Home/Catalog/GEPARALLELUPS-MIB

GEPARALLELUPS-MIB

AI MIB Summary

The GEPARALLELUPS-MIB enables SNMP-based monitoring and management of GE Digital Energy Uninterruptible Power Supply (UPS) units, specifically facilitating the collection of operational telemetry such as input/output voltage, frequency, load percentage, battery status, and temperature data.

The MIB module to describe GE Digital Energy Uninterruptible Power Supplies.
Main OID:
imv.1.3.6.1.4.1.818
2243
Objects
Active
Status
2
Dependencies

Imported Objects

Objects

2243 total
Object Name
imvThe MIB module to describe GE Digital Energy Uninterruptible Power Supplies.
MODULE-IDENTITY
.1.3.6.1.4.1.818
geHardware
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1
geUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1
geDiscoveredUPSsMaskReading this variable returns bit mask indicating which UPSs in a parallel system are alive. Management software should poll only these UPSs on their snmp branches 11-18 as follows: 1 FirstUPS alive 2 SecondUPS alive 4 ThirdUPS alive 8 FourthUPS alive 16 FifthUPS alive 32 SixthUPS alive 64 SeventhUPS alive 128 EigthUPS alive Since the management software should always monitor the GenericUPS branch (10), this value has no meaning for single upses (which provide values on that snmp branch), and should be set to zero in that case.ro
Integer32
.1.3.6.1.4.1.818.1.1.1
geRequestPacketPut the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus. This OID could be used for accede directly to the internally RS485 bus from a remote place.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.2
geReplyPacketContain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket. Every time that a write command has be made at the OID ge RequestPacket, the value of this OID is erased.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.3
geGenericUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10
upsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.1
upsIdentManufacturerThe name of the UPS manufacturer.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.1.1
upsIdentModelThe UPS Model designation.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.1.2
upsIdentUPSSoftwareVersionThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.1.3
upsIdentAgentSoftwareVersionThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.1.4
upsIdentNameA string identifying the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.1.5
upsIdentAttachedDevicesA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.1.6
upsIdentUPSSerialNumberThe UPS serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.1.7
upsIdentComProtVersionThe IMV communication protocol versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.1.8
upsIdentOperatingTimeThe present value of the operating time. total 'on' time since UPS manufacturedro
NonNegativeInteger32 UNITS "seconds"
.1.3.6.1.4.1.818.1.1.10.1.9
upsBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.2
upsBatteryStatusThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.10.2.1
upsSecondsOnBatteryIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*)ro
Integer32 UNITS "seconds"
.1.3.6.1.4.1.818.1.1.10.2.2
upsEstimatedMinutesRemainingAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*)ro
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.10.2.3
upsEstimatedChargeRemainingAn estimate of the battery charge remaining expressed as a percent of full charge.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.10.2.4
upsBatteryVoltageThe magnitude of the present battery voltage.(*)ro
NonNegativeInteger32 UNITS "0.1 Volt DC"
.1.3.6.1.4.1.818.1.1.10.2.5
upsBatteryCurrentThe present battery current.(*)ro
Integer32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.10.2.6
upsBatteryTemperatureThe ambient temperature at or near the UPS Battery casing.(*)ro
Integer32 UNITS "degrees Centigrade"
.1.3.6.1.4.1.818.1.1.10.2.7
upsBatteryRippleThe present DC link RMS voltage ripple.(*)ro
Integer32 UNITS "0.1 Volt RMS"
.1.3.6.1.4.1.818.1.1.10.2.8
upsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.3
upsInputLineBadsA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*)ro
Counter32
.1.3.6.1.4.1.818.1.1.10.3.1
upsInputNumLinesThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.3.2
upsInputTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
SEQUENCE OF UpsInputEntry
.1.3.6.1.4.1.818.1.1.10.3.3
upsInputEntryAn entry containing information applicable to a particular input line.(*)
UpsInputEntry
.1.3.6.1.4.1.818.1.1.10.3.3.1
upsInputLineIndexThe input line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.3.3.1.1
upsInputFrequencyThe present input frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.10.3.3.1.2
upsInputVoltageThe magnitude of the present input voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.10.3.3.1.3
upsInputCurrentThe magnitude of the present input current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.10.3.3.1.4
upsInputTruePowerThe magnitude of the present input true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.10.3.3.1.5
upsInputVoltageMinThe lowest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.10.3.3.1.6
upsInputVoltageMaxThe highest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.10.3.3.1.7
upsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.4
upsOutputSourceThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.10.4.1
upsOutputFrequencyThe present output frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.10.4.2
upsOutputNumLinesThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.4.3
upsOutputTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
SEQUENCE OF UpsOutputEntry
.1.3.6.1.4.1.818.1.1.10.4.4
upsOutputEntryAn entry containing information applicable to a particular output line.(*)
UpsOutputEntry
.1.3.6.1.4.1.818.1.1.10.4.4.1
upsOutputLineIndexThe output line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.4.4.1.1
upsOutputVoltageThe present output voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.10.4.4.1.2
upsOutputCurrentThe present output current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.10.4.4.1.3
upsOutputPowerThe present output true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.10.4.4.1.4
upsOutputPercentLoadThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.10.4.4.1.5
upsOutputPowerFactorThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*)ro
Integer32 (-99..100) UNITS "0.01 cos phi"
.1.3.6.1.4.1.818.1.1.10.4.4.1.6
upsOutputPeakCurrentThe present output peak current.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.10.4.4.1.7
upsOutputShareCurrentIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.10.4.4.1.8
upsBypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.5
upsBypassFrequencyThe present bypass frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.10.5.1
upsBypassNumLinesThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.5.2
upsBypassTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
SEQUENCE OF UpsBypassEntry
.1.3.6.1.4.1.818.1.1.10.5.3
upsBypassEntryAn entry containing information applicable to a particular bypass input.(*)
UpsBypassEntry
.1.3.6.1.4.1.818.1.1.10.5.3.1
upsBypassLineIndexThe bypass line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.5.3.1.1
upsBypassVoltageThe present bypass voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.10.5.3.1.2
upsBypassCurrentThe present bypass current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.10.5.3.1.3
upsBypassPowerThe present true power conveyed by the bypass.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.10.5.3.1.4
upsAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6
upsAlarmsPresentThe present number of active alarm conditions.(*)ro
Gauge32
.1.3.6.1.4.1.818.1.1.10.6.1
upsAlarmTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*)
SEQUENCE OF UpsAlarmEntry
.1.3.6.1.4.1.818.1.1.10.6.2
upsAlarmEntryAn entry containing information applicable to a particular alarm.(*)
UpsAlarmEntry
.1.3.6.1.4.1.818.1.1.10.6.2.1
upsAlarmIdA unique identifier for an alarm condition. This value must remain constant.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.6.2.1.1
upsAlarmDescrA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*)ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.6.2.1.2
upsAlarmTimeThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.6.2.1.3
upsWellKnownAlarms
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3
upsAlarmBatteryBadOne or more batteries have been determined to require replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.1
upsAlarmOnBatteryThe UPS is drawing power from the batteries.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.2
upsAlarmLowBatteryThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.3
upsAlarmDepletedBatteryThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.4
upsAlarmTempBadA temperature is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.5
upsAlarmInputBadAn input condition is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.6
upsAlarmOutputBadAn output condition (other than OutputOverload) is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.7
upsAlarmOutputOverloadThe output load exceeds the UPS output capacity.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.8
upsAlarmOnBypassThe Bypass is presently engaged on the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.9
upsAlarmBypassBadThe Bypass is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.10
upsAlarmOutputOffAsRequestedThe UPS has shutdown as requested, i.e., the output is off.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.11
upsAlarmUpsOffAsRequestedThe entire UPS has shutdown as commanded.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.12
upsAlarmChargerFailedAn uncorrected problem has been detected within the UPS charger subsystem.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.13
upsAlarmUpsOutputOffThe output of the UPS is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.14
upsAlarmUpsSystemOffThe UPS system is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.15
upsAlarmFanFailureThe failure of one or more fans in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.16
upsAlarmFuseFailureThe failure of one or more fuses has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.17
upsAlarmGeneralFaultA general fault in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.18
upsAlarmDiagnosticTestFailedThe result of the last diagnostic test indicates a failure.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.19
upsAlarmCommunicationsLostA problem has been encountered in the communications between the agent and the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.20
upsAlarmAwaitingPowerThe UPS output is off and the UPS is awaiting the return of input power.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.21
upsAlarmShutdownPendingA upsShutdownAfterDelay countdown is underway.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.22
upsAlarmShutdownImminentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.23
upsAlarmTestInProgressA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.24
upsAlarmReceptacleOffThe receptacle are switch off
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.25
upsAlarmHighSpeedBusFailureA problem on the High Speed Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.26
upsAlarmHighSpeedBusJACRCFailureA CRC problem on the Highspeed Bus JA is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.27
upsAlarmConnectivityBusFailureA problem on the Connectivity Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.28
upsAlarmHighSpeedBusJBCRCFailureA CRC problem on the Highspeed Bus JB is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.29
upsAlarmCurrentSharingThe System detects an high current sharing on the parallel system
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.30
upsAlarmDCRippleThe System detects an high ripple voltage on one DC link
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.6.3.31
upsAlarmMaskASpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS.ro
Unsigned32
.1.3.6.1.4.1.818.1.1.10.6.4
upsTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.7
upsTestIdThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*)rw
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.7.1
upsTestSpinLockA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*)rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.7.2
upsTestResultsSummaryThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.10.7.3
upsTestResultsDetailAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.7.4
upsTestStartTimeThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.7.5
upsTestElapsedTimeThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*)ro
TimeInterval (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.7.6
upsWellKnownTests
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.7.7
upsTestNoTestsInitiatedNo tests have been initiated and no test is in progress.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.7.7.1
upsTestAbortTestInProgressThe test in progress is to be aborted / the test in progress was aborted.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.7.7.2
upsTestGeneralSystemsTestThe manufacturer's standard test of UPS device systems.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.7.7.3
upsTestQuickBatteryTestA test that is sufficient to determine if the battery needs replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.7.7.4
upsTestDeepBatteryCalibrationThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.7.7.5
upsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.8
upsShutdownTypeThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.8.1
upsShutdownAfterDelaySetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*)rw
Integer32 (-1..2147483647) UNITS "seconds"
.1.3.6.1.4.1.818.1.1.10.8.2
upsStartupAfterDelaySetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*)rw
Integer32 (-1..2147483647) UNITS "seconds"
.1.3.6.1.4.1.818.1.1.10.8.3
upsRebootWithDurationSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)rw
Integer32 (-1..300) UNITS "seconds"
.1.3.6.1.4.1.818.1.1.10.8.4
upsAutoRestartSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.8.5
upsReceptaclesNumThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.8.6
upsReceptacleTableA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
SEQUENCE OF UpsReceptacleEntry
.1.3.6.1.4.1.818.1.1.10.8.7
upsReceptacleEntryAn entry containing information applicable to a particular receptacle.
UpsReceptacleEntry
.1.3.6.1.4.1.818.1.1.10.8.7.1
upsReceptacleLineIndexThe receptacle line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.8.7.1.1
upsReceptacleOnOffThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on.rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.8.7.1.2
upsUPSModeThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode)rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.8.8
upsRectifierOnOffThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.8.9
upsBatteryChargeMethodThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.8.10
upsInverterOnOffThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.8.11
upsBypassOnOffThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.8.12
upsLoadSourceThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.8.13
upsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.9
upsConfigInputVoltageThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.10.9.1
upsConfigInputFreqThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.10.9.2
upsConfigOutputVoltageThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.10.9.3
upsConfigOutputFreqThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.10.9.4
upsConfigOutputVAThe magnitude of the nominal Volt-Amp rating.(*)ro
NonNegativeInteger32 UNITS "Volt-Amps"
.1.3.6.1.4.1.818.1.1.10.9.5
upsConfigOutputPowerThe magnitude of the nominal true power rating.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.10.9.6
upsConfigLowBattTimeThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*)rw
NonNegativeInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.10.9.7
upsConfigAudibleStatusThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.9.8
upsConfigLowVoltageTransferPointThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.10.9.9
upsConfigHighVoltageTransferPointThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.10.9.10
upsConfigBatteryCapacityThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.rw
NonNegativeInteger32 UNITS "Amps Hours"
.1.3.6.1.4.1.818.1.1.10.9.11
upsConfigBatteryChargeCurrentThe maximum battery charge current, including external chargers.rw
NonNegativeInteger32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.10.9.12
upsConfigNoLoadShutdownDis- or enable 'no load' shutdown from the contact interface.rw
Enumeration
.1.3.6.1.4.1.818.1.1.10.9.13
upsConfigStartDelayMinimum required autonomy time before the UPS may perform an autorestart.rw
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.10.9.14
upsGetSet
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.10
upsEventGetNextThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.10.1
upsEventGetPreviousThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.10.2
upsEventSetStartingTimeStampThe timestamp which is used as starting point for downloading events from the UPS event bufferrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.3
upsEventRetreiveCurrentTimeStampThe current timestamp is retreived from the UPSro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.4
upsEventTableSizeThe number of entries in the event table. This object indicates the number of rows in the event table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.5
upsEventTableA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..10)): PDU-SET upsSetStartingTimeStamp <time> PDU-SET upsEventGetNext <number> PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize.
SEQUENCE OF UpsEventEntry
.1.3.6.1.4.1.818.1.1.10.10.6
upsEventEntryAn entry containing information applicable to a particular event.
UpsEventEntry
.1.3.6.1.4.1.818.1.1.10.10.6.1
upsEventLineIndexThe event line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.10.6.1.1
upsEventCodeThe event code in numerical format.ro
Integer32
.1.3.6.1.4.1.818.1.1.10.10.6.1.2
upsEventStatusThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.6.1.3
upsEventTimeThe timestamp of the moment the event was generated.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.6.1.4
upsParametersReadThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.10.7
upsParametersWriteThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the first value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.10.8
upsParametersStartAddressThe address which is used as starting point for downloading parameters from the UPSrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.9
upsParameterTableSizeThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.10
upsParameterTableA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..16)): Read sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParametersRead <number> PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue <number> PDU-SET upsParametersWrite <number>
SEQUENCE OF UpsParameterEntry
.1.3.6.1.4.1.818.1.1.10.10.11
upsParameterEntryAn entry containing information applicable to a particular parameter.
UpsParameterEntry
.1.3.6.1.4.1.818.1.1.10.10.11.1
upsParameterLineIndexThe parameter line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.10.10.11.1.1
upsParameterValueThe parameter value in numerical format.rw
Integer32
.1.3.6.1.4.1.818.1.1.10.10.11.1.2
upsStatusThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValuesro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.12
upsMainsStatisticsMBfailCount of main bypass failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.13
upsMainsStatisticsMRfailCount of mains rectifier failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.14
upsMainsStatisticsB2Count of transients on the mains bypass (0..2 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.15
upsMainsStatisticsB5Count of transients on the mains bypass (2..5 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.16
upsMainsStatisticsB10Count of transients on the mains bypass (5..10 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.17
upsMainsStatisticsB200Count of transients on the mains bypass (10..200 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.18
upsMainsStatisticsBypRelBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.19
upsTimegenThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPgenERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps.rw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.10.10.20
upsRequestPermissionAn encrypted code is send to enable use of restricted write objects during a limited period of time.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.10.21
upsEventGetCodeThe code which is used as starting point to downloading the events from the UPS event buffer.rw
Integer32
.1.3.6.1.4.1.818.1.1.10.10.22
upsEventSpinLockA spin lock on the event subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.10.23
upsParameterSpinLockA spin lock on the parameters subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.10.10.24
geUPSTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.11
upsTrapAlarmBatteryBadOne or more batteries have been determined to require replacement.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.1
upsTrapAlarmOnBatteryThe UPS is drawing power from the batteries.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.2
upsTrapAlarmLowBatteryThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.3
upsTrapAlarmDepletedBatteryThe UPS will be unable to sustain the present load when and if the utility power is lost)
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.4
upsTrapAlarmTempBadA temperature is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.5
upsTrapAlarmInputBadAn input condition is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.6
upsTrapAlarmOutputBadAn output condition (other than OutputOverload) is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.7
upsTrapAlarmOutputOverloadThe output load exceeds the UPS output capacity.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.8
upsTrapAlarmOnBypassThe Bypass is presently engaged on the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.9
upsTrapAlarmBypassBadThe Bypass is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.10
upsTrapAlarmOutputOffAsRequestedThe UPS has shutdown as requested, i.e., the output is off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.11
upsTrapAlarmUpsOffAsRequestedThe entire UPS has shutdown as commanded.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.12
upsTrapAlarmChargerFailedAn uncorrected problem has been detected within the UPS charger subsystem.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.13
upsTrapAlarmUpsOutputOffThe output of the UPS is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.14
upsTrapAlarmUpsSystemOffThe UPS system is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.15
upsTrapAlarmFanFailureThe failure of one or more fans in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.16
upsTrapAlarmFuseFailureThe failure of one or more fuses has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.17
upsTrapAlarmGeneralFaultA general fault in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.18
upsTrapAlarmDiagnosticTestFailedThe result of the last diagnostic test indicates a failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.19
upsTrapAlarmCommunicationsLostA problem has been encountered in the communication between the agent and the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.20
upsTrapAlarmAwaitingPowerThe UPS output is off and the UPS is awaiting the return of the input power (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.21
upsTrapAlarmShutdownPendingA upsShutdownAfterDelay countdown is underway.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.22
upsTrapAlarmShutdownImminentThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.23
upsTrapAlarmTestInProgressA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.24
upsTrapAlarmReceptacleOffA receptacle has been switched off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.25
upsTrapAlarmHighspeedBusFailureA problem on the Highspeed Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.26
upsTrapAlarmHighspeedBusJACRCFailureA CRC failure on the Highspeed Bus JA is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.27
upsTrapAlarmConnectivityBusFailureA problem on the Connectivity Bus is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.28
upsTrapAlarmHighspeedBusJBCRCFailureA CRC failure on the Highspeed Bus JB is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.29
upsTrapAlarmCurrentSharingFailureAn high current sharing on the parallel system is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.30
upsTrapAlarmDCRippleFailureAn high ripple voltage on his DC link is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.31
upsTrapAlarmBatteryBadRestoredA Battery bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.33
upsTrapAlarmOnBatteryRestoredThe UPS is drawing power from mains again.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.34
upsTrapAlarmLowBatteryRestoredA Low Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.35
upsTrapAlarmDepletedBatteryRestoredA Depleted Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.36
upsTrapAlarmTempBadRestoredA bad temperature condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.37
upsTrapAlarmInputBadRestoredAn input bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.38
upsTrapAlarmOutputBadRestoredAn output bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.39
upsTrapAlarmOutputOverloadRestoredAn output overload condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.40
upsTrapAlarmOnBypassRestoredAn On Bypass condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.41
upsTrapAlarmBypassBadRestoredA Bypass bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.42
upsTrapAlarmOutputOffAsRequestedRestoredA request shutdown has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.43
upsTrapAlarmUpsOffAsRequestedRestoredA entire UPS command has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.44
upsTrapAlarmChargerFailedRestoredA Charger Failer condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.45
upsTrapAlarmUpsOutputOnThe output of the UPS switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.46
upsTrapAlarmUpsSystemOnThe UPS system is switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.47
upsTrapAlarmFanFailureRestoredA Fan failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.48
upsTrapAlarmFuseFailureRestoredA Fuse failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.49
upsTrapAlarmGeneralFaultRestoredA general fault is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.50
upsTrapAlarmDiagnosticTestFailedRestoredA last diagnostic test indicates a failure is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.51
upsTrapAlarmCommunicationsLostRestoredA problem in the communication between the agent and the UPS is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.52
upsTrapAlarmAwaitingPowerRestoredA awaiting power condition is restored (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.53
upsTrapAlarmShutdownPendingRestoredA upsShutdownAfterDelay countdown is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.54
upsTrapAlarmShutdownImminentRestoredA shutdown imminent condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.55
upsTrapAlarmTestInProgressRestoredThe test is in progress is terminated.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.56
upsTrapAlarmReceptacleOnA receptacle has been switched on.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.57
upsTrapAlarmHighspeedBusRestoredA problem on the Highspeed Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.58
upsTrapAlarmHighspeedBusJACRCRestoredA CRC failure on the Highspeed Bus JA is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.59
upsTrapAlarmConnectivityBusRestoredA problem on the Connectivity Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.60
upsTrapAlarmHighspeedBusJBCRCRestoredA CRC failure on the Highspeed Bus JB is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.61
upsTrapAlarmCurrentSharingRestoredAn high current sharing on the parallel system is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.62
upsTrapAlarmDCRippleRestoredAn high ripple voltage on his DC link is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.63
upsTrapAlarmValueLowA measurement value reached a value below its low-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.129
upsTrapAlarmValueHighA measurement value reached a value higher than its high-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.130
upsTrapAlarmValueLowRestoredA ValueLow alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.133
upsTrapAlarmValueHighRestoredA ValueHigh alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.10.11.134
upsDiagnostic
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.10.12
upsDiagnosticBusJACommunicationStatusBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.10.12.1
upsDiagnosticBusJBCommunicationStatusBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.10.12.2
upsDiagnosticBatteryLifetimeThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.10.12.3
upsDiagnosticFansLifetimeThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.10.12.4
upsDiagnosticDCcapacitorsLifetimeThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.10.12.5
upsDiagnosticACcapacitorsLifetimeThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.10.12.6
upsDiagnosticGlobalServiceCheckThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.10.12.7
geFirstUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11
upsIdentfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.1
upsIdentManufacturerfirstThe name of the UPS manufacturer.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.1.1
upsIdentModelfirstThe UPS Model designation.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.1.2
upsIdentUPSSoftwareVersionfirstThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.1.3
upsIdentAgentSoftwareVersionfirstThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.1.4
upsIdentNamefirstA string identifying the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.1.5
upsIdentAttachedDevicesfirstA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.1.6
upsIdentUPSSerialNumberfirstThe UPS serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.1.7
upsIdentComProtVersionfirstThe IMV communication protocol versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.1.8
upsIdentOperatingTimefirstThe present value of the operating time. total 'on' time since UPS manufacturedro
NonNegativeInteger32 UNITS "seconds"
.1.3.6.1.4.1.818.1.1.11.1.9
upsBatteryfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.2
upsBatteryStatusfirstThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.11.2.1
upsSecondsOnBatteryfirstIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*)ro
Integer32 UNITS "seconds"
.1.3.6.1.4.1.818.1.1.11.2.2
upsEstimatedMinutesRemainingfirstAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*)ro
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.11.2.3
upsEstimatedChargeRemainingfirstAn estimate of the battery charge remaining expressed as a percent of full charge.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.11.2.4
upsBatteryVoltagefirstThe magnitude of the present battery voltage.(*)ro
NonNegativeInteger32 UNITS "0.1 Volt DC"
.1.3.6.1.4.1.818.1.1.11.2.5
upsBatteryCurrentfirstThe present battery current.(*)ro
Integer32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.11.2.6
upsBatteryTemperaturefirstThe ambient temperature at or near the UPS Battery casing.(*)ro
Integer32 UNITS "degrees Centigrade"
.1.3.6.1.4.1.818.1.1.11.2.7
upsBatteryRipplefirstThe present DC link RMS voltage ripple.(*)ro
Integer32 UNITS "0.1 Volt RMS"
.1.3.6.1.4.1.818.1.1.11.2.8
upsInputfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.3
upsInputLineBadsfirstA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*)ro
Counter32
.1.3.6.1.4.1.818.1.1.11.3.1
upsInputNumLinesfirstThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.3.2
upsInputFirstTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
SEQUENCE OF UpsInputFirstEntry
.1.3.6.1.4.1.818.1.1.11.3.3
upsInputFirstEntryAn entry containing information applicable to a particular input line.(*)
UpsInputFirstEntry
.1.3.6.1.4.1.818.1.1.11.3.3.1
upsInputLineIndexfirstThe input line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.3.3.1.1
upsInputFrequencyfirstThe present input frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.11.3.3.1.2
upsInputVoltagefirstThe magnitude of the present input voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.11.3.3.1.3
upsInputCurrentfirstThe magnitude of the present input current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.11.3.3.1.4
upsInputTruePowerfirstThe magnitude of the present input true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.11.3.3.1.5
upsInputVoltageMinfirstThe lowest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.11.3.3.1.6
upsInputVoltageMaxfirstThe highest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.11.3.3.1.7
upsOutputfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.4
upsOutputSourcefirstThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.11.4.1
upsOutputFrequencyfirstThe present output frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.11.4.2
upsOutputNumLinesfirstThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.4.3
upsOutputFirstTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
SEQUENCE OF UpsOutputFirstEntry
.1.3.6.1.4.1.818.1.1.11.4.4
upsOutputFirstEntryAn entry containing information applicable to a particular output line.(*)
UpsOutputFirstEntry
.1.3.6.1.4.1.818.1.1.11.4.4.1
upsOutputLineIndexfirstThe output line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.4.4.1.1
upsOutputVoltagefirstThe present output voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.11.4.4.1.2
upsOutputCurrentfirstThe present output current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.11.4.4.1.3
upsOutputPowerfirstThe present output true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.11.4.4.1.4
upsOutputPercentLoadfirstThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.11.4.4.1.5
upsOutputPowerFactorfirstThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*)ro
Integer32 (-99..100) UNITS "0.01 cos phi"
.1.3.6.1.4.1.818.1.1.11.4.4.1.6
upsOutputPeakCurrentfirstThe present output peak current.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.11.4.4.1.7
upsOutputShareCurrentfirstIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.11.4.4.1.8
upsBypassfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.5
upsBypassFrequencyfirstThe present bypass frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.11.5.1
upsBypassNumLinesfirstThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.5.2
upsBypassFirstTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
SEQUENCE OF UpsBypassFirstEntry
.1.3.6.1.4.1.818.1.1.11.5.3
upsBypassFirstEntryAn entry containing information applicable to a particular bypass input.(*)
UpsBypassFirstEntry
.1.3.6.1.4.1.818.1.1.11.5.3.1
upsBypassLineIndexfirstThe bypass line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.5.3.1.1
upsBypassVoltagefirstThe present bypass voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.11.5.3.1.2
upsBypassCurrentfirstThe present bypass current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.11.5.3.1.3
upsBypassPowerfirstThe present true power conveyed by the bypass.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.11.5.3.1.4
upsAlarmfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6
upsAlarmsPresentfirstThe present number of active alarm conditions.(*)ro
Gauge32
.1.3.6.1.4.1.818.1.1.11.6.1
upsAlarmFirstTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*)
SEQUENCE OF UpsAlarmFirstEntry
.1.3.6.1.4.1.818.1.1.11.6.2
upsAlarmFirstEntryAn entry containing information applicable to a particular alarm.(*)
UpsAlarmFirstEntry
