LIEBERT-GP-SRC-MIB
AI MIB Summary
The LIEBERT-GP-SRC-MIB module enables SNMP-based monitoring and management of Liebert POWER series infrastructure, specifically exposing operational metrics such as power status, environmental sensor readings, and alarm states for Liebert GP series UPS and power distribution units.
The MIB module used to register Liebert POWER related SNMP OIDs.
Copyright 2008-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Main OID:
liebertGlobalProductsSrcModule.liebertSrcModuleReg.1
17
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
17 total| Object Name |
|---|
lgpSrcTableA table containing information about SRC device. SEQUENCE OF LgpSrcEntry .lgpSrc.1 |
lgpSrcEntryThis entry defines the contents of the rows for the table
'lgpSrcTable'. A row in this table cannot be created or deleted by
SNMP operations on columns of the table. LgpSrcEntry .lgpSrc.1.1 |
lgpSrcDevIdThis value must remain constant between agent initializations.
This Device ID is used as an index of the table
'lgpSrcTable'.ro Unsigned32 .lgpSrc.1.1.1 |
lgpSrcDevAddressThis value must remain constant between agent initializations.
This Device Address is used as an index of the table
'lgpSrcTable'.ro Unsigned32 .lgpSrc.1.1.2 |
lgpSrcDevStateIndicates the current state of SRC device. The value of this
object is set to enabled(1) if the SRC device has been enabled.
The value of this object is set to standbyOffline(2) if the SRC
device is waiting for an external action to activate it. The value
of this object is set to unavailableOffline(3) if the SRC device is
present but cannot be used. The value of this object is set to
absent(4) if the SRC device is not present or not detected. The
value of this object will be one of the valid device state:
enabled(1), standbyOffline(2), unavailableOffline(3), or
absent(4).ro Enumeration .lgpSrc.1.1.3 |
lgpSrcDevTemperatureDegFThe measured temperature value in Fahrenheit. The value of this
object is only vaild if the lgpSrcDevState object is set to
enabled(1). The value of this object will be set to
unknown(2147483647) if the value of lgpSrcDevState object is set to
one of the following values: standbyOffline(2),
unavailableOffline(3) or absent(4).ro Enumeration .lgpSrc.1.1.4 |
lgpSrcDevTemperatureSetpointDegFThe temperature setting in Fahrenheit for SRC. This setting may
or may not be the setting used from control. Some systems have the
capability to dynamically change the control setting based on
environmental conditions and/or user configuration. The value of
this object is only vaild if the lgpSrcDevState object is set to
enabled(1). The value of this object will be set to
unknown(2147483647) if the value of lgpSrcDevState object is set to
one of the following values: standbyOffline(2),
unavailableOffline(3) or absent(4).rw Enumeration .lgpSrc.1.1.5 |
lgpSrcDevTemperatureDegCThe measured temperature value in Celsius. The value of this
object is only vaild if the lgpSrcDevState object is set to
enabled(1). The value of this object will be set to
unknown(2147483647) if the value of lgpSrcDevState object is set to
one of the following values: standbyOffline(2),
unavailableOffline(3) or absent(4).ro Enumeration .lgpSrc.1.1.6 |
lgpSrcDevTemperatureSetpointDegCThe temperature setting in Celsius for SRC. This setting may or
may not be the setting used from control. Some systems have the
capability to dynamically change the control setting based on
environmental conditions and/or user configuration. The value of
this object is only vaild if the lgpSrcDevState object is set to
enabled(1). The value of this object will be set to
unknown(2147483647) if the value of lgpSrcDevState object is set to
one of the following values: standbyOffline(2),
unavailableOffline(3) or absent(4).rw Enumeration .lgpSrc.1.1.7 |
lgpSrcDevFanSpeedThe present fan speed of the SRC device. This object will be one
of the valid fan speed: low(1), middle(2), high(3) or auto(4) if
the value of lgpSrcDevState object is set to enabled(1). The value
of this object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4).rw Enumeration .lgpSrc.1.1.8 |
lgpSrcDevPowerStatusThe value of this object specifies the power status of SRC device.
Power status cannot be configured by an operator. The value of
this object is set to off(0) if the SRC device is powered off.
The value of this object is set to on(1) if the SRC device is
powered on. The value of this object will be one of the valid power
status: off(0) or on(1) if lgpSrcDevState is enabled(1). The value
of this object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4).rw Enumeration .lgpSrc.1.1.9 |
lgpSrcDevOperatingModeThe present operating mode of the SRC device. This object will be
one of the valid operating mode: cooling(0), dehumidify(1), fan(2),
ai(3) or heating(4) if the value of lgpSrcDevState object is set to
enabled(1). The value of this object will be set to
unknown(2147483647) if the value of lgpSrcDevState object is set to
one of the following values: standbyOffline(2),
unavailableOffline(3) or absent(4).rw Enumeration .lgpSrc.1.1.10 |
lgpSrcDevTemperatureHighThresholdDegFThe high temperature notification threshold. This is the maximum
value of 'lgpSrcDevTemperatureDegF' before the agent sends a
notification. The value of this object is only vaild if the
lgpSrcDevState object is set to enabled(1). The value of this
object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4).rw Enumeration .lgpSrc.1.1.11 |
lgpSrcDevTemperatureLowThresholdDegFThe low temperature notification threshold. This is the minimum
value of 'lgpSrcDevTemperatureDegF' before the agent sends a
notification. The value of this object is only vaild if the
lgpSrcDevState object is set to enabled(1). The value of this
object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4).rw Enumeration .lgpSrc.1.1.12 |
lgpSrcDevTemperatureHighThresholdDegCThe high temperature notification threshold. This is the maximum
value of 'lgpSrcDevTemperatureDegC' before the agent sends a
notification. The value of this object is only vaild if the
lgpSrcDevState object is set to enabled(1). The value of this
object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4).rw Enumeration .lgpSrc.1.1.13 |
lgpSrcDevTemperatureLowThresholdDegCThe low temperature notification threshold. This is the minimum
value of 'lgpSrcDevTemperatureDegC' before the agent sends a
notification. The value of this object is only vaild if the
lgpSrcDevState object is set to enabled(1). The value of this
object will be set to unknown(2147483647) if the value of
lgpSrcDevState object is set to one of the following values:
standbyOffline(2), unavailableOffline(3) or absent(4).rw Enumeration .lgpSrc.1.1.14 |
liebertGlobalProductsSrcModuleThe MIB module used to register Liebert POWER related SNMP OIDs.
Copyright 2008-2008 Liebert Corporation. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Liebert Corporation
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification. MODULE-IDENTITY .liebertSrcModuleReg.1 |