NETTRACK-E3METER-SNMP-MIB
AI MIB Summary
The NETTRACK-E3METER-SNMP-MIB enables SNMP-based monitoring of E3METER IPM traffic analysis appliances, specifically exposing interface statistics, packet counters, and flow session metrics for bandwidth utilization and network performance analysis.
Management Information for E3METER IPM products www.e3meter.com
Main OID:
e3Mib.1.3.6.1.4.1.21695.1.10
95
Objects
Active
Status
2
Dependencies
Imported Objects
Objects
95 total| Object Name |
|---|
nettrack OBJECT IDENTIFIER .1.3.6.1.4.1.21695 |
public OBJECT IDENTIFIER .1.3.6.1.4.1.21695.1 |
e3MibManagement Information for E3METER IPM products www.e3meter.com MODULE-IDENTITY .1.3.6.1.4.1.21695.1.10 |
e3Ipm OBJECT IDENTIFIER .1.3.6.1.4.1.21695.1.10.7 |
e3IpmInfo OBJECT IDENTIFIER .1.3.6.1.4.1.21695.1.10.7.1 |
e3IpmInfoSerialSerial number.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.1.1 |
e3IpmInfoModelModel number.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.1.2 |
e3IpmInfoHWVersionHardware revision.ro Enumeration .1.3.6.1.4.1.21695.1.10.7.1.3 |
e3IpmInfoFWVersionInteger representation of the firmware revision (major.minor) represented as a 16 bit integer.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.1.4 |
e3IpmInfoMetersNumber of power meters in this IPS.ro INTEGER .1.3.6.1.4.1.21695.1.10.7.1.5 |
e3IpmMeterTableThe e3IpmMeterTable holds information related to the powermeters of all IPS nodes. SEQUENCE OF E3IpmMeterEntry .1.3.6.1.4.1.21695.1.10.7.2 |
e3IpmMeterEntryHolds the information related to one specific powermeter. E3IpmMeterEntry .1.3.6.1.4.1.21695.1.10.7.2.1 |
e3IpmMeterNumber of the powermeter of this IPS.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.2.1.1 |
e3IpmEnergyPActive energy in watt hours.ro WattHours UNITS "Wh" .1.3.6.1.4.1.21695.1.10.7.2.1.2 |
e3IpmEnergyQReactive energy in volt-ampere reactives hours.ro VoltAmpereReactiveHours UNITS "varh" .1.3.6.1.4.1.21695.1.10.7.2.1.3 |
e3IpmEnergySApparent energy in volt-ampere hours.ro VoltAmpereHours UNITS "VAh" .1.3.6.1.4.1.21695.1.10.7.2.1.4 |
e3IpmPowerPActive power at a given instant.ro Watts UNITS "W" .1.3.6.1.4.1.21695.1.10.7.2.1.5 |
e3IpmPowerQReactive power at a given instant.ro VoltAmpereReactives UNITS "var" .1.3.6.1.4.1.21695.1.10.7.2.1.6 |
e3IpmPowerSApparent power at a given instant.ro VoltAmperes UNITS "VA" .1.3.6.1.4.1.21695.1.10.7.2.1.7 |
e3IpmUrmsRMS voltage at a given instant.ro MilliVolts UNITS "mV" .1.3.6.1.4.1.21695.1.10.7.2.1.8 |
e3IpmIrmsRMS current at a given instant.ro MilliAmperes UNITS "mA" .1.3.6.1.4.1.21695.1.10.7.2.1.9 |
e3IpmFrequencyFrequency measured a given instant.ro MilliHertz UNITS "mHz" .1.3.6.1.4.1.21695.1.10.7.2.1.10 |
e3IpmChannelNameChannel name.ro OCTET STRING .1.3.6.1.4.1.21695.1.10.7.2.1.11 |
e3IpmChannelTypeChannel type: For neutral wire channels, only I_rms will contain meaningful values.ro Enumeration .1.3.6.1.4.1.21695.1.10.7.2.1.12 |
e3IpmSensorTableThe e3IpmSensorTable holds information related to the sensor of this IPM. SEQUENCE OF E3IpmSensorEntry .1.3.6.1.4.1.21695.1.10.7.3 |
e3IpmSensorEntryHolds the information related to one specific sensor. E3IpmSensorEntry .1.3.6.1.4.1.21695.1.10.7.3.1 |
e3IpmSensorSensor port number.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.3.1.1 |
e3IpmSensorTypeSensor type.ro Enumeration .1.3.6.1.4.1.21695.1.10.7.3.1.2 |
e3IpmSensorVersionSensor version.ro OCTET STRING .1.3.6.1.4.1.21695.1.10.7.3.1.3 |
e3IpmSensorTemperatureCelsiusTemperature in tenth degrees.ro DeciDegreesCelsius UNITS "deg-C/10" .1.3.6.1.4.1.21695.1.10.7.3.1.4 |