.1.3.6.1.4.1.818.1.1.11.6.2.1
upsAlarmIdfirstA unique identifier for an alarm condition. This value must remain constant.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.6.2.1.1
upsAlarmDescrfirstA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*)ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.6.2.1.2
upsAlarmTimefirstThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.6.2.1.3
upsWellKnownAlarmsfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3
upsAlarmBatteryBadfirstOne or more batteries have been determined to require replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.1
upsAlarmOnBatteryfirstThe UPS is drawing power from the batteries.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.2
upsAlarmLowBatteryfirstThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.3
upsAlarmDepletedBatteryfirstThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.4
upsAlarmTempBadfirstA temperature is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.5
upsAlarmInputBadfirstAn input condition is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.6
upsAlarmOutputBadfirstAn output condition (other than OutputOverload) is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.7
upsAlarmOutputOverloadfirstThe output load exceeds the UPS output capacity.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.8
upsAlarmOnBypassfirstThe Bypass is presently engaged on the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.9
upsAlarmBypassBadfirstThe Bypass is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.10
upsAlarmOutputOffAsRequestedfirstThe UPS has shutdown as requested, i.e., the output is off.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.11
upsAlarmUpsOffAsRequestedfirstThe entire UPS has shutdown as commanded.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.12
upsAlarmChargerFailedfirstAn uncorrected problem has been detected within the UPS charger subsystem.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.13
upsAlarmUpsOutputOfffirstThe output of the UPS is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.14
upsAlarmUpsSystemOfffirstThe UPS system is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.15
upsAlarmFanFailurefirstThe failure of one or more fans in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.16
upsAlarmFuseFailurefirstThe failure of one or more fuses has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.17
upsAlarmGeneralFaultfirstA general fault in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.18
upsAlarmDiagnosticTestFailedfirstThe result of the last diagnostic test indicates a failure.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.19
upsAlarmCommunicationsLostfirstA problem has been encountered in the communications between the agent and the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.20
upsAlarmAwaitingPowerfirstThe UPS output is off and the UPS is awaiting the return of input power.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.21
upsAlarmShutdownPendingfirstA upsShutdownAfterDelay countdown is underway.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.22
upsAlarmShutdownImminentfirstThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.23
upsAlarmTestInProgressfirstA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.24
upsAlarmReceptacleOfffirstThe receptacle are switch off
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.25
upsAlarmHighSpeedBusFailurefirstA problem on the High Speed Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.26
upsAlarmHighSpeedBusJACRCFailurefirstA CRC failure on High Speed Bus JA is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.27
upsAlarmConnectivityBusFailurefirstA problem on the Connectivity Bus communication is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.28
upsAlarmHighSpeedBusJBCRCFailurefirstA CRC failure on High Speed Bus JB is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.29
upsAlarmCurrentSharingfirstThe UPS detects an high current sharing on the parallel system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.30
upsAlarmDCRipplefirstThe UPS detects an high ripple voltage on his DC link.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.6.3.31
upsAlarmMaskAfirstSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS.ro
Unsigned32
.1.3.6.1.4.1.818.1.1.11.6.4
upsTestfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.7
upsTestIdfirstThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*)rw
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.7.1
upsTestSpinLockfirstA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*)rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.7.2
upsTestResultsSummaryfirstThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.11.7.3
upsTestResultsDetailfirstAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.7.4
upsTestStartTimefirstThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.7.5
upsTestElapsedTimefirstThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*)ro
TimeInterval (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.7.6
upsWellKnownTestsfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.7.7
upsTestNoTestsInitiatedfirstNo tests have been initiated and no test is in progress.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.7.7.1
upsTestAbortTestInProgressfirstThe test in progress is to be aborted / the test in progress was aborted.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.7.7.2
upsTestGeneralSystemsTestfirstThe manufacturer's standard test of UPS device systems.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.7.7.3
upsTestQuickBatteryTestfirstA test that is sufficient to determine if the battery needs replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.7.7.4
upsTestDeepBatteryCalibrationfirstThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.7.7.5
upsControlfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.8
upsShutdownTypefirstThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.8.1
upsShutdownAfterDelayfirstSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*)rw
Integer32 (-1..2147483647) UNITS "seconds"
.1.3.6.1.4.1.818.1.1.11.8.2
upsStartupAfterDelayfirstSetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*)rw
Integer32 (-1..2147483647) UNITS "seconds"
.1.3.6.1.4.1.818.1.1.11.8.3
upsRebootWithDurationfirstSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)rw
Integer32 (-1..300) UNITS "seconds"
.1.3.6.1.4.1.818.1.1.11.8.4
upsAutoRestartfirstSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.8.5
upsReceptaclesNumfirstThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.8.6
upsReceptacleFirstTableA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
SEQUENCE OF UpsReceptacleFirstEntry
.1.3.6.1.4.1.818.1.1.11.8.7
upsReceptacleFirstEntryAn entry containing information applicable to a particular receptacle.
UpsReceptacleFirstEntry
.1.3.6.1.4.1.818.1.1.11.8.7.1
upsReceptacleLineIndexfirstThe receptacle line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.8.7.1.1
upsReceptacleOnOfffirstThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on.rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.8.7.1.2
upsUPSModefirstThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode)rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.8.8
upsRectifierOnOfffirstThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.8.9
upsBatteryChargeMethodfirstThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.8.10
upsInverterOnOfffirstThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.8.11
upsBypassOnOfffirstThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.8.12
upsLoadSourcefirstThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.8.13
upsConfigfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.9
upsConfigInputVoltagefirstThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.11.9.1
upsConfigInputFreqfirstThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.11.9.2
upsConfigOutputVoltagefirstThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.11.9.3
upsConfigOutputFreqfirstThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.11.9.4
upsConfigOutputVAfirstThe magnitude of the nominal Volt-Amp rating.(*)ro
NonNegativeInteger32 UNITS "Volt-Amps"
.1.3.6.1.4.1.818.1.1.11.9.5
upsConfigOutputPowerfirstThe magnitude of the nominal true power rating.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.11.9.6
upsConfigLowBattTimefirstThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*)rw
NonNegativeInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.11.9.7
upsConfigAudibleStatusfirstThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.9.8
upsConfigLowVoltageTransferPointfirstThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.11.9.9
upsConfigHighVoltageTransferPointfirstThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.11.9.10
upsConfigBatteryCapacityfirstThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.rw
NonNegativeInteger32 UNITS "Amps Hours"
.1.3.6.1.4.1.818.1.1.11.9.11
upsConfigBatteryChargeCurrentfirstThe maximum battery charge current, including external chargers.rw
NonNegativeInteger32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.11.9.12
upsConfigNoLoadShutdownfirstDis- or enable 'no load' shutdown from the contact interface.rw
Enumeration
.1.3.6.1.4.1.818.1.1.11.9.13
upsConfigStartDelayfirstMinimum required autonomy time before the UPS may perform an autorestart.rw
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.11.9.14
upsGetSetfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.10
upsEventGetNextfirstThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.10.1
upsEventGetPreviousfirstThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.10.2
upsEventSetStartingTimeStampfirstThe timestamp which is used as starting point for downloading events from the UPS event bufferrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.3
upsEventRetreiveCurrentTimeStampfirstThe current timestamp is retreived from the UPSro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.4
upsEventTableSizefirstThe number of entries in the event table. This object indicates the number of rows in the event table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.5
upsEventFirstTableA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..10)): PDU-SET upsSetStartingTimeStamp <time> PDU-SET upsEventGetNext <number> PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize.
SEQUENCE OF UpsEventFirstEntry
.1.3.6.1.4.1.818.1.1.11.10.6
upsEventFirstEntryAn entry containing information applicable to a particular event.
UpsEventFirstEntry
.1.3.6.1.4.1.818.1.1.11.10.6.1
upsEventLineIndexfirstThe event line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.10.6.1.1
upsEventCodefirstThe event code in numerical format.ro
Integer32
.1.3.6.1.4.1.818.1.1.11.10.6.1.2
upsEventStatusfirstThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.6.1.3
upsEventTimefirstThe timestamp of the moment the event was generated.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.6.1.4
upsParametersReadfirstThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.10.7
upsParametersWritefirstThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the first value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.10.8
upsParametersStartAddressfirstThe address which is used as starting point for downloading parameters from the UPSrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.9
upsParameterTableSizefirstThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.10
upsParameterFirstTableA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..16)): Read sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParametersRead <number> PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue <number> PDU-SET upsParametersWrite <number>
SEQUENCE OF UpsParameterFirstEntry
.1.3.6.1.4.1.818.1.1.11.10.11
upsParameterFirstEntryAn entry containing information applicable to a particular parameter.
UpsParameterFirstEntry
.1.3.6.1.4.1.818.1.1.11.10.11.1
upsParameterLineIndexfirstThe parameter line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.11.10.11.1.1
upsParameterValuefirstThe parameter value in numerical format.rw
Integer32
.1.3.6.1.4.1.818.1.1.11.10.11.1.2
upsStatusfirstThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValuesro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.12
upsMainsStatisticsMBfailfirstCount of main bypass failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.13
upsMainsStatisticsMRfailfirstCount of mains rectifier failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.14
upsMainsStatisticsB2firstCount of transients on the mains bypass (0..2 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.15
upsMainsStatisticsB5firstCount of transients on the mains bypass (2..5 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.16
upsMainsStatisticsB10firstCount of transients on the mains bypass (5..10 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.17
upsMainsStatisticsB200firstCount of transients on the mains bypass (10..200 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.18
upsMainsStatisticsBypRelfirstBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.19
upsTimefirstThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPfirstERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps.rw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.11.10.20
upsRequestPermissionfirstAn encrypted code is send to enable use of restricted write objects during a limited period of time.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.10.21
upsEventGetCodefirstThe code which is used as starting point to downloading the events from the UPS event buffer.rw
Integer32
.1.3.6.1.4.1.818.1.1.11.10.22
upsEventSpinLockfirstA spin lock on the event subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.10.23
upsParameterSpinLockfirstA spin lock on the parameters subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.11.10.24
geUPSTrapsfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.11
upsTrapAlarmBatteryBadfirstOne or more batteries have been determined to require replacement.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.1
upsTrapAlarmOnBatteryfirstThe UPS is drawing power from the batteries.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.2
upsTrapAlarmLowBatteryfirstThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.3
upsTrapAlarmDepletedBatteryfirstThe UPS will be unable to sustain the present load when and if the utility power is lost)
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.4
upsTrapAlarmTempBadfirstA temperature is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.5
upsTrapAlarmInputBadfirstAn input condition is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.6
upsTrapAlarmOutputBadfirstAn output condition (other than OutputOverload) is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.7
upsTrapAlarmOutputOverloadfirstThe output load exceeds the UPS output capacity.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.8
upsTrapAlarmOnBypassfirstThe Bypass is presently engaged on the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.9
upsTrapAlarmBypassBadfirstThe Bypass is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.10
upsTrapAlarmOutputOffAsRequestedfirstThe UPS has shutdown as requested, i.e., the output is off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.11
upsTrapAlarmUpsOffAsRequestedfirstThe entire UPS has shutdown as commanded.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.12
upsTrapAlarmChargerFailedfirstAn uncorrected problem has been detected within the UPS charger subsystem.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.13
upsTrapAlarmUpsOutputOfffirstThe output of the UPS is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.14
upsTrapAlarmUpsSystemOfffirstThe UPS system is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.15
upsTrapAlarmFanFailurefirstThe failure of one or more fans in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.16
upsTrapAlarmFuseFailurefirstThe failure of one or more fuses has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.17
upsTrapAlarmGeneralFaultfirstA general fault in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.18
upsTrapAlarmDiagnosticTestFailedfirstThe result of the last diagnostic test indicates a failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.19
upsTrapAlarmCommunicationsLostfirstA problem has been encountered in the communication between the agent and the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.20
upsTrapAlarmAwaitingPowerfirstThe UPS output is off and the UPS is awaiting the return of the input power (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.21
upsTrapAlarmShutdownPendingfirstA upsShutdownAfterDelay countdown is underway.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.22
upsTrapAlarmShutdownImminentfirstThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.23
upsTrapAlarmTestInProgressfirstA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.24
upsTrapAlarmReceptacleOfffirstA receptacle has been switched off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.25
upsTrapAlarmHighspeedBusFailurefirstA problem on the Highspeed Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.26
upsTrapAlarmHighspeedBusJACRCFailurefirstA CRC failure on the Highspeed Bus JB is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.27
upsTrapAlarmConnectivityBusFailurefirstA problem on the Connectivity Bus communication is detected
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.28
upsTrapAlarmHighspeedBusJBCRCFailurefirstA CRC failure on the Highspeed Bus JB is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.29
upsTrapAlarmCurrentSharingFailurefirstAn high current sharing on the parallel system is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.30
upsTrapAlarmDCRippleFailurefirstAn high ripple voltage on his DC link is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.31
upsTrapAlarmBatteryBadRestoredfirstA Battery bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.33
upsTrapAlarmOnBatteryRestoredfirstThe UPS is drawing power from mains again.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.34
upsTrapAlarmLowBatteryRestoredfirstA Low Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.35
upsTrapAlarmDepletedBatteryRestoredfirstA Depleted Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.36
upsTrapAlarmTempBadRestoredfirstA bad temperature condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.37
upsTrapAlarmInputBadRestoredfirstAn input bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.38
upsTrapAlarmOutputBadRestoredfirstAn output bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.39
upsTrapAlarmOutputOverloadRestoredfirstAn output overload condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.40
upsTrapAlarmOnBypassRestoredfirstAn On Bypass condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.41
upsTrapAlarmBypassBadRestoredfirstA Bypass bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.42
upsTrapAlarmOutputOffAsRequestedRestoredfirstA request shutdown has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.43
upsTrapAlarmUpsOffAsRequestedRestoredfirstA entire UPS command has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.44
upsTrapAlarmChargerFailedRestoredfirstA Charger Failer condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.45
upsTrapAlarmUpsOutputOnfirstThe output of the UPS switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.46
upsTrapAlarmUpsSystemOnfirstThe UPS system is switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.47
upsTrapAlarmFanFailureRestoredfirstA Fan failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.48
upsTrapAlarmFuseFailureRestoredfirstA Fuse failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.49
upsTrapAlarmGeneralFaultRestoredfirstA general fault is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.50
upsTrapAlarmDiagnosticTestFailedRestoredfirstA last diagnostic test indicates a failure is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.51
upsTrapAlarmCommunicationsLostRestoredfirstA problem in the communication between the agent and the UPS is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.52
upsTrapAlarmAwaitingPowerRestoredfirstA awaiting power condition is restored (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.53
upsTrapAlarmShutdownPendingRestoredfirstA upsShutdownAfterDelay countdown is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.54
upsTrapAlarmShutdownImminentRestoredfirstA shutdown imminent condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.55
upsTrapAlarmTestInProgressRestoredfirstThe test is in progress is terminated.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.56
upsTrapAlarmReceptacleOnfirstA receptacle has been switched on.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.57
upsTrapAlarmHighspeedBusRestoredfirstA problem on the Highspeed Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.58
upsTrapAlarmHighspeedBusJACRCRestoredfirstA CRC failure on the Highspeed Bus JA is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.59
upsTrapAlarmConnectivityBusRestoredfirstA problem on the Connectivity Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.60
upsTrapAlarmHighspeedBusJBCRCRestoredfirstA CRC failure on the Highspeed Bus JB is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.61
upsTrapAlarmCurrentSharingRestoredfirstAn high current sharing on the parallel system is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.62
upsTrapAlarmDCRippleRestoredfirstAn high ripple voltage on his DC link is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.63
upsTrapAlarmValueLowfirstA measurement value reached a value below its low-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.129
upsTrapAlarmValueHighfirstA measurement value reached a value higher than its high-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.130
upsTrapAlarmValueLowRestoredfirstA ValueLow alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.133
upsTrapAlarmValueHighRestoredfirstA ValueHigh alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.11.11.134
upsDiagnosticfirst
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.11.12
upsDiagnosticBusJACommunicationStatusfirstBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.11.12.1
upsDiagnosticBusJBCommunicationStatusfirstBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.11.12.2
upsDiagnosticBatteryLifetimefirstThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.11.12.3
upsDiagnosticFansLifetimefirstThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.11.12.4
upsDiagnosticDCcapacitorsLifetimefirstThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.11.12.5
upsDiagnosticACcapacitorsLifetimefirstThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.11.12.6
upsDiagnosticGlobalServiceCheckfirstThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.11.12.7
geSecondUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12
upsIdentsecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.1
upsIdentManufacturersecondThe name of the UPS manufacturer.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.1.1
upsIdentModelsecondThe UPS Model designation.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.1.2
upsIdentUPSSoftwareVersionsecondThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.1.3
upsIdentAgentSoftwareVersionsecondThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.1.4
upsIdentNamesecondA string identifying the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.1.5
upsIdentAttachedDevicessecondA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.1.6
upsIdentUPSSerialNumbersecondThe UPS serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.1.7
upsIdentComProtVersionsecondThe IMV communication protocol versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.1.8
upsIdentOperatingTimesecondThe present value of the operating time. total 'on' time since UPS manufacturedro
NonNegativeInteger32 UNITS "seconds"
.1.3.6.1.4.1.818.1.1.12.1.9
upsBatterysecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.2
upsBatteryStatussecondThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.12.2.1
upsSecondsOnBatterysecondIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*)ro
Integer32 UNITS "seconds"
.1.3.6.1.4.1.818.1.1.12.2.2
upsEstimatedMinutesRemainingsecondAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*)ro
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.12.2.3
upsEstimatedChargeRemainingsecondAn estimate of the battery charge remaining expressed as a percent of full charge.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.12.2.4
upsBatteryVoltagesecondThe magnitude of the present battery voltage.(*)ro
NonNegativeInteger32 UNITS "0.1 Volt DC"
.1.3.6.1.4.1.818.1.1.12.2.5
upsBatteryCurrentsecondThe present battery current.(*)ro
Integer32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.12.2.6
upsBatteryTemperaturesecondThe ambient temperature at or near the UPS Battery casing.(*)ro
Integer32 UNITS "degrees Centigrade"
.1.3.6.1.4.1.818.1.1.12.2.7
upsBatteryRipplesecondThe present DC link RMS voltage ripple.(*)ro
Integer32 UNITS "0.1 Volt RMS"
.1.3.6.1.4.1.818.1.1.12.2.8
upsInputsecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.3
upsInputLineBadssecondA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*)ro
Counter32
.1.3.6.1.4.1.818.1.1.12.3.1
upsInputNumLinessecondThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.3.2
upsInputSecondTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
SEQUENCE OF UpsInputSecondEntry
.1.3.6.1.4.1.818.1.1.12.3.3
upsInputSecondEntryAn entry containing information applicable to a particular input line.(*)
UpsInputSecondEntry
.1.3.6.1.4.1.818.1.1.12.3.3.1
upsInputLineIndexsecondThe input line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.3.3.1.1
upsInputFrequencysecondThe present input frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.12.3.3.1.2
upsInputVoltagesecondThe magnitude of the present input voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.12.3.3.1.3
upsInputCurrentsecondThe magnitude of the present input current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.12.3.3.1.4
upsInputTruePowersecondThe magnitude of the present input true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.12.3.3.1.5
upsInputVoltageMinsecondThe lowest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.12.3.3.1.6
upsInputVoltageMaxsecondThe highest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.12.3.3.1.7
upsOutputsecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.4
upsOutputSourcesecondThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.12.4.1
upsOutputFrequencysecondThe present output frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.12.4.2
upsOutputNumLinessecondThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.4.3
upsOutputSecondTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
SEQUENCE OF UpsOutputSecondEntry
.1.3.6.1.4.1.818.1.1.12.4.4
upsOutputSecondEntryAn entry containing information applicable to a particular output line.(*)
UpsOutputSecondEntry
.1.3.6.1.4.1.818.1.1.12.4.4.1
upsOutputLineIndexsecondThe output line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.4.4.1.1
upsOutputVoltagesecondThe present output voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.12.4.4.1.2
upsOutputCurrentsecondThe present output current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.12.4.4.1.3
upsOutputPowersecondThe present output true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.12.4.4.1.4
upsOutputPercentLoadsecondThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.12.4.4.1.5
upsOutputPowerFactorsecondThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*)ro
Integer32 (-99..100) UNITS "0.01 cos phi"
.1.3.6.1.4.1.818.1.1.12.4.4.1.6
upsOutputPeakCurrentsecondThe present output peak current.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.12.4.4.1.7
upsOutputShareCurrentsecondIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.12.4.4.1.8
upsBypasssecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.5
upsBypassFrequencysecondThe present bypass frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.12.5.1
upsBypassNumLinessecondThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.5.2
upsBypassSecondTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
SEQUENCE OF UpsBypassSecondEntry
.1.3.6.1.4.1.818.1.1.12.5.3
upsBypassSecondEntryAn entry containing information applicable to a particular bypass input.(*)
UpsBypassSecondEntry
.1.3.6.1.4.1.818.1.1.12.5.3.1
upsBypassLineIndexsecondThe bypass line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.5.3.1.1
upsBypassVoltagesecondThe present bypass voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.12.5.3.1.2
upsBypassCurrentsecondThe present bypass current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.12.5.3.1.3
upsBypassPowersecondThe present true power conveyed by the bypass.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.12.5.3.1.4
upsAlarmsecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6
upsAlarmsPresentsecondThe present number of active alarm conditions.(*)ro
Gauge32
.1.3.6.1.4.1.818.1.1.12.6.1
upsAlarmSecondTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*)
SEQUENCE OF UpsAlarmSecondEntry
.1.3.6.1.4.1.818.1.1.12.6.2
upsAlarmSecondEntryAn entry containing information applicable to a particular alarm.(*)
UpsAlarmSecondEntry
.1.3.6.1.4.1.818.1.1.12.6.2.1
upsAlarmIdsecondA unique identifier for an alarm condition. This value must remain constant.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.6.2.1.1
upsAlarmDescrsecondA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*)ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.6.2.1.2
upsAlarmTimesecondThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.6.2.1.3
upsWellKnownAlarmssecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3
upsAlarmBatteryBadsecondOne or more batteries have been determined to require replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.1
upsAlarmOnBatterysecondThe UPS is drawing power from the batteries.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.2
upsAlarmLowBatterysecondThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.3
upsAlarmDepletedBatterysecondThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.4
upsAlarmTempBadsecondA temperature is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.5
upsAlarmInputBadsecondAn input condition is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.6
upsAlarmOutputBadsecondAn output condition (other than OutputOverload) is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.7
upsAlarmOutputOverloadsecondThe output load exceeds the UPS output capacity.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.8
upsAlarmOnBypasssecondThe Bypass is presently engaged on the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.9
upsAlarmBypassBadsecondThe Bypass is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.10
upsAlarmOutputOffAsRequestedsecondThe UPS has shutdown as requested, i.e., the output is off.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.11
upsAlarmUpsOffAsRequestedsecondThe entire UPS has shutdown as commanded.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.12
upsAlarmChargerFailedsecondAn uncorrected problem has been detected within the UPS charger subsystem.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.13
upsAlarmUpsOutputOffsecondThe output of the UPS is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.14
upsAlarmUpsSystemOffsecondThe UPS system is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.15
upsAlarmFanFailuresecondThe failure of one or more fans in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.16
upsAlarmFuseFailuresecondThe failure of one or more fuses has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.17
upsAlarmGeneralFaultsecondA general fault in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.18
upsAlarmDiagnosticTestFailedsecondThe result of the last diagnostic test indicates a failure.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.19
upsAlarmCommunicationsLostsecondA problem has been encountered in the communications between the agent and the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.20
upsAlarmAwaitingPowersecondThe UPS output is off and the UPS is awaiting the return of input power.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.21
upsAlarmShutdownPendingsecondA upsShutdownAfterDelay countdown is underway.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.22
upsAlarmShutdownImminentsecondThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.23
upsAlarmTestInProgresssecondA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.24
upsAlarmReceptacleOffsecondThe receptacle are switch off
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.25
upsAlarmHighSpeedBusFailuresecondA problem on the High Speed Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.26
upsAlarmHighSpeedBusJACRCFailuresecondA High Speed Bus CRC failure on Bus JB is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.27
upsAlarmConnectivityBusFailuresecondA problem on the Connectivity Bus communication is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.28
upsAlarmHighSpeedBusJBCRCFailuresecondA High Speed Bus CRC failure on Bus JB is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.29
upsAlarmCurrentSharingsecondThe UPS detects an high current sharing on the parallel system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.30
upsAlarmDCRipplesecondThe UPS detects an high ripple voltage on his DC link.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.6.3.31
upsAlarmMaskAsecondSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS.ro
Unsigned32
.1.3.6.1.4.1.818.1.1.12.6.4
upsTestsecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.7
upsTestIdsecondThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*)rw
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.7.1
upsTestSpinLocksecondA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*)rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.7.2
upsTestResultsSummarysecondThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.12.7.3
upsTestResultsDetailsecondAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.7.4
upsTestStartTimesecondThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.7.5
upsTestElapsedTimesecondThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*)ro
TimeInterval (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.7.6
upsWellKnownTestssecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.7.7
upsTestNoTestsInitiatedsecondNo tests have been initiated and no test is in progress.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.7.7.1
upsTestAbortTestInProgresssecondThe test in progress is to be aborted / the test in progress was aborted.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.7.7.2
upsTestGeneralSystemsTestsecondThe manufacturer's standard test of UPS device systems.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.7.7.3
upsTestQuickBatteryTestsecondA test that is sufficient to determine if the battery needs replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.7.7.4
upsTestDeepBatteryCalibrationsecondThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.7.7.5
upsControlsecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.8
upsShutdownTypesecondThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.8.1
upsShutdownAfterDelaysecondSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*)rw
Integer32 (-1..2147483647) UNITS "seconds"
.1.3.6.1.4.1.818.1.1.12.8.2
upsStartupAfterDelaysecondSetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*)rw
Integer32 (-1..2147483647) UNITS "seconds"
.1.3.6.1.4.1.818.1.1.12.8.3
upsRebootWithDurationsecondSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)rw
Integer32 (-1..300) UNITS "seconds"
.1.3.6.1.4.1.818.1.1.12.8.4
upsAutoRestartsecondSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.8.5
upsReceptaclesNumsecondThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.8.6
upsReceptacleSecondTableA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
SEQUENCE OF UpsReceptacleSecondEntry
.1.3.6.1.4.1.818.1.1.12.8.7
upsReceptacleSecondEntryAn entry containing information applicable to a particular receptacle.
