Home/Catalog/LIEBERT-GP-SRC-MIB

LIEBERT-GP-SRC-MIB

AI MIB Summary

The LIEBERT-GP-SRC-MIB module enables SNMP-based monitoring and management of Liebert POWER series infrastructure, specifically exposing operational metrics such as power status, environmental sensor readings, and alarm states for Liebert GP series UPS and power distribution units.

The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2008-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Main OID:
liebertGlobalProductsSrcModule.liebertSrcModuleReg.1
17
Objects
Active
Status
3
Dependencies

Imported Objects

Objects

17 total
Object Name
lgpSrcTableA table containing information about SRC device.
SEQUENCE OF LgpSrcEntry
.lgpSrc.1
lgpSrcEntryThis entry defines the contents of the rows for the table 'lgpSrcTable'. A row in this table cannot be created or deleted by SNMP operations on columns of the table.
LgpSrcEntry
.lgpSrc.1.1
lgpSrcDevIdThis value must remain constant between agent initializations. This Device ID is used as an index of the table 'lgpSrcTable'.ro
Unsigned32
.lgpSrc.1.1.1
lgpSrcDevAddressThis value must remain constant between agent initializations. This Device Address is used as an index of the table 'lgpSrcTable'.ro
Unsigned32
.lgpSrc.1.1.2
lgpSrcDevStateIndicates the current state of SRC device. The value of this object is set to enabled(1) if the SRC device has been enabled. The value of this object is set to standbyOffline(2) if the SRC device is waiting for an external action to activate it. The value of this object is set to unavailableOffline(3) if the SRC device is present but cannot be used. The value of this object is set to absent(4) if the SRC device is not present or not detected. The value of this object will be one of the valid device state: enabled(1), standbyOffline(2), unavailableOffline(3), or absent(4).ro
Enumeration
.lgpSrc.1.1.3
lgpSrcDevTemperatureDegFThe measured temperature value in Fahrenheit. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).ro
Enumeration
.lgpSrc.1.1.4
lgpSrcDevTemperatureSetpointDegFThe temperature setting in Fahrenheit for SRC. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).rw
Enumeration
.lgpSrc.1.1.5
lgpSrcDevTemperatureDegCThe measured temperature value in Celsius. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).ro
Enumeration
.lgpSrc.1.1.6
lgpSrcDevTemperatureSetpointDegCThe temperature setting in Celsius for SRC. This setting may or may not be the setting used from control. Some systems have the capability to dynamically change the control setting based on environmental conditions and/or user configuration. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).rw
Enumeration
.lgpSrc.1.1.7
lgpSrcDevFanSpeedThe present fan speed of the SRC device. This object will be one of the valid fan speed: low(1), middle(2), high(3) or auto(4) if the value of lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).rw
Enumeration
.lgpSrc.1.1.8
lgpSrcDevPowerStatusThe value of this object specifies the power status of SRC device. Power status cannot be configured by an operator. The value of this object is set to off(0) if the SRC device is powered off. The value of this object is set to on(1) if the SRC device is powered on. The value of this object will be one of the valid power status: off(0) or on(1) if lgpSrcDevState is enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).rw
Enumeration
.lgpSrc.1.1.9
lgpSrcDevOperatingModeThe present operating mode of the SRC device. This object will be one of the valid operating mode: cooling(0), dehumidify(1), fan(2), ai(3) or heating(4) if the value of lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).rw
Enumeration
.lgpSrc.1.1.10
lgpSrcDevTemperatureHighThresholdDegFThe high temperature notification threshold. This is the maximum value of 'lgpSrcDevTemperatureDegF' before the agent sends a notification. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).rw
Enumeration
.lgpSrc.1.1.11
lgpSrcDevTemperatureLowThresholdDegFThe low temperature notification threshold. This is the minimum value of 'lgpSrcDevTemperatureDegF' before the agent sends a notification. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).rw
Enumeration
.lgpSrc.1.1.12
lgpSrcDevTemperatureHighThresholdDegCThe high temperature notification threshold. This is the maximum value of 'lgpSrcDevTemperatureDegC' before the agent sends a notification. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).rw
Enumeration
.lgpSrc.1.1.13
lgpSrcDevTemperatureLowThresholdDegCThe low temperature notification threshold. This is the minimum value of 'lgpSrcDevTemperatureDegC' before the agent sends a notification. The value of this object is only vaild if the lgpSrcDevState object is set to enabled(1). The value of this object will be set to unknown(2147483647) if the value of lgpSrcDevState object is set to one of the following values: standbyOffline(2), unavailableOffline(3) or absent(4).rw
Enumeration
.lgpSrc.1.1.14
liebertGlobalProductsSrcModuleThe MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2008-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
MODULE-IDENTITY
.liebertSrcModuleReg.1