e3IpmSensorHumidityRelative humidity in per mil.ro Permil UNITS "/1000" .1.3.6.1.4.1.21695.1.10.7.3.1.5 |
e3IpmPGroupTableThe e3IpmPGroupTable holds information related to predefined channel groups. SEQUENCE OF E3IpmPGroupEntry .1.3.6.1.4.1.21695.1.10.7.4 |
e3IpmPGroupEntryHolds the information related to one specific group. E3IpmPGroupEntry .1.3.6.1.4.1.21695.1.10.7.4.1 |
e3IpmPGroupPredefined channel group number.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.4.1.1 |
e3IpmPGNameChannel group name.ro OCTET STRING .1.3.6.1.4.1.21695.1.10.7.4.1.2 |
e3IpmPGMembersA bit set specifying the channels which are members of this channel group. If bit 0 is set, this means that channel CH1 is member of this group. Bit 1 stands for CH2 and so on.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.4.1.3 |
e3IpmPGEnergyPChannel group active energy in watt hours.ro WattHours UNITS "Wh" .1.3.6.1.4.1.21695.1.10.7.4.1.4 |
e3IpmPGEnergyQChannel group reactive energy in volt-ampere reactives hours.ro VoltAmpereReactiveHours UNITS "varh" .1.3.6.1.4.1.21695.1.10.7.4.1.5 |
e3IpmPGEnergySChannel group apparent energy in volt-ampere hours.ro VoltAmpereHours UNITS "VAh" .1.3.6.1.4.1.21695.1.10.7.4.1.6 |
e3IpmPGPowerPChannel group active power at a given instant.ro Watts UNITS "W" .1.3.6.1.4.1.21695.1.10.7.4.1.7 |
e3IpmPGPowerQChannel group reactive power at a given instant.ro VoltAmpereReactives UNITS "var" .1.3.6.1.4.1.21695.1.10.7.4.1.8 |
e3IpmPGPowerSChannel group apparent power at a given instant.ro VoltAmperes UNITS "VA" .1.3.6.1.4.1.21695.1.10.7.4.1.9 |
e3IpmPGIrmsChannel group RMS current at a given instant.ro MilliAmperes UNITS "mA" .1.3.6.1.4.1.21695.1.10.7.4.1.10 |
e3IpmUGroupTableThe e3IpmUGroupTable holds information related to user defined channel groups. SEQUENCE OF E3IpmUGroupEntry .1.3.6.1.4.1.21695.1.10.7.5 |
e3IpmUGroupEntryHolds the information related to one specific group. E3IpmUGroupEntry .1.3.6.1.4.1.21695.1.10.7.5.1 |
e3IpmUGroupUser defined channel group number.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.5.1.1 |
e3IpmUGNameChannel group name.ro OCTET STRING .1.3.6.1.4.1.21695.1.10.7.5.1.2 |
e3IpmUGMembersA bit set specifying the channels which are members of this channel group. If bit 0 is set, this means that channel CH1 is member of this group. Bit 1 stands for CH2 and so on. If no members are configured, the group is inactive.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.5.1.3 |
e3IpmUGEnergyPChannel group active energy in watt hours.ro WattHours UNITS "Wh" .1.3.6.1.4.1.21695.1.10.7.5.1.4 |
e3IpmUGEnergyQChannel group reactive energy in volt-ampere reactives hours.ro VoltAmpereReactiveHours UNITS "varh" .1.3.6.1.4.1.21695.1.10.7.5.1.5 |
e3IpmUGEnergySChannel group apparent energy in volt-ampere hours.ro VoltAmpereHours UNITS "VAh" .1.3.6.1.4.1.21695.1.10.7.5.1.6 |
e3IpmUGPowerPChannel group active power at a given instant.ro Watts UNITS "W" .1.3.6.1.4.1.21695.1.10.7.5.1.7 |
e3IpmUGPowerQChannel group reactive power at a given instant.ro VoltAmpereReactives UNITS "var" .1.3.6.1.4.1.21695.1.10.7.5.1.8 |
e3IpmUGPowerSChannel group apparent power at a given instant.ro VoltAmperes UNITS "VA" .1.3.6.1.4.1.21695.1.10.7.5.1.9 |
e3IpmUGIrmsChannel group RMS current at a given instant.ro MilliAmperes UNITS "mA" .1.3.6.1.4.1.21695.1.10.7.5.1.10 |
e3IpmAlarmTableHolds alarm settings. SEQUENCE OF E3IpmAlarmTableEntry .1.3.6.1.4.1.21695.1.10.7.6 |
e3IpmAlarmTableEntryHolds alarm settings for one specific measured value. E3IpmAlarmTableEntry .1.3.6.1.4.1.21695.1.10.7.6.1 |