UpsReceptacleSecondEntry
.1.3.6.1.4.1.818.1.1.12.8.7.1
upsReceptacleLineIndexsecondThe receptacle line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.8.7.1.1
upsReceptacleOnOffsecondThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on.rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.8.7.1.2
upsUPSModesecondThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode)rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.8.8
upsRectifierOnOffsecondThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.8.9
upsBatteryChargeMethodsecondThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.8.10
upsInverterOnOffsecondThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.8.11
upsBypassOnOffsecondThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.8.12
upsLoadSourcesecondThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.8.13
upsConfigsecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.9
upsConfigInputVoltagesecondThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.12.9.1
upsConfigInputFreqsecondThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.12.9.2
upsConfigOutputVoltagesecondThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.12.9.3
upsConfigOutputFreqsecondThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.12.9.4
upsConfigOutputVAsecondThe magnitude of the nominal Volt-Amp rating.(*)ro
NonNegativeInteger32 UNITS "Volt-Amps"
.1.3.6.1.4.1.818.1.1.12.9.5
upsConfigOutputPowersecondThe magnitude of the nominal true power rating.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.12.9.6
upsConfigLowBattTimesecondThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*)rw
NonNegativeInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.12.9.7
upsConfigAudibleStatussecondThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.9.8
upsConfigLowVoltageTransferPointsecondThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.12.9.9
upsConfigHighVoltageTransferPointsecondThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.12.9.10
upsConfigBatteryCapacitysecondThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.rw
NonNegativeInteger32 UNITS "Amps Hours"
.1.3.6.1.4.1.818.1.1.12.9.11
upsConfigBatteryChargeCurrentsecondThe maximum battery charge current, including external chargers.rw
NonNegativeInteger32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.12.9.12
upsConfigNoLoadShutdownsecondDis- or enable 'no load' shutdown from the contact interface.rw
Enumeration
.1.3.6.1.4.1.818.1.1.12.9.13
upsConfigStartDelaysecondMinimum required autonomy time before the UPS may perform an autorestart.rw
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.12.9.14
upsGetSetsecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.10
upsEventGetNextsecondThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.10.1
upsEventGetPrevioussecondThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.10.2
upsEventSetStartingTimeStampsecondThe timestamp which is used as starting point for downloading events from the UPS event bufferrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.3
upsEventRetreiveCurrentTimeStampsecondThe current timestamp is retreived from the UPSro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.4
upsEventTableSizesecondThe number of entries in the event table. This object indicates the number of rows in the event table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.5
upsEventSecondTableA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..10)): PDU-SET upsSetStartingTimeStamp <time> PDU-SET upsEventGetNext <number> PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize.
SEQUENCE OF UpsEventSecondEntry
.1.3.6.1.4.1.818.1.1.12.10.6
upsEventSecondEntryAn entry containing information applicable to a particular event.
UpsEventSecondEntry
.1.3.6.1.4.1.818.1.1.12.10.6.1
upsEventLineIndexsecondThe event line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.10.6.1.1
upsEventCodesecondThe event code in numerical format.ro
Integer32
.1.3.6.1.4.1.818.1.1.12.10.6.1.2
upsEventStatussecondThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.6.1.3
upsEventTimesecondThe timestamp of the moment the event was generated.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.6.1.4
upsParametersReadsecondThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.10.7
upsParametersWritesecondThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the second value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.10.8
upsParametersStartAddresssecondThe address which is used as starting point for downloading parameters from the UPSrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.9
upsParameterTableSizesecondThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.10
upsParameterSecondTableA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..16)): Read sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParametersRead <number> PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue <number> PDU-SET upsParametersWrite <number>
SEQUENCE OF UpsParameterSecondEntry
.1.3.6.1.4.1.818.1.1.12.10.11
upsParameterSecondEntryAn entry containing information applicable to a particular parameter.
UpsParameterSecondEntry
.1.3.6.1.4.1.818.1.1.12.10.11.1
upsParameterLineIndexsecondThe parameter line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.12.10.11.1.1
upsParameterValuesecondThe parameter value in numerical format.rw
Integer32
.1.3.6.1.4.1.818.1.1.12.10.11.1.2
upsStatussecondThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValuesro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.12
upsMainsStatisticsMBfailsecondCount of main bypass failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.13
upsMainsStatisticsMRfailsecondCount of mains rectifier failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.14
upsMainsStatisticsB2secondCount of transients on the mains bypass (0..2 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.15
upsMainsStatisticsB5secondCount of transients on the mains bypass (2..5 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.16
upsMainsStatisticsB10secondCount of transients on the mains bypass (5..10 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.17
upsMainsStatisticsB200secondCount of transients on the mains bypass (10..200 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.18
upsMainsStatisticsBypRelsecondBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.19
upsTimesecondThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPsecondERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps.rw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.12.10.20
upsRequestPermissionsecondAn encrypted code is send to enable use of restricted write objects during a limited period of time.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.10.21
upsEventGetCodesecondThe code which is used as starting point to downloading the events from the UPS event buffer.rw
Integer32
.1.3.6.1.4.1.818.1.1.12.10.22
upsEventSpinLocksecondA spin lock on the event subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.10.23
upsParameterSpinLocksecondA spin lock on the parameters subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.12.10.24
geUPSTrapssecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.11
upsTrapAlarmBatteryBadsecondOne or more batteries have been determined to require replacement.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.1
upsTrapAlarmOnBatterysecondThe UPS is drawing power from the batteries.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.2
upsTrapAlarmLowBatterysecondThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.3
upsTrapAlarmDepletedBatterysecondThe UPS will be unable to sustain the present load when and if the utility power is lost)
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.4
upsTrapAlarmTempBadsecondA temperature is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.5
upsTrapAlarmInputBadsecondAn input condition is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.6
upsTrapAlarmOutputBadsecondAn output condition (other than OutputOverload) is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.7
upsTrapAlarmOutputOverloadsecondThe output load exceeds the UPS output capacity.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.8
upsTrapAlarmOnBypasssecondThe Bypass is presently engaged on the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.9
upsTrapAlarmBypassBadsecondThe Bypass is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.10
upsTrapAlarmOutputOffAsRequestedsecondThe UPS has shutdown as requested, i.e., the output is off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.11
upsTrapAlarmUpsOffAsRequestedsecondThe entire UPS has shutdown as commanded.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.12
upsTrapAlarmChargerFailedsecondAn uncorrected problem has been detected within the UPS charger subsystem.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.13
upsTrapAlarmUpsOutputOffsecondThe output of the UPS is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.14
upsTrapAlarmUpsSystemOffsecondThe UPS system is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.15
upsTrapAlarmFanFailuresecondThe failure of one or more fans in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.16
upsTrapAlarmFuseFailuresecondThe failure of one or more fuses has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.17
upsTrapAlarmGeneralFaultsecondA general fault in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.18
upsTrapAlarmDiagnosticTestFailedsecondThe result of the last diagnostic test indicates a failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.19
upsTrapAlarmCommunicationsLostsecondA problem has been encountered in the communication between the agent and the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.20
upsTrapAlarmAwaitingPowersecondThe UPS output is off and the UPS is awaiting the return of the input power (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.21
upsTrapAlarmShutdownPendingsecondA upsShutdownAfterDelay countdown is underway.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.22
upsTrapAlarmShutdownImminentsecondThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.23
upsTrapAlarmTestInProgresssecondA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.24
upsTrapAlarmReceptacleOffsecondA receptacle has been switched off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.25
upsTrapAlarmHighspeedBusFailuresecondA problem on the Highspeed Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.26
upsTrapAlarmHighspeedBusJACRCFailuresecondA CRC failure on the Highspeed Bus JA is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.27
upsTrapAlarmConnectivityBusFailuresecondA problem on the Connectivity Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.28
upsTrapAlarmHighspeedBusJBCRCFailuresecondA CRC failure on the Highspeed Bus JB is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.29
upsTrapAlarmCurrentSharingFailuresecondAn high current sharing on the parallel system is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.30
upsTrapAlarmDCRippleFailuresecondAn high ripple voltage on his DC link is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.31
upsTrapAlarmBatteryBadRestoredsecondA Battery bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.33
upsTrapAlarmOnBatteryRestoredsecondThe UPS is drawing power from mains again.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.34
upsTrapAlarmLowBatteryRestoredsecondA Low Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.35
upsTrapAlarmDepletedBatteryRestoredsecondA Depleted Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.36
upsTrapAlarmTempBadRestoredsecondA bad temperature condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.37
upsTrapAlarmInputBadRestoredsecondAn input bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.38
upsTrapAlarmOutputBadRestoredsecondAn output bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.39
upsTrapAlarmOutputOverloadRestoredsecondAn output overload condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.40
upsTrapAlarmOnBypassRestoredsecondAn On Bypass condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.41
upsTrapAlarmBypassBadRestoredsecondA Bypass bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.42
upsTrapAlarmOutputOffAsRequestedRestoredsecondA request shutdown has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.43
upsTrapAlarmUpsOffAsRequestedRestoredsecondA entire UPS command has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.44
upsTrapAlarmChargerFailedRestoredsecondA Charger Failer condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.45
upsTrapAlarmUpsOutputOnsecondThe output of the UPS switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.46
upsTrapAlarmUpsSystemOnsecondThe UPS system is switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.47
upsTrapAlarmFanFailureRestoredsecondA Fan failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.48
upsTrapAlarmFuseFailureRestoredsecondA Fuse failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.49
upsTrapAlarmGeneralFaultRestoredsecondA general fault is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.50
upsTrapAlarmDiagnosticTestFailedRestoredsecondA last diagnostic test indicates a failure is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.51
upsTrapAlarmCommunicationsLostRestoredsecondA problem in the communication between the agent and the UPS is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.52
upsTrapAlarmAwaitingPowerRestoredsecondA awaiting power condition is restored (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.53
upsTrapAlarmShutdownPendingRestoredsecondA upsShutdownAfterDelay countdown is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.54
upsTrapAlarmShutdownImminentRestoredsecondA shutdown imminent condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.55
upsTrapAlarmTestInProgressRestoredsecondThe test is in progress is terminated.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.56
upsTrapAlarmReceptacleOnsecondA receptacle has been switched on.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.57
upsTrapAlarmHighspeedBusRestoredsecondA problem on the Highspeed Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.58
upsTrapAlarmHighspeedBusJACRCRestoredsecondA CRC failure on the Highspeed Bus JA is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.59
upsTrapAlarmConnectivityBusRestoredsecondA problem on the Connectivity Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.60
upsTrapAlarmHighspeedBusJBCRCRestoredsecondA CRC failure on the Highspeed Bus JB is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.61
upsTrapAlarmCurrentSharingRestoredsecondAn high current sharing on the parallel system is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.62
upsTrapAlarmDCRippleRestoredsecondAn high ripple voltage on his DC link is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.63
upsTrapAlarmValueLowsecondA measurement value reached a value below its low-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.129
upsTrapAlarmValueHighsecondA measurement value reached a value higher than its high-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.130
upsTrapAlarmValueLowRestoredsecondA ValueLow alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.133
upsTrapAlarmValueHighRestoredsecondA ValueHigh alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.12.11.134
upsDiagnosticsecond
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.12.12
upsDiagnosticBusJACommunicationStatussecondBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.12.12.1
upsDiagnosticBusJBCommunicationStatussecondBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.12.12.2
upsDiagnosticBatteryLifetimesecondThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.12.12.3
upsDiagnosticFansLifetimesecondThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.12.12.4
upsDiagnosticDCcapacitorsLifetimesecondThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.12.12.5
upsDiagnosticACcapacitorsLifetimesecondThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.12.12.6
upsDiagnosticGlobalServiceChecksecondThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.12.12.7
geThirdUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13
upsIdentthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.1
upsIdentManufacturerthirdThe name of the UPS manufacturer.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.1.1
upsIdentModelthirdThe UPS Model designation.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.1.2
upsIdentUPSSoftwareVersionthirdThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.1.3
upsIdentAgentSoftwareVersionthirdThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.1.4
upsIdentNamethirdA string identifying the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.1.5
upsIdentAttachedDevicesthirdA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.1.6
upsIdentUPSSerialNumberthirdThe UPS serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.1.7
upsIdentComProtVersionthirdThe IMV communication protocol versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.1.8
upsIdentOperatingTimethirdThe present value of the operating time. total 'on' time since UPS manufacturedro
NonNegativeInteger32 UNITS "Seconds"
.1.3.6.1.4.1.818.1.1.13.1.9
upsBatterythird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.2
upsBatteryStatusthirdThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.13.2.1
upsSecondsOnBatterythirdIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*)ro
Integer32 UNITS "Seconds"
.1.3.6.1.4.1.818.1.1.13.2.2
upsEstimatedMinutesRemainingthirdAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*)ro
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.13.2.3
upsEstimatedChargeRemainingthirdAn estimate of the battery charge remaining expressed as a percent of full charge.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.13.2.4
upsBatteryVoltagethirdThe magnitude of the present battery voltage.(*)ro
NonNegativeInteger32 UNITS "0.1 Volt DC"
.1.3.6.1.4.1.818.1.1.13.2.5
upsBatteryCurrentthirdThe present battery current.(*)ro
Integer32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.13.2.6
upsBatteryTemperaturethirdThe ambient temperature at or near the UPS Battery casing.(*)ro
Integer32 UNITS "degrees Centigrade"
.1.3.6.1.4.1.818.1.1.13.2.7
upsBatteryRipplethirdThe present DC link RMS voltage ripple.(*)ro
Integer32 UNITS "0.1 Volt RMS"
.1.3.6.1.4.1.818.1.1.13.2.8
upsInputthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.3
upsInputLineBadsthirdA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*)ro
Counter32
.1.3.6.1.4.1.818.1.1.13.3.1
upsInputNumLinesthirdThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.3.2
upsInputThirdTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
SEQUENCE OF UpsInputThirdEntry
.1.3.6.1.4.1.818.1.1.13.3.3
upsInputThirdEntryAn entry containing information applicable to a particular input line.(*)
UpsInputThirdEntry
.1.3.6.1.4.1.818.1.1.13.3.3.1
upsInputLineIndexthirdThe input line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.3.3.1.1
upsInputFrequencythirdThe present input frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.13.3.3.1.2
upsInputVoltagethirdThe magnitude of the present input voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.13.3.3.1.3
upsInputCurrentthirdThe magnitude of the present input current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.13.3.3.1.4
upsInputTruePowerthirdThe magnitude of the present input true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.13.3.3.1.5
upsInputVoltageMinthirdThe lowest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.13.3.3.1.6
upsInputVoltageMaxthirdThe highest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.13.3.3.1.7
upsOutputthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.4
upsOutputSourcethirdThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.13.4.1
upsOutputFrequencythirdThe present output frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.13.4.2
upsOutputNumLinesthirdThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.4.3
upsOutputThirdTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
SEQUENCE OF UpsOutputThirdEntry
.1.3.6.1.4.1.818.1.1.13.4.4
upsOutputThirdEntryAn entry containing information applicable to a particular output line.(*)
UpsOutputThirdEntry
.1.3.6.1.4.1.818.1.1.13.4.4.1
upsOutputLineIndexthirdThe output line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.4.4.1.1
upsOutputVoltagethirdThe present output voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.13.4.4.1.2
upsOutputCurrentthirdThe present output current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.13.4.4.1.3
upsOutputPowerthirdThe present output true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.13.4.4.1.4
upsOutputPercentLoadthirdThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.13.4.4.1.5
upsOutputPowerFactorthirdThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*)ro
Integer32 (-99..100) UNITS "0.01 cos phi"
.1.3.6.1.4.1.818.1.1.13.4.4.1.6
upsOutputPeakCurrentthirdThe present output peak current.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.13.4.4.1.7
upsOutputShareCurrentthirdIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.13.4.4.1.8
upsBypassthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.5
upsBypassFrequencythirdThe present bypass frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.13.5.1
upsBypassNumLinesthirdThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.5.2
upsBypassThirdTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
SEQUENCE OF UpsBypassThirdEntry
.1.3.6.1.4.1.818.1.1.13.5.3
upsBypassThirdEntryAn entry containing information applicable to a particular bypass input.(*)
UpsBypassThirdEntry
.1.3.6.1.4.1.818.1.1.13.5.3.1
upsBypassLineIndexthirdThe bypass line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.5.3.1.1
upsBypassVoltagethirdThe present bypass voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.13.5.3.1.2
upsBypassCurrentthirdThe present bypass current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.13.5.3.1.3
upsBypassPowerthirdThe present true power conveyed by the bypass.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.13.5.3.1.4
upsAlarmthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6
upsAlarmsPresentthirdThe present number of active alarm conditions.(*)ro
Gauge32
.1.3.6.1.4.1.818.1.1.13.6.1
upsAlarmThirdTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*)
SEQUENCE OF UpsAlarmThirdEntry
.1.3.6.1.4.1.818.1.1.13.6.2
upsAlarmThirdEntryAn entry containing information applicable to a particular alarm.(*)
UpsAlarmThirdEntry
.1.3.6.1.4.1.818.1.1.13.6.2.1
upsAlarmIdthirdA unique identifier for an alarm condition. This value must remain constant.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.6.2.1.1
upsAlarmDescrthirdA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*)ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.6.2.1.2
upsAlarmTimethirdThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.6.2.1.3
upsWellKnownAlarmsthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3
upsAlarmBatteryBadthirdOne or more batteries have been determined to require replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.1
upsAlarmOnBatterythirdThe UPS is drawing power from the batteries.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.2
upsAlarmLowBatterythirdThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.3
upsAlarmDepletedBatterythirdThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.4
upsAlarmTempBadthirdA temperature is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.5
upsAlarmInputBadthirdAn input condition is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.6
upsAlarmOutputBadthirdAn output condition (other than OutputOverload) is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.7
upsAlarmOutputOverloadthirdThe output load exceeds the UPS output capacity.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.8
upsAlarmOnBypassthirdThe Bypass is presently engaged on the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.9
upsAlarmBypassBadthirdThe Bypass is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.10
upsAlarmOutputOffAsRequestedthirdThe UPS has shutdown as requested, i.e., the output is off.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.11
upsAlarmUpsOffAsRequestedthirdThe entire UPS has shutdown as commanded.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.12
upsAlarmChargerFailedthirdAn uncorrected problem has been detected within the UPS charger subsystem.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.13
upsAlarmUpsOutputOffthirdThe output of the UPS is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.14
upsAlarmUpsSystemOffthirdThe UPS system is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.15
upsAlarmFanFailurethirdThe failure of one or more fans in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.16
upsAlarmFuseFailurethirdThe failure of one or more fuses has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.17
upsAlarmGeneralFaultthirdA general fault in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.18
upsAlarmDiagnosticTestFailedthirdThe result of the last diagnostic test indicates a failure.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.19
upsAlarmCommunicationsLostthirdA problem has been encountered in the communications between the agent and the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.20
upsAlarmAwaitingPowerthirdThe UPS output is off and the UPS is awaiting the return of input power.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.21
upsAlarmShutdownPendingthirdA upsShutdownAfterDelay countdown is underway.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.22
upsAlarmShutdownImminentthirdThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.23
upsAlarmTestInProgressthirdA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.24
upsAlarmReceptacleOffthirdThe receptacle are switch off
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.25
upsAlarmHighSpeedBusFailurethirdA problem on the High Speed Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.26
upsAlarmHighSpeedBusJACRCFailurethirdA High Speed Bus CRC failure on Bus JA is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.27
upsAlarmConnectivityBusFailurethirdA problem on the Connectivity Bus communication is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.28
upsAlarmHighSpeedBusJBCRCFailurethirdA High Speed Bus CRC failure on Bus JB is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.29
upsAlarmCurrentSharingthirdThe UPS detects an high current sharing on the parallel system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.30
upsAlarmDCRipplethirdThe UPS detects an high ripple voltage on his DC link.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.6.3.31
upsAlarmMaskAthirdSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS.ro
Unsigned32
.1.3.6.1.4.1.818.1.1.13.6.4
upsTestthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.7
upsTestIdthirdThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*)rw
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.7.1
upsTestSpinLockthirdA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*)rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.7.2
upsTestResultsSummarythirdThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.13.7.3
upsTestResultsDetailthirdAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.7.4
upsTestStartTimethirdThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.7.5
upsTestElapsedTimethirdThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*)ro
TimeInterval (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.7.6
upsWellKnownTeststhird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.7.7
upsTestNoTestsInitiatedthirdNo tests have been initiated and no test is in progress.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.7.7.1
upsTestAbortTestInProgressthirdThe test in progress is to be aborted / the test in progress was aborted.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.7.7.2
upsTestGeneralSystemsTestthirdThe manufacturer's standard test of UPS device systems.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.7.7.3
upsTestQuickBatteryTestthirdA test that is sufficient to determine if the battery needs replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.7.7.4
upsTestDeepBatteryCalibrationthirdThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.7.7.5
upsControlthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.8
upsShutdownTypethirdThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.8.1
upsShutdownAfterDelaythirdSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of Seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*)rw
Integer32 (-1..2147483647) UNITS "Seconds"
.1.3.6.1.4.1.818.1.1.13.8.2
upsStartupAfterDelaythirdSetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*)rw
Integer32 (-1..2147483647) UNITS "Seconds"
.1.3.6.1.4.1.818.1.1.13.8.3
upsRebootWithDurationthirdSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)rw
Integer32 (-1..300) UNITS "Seconds"
.1.3.6.1.4.1.818.1.1.13.8.4
upsAutoRestartthirdSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.8.5
upsReceptaclesNumthirdThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.8.6
upsReceptacleThirdTableA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
SEQUENCE OF UpsReceptacleThirdEntry
.1.3.6.1.4.1.818.1.1.13.8.7
upsReceptacleThirdEntryAn entry containing information applicable to a particular receptacle.
