output system.
This item requires an entry in the properties MIBro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.2.1.22 |
psInputVoltageScaled representation of input 'line' or 'grid' voltage. This is an
RMS value in 1/100 Volts units. This item requires an entry in the
properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.2.1.23 |
psInverterStatusStatus of power supply inverter. Enumerated value indicates current
status of inverter.
1 = OFF,
2 = ON: AC Line Fail,
3 = ON: Local Test Cycle,
4 = ON: Remote test initiated
5 = ALARM: Last Test Failed
This item requires entries in the discrete properties MIB.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.24 |
psMajorAlarmService has been dropped or a service interruption is imminent.
Indicates that an immediate truck roll is appropriate.
Specific alarms and alarm nomenclature varies between vendors.
Vendors should disclose all conditions that contribute to this
alarm in appropriate product literature.
1 = OK,
2 = ALARM.
This item requires entries in the discrete properties MIB.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.25 |
psMinorAlarmA non-service effecting condition has occurred and should
be monitored. Specific alarms and alarm nomenclature varies
between vendors. Vendors should disclose all conditions that
contribute to this alarm in appropriate product literature.
1 = OK,
2 = ALARM
This item requires entries in the discrete properties MIB.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.26 |
psTamperIndicates status of enclosure door. This notification is
NOT included in the 'Major' or 'Minor' alarm fields.
Individual users / installations must determine if a door
open status represents an alarm and if so, of what severity.
1 = CLOSED,
2 = OPEN
This item requires entries in the discrete properties MIB.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.27 |
psTotalStringVoltageScaled representation of the full battery string in 1/100 Volts units.
This item requires an entry in the properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.2.1.28 |
psEquipmentControlEquipment control
1 = Discontinue inverter operation,
2 = Begin inverter operationrw Enumeration .1.3.6.1.4.1.5591.1.4.2.1.29 |
psPowerOutRepresentation of power supply output power in 1 W.
This item requires an entry in the properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.2.1.30 |
psFrequencyOutScaled representation of the power supply output frequency in 1/100 Hz.
This item requires an entry in the properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.2.1.31 |
psRMSCurrentInScaled representation of the power supply RMS input current in 1/100 A.
This item requires an entry in the properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.2.1.32 |
psPowerInRepresentation of the power supply input power in 1 W.
This item requires an entry in the properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.2.1.33 |
psInputVoltagePresenceDigital value indicating that line voltage is present and within
tolerance or not.
1 = lost
2 = ok.
This item requires entries in the discrete properties MIB.ro Enumeration .1.3.6.1.4.1.5591.1.4.2.1.34 |
psFrequencyInOperational frequency for input voltagero Enumeration .1.3.6.1.4.1.5591.1.4.2.1.35 |
psStringTableTable containing strings data SEQUENCE OF PsStringEntry .1.3.6.1.4.1.5591.1.4.3 |
psStringEntryList of information about each string. Indexed by device and string number PsStringEntry .1.3.6.1.4.1.5591.1.4.3.1 |
psStringDeviceAddressIndex into the psStringTable. Corresponds to psDeviceAddress in psDeviceTable.ro INTEGER ( 1..8 ) .1.3.6.1.4.1.5591.1.4.3.1.1 |
psStringIndex into the psStringTable.ro INTEGER ( 1..2 ) .1.3.6.1.4.1.5591.1.4.3.1.2 |
psStringChargeCurrentScaled representation of battery string charge current.
This is an RMS value in 1/100 Amps. When batteries being discharged,
this value will = 0.
This item requires an entry in the properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.3.1.3 |
psStringDischargeCurrentScaled representation of battery string discharge current. This is
an RMS value in 1/100 Amps.If multiple strings are installed but only
one measurement sensor is used, this value represents the total battery
discharge current. When batteries are being charged, this value will = 0.
This item requires an entry in the properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.3.1.4 |
psStringFloatScaled representation of battery 'float' charge current in 1/100 Amps.
This field will be '0' under conditions other than during
actual float charging. When this field is non-zero (reporting
float current), other battery current values (charge and discharge)
should be discarded. If multiple strings are installed but only
one measurement sensor is used, this field represents the total float
current.
This item requires an entry in the properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.3.1.5 |
psBatteryTableTable containing batteries voltages SEQUENCE OF PsBatteryEntry .1.3.6.1.4.1.5591.1.4.4 |
psBatteryEntryList of information about each battery.Indexed by device number and string PsBatteryEntry .1.3.6.1.4.1.5591.1.4.4.1 |
psBatteryDeviceAddressIndex into the psBatteryTable. Corresponds to psDeviceAddress in psDeviceTable.ro INTEGER ( 1..8 ) .1.3.6.1.4.1.5591.1.4.4.1.1 |
psBatteryStringIndex into the psBatteryTable. Corresponds to psString in psStringTable.ro INTEGER ( 1..2 ) .1.3.6.1.4.1.5591.1.4.4.1.2 |
psBatteryIndex into the psBatteryTable.ro INTEGER ( 1..8 ) .1.3.6.1.4.1.5591.1.4.4.1.3 |
psBatteryVoltageScaled representation of an individual battery voltage in 1/100 Volts.
String 'A' is used if only one battery string is active.
This item requires an entry in the properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.4.1.4 |
psOutputTableTable containing output currents SEQUENCE OF PsOutputEntry .1.3.6.1.4.1.5591.1.4.5 |
psOutputEntryList of information about each Output port. Indexed by device and port number PsOutputEntry .1.3.6.1.4.1.5591.1.4.5.1 |
psOutputDeviceAddressIndex into the psOutputTable.Corresponds to psDeviceAddress in psDeviceTable.ro INTEGER ( 1..8 ) .1.3.6.1.4.1.5591.1.4.5.1.1 |
psOutputIndex into the psOutputTable. Output numberro INTEGER ( 1..5 ) .1.3.6.1.4.1.5591.1.4.5.1.2 |
psOutputCurrentScaled representation of power supply RMS output current in 1/100 Amps.
This value is the total power supply output current if only one output
is active. If multiple outputs are active, this value represents output
#1 current. This item requires an entry in the properties MIB.ro INTEGER ( 0..65535 ) .1.3.6.1.4.1.5591.1.4.5.1.3 |
psTemperatureSensorTableTable containing temperature sensors information SEQUENCE OF PsTemperatureSensorEntry .1.3.6.1.4.1.5591.1.4.6 |
psTemperatureSensorEntryList of information about each Temperature sensor. Indexed by device and Sensor number PsTemperatureSensorEntry .1.3.6.1.4.1.5591.1.4.6.1 |
psTempDeviceAddressIndex into the psTemperatureSensorTable.Corresponds to psDeviceAddress in psDeviceTable.ro INTEGER ( 1..8 ) .1.3.6.1.4.1.5591.1.4.6.1.1 |
psTemperatureSensorIndex into the psTemperatureSensorTable. Temperature sensor numberro INTEGER ( 1..2 ) .1.3.6.1.4.1.5591.1.4.6.1.2 |
psTemperatureScaled representation of temperature.
in degrees C with a range of -40 to + 80 degrees C.
This item requires an entry in the properties MIB.ro INTEGER ( -40..80 ) .1.3.6.1.4.1.5591.1.4.6.1.3 |