e3IpmAlarmIndexDefines the alarm described by the current entry. There are alarms for the current of all phases, for the temperature and the relative humidity.ro Enumeration .1.3.6.1.4.1.21695.1.10.7.6.1.1 |
e3IpmAlarmStateShows this alarm entries' state. If no alarm settings are defined, the state is unknown.ro Enumeration .1.3.6.1.4.1.21695.1.10.7.6.1.2 |
e3IpmAlarmCritLowSetTrue if a 'critical low' alarm level for the current entry is defined, false otherwise.ro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21695.1.10.7.6.1.3 |
e3IpmAlarmCritLowThe 'critical low' alarm level for the current entry in hundredths of the relevant unit (i.e. amperes, degrees celsius and %RH). If no alarm level is configured, this reads 0.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.6.1.4 |
e3IpmAlarmWarnLowSetTrue if a 'warn low' alarm level for the current entry is defined, false otherwise.ro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21695.1.10.7.6.1.5 |
e3IpmAlarmWarnLowThe 'warn low' alarm level for the current entry in hundredths of the relevant unit (i.e. amperes, degrees celsius and %RH). If no alarm level is configured, this reads 0.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.6.1.6 |
e3IpmAlarmWarnHighSetTrue if a 'warn high' alarm level for the current entry is defined, false otherwise.ro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21695.1.10.7.6.1.7 |
e3IpmAlarmWarnHighThe 'warn high' alarm level for the current entry in hundredths of the relevant unit (i.e. amperes, degrees celsius and %RH). If no alarm level is configured, this reads 0.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.6.1.8 |
e3IpmAlarmCritHighSetTrue if a 'critical high' alarm level for the current entry is defined, false otherwise.ro TruthValue (SNMPv2-TC) .1.3.6.1.4.1.21695.1.10.7.6.1.9 |
e3IpmAlarmCritHighThe 'critical high' alarm level for the current entry in hundredths of the relevant unit (i.e. amperes, degrees celsius and %RH). If no alarm level is configured, this reads 0.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.6.1.10 |
e3IpmRcmTableTable holding all residual current monitoring (RCM) data of this IPS.ro Integer32 .1.3.6.1.4.1.21695.1.10.7.7 |
e3IpmRcmTableEntryOne entry in the RCM table. E3IpmRcmTableEntry .1.3.6.1.4.1.21695.1.10.7.7.1 |
e3IpmRcmChannelRCM channel: 0 (total) is the total of all phases in this IPS.ro Enumeration .1.3.6.1.4.1.21695.1.10.7.7.1.1 |
e3IpmRcmAcLimitThe factory configured AC RCM limit. Any measurement higher than this limit is considered a critical problem.ro MilliAmperes UNITS "mA" .1.3.6.1.4.1.21695.1.10.7.7.1.2 |
e3IpmRcmDcLimitThe factory configured DC RCM limit. Any measurement higher than this limit is considered a critical problem.ro MilliAmperes UNITS "mA" .1.3.6.1.4.1.21695.1.10.7.7.1.3 |
e3IpmRcmStatusStatus of the RcmAc/RcmDc data. If the residual current cannot be measured, 0 (unknown) is signalled here, otherwise 1 (valid).ro Enumeration .1.3.6.1.4.1.21695.1.10.7.7.1.4 |
e3IpmRcmAcThe latest AC RCM measurement.ro MilliAmperes UNITS "mA" .1.3.6.1.4.1.21695.1.10.7.7.1.5 |
e3IpmRcmDcThe latest DC RCM measurement.ro MilliAmperes UNITS "mA" .1.3.6.1.4.1.21695.1.10.7.7.1.6 |
e3IpmTraps OBJECT IDENTIFIER .1.3.6.1.4.1.21695.1.10.8 |
e3IpmCurrentCritLowThe e3IpmCurrentCritLow is triggered when the current on the given channel is less than or equal to the configured critical low threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.1 |