UpsReceptacleThirdEntry
.1.3.6.1.4.1.818.1.1.13.8.7.1
upsReceptacleLineIndexthirdThe receptacle line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.8.7.1.1
upsReceptacleOnOffthirdThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on.rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.8.7.1.2
upsUPSModethirdThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode)rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.8.8
upsRectifierOnOffthirdThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.8.9
upsBatteryChargeMethodthirdThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.8.10
upsInverterOnOffthirdThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.8.11
upsBypassOnOffthirdThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.8.12
upsLoadSourcethirdThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.8.13
upsConfigthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.9
upsConfigInputVoltagethirdThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.13.9.1
upsConfigInputFreqthirdThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.13.9.2
upsConfigOutputVoltagethirdThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.13.9.3
upsConfigOutputFreqthirdThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.13.9.4
upsConfigOutputVAthirdThe magnitude of the nominal Volt-Amp rating.(*)ro
NonNegativeInteger32 UNITS "Volt-Amps"
.1.3.6.1.4.1.818.1.1.13.9.5
upsConfigOutputPowerthirdThe magnitude of the nominal true power rating.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.13.9.6
upsConfigLowBattTimethirdThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*)rw
NonNegativeInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.13.9.7
upsConfigAudibleStatusthirdThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.9.8
upsConfigLowVoltageTransferPointthirdThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.13.9.9
upsConfigHighVoltageTransferPointthirdThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.13.9.10
upsConfigBatteryCapacitythirdThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.rw
NonNegativeInteger32 UNITS "Amps Hours"
.1.3.6.1.4.1.818.1.1.13.9.11
upsConfigBatteryChargeCurrentthirdThe maximum battery charge current, including external chargers.rw
NonNegativeInteger32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.13.9.12
upsConfigNoLoadShutdownthirdDis- or enable 'no load' shutdown from the contact interface.rw
Enumeration
.1.3.6.1.4.1.818.1.1.13.9.13
upsConfigStartDelaythirdMinimum required autonomy time before the UPS may perform an autorestart.rw
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.13.9.14
upsGetSetthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.10
upsEventGetNextthirdThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.10.1
upsEventGetPreviousthirdThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.10.2
upsEventSetStartingTimeStampthirdThe timestamp which is used as starting point for downloading events from the UPS event bufferrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.3
upsEventRetreiveCurrentTimeStampthirdThe current timestamp is retreived from the UPSro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.4
upsEventTableSizethirdThe number of entries in the event table. This object indicates the number of rows in the event table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.5
upsEventThirdTableA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..10)): PDU-SET upsSetStartingTimeStamp <time> PDU-SET upsEventGetNext <number> PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize.
SEQUENCE OF UpsEventThirdEntry
.1.3.6.1.4.1.818.1.1.13.10.6
upsEventThirdEntryAn entry containing information applicable to a particular event.
UpsEventThirdEntry
.1.3.6.1.4.1.818.1.1.13.10.6.1
upsEventLineIndexthirdThe event line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.10.6.1.1
upsEventCodethirdThe event code in numerical format.ro
Integer32
.1.3.6.1.4.1.818.1.1.13.10.6.1.2
upsEventStatusthirdThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.6.1.3
upsEventTimethirdThe timestamp of the moment the event was generated.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.6.1.4
upsParametersReadthirdThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.10.7
upsParametersWritethirdThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the third value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.10.8
upsParametersStartAddressthirdThe address which is used as starting point for downloading parameters from the UPSrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.9
upsParameterTableSizethirdThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.10
upsParameterThirdTableA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..16)): Read sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParametersRead <number> PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue <number> PDU-SET upsParametersWrite <number>
SEQUENCE OF UpsParameterThirdEntry
.1.3.6.1.4.1.818.1.1.13.10.11
upsParameterThirdEntryAn entry containing information applicable to a particular parameter.
UpsParameterThirdEntry
.1.3.6.1.4.1.818.1.1.13.10.11.1
upsParameterLineIndexthirdThe parameter line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.13.10.11.1.1
upsParameterValuethirdThe parameter value in numerical format.rw
Integer32
.1.3.6.1.4.1.818.1.1.13.10.11.1.2
upsStatusthirdThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValuesro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.12
upsMainsStatisticsMBfailthirdCount of main bypass failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.13
upsMainsStatisticsMRfailthirdCount of mains rectifier failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.14
upsMainsStatisticsB2thirdCount of transients on the mains bypass (0..2 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.15
upsMainsStatisticsB5thirdCount of transients on the mains bypass (2..5 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.16
upsMainsStatisticsB10thirdCount of transients on the mains bypass (5..10 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.17
upsMainsStatisticsB200thirdCount of transients on the mains bypass (10..200 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.18
upsMainsStatisticsBypRelthirdBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.19
upsTimethirdThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMP second ERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps.rw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.13.10.20
upsRequestPermissionthirdAn encrypted code is send to enable use of restricted write objects during a limited period of time.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.10.21
upsEventGetCodethirdThe code which is used as starting point to downloading the events from the UPS event buffer.rw
Integer32
.1.3.6.1.4.1.818.1.1.13.10.22
upsEventSpinLockthirdA spin lock on the event subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.10.23
upsParameterSpinLockthirdA spin lock on the parameters subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.13.10.24
geUPSTrapsthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.11
upsTrapAlarmBatteryBadthirdOne or more batteries have been determined to require replacement.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.1
upsTrapAlarmOnBatterythirdThe UPS is drawing power from the batteries.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.2
upsTrapAlarmLowBatterythirdThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.3
upsTrapAlarmDepletedBatterythirdThe UPS will be unable to sustain the present load when and if the utility power is lost)
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.4
upsTrapAlarmTempBadthirdA temperature is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.5
upsTrapAlarmInputBadthirdAn input condition is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.6
upsTrapAlarmOutputBadthirdAn output condition (other than OutputOverload) is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.7
upsTrapAlarmOutputOverloadthirdThe output load exceeds the UPS output capacity.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.8
upsTrapAlarmOnBypassthirdThe Bypass is presently engaged on the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.9
upsTrapAlarmBypassBadthirdThe Bypass is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.10
upsTrapAlarmOutputOffAsRequestedthirdThe UPS has shutdown as requested, i.e., the output is off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.11
upsTrapAlarmUpsOffAsRequestedthirdThe entire UPS has shutdown as commanded.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.12
upsTrapAlarmChargerFailedthirdAn uncorrected problem has been detected within the UPS charger subsystem.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.13
upsTrapAlarmUpsOutputOffthirdThe output of the UPS is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.14
upsTrapAlarmUpsSystemOffthirdThe UPS system is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.15
upsTrapAlarmFanFailurethirdThe failure of one or more fans in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.16
upsTrapAlarmFuseFailurethirdThe failure of one or more fuses has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.17
upsTrapAlarmGeneralFaultthirdA general fault in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.18
upsTrapAlarmDiagnosticTestFailedthirdThe result of the last diagnostic test indicates a failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.19
upsTrapAlarmCommunicationsLostthirdA problem has been encountered in the communication between the agent and the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.20
upsTrapAlarmAwaitingPowerthirdThe UPS output is off and the UPS is awaiting the return of the input power (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.21
upsTrapAlarmShutdownPendingthirdA upsShutdownAfterDelay countdown is underway.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.22
upsTrapAlarmShutdownImminentthirdThe UPS will turn off power to the load in less than 5 secondss; this may be either a timed shutdown or a low battery shutdown.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.23
upsTrapAlarmTestInProgressthirdA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.24
upsTrapAlarmReceptacleOffthirdA receptacle has been switched off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.25
upsTrapAlarmHighspeedBusFailurethirdA problem on the Highspeed Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.26
upsTrapAlarmHighspeedBusJACRCFailurethirdA CRC failure on the Highspeed Bus JA is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.27
upsTrapAlarmConnectivityBusFailurethirdA problem on the Connectivity Bus communication is detected
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.28
upsTrapAlarmHighspeedBusJBCRCFailurethirdA CRC failure on the Highspeed Bus JB is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.29
upsTrapAlarmCurrentSharingFailurethirdAn high current sharing on the parallel system is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.30
upsTrapAlarmDCRippleFailurethirdAn high ripple voltage on his DC link is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.31
upsTrapAlarmBatteryBadRestoredthirdA Battery bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.33
upsTrapAlarmOnBatteryRestoredthirdThe UPS is drawing power from mains again.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.34
upsTrapAlarmLowBatteryRestoredthirdA Low Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.35
upsTrapAlarmDepletedBatteryRestoredthirdA Depleted Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.36
upsTrapAlarmTempBadRestoredthirdA bad temperature condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.37
upsTrapAlarmInputBadRestoredthirdAn input bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.38
upsTrapAlarmOutputBadRestoredthirdAn output bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.39
upsTrapAlarmOutputOverloadRestoredthirdAn output overload condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.40
upsTrapAlarmOnBypassRestoredthirdAn On Bypass condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.41
upsTrapAlarmBypassBadRestoredthirdA Bypass bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.42
upsTrapAlarmOutputOffAsRequestedRestoredthirdA request shutdown has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.43
upsTrapAlarmUpsOffAsRequestedRestoredthirdA entire UPS command has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.44
upsTrapAlarmChargerFailedRestoredthirdA Charger Failer condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.45
upsTrapAlarmUpsOutputOnthirdThe output of the UPS switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.46
upsTrapAlarmUpsSystemOnthirdThe UPS system is switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.47
upsTrapAlarmFanFailureRestoredthirdA Fan failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.48
upsTrapAlarmFuseFailureRestoredthirdA Fuse failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.49
upsTrapAlarmGeneralFaultRestoredthirdA general fault is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.50
upsTrapAlarmDiagnosticTestFailedRestoredthirdA last diagnostic test indicates a failure is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.51
upsTrapAlarmCommunicationsLostRestoredthirdA problem in the communication between the agent and the UPS is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.52
upsTrapAlarmAwaitingPowerRestoredthirdA awaiting power condition is restored (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.53
upsTrapAlarmShutdownPendingRestoredthirdA upsShutdownAfterDelay countdown is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.54
upsTrapAlarmShutdownImminentRestoredthirdA shutdown imminent condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.55
upsTrapAlarmTestInProgressRestoredthirdThe test is in progress is terminated.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.56
upsTrapAlarmReceptacleOnthirdA receptacle has been switched on.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.57
upsTrapAlarmHighspeedBusRestorethirdA problem on the Highspeed Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.58
upsTrapAlarmHighspeedBusJACRCRestorethirdA CRC failure on the Highspeed Bus JA is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.59
upsTrapAlarmConnectivityBusRestorethirdA problem on the Connectivity Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.60
upsTrapAlarmHighspeedBusJBCRCRestoredthirdA CRC failure on the Highspeed Bus JB is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.61
upsTrapAlarmCurrentSharingRestoredthirdAn high current sharing on the parallel system is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.62
upsTrapAlarmDCRippleRestoredthirdAn high ripple voltage on his DC link is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.63
upsTrapAlarmValueLowthirdA measurement value reached a value below its low-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.129
upsTrapAlarmValueHighthirdA measurement value reached a value higher than its high-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.130
upsTrapAlarmValueLowRestoredthirdA ValueLow alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.133
upsTrapAlarmValueHighRestoredthirdA ValueHigh alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.13.11.134
upsDiagnosticthird
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.13.12
upsDiagnosticBusJACommunicationStatusthirdBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.13.12.1
upsDiagnosticBusJBCommunicationStatusthirdBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.13.12.2
upsDiagnosticBatteryLifetimethirdThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.13.12.3
upsDiagnosticFansLifetimethirdThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.13.12.4
upsDiagnosticDCcapacitorsLifetimethirdThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.13.12.5
upsDiagnosticACcapacitorsLifetimethirdThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.13.12.6
upsDiagnosticGlobalServiceCheckthirdThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.13.12.7
geFourthUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14
upsIdentfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.1
upsIdentManufacturerfourthThe name of the UPS manufacturer.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.1.1
upsIdentModelfourthThe UPS Model designation.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.1.2
upsIdentUPSSoftwareVersionfourthThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.1.3
upsIdentAgentSoftwareVersionfourthThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.1.4
upsIdentNamefourthA string identifying the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.1.5
upsIdentAttachedDevicesfourthA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.1.6
upsIdentUPSSerialNumberfourthThe UPS serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.1.7
upsIdentComProtVersionfourthThe IMV communication protocol versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.1.8
upsIdentOperatingTimefourthThe present value of the operating time. total 'on' time since UPS manufacturedro
NonNegativeInteger32 UNITS "fourths"
.1.3.6.1.4.1.818.1.1.14.1.9
upsBatteryfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.2
upsBatteryStatusfourthThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.14.2.1
upsSecondsOnBatteryfourthIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*)ro
Integer32 UNITS "fourths"
.1.3.6.1.4.1.818.1.1.14.2.2
upsEstimatedMinutesRemainingfourthAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*)ro
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.14.2.3
upsEstimatedChargeRemainingfourthAn estimate of the battery charge remaining expressed as a percent of full charge.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.14.2.4
upsBatteryVoltagefourthThe magnitude of the present battery voltage.(*)ro
NonNegativeInteger32 UNITS "0.1 Volt DC"
.1.3.6.1.4.1.818.1.1.14.2.5
upsBatteryCurrentfourthThe present battery current.(*)ro
Integer32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.14.2.6
upsBatteryTemperaturefourthThe ambient temperature at or near the UPS Battery casing.(*)ro
Integer32 UNITS "degrees Centigrade"
.1.3.6.1.4.1.818.1.1.14.2.7
upsBatteryRipplefourthThe present DC link RMS voltage ripple.(*)ro
Integer32 UNITS "0.1 Volt RMS"
.1.3.6.1.4.1.818.1.1.14.2.8
upsInputfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.3
upsInputLineBadsfourthA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*)ro
Counter32
.1.3.6.1.4.1.818.1.1.14.3.1
upsInputNumLinesfourthThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.3.2
upsInputFourthTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
SEQUENCE OF UpsInputFourthEntry
.1.3.6.1.4.1.818.1.1.14.3.3
upsInputFourthEntryAn entry containing information applicable to a particular input line.(*)
UpsInputFourthEntry
.1.3.6.1.4.1.818.1.1.14.3.3.1
upsInputLineIndexfourthThe input line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.3.3.1.1
upsInputFrequencyfourthThe present input frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.14.3.3.1.2
upsInputVoltagefourthThe magnitude of the present input voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.14.3.3.1.3
upsInputCurrentfourthThe magnitude of the present input current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.14.3.3.1.4
upsInputTruePowerfourthThe magnitude of the present input true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.14.3.3.1.5
upsInputVoltageMinfourthThe lowest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.14.3.3.1.6
upsInputVoltageMaxfourthThe highest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.14.3.3.1.7
upsOutputfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.4
upsOutputSourcefourthThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.14.4.1
upsOutputFrequencyfourthThe present output frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.14.4.2
upsOutputNumLinesfourthThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.4.3
upsOutputFourthTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
SEQUENCE OF UpsOutputFourthEntry
.1.3.6.1.4.1.818.1.1.14.4.4
upsOutputFourthEntryAn entry containing information applicable to a particular output line.(*)
UpsOutputFourthEntry
.1.3.6.1.4.1.818.1.1.14.4.4.1
upsOutputLineIndexfourthThe output line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.4.4.1.1
upsOutputVoltagefourthThe present output voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.14.4.4.1.2
upsOutputCurrentfourthThe present output current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.14.4.4.1.3
upsOutputPowerfourthThe present output true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.14.4.4.1.4
upsOutputPercentLoadfourthThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.14.4.4.1.5
upsOutputPowerFactorfourthThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*)ro
Integer32 (-99..100) UNITS "0.01 cos phi"
.1.3.6.1.4.1.818.1.1.14.4.4.1.6
upsOutputPeakCurrentfourthThe present output peak current.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.14.4.4.1.7
upsOutputShareCurrentfourthIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.14.4.4.1.8
upsBypassfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.5
upsBypassFrequencyfourthThe present bypass frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.14.5.1
upsBypassNumLinesfourthThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.5.2
upsBypassFourthTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
SEQUENCE OF UpsBypassFourthEntry
.1.3.6.1.4.1.818.1.1.14.5.3
upsBypassFourthEntryAn entry containing information applicable to a particular bypass input.(*)
UpsBypassFourthEntry
.1.3.6.1.4.1.818.1.1.14.5.3.1
upsBypassLineIndexfourthThe bypass line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.5.3.1.1
upsBypassVoltagefourthThe present bypass voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.14.5.3.1.2
upsBypassCurrentfourthThe present bypass current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.14.5.3.1.3
upsBypassPowerfourthThe present true power conveyed by the bypass.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.14.5.3.1.4
upsAlarmfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6
upsAlarmsPresentfourthThe present number of active alarm conditions.(*)ro
Gauge32
.1.3.6.1.4.1.818.1.1.14.6.1
upsAlarmFourthTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*)
SEQUENCE OF UpsAlarmFourthEntry
.1.3.6.1.4.1.818.1.1.14.6.2
upsAlarmFourthEntryAn entry containing information applicable to a particular alarm.(*)
UpsAlarmFourthEntry
.1.3.6.1.4.1.818.1.1.14.6.2.1
upsAlarmIdfourthA unique identifier for an alarm condition. This value must remain constant.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.6.2.1.1
upsAlarmDescrfourthA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*)ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.6.2.1.2
upsAlarmTimefourthThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.6.2.1.3
upsWellKnownAlarmsfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3
upsAlarmBatteryBadfourthOne or more batteries have been determined to require replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.1
upsAlarmOnBatteryfourthThe UPS is drawing power from the batteries.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.2
upsAlarmLowBatteryfourthThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.3
upsAlarmDepletedBatteryfourthThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.4
upsAlarmTempBadfourthA temperature is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.5
upsAlarmInputBadfourthAn input condition is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.6
upsAlarmOutputBadfourthAn output condition (other than OutputOverload) is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.7
upsAlarmOutputOverloadfourthThe output load exceeds the UPS output capacity.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.8
upsAlarmOnBypassfourthThe Bypass is presently engaged on the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.9
upsAlarmBypassBadfourthThe Bypass is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.10
upsAlarmOutputOffAsRequestedfourthThe UPS has shutdown as requested, i.e., the output is off.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.11
upsAlarmUpsOffAsRequestedfourthThe entire UPS has shutdown as commanded.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.12
upsAlarmChargerFailedfourthAn uncorrected problem has been detected within the UPS charger subsystem.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.13
upsAlarmUpsOutputOfffourthThe output of the UPS is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.14
upsAlarmUpsSystemOfffourthThe UPS system is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.15
upsAlarmFanFailurefourthThe failure of one or more fans in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.16
upsAlarmFuseFailurefourthThe failure of one or more fuses has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.17
upsAlarmGeneralFaultfourthA general fault in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.18
upsAlarmDiagnosticTestFailedfourthThe result of the last diagnostic test indicates a failure.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.19
upsAlarmCommunicationsLostfourthA problem has been encountered in the communications between the agent and the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.20
upsAlarmAwaitingPowerfourthThe UPS output is off and the UPS is awaiting the return of input power.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.21
upsAlarmShutdownPendingfourthA upsShutdownAfterDelay countdown is underway.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.22
upsAlarmShutdownImminentfourthThe UPS will turn off power to the load in less than 5 fourths; this may be either a timed shutdown or a low battery shutdown.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.23
upsAlarmTestInProgressfourthA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.24
upsAlarmReceptacleOfffourthThe receptacle are switch off
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.25
upsAlarmHighSpeedBusFailurefourthA problem on the High Speed Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.26
upsAlarmHighSpeedBusJACRCFailurefourthA High Speed Bus CRC failure on Bus JA is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.27
upsAlarmConnectivityBusFailurefourthA problem on the Connectivity Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.28
upsAlarmHighSpeedBusJBCRCFailurefourthA High Speed Bus CRC failure on Bus JB is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.29
upsAlarmCurrentSharingfourthThe UPS detects an high current sharing on the parallel system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.30
upsAlarmDCRipplefourthThe UPS detects an high ripple voltage on his DC link.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.6.3.31
upsAlarmMaskAfourthSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS.ro
Unsigned32
.1.3.6.1.4.1.818.1.1.14.6.4
upsTestfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.7
upsTestIdfourthThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*)rw
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.7.1
upsTestSpinLockfourthA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*)rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.7.2
upsTestResultsSummaryfourthThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.14.7.3
upsTestResultsDetailfourthAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.7.4
upsTestStartTimefourthThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.7.5
upsTestElapsedTimefourthThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*)ro
TimeInterval (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.7.6
upsWellKnownTestsfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.7.7
upsTestNoTestsInitiatedfourthNo tests have been initiated and no test is in progress.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.7.7.1
upsTestAbortTestInProgressfourthThe test in progress is to be aborted / the test in progress was aborted.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.7.7.2
upsTestGeneralSystemsTestfourthThe manufacturer's standard test of UPS device systems.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.7.7.3
upsTestQuickBatteryTestfourthA test that is sufficient to determine if the battery needs replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.7.7.4
upsTestDeepBatteryCalibrationfourthThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.7.7.5
upsControlfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.8
upsShutdownTypefourthThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.8.1
upsShutdownAfterDelayfourthSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of fourths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of fourths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*)rw
Integer32 (-1..2147483647) UNITS "fourths"
.1.3.6.1.4.1.818.1.1.14.8.2
upsStartupAfterDelayfourthSetting this object will start the output after the indicated number of fourths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of fourths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*)rw
Integer32 (-1..2147483647) UNITS "fourths"
.1.3.6.1.4.1.818.1.1.14.8.3
upsRebootWithDurationfourthSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of fourths, after which time the output will be started, including starting the UPS, if necessary. If the number of fourths required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 fourths. When read, upsRebootWithDuration shall return the number of fourths remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)rw
Integer32 (-1..300) UNITS "fourths"
.1.3.6.1.4.1.818.1.1.14.8.4
upsAutoRestartfourthSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.8.5
upsReceptaclesNumfourthThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.8.6
upsReceptacleFourthTableA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
SEQUENCE OF UpsReceptacleFourthEntry
.1.3.6.1.4.1.818.1.1.14.8.7
upsReceptacleFourthEntryAn entry containing information applicable to a particular receptacle.
UpsReceptacleFourthEntry
.1.3.6.1.4.1.818.1.1.14.8.7.1
upsReceptacleLineIndexfourthThe receptacle line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.8.7.1.1
upsReceptacleOnOfffourthThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on.rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.8.7.1.2
upsUPSModefourthThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode)rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.8.8
upsRectifierOnOfffourthThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.8.9
upsBatteryChargeMethodfourthThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.8.10
upsInverterOnOfffourthThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.8.11
upsBypassOnOfffourthThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.8.12
upsLoadSourcefourthThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.8.13
upsConfigfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.9
upsConfigInputVoltagefourthThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.14.9.1
upsConfigInputFreqfourthThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.14.9.2
upsConfigOutputVoltagefourthThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.14.9.3
upsConfigOutputFreqfourthThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.14.9.4
upsConfigOutputVAfourthThe magnitude of the nominal Volt-Amp rating.(*)ro
NonNegativeInteger32 UNITS "Volt-Amps"
.1.3.6.1.4.1.818.1.1.14.9.5
upsConfigOutputPowerfourthThe magnitude of the nominal true power rating.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.14.9.6
upsConfigLowBattTimefourthThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*)rw
NonNegativeInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.14.9.7
upsConfigAudibleStatusfourthThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.9.8
upsConfigLowVoltageTransferPointfourthThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.14.9.9
upsConfigHighVoltageTransferPointfourthThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.14.9.10
upsConfigBatteryCapacityfourthThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.rw
NonNegativeInteger32 UNITS "Amps Hours"
.1.3.6.1.4.1.818.1.1.14.9.11
upsConfigBatteryChargeCurrentfourthThe maximum battery charge current, including external chargers.rw
NonNegativeInteger32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.14.9.12
upsConfigNoLoadShutdownfourthDis- or enable 'no load' shutdown from the contact interface.rw
Enumeration
.1.3.6.1.4.1.818.1.1.14.9.13
upsConfigStartDelayfourthMinimum required autonomy time before the UPS may perform an autorestart.rw
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.14.9.14
upsGetSetfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.10
upsEventGetNextfourthThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.10.1
upsEventGetPreviousfourthThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.10.2
upsEventSetStartingTimeStampfourthThe timestamp which is used as starting point for downloading events from the UPS event bufferrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.3
upsEventRetreiveCurrentTimeStampfourthThe current timestamp is retreived from the UPSro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.4
upsEventTableSizefourthThe number of entries in the event table. This object indicates the number of rows in the event table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.5
upsEventFourthTableA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..10)): PDU-SET upsSetStartingTimeStamp <time> PDU-SET upsEventGetNext <number> PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize.
SEQUENCE OF UpsEventFourthEntry
.1.3.6.1.4.1.818.1.1.14.10.6
upsEventFourthEntryAn entry containing information applicable to a particular event.
UpsEventFourthEntry
.1.3.6.1.4.1.818.1.1.14.10.6.1
upsEventLineIndexfourthThe event line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.10.6.1.1
upsEventCodefourthThe event code in numerical format.ro
Integer32
.1.3.6.1.4.1.818.1.1.14.10.6.1.2
upsEventStatusfourthThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.6.1.3
upsEventTimefourthThe timestamp of the moment the event was generated.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.6.1.4
upsParametersReadfourthThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.10.7
upsParametersWritefourthThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the fourth value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.10.8
upsParametersStartAddressfourthThe address which is used as starting point for downloading parameters from the UPSrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.9
upsParameterTableSizefourthThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.10
upsParameterFourthTableA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..16)): Read sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParametersRead <number> PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue <number> PDU-SET upsParametersWrite <number>
SEQUENCE OF UpsParameterFourthEntry
.1.3.6.1.4.1.818.1.1.14.10.11
upsParameterFourthEntryAn entry containing information applicable to a particular parameter.
UpsParameterFourthEntry
.1.3.6.1.4.1.818.1.1.14.10.11.1
upsParameterLineIndexfourthThe parameter line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.14.10.11.1.1
upsParameterValuefourthThe parameter value in numerical format.rw
Integer32
.1.3.6.1.4.1.818.1.1.14.10.11.1.2
upsStatusfourthThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValuesro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.12
upsMainsStatisticsMBfailfourthCount of main bypass failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.13
upsMainsStatisticsMRfailfourthCount of mains rectifier failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.14
upsMainsStatisticsB2fourthCount of transients on the mains bypass (0..2 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.15
upsMainsStatisticsB5fourthCount of transients on the mains bypass (2..5 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.16
upsMainsStatisticsB10fourthCount of transients on the mains bypass (5..10 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.17
upsMainsStatisticsB200fourthCount of transients on the mains bypass (10..200 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.18
upsMainsStatisticsBypRelfourthBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.19
upsTimefourthThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPfourthERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps.rw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.14.10.20
upsRequestPermissionfourthAn encrypted code is send to enable use of restricted write objects during a limited period of time.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.10.21
upsEventGetCodefourthThe code which is used as starting point to downloading the events from the UPS event buffer.rw
Integer32
.1.3.6.1.4.1.818.1.1.14.10.22
upsEventSpinLockfourthA spin lock on the event subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.10.23
upsParameterSpinLockfourthA spin lock on the parameters subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.14.10.24
geUPSTrapsfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.11
upsTrapAlarmBatteryBadfourthOne or more batteries have been determined to require replacement.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.1
upsTrapAlarmOnBatteryfourthThe UPS is drawing power from the batteries.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.2
upsTrapAlarmLowBatteryfourthThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.3
upsTrapAlarmDepletedBatteryfourthThe UPS will be unable to sustain the present load when and if the utility power is lost)
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.4
upsTrapAlarmTempBadfourthA temperature is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.5
upsTrapAlarmInputBadfourthAn input condition is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.6
upsTrapAlarmOutputBadfourthAn output condition (other than OutputOverload) is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.7
upsTrapAlarmOutputOverloadfourthThe output load exceeds the UPS output capacity.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.8
upsTrapAlarmOnBypassfourthThe Bypass is presently engaged on the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.9
upsTrapAlarmBypassBadfourthThe Bypass is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.10
upsTrapAlarmOutputOffAsRequestedfourthThe UPS has shutdown as requested, i.e., the output is off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.11
upsTrapAlarmUpsOffAsRequestedfourthThe entire UPS has shutdown as commanded.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.12
upsTrapAlarmChargerFailedfourthAn uncorrected problem has been detected within the UPS charger subsystem.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.13
upsTrapAlarmUpsOutputOfffourthThe output of the UPS is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.14
upsTrapAlarmUpsSystemOfffourthThe UPS system is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.15
upsTrapAlarmFanFailurefourthThe failure of one or more fans in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.16
upsTrapAlarmFuseFailurefourthThe failure of one or more fuses has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.17
upsTrapAlarmGeneralFaultfourthA general fault in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.18
upsTrapAlarmDiagnosticTestFailedfourthThe result of the last diagnostic test indicates a failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.19
upsTrapAlarmCommunicationsLostfourthA problem has been encountered in the communication between the agent and the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.20
upsTrapAlarmAwaitingPowerfourthThe UPS output is off and the UPS is awaiting the return of the input power (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.21
upsTrapAlarmShutdownPendingfourthA upsShutdownAfterDelay countdown is underway.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.22
upsTrapAlarmShutdownImminentfourthThe UPS will turn off power to the load in less than 5 fourths; this may be either a timed shutdown or a low battery shutdown.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.23
upsTrapAlarmTestInProgressfourthA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.24
upsTrapAlarmReceptacleOfffourthA receptacle has been switched off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.25
upsTrapAlarmHighspeedBusFailurefourthA problem on the Highspeed Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.26
upsTrapAlarmHighspeedBusJACRCFailurefourthA CRC failure on the Highspeed Bus JA is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.27
upsTrapAlarmConnectivityBusFailurefourthA problem on the Connectivity Bus communication is detected
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.28
upsTrapAlarmHighspeedBusJBCRCFailurefourthA CRC failure on the Highspeed Bus JB is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.29
upsTrapAlarmCurrentSharingFailurefourthAn high current sharing on the parallel system is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.30
upsTrapAlarmDCRippleFailurefourthAn high ripple voltage on his DC link is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.31
upsTrapAlarmBatteryBadRestoredfourthA Battery bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.33
upsTrapAlarmOnBatteryRestoredfourthThe UPS is drawing power from mains again.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.34
upsTrapAlarmLowBatteryRestoredfourthA Low Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.35
upsTrapAlarmDepletedBatteryRestoredfourthA Depleted Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.36
upsTrapAlarmTempBadRestoredfourthA bad temperature condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.37
upsTrapAlarmInputBadRestoredfourthAn input bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.38
upsTrapAlarmOutputBadRestoredfourthAn output bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.39
upsTrapAlarmOutputOverloadRestoredfourthAn output overload condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.40
upsTrapAlarmOnBypassRestoredfourthAn On Bypass condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.41
upsTrapAlarmBypassBadRestoredfourthA Bypass bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.42
upsTrapAlarmOutputOffAsRequestedRestoredfourthA request shutdown has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.43
upsTrapAlarmUpsOffAsRequestedRestoredfourthA entire UPS command has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.44
upsTrapAlarmChargerFailedRestoredfourthA Charger Failer condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.45
upsTrapAlarmUpsOutputOnfourthThe output of the UPS switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.46
upsTrapAlarmUpsSystemOnfourthThe UPS system is switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.47
upsTrapAlarmFanFailureRestoredfourthA Fan failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.48
upsTrapAlarmFuseFailureRestoredfourthA Fuse failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.49
upsTrapAlarmGeneralFaultRestoredfourthA general fault is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.50
upsTrapAlarmDiagnosticTestFailedRestoredfourthA last diagnostic test indicates a failure is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.51
upsTrapAlarmCommunicationsLostRestoredfourthA problem in the communication between the agent and the UPS is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.52
upsTrapAlarmAwaitingPowerRestoredfourthA awaiting power condition is restored (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.53
upsTrapAlarmShutdownPendingRestoredfourthA upsShutdownAfterDelay countdown is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.54
upsTrapAlarmShutdownImminentRestoredfourthA shutdown imminent condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.55
upsTrapAlarmTestInProgressRestoredfourthThe test is in progress is terminated.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.56
upsTrapAlarmReceptacleOnfourthA receptacle has been switched on.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.57
upsTrapAlarmHighspeedBusRestorefourthA problem on the Highspeed Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.58
upsTrapAlarmHighspeedBusJACRCRestorefourthA CRC failure on the Highspeed Bus JA is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.59
upsTrapAlarmConnectivityBusRestorefourthA problem on the Connectivity Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.60
upsTrapAlarmHighspeedBusJBCRCRestoredfourthA CRC failure on the Highspeed Bus JB is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.61
upsTrapAlarmCurrentSharingRestoredfourthAn high current sharing on the parallel system is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.62
upsTrapAlarmDCRippleRestoredfourthAn high ripple voltage on his DC link is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.63
upsTrapAlarmValueLowfourthA measurement value reached a value below its low-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.129
upsTrapAlarmValueHighfourthA measurement value reached a value higher than its high-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.130
upsTrapAlarmValueLowRestoredfourthA ValueLow alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.133
upsTrapAlarmValueHighRestoredfourthA ValueHigh alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.14.11.134
upsDiagnosticfourth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.14.12
upsDiagnosticBusJACommunicationStatusfourthBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.14.12.1
upsDiagnosticBusJBCommunicationStatusfourthBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.14.12.2
upsDiagnosticBatteryLifetimefourthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.14.12.3
upsDiagnosticFansLifetimefourthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.14.12.4
upsDiagnosticDCcapacitorsLifetimefourthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.14.12.5
upsDiagnosticACcapacitorsLifetimefourthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.14.12.6
upsDiagnosticGlobalServiceCheckfourthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.14.12.7
geFifthUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15
upsIdentfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.1
upsIdentManufacturerfifthThe name of the UPS manufacturer.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.1.1
upsIdentModelfifthThe UPS Model designation.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.1.2
upsIdentUPSSoftwareVersionfifthThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.1.3
upsIdentAgentSoftwareVersionfifthThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.1.4
upsIdentNamefifthA string identifying the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.1.5
upsIdentAttachedDevicesfifthA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.1.6
upsIdentUPSSerialNumberfifthThe UPS serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.1.7
upsIdentComProtVersionfifthThe IMV communication protocol versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.1.8
upsIdentOperatingTimefifthThe present value of the operating time. total 'on' time since UPS manufacturedro
NonNegativeInteger32 UNITS "fifths"
.1.3.6.1.4.1.818.1.1.15.1.9
upsBatteryfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.2
upsBatteryStatusfifthThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.15.2.1
upsSecondsOnBatteryfifthIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*)ro
Integer32 UNITS "fifths"
.1.3.6.1.4.1.818.1.1.15.2.2
upsEstimatedMinutesRemainingfifthAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*)ro
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.15.2.3
upsEstimatedChargeRemainingfifthAn estimate of the battery charge remaining expressed as a percent of full charge.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.15.2.4
upsBatteryVoltagefifthThe magnitude of the present battery voltage.(*)ro
NonNegativeInteger32 UNITS "0.1 Volt DC"
.1.3.6.1.4.1.818.1.1.15.2.5
upsBatteryCurrentfifthThe present battery current.(*)ro
Integer32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.15.2.6
upsBatteryTemperaturefifthThe ambient temperature at or near the UPS Battery casing.(*)ro
Integer32 UNITS "degrees Centigrade"
.1.3.6.1.4.1.818.1.1.15.2.7
upsBatteryRipplefifthThe present DC link RMS voltage ripple.(*)ro
Integer32 UNITS "0.1 Volt RMS"
.1.3.6.1.4.1.818.1.1.15.2.8
upsInputfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.3
upsInputLineBadsfifthA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*)ro
Counter32
.1.3.6.1.4.1.818.1.1.15.3.1
upsInputNumLinesfifthThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.3.2
upsInputFifthTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
SEQUENCE OF UpsInputFifthEntry
.1.3.6.1.4.1.818.1.1.15.3.3
upsInputFifthEntryAn entry containing information applicable to a particular input line.(*)
UpsInputFifthEntry
.1.3.6.1.4.1.818.1.1.15.3.3.1
upsInputLineIndexfifthThe input line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.3.3.1.1
upsInputFrequencyfifthThe present input frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.15.3.3.1.2
upsInputVoltagefifthThe magnitude of the present input voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.15.3.3.1.3
upsInputCurrentfifthThe magnitude of the present input current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.15.3.3.1.4
upsInputTruePowerfifthThe magnitude of the present input true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.15.3.3.1.5
upsInputVoltageMinfifthThe lowest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.15.3.3.1.6
upsInputVoltageMaxfifthThe highest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.15.3.3.1.7
upsOutputfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.4
upsOutputSourcefifthThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.15.4.1
upsOutputFrequencyfifthThe present output frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.15.4.2
upsOutputNumLinesfifthThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.4.3
upsOutputFifthTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
SEQUENCE OF UpsOutputFifthEntry
.1.3.6.1.4.1.818.1.1.15.4.4
upsOutputFifthEntryAn entry containing information applicable to a particular output line.(*)
UpsOutputFifthEntry
.1.3.6.1.4.1.818.1.1.15.4.4.1
upsOutputLineIndexfifthThe output line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.4.4.1.1
upsOutputVoltagefifthThe present output voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.15.4.4.1.2
upsOutputCurrentfifthThe present output current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.15.4.4.1.3
upsOutputPowerfifthThe present output true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.15.4.4.1.4
upsOutputPercentLoadfifthThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.15.4.4.1.5
upsOutputPowerFactorfifthThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*)ro
Integer32 (-99..100) UNITS "0.01 cos phi"
.1.3.6.1.4.1.818.1.1.15.4.4.1.6
upsOutputPeakCurrentfifthThe present output peak current.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.15.4.4.1.7
upsOutputShareCurrentfifthIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.15.4.4.1.8
upsBypassfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.5
upsBypassFrequencyfifthThe present bypass frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.15.5.1
upsBypassNumLinesfifthThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.5.2
upsBypassFifthTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
SEQUENCE OF UpsBypassFifthEntry
.1.3.6.1.4.1.818.1.1.15.5.3
upsBypassFifthEntryAn entry containing information applicable to a particular bypass input.(*)
UpsBypassFifthEntry
.1.3.6.1.4.1.818.1.1.15.5.3.1
upsBypassLineIndexfifthThe bypass line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.5.3.1.1
upsBypassVoltagefifthThe present bypass voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.15.5.3.1.2
upsBypassCurrentfifthThe present bypass current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.15.5.3.1.3
upsBypassPowerfifthThe present true power conveyed by the bypass.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.15.5.3.1.4
upsAlarmfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6
upsAlarmsPresentfifthThe present number of active alarm conditions.(*)ro
Gauge32
.1.3.6.1.4.1.818.1.1.15.6.1
upsAlarmFifthTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*)
SEQUENCE OF UpsAlarmFifthEntry
.1.3.6.1.4.1.818.1.1.15.6.2
upsAlarmFifthEntryAn entry containing information applicable to a particular alarm.(*)
UpsAlarmFifthEntry
.1.3.6.1.4.1.818.1.1.15.6.2.1
upsAlarmIdfifthA unique identifier for an alarm condition. This value must remain constant.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.6.2.1.1
upsAlarmDescrfifthA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*)ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.6.2.1.2
upsAlarmTimefifthThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.6.2.1.3
upsWellKnownAlarmsfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3
upsAlarmBatteryBadfifthOne or more batteries have been determined to require replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.1
upsAlarmOnBatteryfifthThe UPS is drawing power from the batteries.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.2
upsAlarmLowBatteryfifthThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.3
upsAlarmDepletedBatteryfifthThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.4
upsAlarmTempBadfifthA temperature is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.5
upsAlarmInputBadfifthAn input condition is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.6
upsAlarmOutputBadfifthAn output condition (other than OutputOverload) is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.7
upsAlarmOutputOverloadfifthThe output load exceeds the UPS output capacity.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.8
upsAlarmOnBypassfifthThe Bypass is presently engaged on the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.9
upsAlarmBypassBadfifthThe Bypass is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.10
upsAlarmOutputOffAsRequestedfifthThe UPS has shutdown as requested, i.e., the output is off.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.11
upsAlarmUpsOffAsRequestedfifthThe entire UPS has shutdown as commanded.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.12
upsAlarmChargerFailedfifthAn uncorrected problem has been detected within the UPS charger subsystem.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.13
upsAlarmUpsOutputOfffifthThe output of the UPS is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.14
upsAlarmUpsSystemOfffifthThe UPS system is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.15
upsAlarmFanFailurefifthThe failure of one or more fans in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.16
upsAlarmFuseFailurefifthThe failure of one or more fuses has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.17
upsAlarmGeneralFaultfifthA general fault in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.18
upsAlarmDiagnosticTestFailedfifthThe result of the last diagnostic test indicates a failure.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.19
upsAlarmCommunicationsLostfifthA problem has been encountered in the communications between the agent and the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.20
upsAlarmAwaitingPowerfifthThe UPS output is off and the UPS is awaiting the return of input power.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.21
upsAlarmShutdownPendingfifthA upsShutdownAfterDelay countdown is underway.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.22
upsAlarmShutdownImminentfifthThe UPS will turn off power to the load in less than 5 fifths; this may be either a timed shutdown or a low battery shutdown.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.23
upsAlarmTestInProgressfifthA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.24
upsAlarmReceptacleOfffifthThe receptacle are switch off
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.25
upsAlarmHighSpeedBusFailurefifthA problem on the High Speed Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.26
upsAlarmHighSpeedBusJACRCFailurefifthA High Speed Bus CRC failure on Bus JA is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.27
upsAlarmConnectivityBusFailurefifthA problem on the Connectivity Bus communication is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.28
upsAlarmHighSpeedBusJBCRCFailurefifthA High Speed Bus CRC failure on Bus JB is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.29
upsAlarmCurrentSharingfifthThe UPS detects an high current sharing on the parallel system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.30
upsAlarmDCRipplefifthThe UPS detects an high ripple voltage on his DC link.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.6.3.31
upsAlarmMaskAfifthSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS.ro
Unsigned32
.1.3.6.1.4.1.818.1.1.15.6.4
upsTestfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.7
upsTestIdfifthThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*)rw
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.7.1
upsTestSpinLockfifthA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*)rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.7.2
upsTestResultsSummaryfifthThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.15.7.3
upsTestResultsDetailfifthAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.7.4
upsTestStartTimefifthThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.7.5
upsTestElapsedTimefifthThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*)ro
TimeInterval (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.7.6
upsWellKnownTestsfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.7.7
upsTestNoTestsInitiatedfifthNo tests have been initiated and no test is in progress.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.7.7.1
upsTestAbortTestInProgressfifthThe test in progress is to be aborted / the test in progress was aborted.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.7.7.2
upsTestGeneralSystemsTestfifthThe manufacturer's standard test of UPS device systems.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.7.7.3
upsTestQuickBatteryTestfifthA test that is sufficient to determine if the battery needs replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.7.7.4
upsTestDeepBatteryCalibrationfifthThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.7.7.5
upsControlfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.8
upsShutdownTypefifthThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.8.1
upsShutdownAfterDelayfifthSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of fifths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of fifths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*)rw
Integer32 (-1..2147483647) UNITS "fifths"
.1.3.6.1.4.1.818.1.1.15.8.2
upsStartupAfterDelayfifthSetting this object will start the output after the indicated number of fifths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of fifths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*)rw
Integer32 (-1..2147483647) UNITS "fifths"
.1.3.6.1.4.1.818.1.1.15.8.3
upsRebootWithDurationfifthSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of fifths, after which time the output will be started, including starting the UPS, if necessary. If the number of fifths required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 fifths. When read, upsRebootWithDuration shall return the number of fifths remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)rw
Integer32 (-1..300) UNITS "fifths"
.1.3.6.1.4.1.818.1.1.15.8.4
upsAutoRestartfifthSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.8.5
upsReceptaclesNumfifthThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.8.6
upsReceptacleFifthTableA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
SEQUENCE OF UpsReceptacleFifthEntry
.1.3.6.1.4.1.818.1.1.15.8.7
upsReceptacleFifthEntryAn entry containing information applicable to a particular receptacle.
UpsReceptacleFifthEntry
.1.3.6.1.4.1.818.1.1.15.8.7.1
upsReceptacleLineIndexfifthThe receptacle line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.8.7.1.1
upsReceptacleOnOfffifthThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on.rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.8.7.1.2
upsUPSModefifthThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode)rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.8.8
upsRectifierOnOfffifthThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.8.9
upsBatteryChargeMethodfifthThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.8.10
upsInverterOnOfffifthThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.8.11
upsBypassOnOfffifthThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.8.12
upsLoadSourcefifthThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.8.13
upsConfigfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.9
upsConfigInputVoltagefifthThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.15.9.1
upsConfigInputFreqfifthThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.15.9.2
upsConfigOutputVoltagefifthThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.15.9.3
upsConfigOutputFreqfifthThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.15.9.4
upsConfigOutputVAfifthThe magnitude of the nominal Volt-Amp rating.(*)ro
NonNegativeInteger32 UNITS "Volt-Amps"
.1.3.6.1.4.1.818.1.1.15.9.5
upsConfigOutputPowerfifthThe magnitude of the nominal true power rating.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.15.9.6
upsConfigLowBattTimefifthThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*)rw
NonNegativeInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.15.9.7
upsConfigAudibleStatusfifthThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.9.8
upsConfigLowVoltageTransferPointfifthThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.15.9.9
upsConfigHighVoltageTransferPointfifthThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.15.9.10
upsConfigBatteryCapacityfifthThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.rw
NonNegativeInteger32 UNITS "Amps Hours"
.1.3.6.1.4.1.818.1.1.15.9.11
upsConfigBatteryChargeCurrentfifthThe maximum battery charge current, including external chargers.rw
NonNegativeInteger32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.15.9.12
upsConfigNoLoadShutdownfifthDis- or enable 'no load' shutdown from the contact interface.rw
Enumeration
.1.3.6.1.4.1.818.1.1.15.9.13
upsConfigStartDelayfifthMinimum required autonomy time before the UPS may perform an autorestart.rw
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.15.9.14
upsGetSetfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.10
upsEventGetNextfifthThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.10.1
upsEventGetPreviousfifthThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.10.2
upsEventSetStartingTimeStampfifthThe timestamp which is used as starting point for downloading events from the UPS event bufferrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.3
upsEventRetreiveCurrentTimeStampfifthThe current timestamp is retreived from the UPSro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.4
upsEventTableSizefifthThe number of entries in the event table. This object indicates the number of rows in the event table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.5
upsEventFifthTableA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..10)): PDU-SET upsSetStartingTimeStamp <time> PDU-SET upsEventGetNext <number> PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize.