e3IpmCurrentWarnLowThe e3IpmCurrentWarnLow is triggered when the current on the given channel is less than or equal to the configured warn low threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.2 |
e3IpmCurrentNormalThe e3IpmCurrentNormal is triggered when the current on the given channel is not outside any configured limits. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.3 |
e3IpmCurrentWarnHighThe e3IpmCurrentWarnHigh is triggered when the current on the given channel is greater than or equal to the configured warn high threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.4 |
e3IpmCurrentCritHighThe e3IpmCurrentCritHigh is triggered when the current on the given channel is greater than or equal to the configured critical high threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.5 |
e3IpmTempCritLowThe e3IpmTempCritLow is triggered when the temperature on the given sensor is less than or equal to the configured critical low threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.6 |
e3IpmTempWarnLowThe e3IpmTempWarnLow is triggered when the temperature on the given sensor is less than or equal to the configured warn low threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.7 |
e3IpmTempNormalThe e3IpmTempNormal is triggered when the temperature on the given sensor is not outside any configured limits. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.8 |
e3IpmTempWarnHighThe e3IpmTempWarnHigh is triggered when the temperature on the given sensor is greater than or equal to the configured warn high threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.9 |
e3IpmTempCritHighThe e3IpmTempCritHigh is triggered when the temperature on the given sensor is greater than or equal to the configured critical high threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.10 |
e3IpmRHCritLowThe e3IpmRHCritLow is triggered when the relative humidity on the given sensor is less than or equal to the configured critical low threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.11 |
e3IpmRHWarnLowThe e3IpmRHWarnLow is triggered when the relative humidity on the given sensor is less than or equal to the configured warn low threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.12 |
e3IpmRHNormalThe e3IpmRHNormal is triggered when the relative humidity on the given sensor is not outside any configured limits. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.13 |
e3IpmRHWarnHighThe e3IpmRHWarnHigh is triggered when the relative humidity on the given sensor is greater than or equal to the configured warn high threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.14 |
e3IpmRHCritHighThe e3IpmRHCritHigh is triggered when the relative humidity on the given sensor is greater than or equal to the configured critical high threshold. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.15 |
e3IpmRcmAcNormalThe e3IpmRcmAcNormal is triggered when the AC part of the residual current falls below the factory-configured limit. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.16 |
e3IpmRcmAcCritHighThe e3IpmRcmAcCritHigh is triggered when the AC part of the residual current is greater than the factory-configured limit. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.17 |
e3IpmRcmDcNormalThe e3IpmRcmDcNormal is triggered when the DC part of the residual current falls below the factory-configured limit. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.18 |
e3IpmRcmDcCritHighThe e3IpmRcmDcCritHigh is triggered when the DC part of the residual current is greater than the factory-configured limit. NOTIFICATION-TYPE .1.3.6.1.4.1.21695.1.10.8.19 |