SEQUENCE OF UpsEventFifthEntry
.1.3.6.1.4.1.818.1.1.15.10.6
upsEventFifthEntryAn entry containing information applicable to a particular event.
UpsEventFifthEntry
.1.3.6.1.4.1.818.1.1.15.10.6.1
upsEventLineIndexfifthThe event line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.10.6.1.1
upsEventCodefifthThe event code in numerical format.ro
Integer32
.1.3.6.1.4.1.818.1.1.15.10.6.1.2
upsEventStatusfifthThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.6.1.3
upsEventTimefifthThe timestamp of the moment the event was generated.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.6.1.4
upsParametersReadfifthThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.10.7
upsParametersWritefifthThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the fifth value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.10.8
upsParametersStartAddressfifthThe address which is used as starting point for downloading parameters from the UPSrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.9
upsParameterTableSizefifthThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.10
upsParameterFifthTableA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..16)): Read sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParametersRead <number> PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue <number> PDU-SET upsParametersWrite <number>
SEQUENCE OF UpsParameterFifthEntry
.1.3.6.1.4.1.818.1.1.15.10.11
upsParameterFifthEntryAn entry containing information applicable to a particular parameter.
UpsParameterFifthEntry
.1.3.6.1.4.1.818.1.1.15.10.11.1
upsParameterLineIndexfifthThe parameter line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.15.10.11.1.1
upsParameterValuefifthThe parameter value in numerical format.rw
Integer32
.1.3.6.1.4.1.818.1.1.15.10.11.1.2
upsStatusfifthThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValuesro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.12
upsMainsStatisticsMBfailfifthCount of main bypass failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.13
upsMainsStatisticsMRfailfifthCount of mains rectifier failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.14
upsMainsStatisticsB2fifthCount of transients on the mains bypass (0..2 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.15
upsMainsStatisticsB5fifthCount of transients on the mains bypass (2..5 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.16
upsMainsStatisticsB10fifthCount of transients on the mains bypass (5..10 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.17
upsMainsStatisticsB200fifthCount of transients on the mains bypass (10..200 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.18
upsMainsStatisticsBypRelfifthBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.19
upsTimefifthThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPfifthERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps.rw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.15.10.20
upsRequestPermissionfifthAn encrypted code is send to enable use of restricted write objects during a limited period of time.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.10.21
upsEventGetCodefifthThe code which is used as starting point to downloading the events from the UPS event buffer.rw
Integer32
.1.3.6.1.4.1.818.1.1.15.10.22
upsEventSpinLockfifthA spin lock on the event subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.10.23
upsParameterSpinLockfifthA spin lock on the parameters subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.15.10.24
geUPSTrapsfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.11
upsTrapAlarmBatteryBadfifthOne or more batteries have been determined to require replacement.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.1
upsTrapAlarmOnBatteryfifthThe UPS is drawing power from the batteries.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.2
upsTrapAlarmLowBatteryfifthThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.3
upsTrapAlarmDepletedBatteryfifthThe UPS will be unable to sustain the present load when and if the utility power is lost)
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.4
upsTrapAlarmTempBadfifthA temperature is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.5
upsTrapAlarmInputBadfifthAn input condition is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.6
upsTrapAlarmOutputBadfifthAn output condition (other than OutputOverload) is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.7
upsTrapAlarmOutputOverloadfifthThe output load exceeds the UPS output capacity.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.8
upsTrapAlarmOnBypassfifthThe Bypass is presently engaged on the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.9
upsTrapAlarmBypassBadfifthThe Bypass is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.10
upsTrapAlarmOutputOffAsRequestedfifthThe UPS has shutdown as requested, i.e., the output is off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.11
upsTrapAlarmUpsOffAsRequestedfifthThe entire UPS has shutdown as commanded.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.12
upsTrapAlarmChargerFailedfifthAn uncorrected problem has been detected within the UPS charger subsystem.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.13
upsTrapAlarmUpsOutputOfffifthThe output of the UPS is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.14
upsTrapAlarmUpsSystemOfffifthThe UPS system is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.15
upsTrapAlarmFanFailurefifthThe failure of one or more fans in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.16
upsTrapAlarmFuseFailurefifthThe failure of one or more fuses has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.17
upsTrapAlarmGeneralFaultfifthA general fault in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.18
upsTrapAlarmDiagnosticTestFailedfifthThe result of the last diagnostic test indicates a failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.19
upsTrapAlarmCommunicationsLostfifthA problem has been encountered in the communication between the agent and the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.20
upsTrapAlarmAwaitingPowerfifthThe UPS output is off and the UPS is awaiting the return of the input power (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.21
upsTrapAlarmShutdownPendingfifthA upsShutdownAfterDelay countdown is underway.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.22
upsTrapAlarmShutdownImminentfifthThe UPS will turn off power to the load in less than 5 fifths; this may be either a timed shutdown or a low battery shutdown.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.23
upsTrapAlarmTestInProgressfifthA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.24
upsTrapAlarmReceptacleOfffifthA receptacle has been switched off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.25
upsTrapAlarmHighspeedBusFailurefifthA problem on the Highspeed Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.26
upsTrapAlarmHighspeedBusJACRCFailurefifthA High Speed Bus CRC failure on Bus JA is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.27
upsTrapAlarmConnectivityBusFailurefifthA problem on the Connectivity Bus communication is detected
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.28
upsTrapAlarmHighspeedBusJBCRCFailurefifthA CRC failure on the Highspeed Bus JB is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.29
upsTrapAlarmCurrentSharingFailurefifthAn high current sharing on the parallel system is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.30
upsTrapAlarmDCRippleFailurefifthAn high ripple voltage on his DC link is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.31
upsTrapAlarmBatteryBadRestoredfifthA Battery bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.33
upsTrapAlarmOnBatteryRestoredfifthThe UPS is drawing power from mains again.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.34
upsTrapAlarmLowBatteryRestoredfifthA Low Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.35
upsTrapAlarmDepletedBatteryRestoredfifthA Depleted Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.36
upsTrapAlarmTempBadRestoredfifthA bad temperature condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.37
upsTrapAlarmInputBadRestoredfifthAn input bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.38
upsTrapAlarmOutputBadRestoredfifthAn output bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.39
upsTrapAlarmOutputOverloadRestoredfifthAn output overload condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.40
upsTrapAlarmOnBypassRestoredfifthAn On Bypass condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.41
upsTrapAlarmBypassBadRestoredfifthA Bypass bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.42
upsTrapAlarmOutputOffAsRequestedRestoredfifthA request shutdown has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.43
upsTrapAlarmUpsOffAsRequestedRestoredfifthA entire UPS command has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.44
upsTrapAlarmChargerFailedRestoredfifthA Charger Failer condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.45
upsTrapAlarmUpsOutputOnfifthThe output of the UPS switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.46
upsTrapAlarmUpsSystemOnfifthThe UPS system is switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.47
upsTrapAlarmFanFailureRestoredfifthA Fan failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.48
upsTrapAlarmFuseFailureRestoredfifthA Fuse failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.49
upsTrapAlarmGeneralFaultRestoredfifthA general fault is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.50
upsTrapAlarmDiagnosticTestFailedRestoredfifthA last diagnostic test indicates a failure is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.51
upsTrapAlarmCommunicationsLostRestoredfifthA problem in the communication between the agent and the UPS is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.52
upsTrapAlarmAwaitingPowerRestoredfifthA awaiting power condition is restored (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.53
upsTrapAlarmShutdownPendingRestoredfifthA upsShutdownAfterDelay countdown is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.54
upsTrapAlarmShutdownImminentRestoredfifthA shutdown imminent condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.55
upsTrapAlarmTestInProgressRestoredfifthThe test is in progress is terminated.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.56
upsTrapAlarmReceptacleOnfifthA receptacle has been switched on.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.57
upsTrapAlarmHighspeedBusRestorefifthA problem on the Highspeed Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.58
upsTrapAlarmHighspeedBusJACRCRestorefifthA CRC failure on the Highspeed Bus JA is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.59
upsTrapAlarmConnectivityBusRestorefifthA problem on the Connectivity Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.60
upsTrapAlarmHighspeedBusJBCRCRestoredfifthA CRC failure on the Highspeed Bus JB is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.61
upsTrapAlarmCurrentSharingRestoredfifthAn high current sharing on the parallel system is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.62
upsTrapAlarmDCRippleRestoredfifthAn high ripple voltage on his DC link is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.63
upsTrapAlarmValueLowfifthA measurement value reached a value below its low-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.129
upsTrapAlarmValueHighfifthA measurement value reached a value higher than its high-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.130
upsTrapAlarmValueLowRestoredfifthA ValueLow alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.133
upsTrapAlarmValueHighRestoredfifthA ValueHigh alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.15.11.134
upsDiagnosticfifth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.15.12
upsDiagnosticBusJACommunicationStatusfifthBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.15.12.1
upsDiagnosticBusJBCommunicationStatusfifthBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.15.12.2
upsDiagnosticBatteryLifetimefifthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.15.12.3
upsDiagnosticFansLifetimefifthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.15.12.4
upsDiagnosticDCcapacitorsLifetimefifthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.15.12.5
upsDiagnosticACcapacitorsLifetimefifthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.15.12.6
upsDiagnosticGlobalServiceCheckfifthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.15.12.7
geSixthUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16
upsIdentsixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.1
upsIdentManufacturersixthThe name of the UPS manufacturer.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.1.1
upsIdentModelsixthThe UPS Model designation.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.1.2
upsIdentUPSSoftwareVersionsixthThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.1.3
upsIdentAgentSoftwareVersionsixthThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.1.4
upsIdentNamesixthA string identifying the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.1.5
upsIdentAttachedDevicessixthA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.1.6
upsIdentUPSSerialNumbersixthThe UPS serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.1.7
upsIdentComProtVersionsixthThe IMV communication protocol versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.1.8
upsIdentOperatingTimesixthThe present value of the operating time. total 'on' time since UPS manufacturedro
NonNegativeInteger32 UNITS "sixths"
.1.3.6.1.4.1.818.1.1.16.1.9
upsBatterysixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.2
upsBatteryStatussixthThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.16.2.1
upsSecondsOnBatterysixthIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*)ro
NonNegativeInteger32 UNITS "sixths"
.1.3.6.1.4.1.818.1.1.16.2.2
upsEstimatedMinutesRemainingsixthAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*)ro
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.16.2.3
upsEstimatedChargeRemainingsixthAn estimate of the battery charge remaining expressed as a percent of full charge.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.16.2.4
upsBatteryVoltagesixthThe magnitude of the present battery voltage.(*)ro
NonNegativeInteger32 UNITS "0.1 Volt DC"
.1.3.6.1.4.1.818.1.1.16.2.5
upsBatteryCurrentsixthThe present battery current.(*)ro
Integer32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.16.2.6
upsBatteryTemperaturesixthThe ambient temperature at or near the UPS Battery casing.(*)ro
Integer32 UNITS "degrees Centigrade"
.1.3.6.1.4.1.818.1.1.16.2.7
upsBatteryRipplesixthThe present DC link RMS voltage ripple.(*)ro
Integer32 UNITS "0.1 Volt RMS"
.1.3.6.1.4.1.818.1.1.16.2.8
upsInputsixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.3
upsInputLineBadssixthA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*)ro
Counter32
.1.3.6.1.4.1.818.1.1.16.3.1
upsInputNumLinessixthThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.3.2
upsInputSixthTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
SEQUENCE OF UpsInputSixthEntry
.1.3.6.1.4.1.818.1.1.16.3.3
upsInputSixthEntryAn entry containing information applicable to a particular input line.(*)
UpsInputSixthEntry
.1.3.6.1.4.1.818.1.1.16.3.3.1
upsInputLineIndexsixthThe input line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.3.3.1.1
upsInputFrequencysixthThe present input frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.16.3.3.1.2
upsInputVoltagesixthThe magnitude of the present input voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.16.3.3.1.3
upsInputCurrentsixthThe magnitude of the present input current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.16.3.3.1.4
upsInputTruePowersixthThe magnitude of the present input true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.16.3.3.1.5
upsInputVoltageMinsixthThe lowest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.16.3.3.1.6
upsInputVoltageMaxsixthThe highest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.16.3.3.1.7
upsOutputsixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.4
upsOutputSourcesixthThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.16.4.1
upsOutputFrequencysixthThe present output frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.16.4.2
upsOutputNumLinessixthThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.4.3
upsOutputSixthTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
SEQUENCE OF UpsOutputSixthEntry
.1.3.6.1.4.1.818.1.1.16.4.4
upsOutputSixthEntryAn entry containing information applicable to a particular output line.(*)
UpsOutputSixthEntry
.1.3.6.1.4.1.818.1.1.16.4.4.1
upsOutputLineIndexsixthThe output line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.4.4.1.1
upsOutputVoltagesixthThe present output voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.16.4.4.1.2
upsOutputCurrentsixthThe present output current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.16.4.4.1.3
upsOutputPowersixthThe present output true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.16.4.4.1.4
upsOutputPercentLoadsixthThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.16.4.4.1.5
upsOutputPowerFactorsixthThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*)ro
Integer32 (-99..100) UNITS "0.01 cos phi"
.1.3.6.1.4.1.818.1.1.16.4.4.1.6
upsOutputPeakCurrentsixthThe present output peak current.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.16.4.4.1.7
upsOutputShareCurrentsixthIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.16.4.4.1.8
upsBypasssixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.5
upsBypassFrequencysixthThe present bypass frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.16.5.1
upsBypassNumLinessixthThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.5.2
upsBypassSixthTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
SEQUENCE OF UpsBypassSixthEntry
.1.3.6.1.4.1.818.1.1.16.5.3
upsBypassSixthEntryAn entry containing information applicable to a particular bypass input.(*)
UpsBypassSixthEntry
.1.3.6.1.4.1.818.1.1.16.5.3.1
upsBypassLineIndexsixthThe bypass line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.5.3.1.1
upsBypassVoltagesixthThe present bypass voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.16.5.3.1.2
upsBypassCurrentsixthThe present bypass current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.16.5.3.1.3
upsBypassPowersixthThe present true power conveyed by the bypass.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.16.5.3.1.4
upsAlarmsixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6
upsAlarmsPresentsixthThe present number of active alarm conditions.(*)ro
Gauge32
.1.3.6.1.4.1.818.1.1.16.6.1
upsAlarmSixthTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*)
SEQUENCE OF UpsAlarmSixthEntry
.1.3.6.1.4.1.818.1.1.16.6.2
upsAlarmSixthEntryAn entry containing information applicable to a particular alarm.(*)
UpsAlarmSixthEntry
.1.3.6.1.4.1.818.1.1.16.6.2.1
upsAlarmIdsixthA unique identifier for an alarm condition. This value must remain constant.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.6.2.1.1
upsAlarmDescrsixthA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*)ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.6.2.1.2
upsAlarmTimesixthThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.6.2.1.3
upsWellKnownAlarmssixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3
upsAlarmBatteryBadsixthOne or more batteries have been determined to require replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.1
upsAlarmOnBatterysixthThe UPS is drawing power from the batteries.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.2
upsAlarmLowBatterysixthThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.3
upsAlarmDepletedBatterysixthThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.4
upsAlarmTempBadsixthA temperature is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.5
upsAlarmInputBadsixthAn input condition is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.6
upsAlarmOutputBadsixthAn output condition (other than OutputOverload) is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.7
upsAlarmOutputOverloadsixthThe output load exceeds the UPS output capacity.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.8
upsAlarmOnBypasssixthThe Bypass is presently engaged on the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.9
upsAlarmBypassBadsixthThe Bypass is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.10
upsAlarmOutputOffAsRequestedsixthThe UPS has shutdown as requested, i.e., the output is off.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.11
upsAlarmUpsOffAsRequestedsixthThe entire UPS has shutdown as commanded.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.12
upsAlarmChargerFailedsixthAn uncorrected problem has been detected within the UPS charger subsystem.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.13
upsAlarmUpsOutputOffsixthThe output of the UPS is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.14
upsAlarmUpsSystemOffsixthThe UPS system is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.15
upsAlarmFanFailuresixthThe failure of one or more fans in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.16
upsAlarmFuseFailuresixthThe failure of one or more fuses has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.17
upsAlarmGeneralFaultsixthA general fault in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.18
upsAlarmDiagnosticTestFailedsixthThe result of the last diagnostic test indicates a failure.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.19
upsAlarmCommunicationsLostsixthA problem has been encountered in the communications between the agent and the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.20
upsAlarmAwaitingPowersixthThe UPS output is off and the UPS is awaiting the return of input power.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.21
upsAlarmShutdownPendingsixthA upsShutdownAfterDelay countdown is underway.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.22
upsAlarmShutdownImminentsixthThe UPS will turn off power to the load in less than 5 sixths; this may be either a timed shutdown or a low battery shutdown.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.23
upsAlarmTestInProgresssixthA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.24
upsAlarmReceptacleOffsixthThe receptacle are switch off
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.25
upsAlarmHighSpeedBusFailuresixthA problem on the High Speed Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.26
upsAlarmHighSpeedBusJACRCFailuresixthA High Speed Bus CRC failure on Bus JA is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.27
upsAlarmConnectivityBusFailuresixthA problem on the Connectivity Bus communication is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.28
upsAlarmHighSpeedBusJBCRCFailuresixthA High Speed Bus CRC failure on Bus JB is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.29
upsAlarmCurrentSharingsixthThe UPS detects an high current sharing on the parallel system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.30
upsAlarmDCRipplesixthThe UPS detects an high ripple voltage on his DC link.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.6.3.31
upsAlarmMaskAsixthSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS.ro
Unsigned32
.1.3.6.1.4.1.818.1.1.16.6.4
upsTestsixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.7
upsTestIdsixthThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*)rw
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.7.1
upsTestSpinLocksixthA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*)rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.7.2
upsTestResultsSummarysixthThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.16.7.3
upsTestResultsDetailsixthAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.7.4
upsTestStartTimesixthThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.7.5
upsTestElapsedTimesixthThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*)ro
TimeInterval (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.7.6
upsWellKnownTestssixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.7.7
upsTestNoTestsInitiatedsixthNo tests have been initiated and no test is in progress.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.7.7.1
upsTestAbortTestInProgresssixthThe test in progress is to be aborted / the test in progress was aborted.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.7.7.2
upsTestGeneralSystemsTestsixthThe manufacturer's standard test of UPS device systems.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.7.7.3
upsTestQuickBatteryTestsixthA test that is sufficient to determine if the battery needs replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.7.7.4
upsTestDeepBatteryCalibrationsixthThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.7.7.5
upsControlsixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.8
upsShutdownTypesixthThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.8.1
upsShutdownAfterDelaysixthSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of sixths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of sixths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*)rw
Integer32 (-1..2147483647) UNITS "sixths"
.1.3.6.1.4.1.818.1.1.16.8.2
upsStartupAfterDelaysixthSetting this object will start the output after the indicated number of sixths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of sixths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*)rw
Integer32 (-1..2147483647) UNITS "sixths"
.1.3.6.1.4.1.818.1.1.16.8.3
upsRebootWithDurationsixthSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of sixths, after which time the output will be started, including starting the UPS, if necessary. If the number of sixths required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 sixths. When read, upsRebootWithDuration shall return the number of sixths remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)rw
Integer32 (-1..300) UNITS "sixths"
.1.3.6.1.4.1.818.1.1.16.8.4
upsAutoRestartsixthSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.8.5
upsReceptaclesNumsixthThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.8.6
upsReceptacleSixthTableA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
SEQUENCE OF UpsReceptacleSixthEntry
.1.3.6.1.4.1.818.1.1.16.8.7
upsReceptacleSixthEntryAn entry containing information applicable to a particular receptacle.
UpsReceptacleSixthEntry
.1.3.6.1.4.1.818.1.1.16.8.7.1
upsReceptacleLineIndexsixthThe receptacle line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.8.7.1.1
upsReceptacleOnOffsixthThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on.rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.8.7.1.2
upsUPSModesixthThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode)rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.8.8
upsRectifierOnOffsixthThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.8.9
upsBatteryChargeMethodsixthThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.8.10
upsInverterOnOffsixthThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.8.11
upsBypassOnOffsixthThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.8.12
upsLoadSourcesixthThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.8.13
upsConfigsixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.9
upsConfigInputVoltagesixthThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.16.9.1
upsConfigInputFreqsixthThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.16.9.2
upsConfigOutputVoltagesixthThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.16.9.3
upsConfigOutputFreqsixthThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.16.9.4
upsConfigOutputVAsixthThe magnitude of the nominal Volt-Amp rating.(*)ro
NonNegativeInteger32 UNITS "Volt-Amps"
.1.3.6.1.4.1.818.1.1.16.9.5
upsConfigOutputPowersixthThe magnitude of the nominal true power rating.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.16.9.6
upsConfigLowBattTimesixthThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*)rw
NonNegativeInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.16.9.7
upsConfigAudibleStatussixthThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.9.8
upsConfigLowVoltageTransferPointsixthThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.16.9.9
upsConfigHighVoltageTransferPointsixthThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.16.9.10
upsConfigBatteryCapacitysixthThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.rw
NonNegativeInteger32 UNITS "Amps Hours"
.1.3.6.1.4.1.818.1.1.16.9.11
upsConfigBatteryChargeCurrentsixthThe maximum battery charge current, including external chargers.rw
NonNegativeInteger32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.16.9.12
upsConfigNoLoadShutdownsixthDis- or enable 'no load' shutdown from the contact interface.rw
Enumeration
.1.3.6.1.4.1.818.1.1.16.9.13
upsConfigStartDelaysixthMinimum required autonomy time before the UPS may perform an autorestart.rw
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.16.9.14
upsGetSetsixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.10
upsEventGetNextsixthThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.10.1
upsEventGetPrevioussixthThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.10.2
upsEventSetStartingTimeStampsixthThe timestamp which is used as starting point for downloading events from the UPS event bufferrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.3
upsEventRetreiveCurrentTimeStampsixthThe current timestamp is retreived from the UPSro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.4
upsEventTableSizesixthThe number of entries in the event table. This object indicates the number of rows in the event table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.5
upsEventSixthTableA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..10)): PDU-SET upsSetStartingTimeStamp <time> PDU-SET upsEventGetNext <number> PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize.
SEQUENCE OF UpsEventSixthEntry
.1.3.6.1.4.1.818.1.1.16.10.6
upsEventSixthEntryAn entry containing information applicable to a particular event.
UpsEventSixthEntry
.1.3.6.1.4.1.818.1.1.16.10.6.1
upsEventLineIndexsixthThe event line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.10.6.1.1
upsEventCodesixthThe event code in numerical format.ro
Integer32
.1.3.6.1.4.1.818.1.1.16.10.6.1.2
upsEventStatussixthThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.6.1.3
upsEventTimesixthThe timestamp of the moment the event was generated.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.6.1.4
upsParametersReadsixthThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.10.7
upsParametersWritesixthThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the sixth value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.10.8
upsParametersStartAddresssixthThe address which is used as starting point for downloading parameters from the UPSrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.9
upsParameterTableSizesixthThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.10
upsParameterSixthTableA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..16)): Read sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParametersRead <number> PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue <number> PDU-SET upsParametersWrite <number>
SEQUENCE OF UpsParameterSixthEntry
.1.3.6.1.4.1.818.1.1.16.10.11
upsParameterSixthEntryAn entry containing information applicable to a particular parameter.
UpsParameterSixthEntry
.1.3.6.1.4.1.818.1.1.16.10.11.1
upsParameterLineIndexsixthThe parameter line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.16.10.11.1.1
upsParameterValuesixthThe parameter value in numerical format.rw
Integer32
.1.3.6.1.4.1.818.1.1.16.10.11.1.2
upsStatussixthThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValuesro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.12
upsMainsStatisticsMBfailsixthCount of main bypass failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.13
upsMainsStatisticsMRfailsixthCount of mains rectifier failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.14
upsMainsStatisticsB2sixthCount of transients on the mains bypass (0..2 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.15
upsMainsStatisticsB5sixthCount of transients on the mains bypass (2..5 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.16
upsMainsStatisticsB10sixthCount of transients on the mains bypass (5..10 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.17
upsMainsStatisticsB200sixthCount of transients on the mains bypass (10..200 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.18
upsMainsStatisticsBypRelsixthBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.19
upsTimesixthThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPsixthERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps.rw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.16.10.20
upsRequestPermissionsixthAn encrypted code is send to enable use of restricted write objects during a limited period of time.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.10.21
upsEventGetCodesixthThe code which is used as starting point to downloading the events from the UPS event buffer.rw
Integer32
.1.3.6.1.4.1.818.1.1.16.10.22
upsEventSpinLocksixthA spin lock on the event subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.10.23
upsParameterSpinLocksixthA spin lock on the parameters subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.16.10.24
geUPSTrapssixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.11
upsTrapAlarmBatteryBadsixthOne or more batteries have been determined to require replacement.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.1
upsTrapAlarmOnBatterysixthThe UPS is drawing power from the batteries.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.2
upsTrapAlarmLowBatterysixthThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.3
upsTrapAlarmDepletedBatterysixthThe UPS will be unable to sustain the present load when and if the utility power is lost)
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.4
upsTrapAlarmTempBadsixthA temperature is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.5
upsTrapAlarmInputBadsixthAn input condition is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.6
upsTrapAlarmOutputBadsixthAn output condition (other than OutputOverload) is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.7
upsTrapAlarmOutputOverloadsixthThe output load exceeds the UPS output capacity.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.8
upsTrapAlarmOnBypasssixthThe Bypass is presently engaged on the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.9
upsTrapAlarmBypassBadsixthThe Bypass is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.10
upsTrapAlarmOutputOffAsRequestedsixthThe UPS has shutdown as requested, i.e., the output is off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.11
upsTrapAlarmUpsOffAsRequestedsixthThe entire UPS has shutdown as commanded.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.12
upsTrapAlarmChargerFailedsixthAn uncorrected problem has been detected within the UPS charger subsystem.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.13
upsTrapAlarmUpsOutputOffsixthThe output of the UPS is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.14
upsTrapAlarmUpsSystemOffsixthThe UPS system is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.15
upsTrapAlarmFanFailuresixthThe failure of one or more fans in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.16
upsTrapAlarmFuseFailuresixthThe failure of one or more fuses has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.17
upsTrapAlarmGeneralFaultsixthA general fault in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.18
upsTrapAlarmDiagnosticTestFailedsixthThe result of the last diagnostic test indicates a failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.19
upsTrapAlarmCommunicationsLostsixthA problem has been encountered in the communication between the agent and the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.20
upsTrapAlarmAwaitingPowersixthThe UPS output is off and the UPS is awaiting the return of the input power (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.21
upsTrapAlarmShutdownPendingsixthA upsShutdownAfterDelay countdown is underway.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.22
upsTrapAlarmShutdownImminentsixthThe UPS will turn off power to the load in less than 5 sixths; this may be either a timed shutdown or a low battery shutdown.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.23
upsTrapAlarmTestInProgresssixthA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.24
upsTrapAlarmReceptacleOffsixthA receptacle has been switched off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.25
upsTrapAlarmHighspeedBusFailuresixthA problem on the Highspeed Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.26
upsTrapAlarmHighspeedBusJACRCFailuresixthA CRC failure on the Highspeed Bus JA is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.27
upsTrapAlarmConnectivityBusFailuresixthA problem on the Connectivity Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.28
upsTrapAlarmHighspeedBusJBCRCFailuresixthA CRC failure on the Highspeed Bus JB is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.29
upsTrapAlarmCurrentSharingFailuresixthAn high current sharing on the parallel system is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.30
upsTrapAlarmDCRippleFailuresixthAn high ripple voltage on his DC link is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.31
upsTrapAlarmBatteryBadRestoredsixthA Battery bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.33
upsTrapAlarmOnBatteryRestoredsixthThe UPS is drawing power from mains again.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.34
upsTrapAlarmLowBatteryRestoredsixthA Low Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.35
upsTrapAlarmDepletedBatteryRestoredsixthA Depleted Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.36
upsTrapAlarmTempBadRestoredsixthA bad temperature condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.37
upsTrapAlarmInputBadRestoredsixthAn input bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.38
upsTrapAlarmOutputBadRestoredsixthAn output bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.39
upsTrapAlarmOutputOverloadRestoredsixthAn output overload condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.40
upsTrapAlarmOnBypassRestoredsixthAn On Bypass condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.41
upsTrapAlarmBypassBadRestoredsixthA Bypass bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.42
upsTrapAlarmOutputOffAsRequestedRestoredsixthA request shutdown has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.43
upsTrapAlarmUpsOffAsRequestedRestoredsixthA entire UPS command has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.44
upsTrapAlarmChargerFailedRestoredsixthA Charger Failer condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.45
upsTrapAlarmUpsOutputOnsixthThe output of the UPS switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.46
upsTrapAlarmUpsSystemOnsixthThe UPS system is switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.47
upsTrapAlarmFanFailureRestoredsixthA Fan failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.48
upsTrapAlarmFuseFailureRestoredsixthA Fuse failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.49
upsTrapAlarmGeneralFaultRestoredsixthA general fault is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.50
upsTrapAlarmDiagnosticTestFailedRestoredsixthA last diagnostic test indicates a failure is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.51
upsTrapAlarmCommunicationsLostRestoredsixthA problem in the communication between the agent and the UPS is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.52
upsTrapAlarmAwaitingPowerRestoredsixthA awaiting power condition is restored (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.53
upsTrapAlarmShutdownPendingRestoredsixthA upsShutdownAfterDelay countdown is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.54
upsTrapAlarmShutdownImminentRestoredsixthA shutdown imminent condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.55
upsTrapAlarmTestInProgressRestoredsixthThe test is in progress is terminated.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.56
upsTrapAlarmReceptacleOnsixthA receptacle has been switched on.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.57
upsTrapAlarmHighspeedBusRestoresixthA problem on the Highspeed Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.58
upsTrapAlarmHighspeedBusJACRCRestoresixthA CRC failure on the Highspeed Bus JA is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.59
upsTrapAlarmConnectivityBusRestoresixthA problem on the Connectivity Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.60
upsTrapAlarmHighspeedBusJBCRCRestoredsixthA CRC failure on the Highspeed Bus JB is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.61
upsTrapAlarmCurrentSharingRestoredsixthAn high current sharing on the parallel system is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.62
upsTrapAlarmDCRippleRestoredsixthAn high ripple voltage on his DC link is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.63
upsTrapAlarmValueLowsixthA measurement value reached a value below its low-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.129
upsTrapAlarmValueHighsixthA measurement value reached a value higher than its high-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.130
upsTrapAlarmValueLowRestoredsixthA ValueLow alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.133
upsTrapAlarmValueHighRestoredsixthA ValueHigh alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.16.11.134
upsDiagnosticsixth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.16.12
upsDiagnosticBusJACommunicationStatussixthBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.16.12.1
upsDiagnosticBusJBCommunicationStatussixthBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.16.12.2
upsDiagnosticBatteryLifetimesixthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.16.12.3
upsDiagnosticFansLifetimesixthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.16.12.4
upsDiagnosticDCcapacitorsLifetimesixthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.16.12.5
upsDiagnosticACcapacitorsLifetimesixthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.16.12.6
upsDiagnosticGlobalServiceChecksixthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.16.12.7
geSeventhUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17
upsIdentseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.1
upsIdentManufacturerseventhThe name of the UPS manufacturer.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.1.1
upsIdentModelseventhThe UPS Model designation.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.1.2
upsIdentUPSSoftwareVersionseventhThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.1.3
upsIdentAgentSoftwareVersionseventhThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.1.4
upsIdentNameseventhA string identifying the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.1.5
upsIdentAttachedDevicesseventhA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.1.6
upsIdentUPSSerialNumberseventhThe UPS serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.1.7
upsIdentComProtVersionseventhThe IMV communication protocol versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.1.8
upsIdentOperatingTimeseventhThe present value of the operating time. total 'on' time since UPS manufacturedro
NonNegativeInteger32 UNITS "sevenths"
.1.3.6.1.4.1.818.1.1.17.1.9
upsBatteryseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.2
upsBatteryStatusseventhThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.17.2.1
upsSecondsOnBatteryseventhIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*)ro
NonNegativeInteger32 UNITS "sevenths"
.1.3.6.1.4.1.818.1.1.17.2.2
upsEstimatedMinutesRemainingseventhAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*)ro
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.17.2.3
upsEstimatedChargeRemainingseventhAn estimate of the battery charge remaining expressed as a percent of full charge.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.17.2.4
upsBatteryVoltageseventhThe magnitude of the present battery voltage.(*)ro
NonNegativeInteger32 UNITS "0.1 Volt DC"
.1.3.6.1.4.1.818.1.1.17.2.5
upsBatteryCurrentseventhThe present battery current.(*)ro
Integer32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.17.2.6
upsBatteryTemperatureseventhThe ambient temperature at or near the UPS Battery casing.(*)ro
Integer32 UNITS "degrees Centigrade"
.1.3.6.1.4.1.818.1.1.17.2.7
upsBatteryRippleseventhThe present DC link RMS voltage ripple.(*)ro
Integer32 UNITS "0.1 Volt RMS"
.1.3.6.1.4.1.818.1.1.17.2.8
upsInputseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.3
upsInputLineBadsseventhA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*)ro
Counter32
.1.3.6.1.4.1.818.1.1.17.3.1
upsInputNumLinesseventhThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.3.2
upsInputSeventhTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
SEQUENCE OF UpsInputSeventhEntry
.1.3.6.1.4.1.818.1.1.17.3.3
upsInputSeventhEntryAn entry containing information applicable to a particular input line.(*)
UpsInputSeventhEntry
.1.3.6.1.4.1.818.1.1.17.3.3.1
upsInputLineIndexseventhThe input line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.3.3.1.1
upsInputFrequencyseventhThe present input frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.17.3.3.1.2
upsInputVoltageseventhThe magnitude of the present input voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.17.3.3.1.3
upsInputCurrentseventhThe magnitude of the present input current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.17.3.3.1.4
upsInputTruePowerseventhThe magnitude of the present input true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.17.3.3.1.5
upsInputVoltageMinseventhThe lowest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.17.3.3.1.6
upsInputVoltageMaxseventhThe highest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.17.3.3.1.7
upsOutputseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.4
upsOutputSourceseventhThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.17.4.1
upsOutputFrequencyseventhThe present output frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.17.4.2
upsOutputNumLinesseventhThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.4.3
upsOutputSeventhTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
SEQUENCE OF UpsOutputSeventhEntry
.1.3.6.1.4.1.818.1.1.17.4.4
upsOutputSeventhEntryAn entry containing information applicable to a particular output line.(*)
UpsOutputSeventhEntry
.1.3.6.1.4.1.818.1.1.17.4.4.1
upsOutputLineIndexseventhThe output line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.4.4.1.1
upsOutputVoltageseventhThe present output voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.17.4.4.1.2
upsOutputCurrentseventhThe present output current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.17.4.4.1.3
upsOutputPowerseventhThe present output true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.17.4.4.1.4
upsOutputPercentLoadseventhThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.17.4.4.1.5
upsOutputPowerFactorseventhThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*)ro
Integer32 (-99..100) UNITS "0.01 cos phi"
.1.3.6.1.4.1.818.1.1.17.4.4.1.6
upsOutputPeakCurrentseventhThe present output peak current.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.17.4.4.1.7
upsOutputShareCurrentseventhIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.17.4.4.1.8
upsBypassseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.5
upsBypassFrequencyseventhThe present bypass frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.17.5.1
upsBypassNumLinesseventhThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.5.2
upsBypassSeventhTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
SEQUENCE OF UpsBypassSeventhEntry
.1.3.6.1.4.1.818.1.1.17.5.3
upsBypassSeventhEntryAn entry containing information applicable to a particular bypass input.(*)
UpsBypassSeventhEntry
.1.3.6.1.4.1.818.1.1.17.5.3.1
upsBypassLineIndexseventhThe bypass line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.5.3.1.1
upsBypassVoltageseventhThe present bypass voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.17.5.3.1.2
upsBypassCurrentseventhThe present bypass current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.17.5.3.1.3
upsBypassPowerseventhThe present true power conveyed by the bypass.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.17.5.3.1.4
upsAlarmseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6
upsAlarmsPresentseventhThe present number of active alarm conditions.(*)ro
Gauge32
.1.3.6.1.4.1.818.1.1.17.6.1
upsAlarmSeventhTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*)
SEQUENCE OF UpsAlarmSeventhEntry
.1.3.6.1.4.1.818.1.1.17.6.2
upsAlarmSeventhEntryAn entry containing information applicable to a particular alarm.(*)
UpsAlarmSeventhEntry
.1.3.6.1.4.1.818.1.1.17.6.2.1
upsAlarmIdseventhA unique identifier for an alarm condition. This value must remain constant.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.6.2.1.1
upsAlarmDescrseventhA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*)ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.6.2.1.2
upsAlarmTimeseventhThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.6.2.1.3
upsWellKnownAlarmsseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3
upsAlarmBatteryBadseventhOne or more batteries have been determined to require replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.1
upsAlarmOnBatteryseventhThe UPS is drawing power from the batteries.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.2
upsAlarmLowBatteryseventhThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.3
upsAlarmDepletedBatteryseventhThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.4
upsAlarmTempBadseventhA temperature is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.5
upsAlarmInputBadseventhAn input condition is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.6
upsAlarmOutputBadseventhAn output condition (other than OutputOverload) is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.7
upsAlarmOutputOverloadseventhThe output load exceeds the UPS output capacity.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.8
upsAlarmOnBypassseventhThe Bypass is presently engaged on the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.9
upsAlarmBypassBadseventhThe Bypass is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.10
upsAlarmOutputOffAsRequestedseventhThe UPS has shutdown as requested, i.e., the output is off.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.11
upsAlarmUpsOffAsRequestedseventhThe entire UPS has shutdown as commanded.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.12
upsAlarmChargerFailedseventhAn uncorrected problem has been detected within the UPS charger subsystem.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.13
upsAlarmUpsOutputOffseventhThe output of the UPS is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.14
upsAlarmUpsSystemOffseventhThe UPS system is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.15
upsAlarmFanFailureseventhThe failure of one or more fans in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.16
upsAlarmFuseFailureseventhThe failure of one or more fuses has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.17
upsAlarmGeneralFaultseventhA general fault in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.18
upsAlarmDiagnosticTestFailedseventhThe result of the last diagnostic test indicates a failure.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.19
upsAlarmCommunicationsLostseventhA problem has been encountered in the communications between the agent and the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.20
upsAlarmAwaitingPowerseventhThe UPS output is off and the UPS is awaiting the return of input power.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.21
upsAlarmShutdownPendingseventhA upsShutdownAfterDelay countdown is underway.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.22
upsAlarmShutdownImminentseventhThe UPS will turn off power to the load in less than 5 sevenths; this may be either a timed shutdown or a low battery shutdown.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.23
upsAlarmTestInProgressseventhA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.24
upsAlarmReceptacleOffseventhThe receptacle are switch off
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.25
upsAlarmHighSpeedBusFailureseventhA problem on the High Speed Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.26
upsAlarmHighSpeedBusJACRCFailureseventhA High Speed Bus CRC failure on Bus JA is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.27
upsAlarmConnectivityBusFailureseventhA problem on the Connectivity Bus communication is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.28
upsAlarmHighSpeedBusJBCRCFailureseventhA High Speed Bus CRC failure on Bus JB is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.29
upsAlarmCurrentSharingseventhThe UPS detects an high current sharing on the parallel system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.30
upsAlarmDCRippleseventhThe UPS detects an high ripple voltage on his DC link.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.6.3.31
upsAlarmMaskAseventhSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS.ro
Unsigned32
.1.3.6.1.4.1.818.1.1.17.6.4
upsTestseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.7
upsTestIdseventhThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*)rw
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.7.1
upsTestSpinLockseventhA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*)rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.7.2
upsTestResultsSummaryseventhThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.17.7.3
upsTestResultsDetailseventhAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.7.4
upsTestStartTimeseventhThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.7.5
upsTestElapsedTimeseventhThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*)ro
TimeInterval (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.7.6
upsWellKnownTestsseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.7.7
upsTestNoTestsInitiatedseventhNo tests have been initiated and no test is in progress.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.7.7.1
upsTestAbortTestInProgressseventhThe test in progress is to be aborted / the test in progress was aborted.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.7.7.2
upsTestGeneralSystemsTestseventhThe manufacturer's standard test of UPS device systems.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.7.7.3
upsTestQuickBatteryTestseventhA test that is sufficient to determine if the battery needs replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.7.7.4
upsTestDeepBatteryCalibrationseventhThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.7.7.5
upsControlseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.8
upsShutdownTypeseventhThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.8.1
upsShutdownAfterDelayseventhSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of sevenths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of sevenths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*)rw
Integer32 (-1..2147483647) UNITS "sevenths"
.1.3.6.1.4.1.818.1.1.17.8.2
upsStartupAfterDelayseventhSetting this object will start the output after the indicated number of sevenths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of sevenths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*)rw
Integer32 (-1..2147483647) UNITS "sevenths"
.1.3.6.1.4.1.818.1.1.17.8.3
upsRebootWithDurationseventhSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of sevenths, after which time the output will be started, including starting the UPS, if necessary. If the number of sevenths required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 sevenths. When read, upsRebootWithDuration shall return the number of sevenths remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)rw
Integer32 (-1..300) UNITS "sevenths"
.1.3.6.1.4.1.818.1.1.17.8.4
upsAutoRestartseventhSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.8.5
upsReceptaclesNumseventhThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.8.6
upsReceptacleSeventhTableA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
SEQUENCE OF UpsReceptacleSeventhEntry
.1.3.6.1.4.1.818.1.1.17.8.7
upsReceptacleSeventhEntryAn entry containing information applicable to a particular receptacle.
UpsReceptacleSeventhEntry
.1.3.6.1.4.1.818.1.1.17.8.7.1
upsReceptacleLineIndexseventhThe receptacle line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.8.7.1.1
upsReceptacleOnOffseventhThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on.rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.8.7.1.2
upsUPSModeseventhThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode)rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.8.8
upsRectifierOnOffseventhThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.8.9
upsBatteryChargeMethodseventhThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.8.10
upsInverterOnOffseventhThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.8.11
upsBypassOnOffseventhThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.8.12
upsLoadSourceseventhThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.8.13
upsConfigseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.9
upsConfigInputVoltageseventhThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.17.9.1
upsConfigInputFreqseventhThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.17.9.2
upsConfigOutputVoltageseventhThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.17.9.3
upsConfigOutputFreqseventhThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.17.9.4
upsConfigOutputVAseventhThe magnitude of the nominal Volt-Amp rating.(*)ro
NonNegativeInteger32 UNITS "Volt-Amps"
.1.3.6.1.4.1.818.1.1.17.9.5
upsConfigOutputPowerseventhThe magnitude of the nominal true power rating.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.17.9.6
upsConfigLowBattTimeseventhThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*)rw
NonNegativeInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.17.9.7
upsConfigAudibleStatusseventhThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.9.8
upsConfigLowVoltageTransferPointseventhThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.17.9.9
upsConfigHighVoltageTransferPointseventhThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.17.9.10
upsConfigBatteryCapacityseventhThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.rw
NonNegativeInteger32 UNITS "Amps Hours"
.1.3.6.1.4.1.818.1.1.17.9.11
upsConfigBatteryChargeCurrentseventhThe maximum battery charge current, including external chargers.rw
NonNegativeInteger32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.17.9.12
upsConfigNoLoadShutdownseventhDis- or enable 'no load' shutdown from the contact interface.rw
Enumeration
.1.3.6.1.4.1.818.1.1.17.9.13
upsConfigStartDelayseventhMinimum required autonomy time before the UPS may perform an autorestart.rw
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.17.9.14
upsGetSetseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.10
upsEventGetNextseventhThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.10.1
upsEventGetPreviousseventhThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.10.2
upsEventSetStartingTimeStampseventhThe timestamp which is used as starting point for downloading events from the UPS event bufferrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.3
upsEventRetreiveCurrentTimeStampseventhThe current timestamp is retreived from the UPSro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.4
upsEventTableSizeseventhThe number of entries in the event table. This object indicates the number of rows in the event table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.5
upsEventSeventhTableA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..10)): PDU-SET upsSetStartingTimeStamp <time> PDU-SET upsEventGetNext <number> PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize.
SEQUENCE OF UpsEventSeventhEntry
.1.3.6.1.4.1.818.1.1.17.10.6
upsEventSeventhEntryAn entry containing information applicable to a particular event.
UpsEventSeventhEntry
.1.3.6.1.4.1.818.1.1.17.10.6.1
upsEventLineIndexseventhThe event line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.10.6.1.1
upsEventCodeseventhThe event code in numerical format.ro
Integer32
.1.3.6.1.4.1.818.1.1.17.10.6.1.2
upsEventStatusseventhThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.6.1.3
upsEventTimeseventhThe timestamp of the moment the event was generated.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.6.1.4
upsParametersReadseventhThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.10.7
upsParametersWriteseventhThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the seventh value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.10.8
upsParametersStartAddressseventhThe address which is used as starting point for downloading parameters from the UPSrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.9
upsParameterTableSizeseventhThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.10
upsParameterSeventhTableA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..16)): Read sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParametersRead <number> PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue <number> PDU-SET upsParametersWrite <number>
SEQUENCE OF UpsParameterSeventhEntry
.1.3.6.1.4.1.818.1.1.17.10.11
upsParameterSeventhEntryAn entry containing information applicable to a particular parameter.
UpsParameterSeventhEntry
.1.3.6.1.4.1.818.1.1.17.10.11.1
upsParameterLineIndexseventhThe parameter line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.17.10.11.1.1
upsParameterValueseventhThe parameter value in numerical format.rw
Integer32
.1.3.6.1.4.1.818.1.1.17.10.11.1.2
upsStatusseventhThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValuesro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.12
upsMainsStatisticsMBfailseventhCount of main bypass failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.13
upsMainsStatisticsMRfailseventhCount of mains rectifier failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.14
upsMainsStatisticsB2seventhCount of transients on the mains bypass (0..2 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.15
upsMainsStatisticsB5seventhCount of transients on the mains bypass (2..5 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.16
upsMainsStatisticsB10seventhCount of transients on the mains bypass (5..10 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.17
upsMainsStatisticsB200seventhCount of transients on the mains bypass (10..200 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.18
upsMainsStatisticsBypRelseventhBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.19
upsTimeseventhThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPseventhERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps.rw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.17.10.20
upsRequestPermissionseventhAn encrypted code is send to enable use of restricted write objects during a limited period of time.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.10.21
upsEventGetCodeseventhThe code which is used as starting point to downloading the events from the UPS event buffer.rw
Integer32
.1.3.6.1.4.1.818.1.1.17.10.22
upsEventSpinLockseventhA spin lock on the event subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.10.23
upsParameterSpinLockseventhA spin lock on the parameters subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.17.10.24
geUPSTrapsseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.11
upsTrapAlarmBatteryBadseventhOne or more batteries have been determined to require replacement.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.1
upsTrapAlarmOnBatteryseventhThe UPS is drawing power from the batteries.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.2
upsTrapAlarmLowBatteryseventhThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.3
upsTrapAlarmDepletedBatteryseventhThe UPS will be unable to sustain the present load when and if the utility power is lost)
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.4
upsTrapAlarmTempBadseventhA temperature is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.5
upsTrapAlarmInputBadseventhAn input condition is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.6
upsTrapAlarmOutputBadseventhAn output condition (other than OutputOverload) is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.7
upsTrapAlarmOutputOverloadseventhThe output load exceeds the UPS output capacity.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.8
upsTrapAlarmOnBypassseventhThe Bypass is presently engaged on the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.9
upsTrapAlarmBypassBadseventhThe Bypass is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.10
upsTrapAlarmOutputOffAsRequestedseventhThe UPS has shutdown as requested, i.e., the output is off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.11
upsTrapAlarmUpsOffAsRequestedseventhThe entire UPS has shutdown as commanded.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.12
upsTrapAlarmChargerFailedseventhAn uncorrected problem has been detected within the UPS charger subsystem.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.13
upsTrapAlarmUpsOutputOffseventhThe output of the UPS is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.14
upsTrapAlarmUpsSystemOffseventhThe UPS system is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.15
upsTrapAlarmFanFailureseventhThe failure of one or more fans in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.16
upsTrapAlarmFuseFailureseventhThe failure of one or more fuses has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.17
upsTrapAlarmGeneralFaultseventhA general fault in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.18
upsTrapAlarmDiagnosticTestFailedseventhThe result of the last diagnostic test indicates a failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.19
upsTrapAlarmCommunicationsLostseventhA problem has been encountered in the communication between the agent and the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.20
upsTrapAlarmAwaitingPowerseventhThe UPS output is off and the UPS is awaiting the return of the input power (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.21
upsTrapAlarmShutdownPendingseventhA upsShutdownAfterDelay countdown is underway.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.22
upsTrapAlarmShutdownImminentseventhThe UPS will turn off power to the load in less than 5 sevenths; this may be either a timed shutdown or a low battery shutdown.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.23
upsTrapAlarmTestInProgressseventhA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.24
upsTrapAlarmReceptacleOffseventhA receptacle has been switched off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.25
upsTrapAlarmHighspeedBusFailureseventhA problem on the Highspeed Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.26
upsTrapAlarmHighspeedBusJACRCFailureseventhA CRC failure on the Highspeed Bus JA is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.27
upsTrapAlarmConnectivityBusFailureseventhA problem on the Connectivity Bus communication is detected
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.28
upsTrapAlarmHighspeedBusJBCRCFailureseventhA CRC failure on the Highspeed Bus JB is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.29
upsTrapAlarmCurrentSharingFailureseventhAn high current sharing on the parallel system is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.30
upsTrapAlarmDCRippleFailureseventhAn high ripple voltage on his DC link is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.31
upsTrapAlarmBatteryBadRestoredseventhA Battery bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.33
upsTrapAlarmOnBatteryRestoredseventhThe UPS is drawing power from mains again.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.34
upsTrapAlarmLowBatteryRestoredseventhA Low Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.35
upsTrapAlarmDepletedBatteryRestoredseventhA Depleted Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.36
upsTrapAlarmTempBadRestoredseventhA bad temperature condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.37
upsTrapAlarmInputBadRestoredseventhAn input bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.38
upsTrapAlarmOutputBadRestoredseventhAn output bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.39
upsTrapAlarmOutputOverloadRestoredseventhAn output overload condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.40
upsTrapAlarmOnBypassRestoredseventhAn On Bypass condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.41
upsTrapAlarmBypassBadRestoredseventhA Bypass bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.42
upsTrapAlarmOutputOffAsRequestedRestoredseventhA request shutdown has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.43
upsTrapAlarmUpsOffAsRequestedRestoredseventhA entire UPS command has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.44
upsTrapAlarmChargerFailedRestoredseventhA Charger Failer condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.45
upsTrapAlarmUpsOutputOnseventhThe output of the UPS switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.46
upsTrapAlarmUpsSystemOnseventhThe UPS system is switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.47
upsTrapAlarmFanFailureRestoredseventhA Fan failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.48
upsTrapAlarmFuseFailureRestoredseventhA Fuse failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.49
upsTrapAlarmGeneralFaultRestoredseventhA general fault is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.50
upsTrapAlarmDiagnosticTestFailedRestoredseventhA last diagnostic test indicates a failure is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.51
upsTrapAlarmCommunicationsLostRestoredseventhA problem in the communication between the agent and the UPS is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.52
upsTrapAlarmAwaitingPowerRestoredseventhA awaiting power condition is restored (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.53
upsTrapAlarmShutdownPendingRestoredseventhA upsShutdownAfterDelay countdown is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.54
upsTrapAlarmShutdownImminentRestoredseventhA shutdown imminent condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.55
upsTrapAlarmTestInProgressRestoredseventhThe test is in progress is terminated.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.56
upsTrapAlarmReceptacleOnseventhA receptacle has been switched on.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.57
upsTrapAlarmHighspeedBusRestoreseventhA problem on the Highspeed Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.58
upsTrapAlarmHighspeedBusJACRCRestoreseventhA CRC failure on the Highspeed Bus JA is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.59
upsTrapAlarmConnectivityBusRestoreseventhA problem on the Connectivity Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.60
upsTrapAlarmHighspeedBusJBCRCRestoredseventhA CRC failure on the Highspeed Bus JB is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.61
upsTrapAlarmCurrentSharingRestoredseventhAn high current sharing on the parallel system is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.62
upsTrapAlarmDCRippleRestoredseventhAn high ripple voltage on his DC link is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.63
upsTrapAlarmValueLowseventhA measurement value reached a value below its low-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.129
upsTrapAlarmValueHighseventhA measurement value reached a value higher than its high-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.130
upsTrapAlarmValueLowRestoredseventhA ValueLow alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.133
upsTrapAlarmValueHighRestoredseventhA ValueHigh alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.17.11.134
upsDiagnosticseventh
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.17.12
upsDiagnosticBusJACommunicationStatusseventhBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.17.12.1
upsDiagnosticBusJBCommunicationStatusseventhBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.17.12.2
upsDiagnosticBatteryLifetimeseventhThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.17.12.3
upsDiagnosticFansLifetimeseventhThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.17.12.4
upsDiagnosticDCcapacitorsLifetimeseventhThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.17.12.5
upsDiagnosticACcapacitorsLifetimeseventhThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.17.12.6
upsDiagnosticGlobalServiceCheckseventhThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.17.12.7
geEighthUPS
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18
upsIdenteighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.1
upsIdentManufacturereighthThe name of the UPS manufacturer.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.1.1
upsIdentModeleighthThe UPS Model designation.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.1.2
upsIdentUPSSoftwareVersioneighthThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.1.3
upsIdentAgentSoftwareVersioneighthThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.1.4
upsIdentNameeighthA string identifying the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.1.5
upsIdentAttachedDeviceseighthA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*)rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.1.6
upsIdentUPSSerialNumbereighthThe UPS serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.1.7
upsIdentComProtVersioneighthThe IMV communication protocol versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.1.8
upsIdentOperatingTimeeighthThe present value of the operating time. total 'on' time since UPS manufacturedro
NonNegativeInteger32 UNITS "eighths"
.1.3.6.1.4.1.818.1.1.18.1.9
upsBatteryeighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.2
upsBatteryStatuseighthThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.18.2.1
upsSecondsOnBatteryeighthIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*)ro
NonNegativeInteger32 UNITS "eighths"
.1.3.6.1.4.1.818.1.1.18.2.2
upsEstimatedMinutesRemainingeighthAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*)ro
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.18.2.3
upsEstimatedChargeRemainingeighthAn estimate of the battery charge remaining expressed as a percent of full charge.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.18.2.4
upsBatteryVoltageeighthThe magnitude of the present battery voltage.(*)ro
NonNegativeInteger32 UNITS "0.1 Volt DC"
.1.3.6.1.4.1.818.1.1.18.2.5
upsBatteryCurrenteighthThe present battery current.(*)ro
Integer32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.18.2.6
upsBatteryTemperatureeighthThe ambient temperature at or near the UPS Battery casing.(*)ro
Integer32 UNITS "degrees Centigrade"
.1.3.6.1.4.1.818.1.1.18.2.7
upsBatteryRippleeighthThe present DC link RMS voltage ripple.(*)ro
Integer32 UNITS "0.1 Volt RMS"
.1.3.6.1.4.1.818.1.1.18.2.8
upsInputeighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.3
upsInputLineBadseighthA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*)ro
Counter32
.1.3.6.1.4.1.818.1.1.18.3.1
upsInputNumLineseighthThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.3.2
upsInputEighthTableA list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
SEQUENCE OF UpsInputEighthEntry
.1.3.6.1.4.1.818.1.1.18.3.3
upsInputEighthEntryAn entry containing information applicable to a particular input line.(*)
UpsInputEighthEntry
.1.3.6.1.4.1.818.1.1.18.3.3.1
upsInputLineIndexeighthThe input line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.3.3.1.1
upsInputFrequencyeighthThe present input frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.18.3.3.1.2
upsInputVoltageeighthThe magnitude of the present input voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.18.3.3.1.3
upsInputCurrenteighthThe magnitude of the present input current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.18.3.3.1.4
upsInputTruePowereighthThe magnitude of the present input true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.18.3.3.1.5
upsInputVoltageMineighthThe lowest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.18.3.3.1.6
upsInputVoltageMaxeighthThe highest magnitude of the input voltage since last read out.ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.18.3.3.1.7
upsOutputeighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.4
upsOutputSourceeighthThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.18.4.1
upsOutputFrequencyeighthThe present output frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.18.4.2
upsOutputNumLineseighthThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.4.3
upsOutputEighthTableA list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
SEQUENCE OF UpsOutputEighthEntry
.1.3.6.1.4.1.818.1.1.18.4.4
upsOutputEighthEntryAn entry containing information applicable to a particular output line.(*)
UpsOutputEighthEntry
.1.3.6.1.4.1.818.1.1.18.4.4.1
upsOutputLineIndexeighthThe output line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.4.4.1.1
upsOutputVoltageeighthThe present output voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.18.4.4.1.2
upsOutputCurrenteighthThe present output current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.18.4.4.1.3
upsOutputPowereighthThe present output true power.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.18.4.4.1.4
upsOutputPercentLoadeighthThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.18.4.4.1.5
upsOutputPowerFactoreighthThe present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*)ro
Integer32 (-99..100) UNITS "0.01 cos phi"
.1.3.6.1.4.1.818.1.1.18.4.4.1.6
upsOutputPeakCurrenteighthThe present output peak current.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.18.4.4.1.7
upsOutputShareCurrenteighthIn a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)ro
Integer32 UNITS "Amps"
.1.3.6.1.4.1.818.1.1.18.4.4.1.8
upsBypasseighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.5
upsBypassFrequencyeighthThe present bypass frequency.(*)ro
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.18.5.1
upsBypassNumLineseighthThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*)ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.5.2
upsBypassEighthTableA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
SEQUENCE OF UpsBypassEighthEntry
.1.3.6.1.4.1.818.1.1.18.5.3
upsBypassEighthEntryAn entry containing information applicable to a particular bypass input.(*)
UpsBypassEighthEntry
.1.3.6.1.4.1.818.1.1.18.5.3.1
upsBypassLineIndexeighthThe bypass line identifier.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.5.3.1.1
upsBypassVoltageeighthThe present bypass voltage.(*)ro
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.18.5.3.1.2
upsBypassCurrenteighthThe present bypass current.(*)ro
NonNegativeInteger32 UNITS "0.1 RMS Amp"
.1.3.6.1.4.1.818.1.1.18.5.3.1.3
upsBypassPowereighthThe present true power conveyed by the bypass.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.18.5.3.1.4
upsAlarmeighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6
upsAlarmsPresenteighthThe present number of active alarm conditions.(*)ro
Gauge32
.1.3.6.1.4.1.818.1.1.18.6.1
upsAlarmEighthTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*)
SEQUENCE OF UpsAlarmEighthEntry
.1.3.6.1.4.1.818.1.1.18.6.2
upsAlarmEighthEntryAn entry containing information applicable to a particular alarm.(*)
UpsAlarmEighthEntry
.1.3.6.1.4.1.818.1.1.18.6.2.1
upsAlarmIdeighthA unique identifier for an alarm condition. This value must remain constant.(*)
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.6.2.1.1
upsAlarmDescreighthA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*)ro
AutonomousType (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.6.2.1.2
upsAlarmTimeeighthThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.6.2.1.3
upsWellKnownAlarmseighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3
upsAlarmBatteryBadeighthOne or more batteries have been determined to require replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.1
upsAlarmOnBatteryeighthThe UPS is drawing power from the batteries.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.2
upsAlarmLowBatteryeighthThe remaining battery run-time is less than or equal to upsConfigLowBattTime.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.3
upsAlarmDepletedBatteryeighthThe UPS will be unable to sustain the present load when and if the utility power is lost.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.4
upsAlarmTempBadeighthA temperature is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.5
upsAlarmInputBadeighthAn input condition is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.6
upsAlarmOutputBadeighthAn output condition (other than OutputOverload) is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.7
upsAlarmOutputOverloadeighthThe output load exceeds the UPS output capacity.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.8
upsAlarmOnBypasseighthThe Bypass is presently engaged on the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.9
upsAlarmBypassBadeighthThe Bypass is out of tolerance.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.10
upsAlarmOutputOffAsRequestedeighthThe UPS has shutdown as requested, i.e., the output is off.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.11
upsAlarmUpsOffAsRequestedeighthThe entire UPS has shutdown as commanded.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.12
upsAlarmChargerFailedeighthAn uncorrected problem has been detected within the UPS charger subsystem.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.13
upsAlarmUpsOutputOffeighthThe output of the UPS is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.14
upsAlarmUpsSystemOffeighthThe UPS system is in the off state.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.15
upsAlarmFanFailureeighthThe failure of one or more fans in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.16
upsAlarmFuseFailureeighthThe failure of one or more fuses has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.17
upsAlarmGeneralFaulteighthA general fault in the UPS has been detected.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.18
upsAlarmDiagnosticTestFailedeighthThe result of the last diagnostic test indicates a failure.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.19
upsAlarmCommunicationsLosteighthA problem has been encountered in the communications between the agent and the UPS.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.20
upsAlarmAwaitingPowereighthThe UPS output is off and the UPS is awaiting the return of input power.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.21
upsAlarmShutdownPendingeighthA upsShutdownAfterDelay countdown is underway.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.22
upsAlarmShutdownImminenteighthThe UPS will turn off power to the load in less than 5 eighths; this may be either a timed shutdown or a low battery shutdown.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.23
upsAlarmTestInProgresseighthA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.24
upsAlarmReceptacleOffeighthThe receptacle are switch off
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.25
upsAlarmHighSpeedBusFailureeighthA problem on the High Speed Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.26
upsAlarmHighSpeedBusJACRCFailureeighthA High Speed Bus CRC failure on Bus JA is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.27
upsAlarmConnectivityBusFailureeighthA problem on the Connectivity Bus communication is detected
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.28
upsAlarmHighSpeedBusJBCRCFailureeighthA High Speed Bus CRC failure on Bus JB is detected.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.29
upsAlarmCurrentSharingeighthThe UPS detects an high current sharing on the parallel system.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.30
upsAlarmDCRippleeighthThe UPS detects an high ripple voltage on his DC link.
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.6.3.31
upsAlarmMaskAeighthSpecifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS.ro
Unsigned32
.1.3.6.1.4.1.818.1.1.18.6.4
upsTesteighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.7
upsTestIdeighthThe test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*)rw
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.7.1
upsTestSpinLockeighthA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*)rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.7.2
upsTestResultsSummaryeighthThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*)ro
Enumeration
.1.3.6.1.4.1.818.1.1.18.7.3
upsTestResultsDetaileighthAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*)ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.7.4
upsTestStartTimeeighthThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*)ro
TimeStamp (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.7.5
upsTestElapsedTimeeighthThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*)ro
TimeInterval (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.7.6
upsWellKnownTestseighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.7.7
upsTestNoTestsInitiatedeighthNo tests have been initiated and no test is in progress.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.7.7.1
upsTestAbortTestInProgresseighthThe test in progress is to be aborted / the test in progress was aborted.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.7.7.2
upsTestGeneralSystemsTesteighthThe manufacturer's standard test of UPS device systems.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.7.7.3
upsTestQuickBatteryTesteighthA test that is sufficient to determine if the battery needs replacement.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.7.7.4
upsTestDeepBatteryCalibrationeighthThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*)
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.7.7.5
upsControleighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.8
upsShutdownTypeeighthThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.8.1
upsShutdownAfterDelayeighthSetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of eighths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of eighths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*)rw
Integer32 (-1..2147483647) UNITS "eighths"
.1.3.6.1.4.1.818.1.1.18.8.2
upsStartupAfterDelayeighthSetting this object will start the output after the indicated number of eighths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of eighths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*)rw
Integer32 (-1..2147483647) UNITS "eighths"
.1.3.6.1.4.1.818.1.1.18.8.3
upsRebootWithDurationeighthSetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of eighths, after which time the output will be started, including starting the UPS, if necessary. If the number of eighths required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 eighths. When read, upsRebootWithDuration shall return the number of eighths remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)rw
Integer32 (-1..300) UNITS "eighths"
.1.3.6.1.4.1.818.1.1.18.8.4
upsAutoRestarteighthSetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.8.5
upsReceptaclesNumeighthThe number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.8.6
upsReceptacleEighthTableA list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
SEQUENCE OF UpsReceptacleEighthEntry
.1.3.6.1.4.1.818.1.1.18.8.7
upsReceptacleEighthEntryAn entry containing information applicable to a particular receptacle.
UpsReceptacleEighthEntry
.1.3.6.1.4.1.818.1.1.18.8.7.1
upsReceptacleLineIndexeighthThe receptacle line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.8.7.1.1
upsReceptacleOnOffeighthThe present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on.rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.8.7.1.2
upsUPSModeeighthThe operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode)rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.8.8
upsRectifierOnOffeighthThe present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.8.9
upsBatteryChargeMethodeighthThe present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.8.10
upsInverterOnOffeighthThe present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.8.11
upsBypassOnOffeighthThe present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.8.12
upsLoadSourceeighthThe present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen.rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.8.13
upsConfigeighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.9
upsConfigInputVoltageeighthThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.18.9.1
upsConfigInputFreqeighthThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.18.9.2
upsConfigOutputVoltageeighthThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.18.9.3
upsConfigOutputFreqeighthThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw
NonNegativeInteger32 UNITS "0.1 Hertz"
.1.3.6.1.4.1.818.1.1.18.9.4
upsConfigOutputVAeighthThe magnitude of the nominal Volt-Amp rating.(*)ro
NonNegativeInteger32 UNITS "Volt-Amps"
.1.3.6.1.4.1.818.1.1.18.9.5
upsConfigOutputPowereighthThe magnitude of the nominal true power rating.(*)ro
NonNegativeInteger32 UNITS "Watts"
.1.3.6.1.4.1.818.1.1.18.9.6
upsConfigLowBattTimeeighthThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*)rw
NonNegativeInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.18.9.7
upsConfigAudibleStatuseighthThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*)rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.9.8
upsConfigLowVoltageTransferPointeighthThe minimum input line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.18.9.9
upsConfigHighVoltageTransferPointeighthThe maximum line voltage allowed before the UPS system transfers to battery backup.(*)rw
NonNegativeInteger32 UNITS "RMS Volts"
.1.3.6.1.4.1.818.1.1.18.9.10
upsConfigBatteryCapacityeighthThe installed battery capacity. This value is the 'factory'-value, not the value after calibration.rw
NonNegativeInteger32 UNITS "Amps Hours"
.1.3.6.1.4.1.818.1.1.18.9.11
upsConfigBatteryChargeCurrenteighthThe maximum battery charge current, including external chargers.rw
NonNegativeInteger32 UNITS "0.1 Amp DC"
.1.3.6.1.4.1.818.1.1.18.9.12
upsConfigNoLoadShutdowneighthDis- or enable 'no load' shutdown from the contact interface.rw
Enumeration
.1.3.6.1.4.1.818.1.1.18.9.13
upsConfigStartDelayeighthMinimum required autonomy time before the UPS may perform an autorestart.rw
PositiveInteger32 UNITS "minutes"
.1.3.6.1.4.1.818.1.1.18.9.14
upsGetSeteighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.10
upsEventGetNexteighthThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.10.1
upsEventGetPreviouseighthThe number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.10.2
upsEventSetStartingTimeStampeighthThe timestamp which is used as starting point for downloading events from the UPS event bufferrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.3
upsEventRetreiveCurrentTimeStampeighthThe current timestamp is retreived from the UPSro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.4
upsEventTableSizeeighthThe number of entries in the event table. This object indicates the number of rows in the event table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.5
upsEventEighthTableA list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..10)): PDU-SET upsSetStartingTimeStamp <time> PDU-SET upsEventGetNext <number> PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize.
SEQUENCE OF UpsEventEighthEntry
.1.3.6.1.4.1.818.1.1.18.10.6
upsEventEighthEntryAn entry containing information applicable to a particular event.
UpsEventEighthEntry
.1.3.6.1.4.1.818.1.1.18.10.6.1
upsEventLineIndexeighthThe event line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.10.6.1.1
upsEventCodeeighthThe event code in numerical format.ro
Integer32
.1.3.6.1.4.1.818.1.1.18.10.6.1.2
upsEventStatuseighthThe status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.6.1.3
upsEventTimeeighthThe timestamp of the moment the event was generated.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.6.1.4
upsParametersReadeighthThe number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.10.7
upsParametersWriteeighthThe number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the eighth value of the table with the lowest index number.rw
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.10.8
upsParametersStartAddresseighthThe address which is used as starting point for downloading parameters from the UPSrw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.9
upsParameterTableSizeeighthThe number of entries in the parameter table. This object indicates the number of rows in the parameter table.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.10
upsParameterEighthTableA list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message (<number> is (1..16)): Read sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParametersRead <number> PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue <number> The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress <addr> PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue <number> PDU-SET upsParametersWrite <number>
SEQUENCE OF UpsParameterEighthEntry
.1.3.6.1.4.1.818.1.1.18.10.11
upsParameterEighthEntryAn entry containing information applicable to a particular parameter.
UpsParameterEighthEntry
.1.3.6.1.4.1.818.1.1.18.10.11.1
upsParameterLineIndexeighthThe parameter line identifier.
PositiveInteger32
.1.3.6.1.4.1.818.1.1.18.10.11.1.1
upsParameterValueeighthThe parameter value in numerical format.rw
Integer32
.1.3.6.1.4.1.818.1.1.18.10.11.1.2
upsStatuseighthThe global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValuesro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.12
upsMainsStatisticsMBfaileighthCount of main bypass failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.13
upsMainsStatisticsMRfaileighthCount of mains rectifier failures (>200 ms), since UPS installation.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.14
upsMainsStatisticsB2eighthCount of transients on the mains bypass (0..2 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.15
upsMainsStatisticsB5eighthCount of transients on the mains bypass (2..5 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.16
upsMainsStatisticsB10eighthCount of transients on the mains bypass (5..10 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.17
upsMainsStatisticsB200eighthCount of transients on the mains bypass (10..200 ms), during the last 7 days.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.18
upsMainsStatisticsBypReleighthBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.ro
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.19
upsTimeeighthThe current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPeighthERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps.rw
NonNegativeInteger32
.1.3.6.1.4.1.818.1.1.18.10.20
upsRequestPermissioneighthAn encrypted code is send to enable use of restricted write objects during a limited period of time.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.10.21
upsEventGetCodeeighthThe code which is used as starting point to downloading the events from the UPS event buffer.rw
Integer32
.1.3.6.1.4.1.818.1.1.18.10.22
upsEventSpinLockeighthA spin lock on the event subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.10.23
upsParameterSpinLockeighthA spin lock on the parameters subsystem.rw
TestAndIncr (SNMPv2-TC)
.1.3.6.1.4.1.818.1.1.18.10.24
geUPSTrapseighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.11
upsTrapAlarmBatteryBadeighthOne or more batteries have been determined to require replacement.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.1
upsTrapAlarmOnBatteryeighthThe UPS is drawing power from the batteries.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.2
upsTrapAlarmLowBatteryeighthThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.3
upsTrapAlarmDepletedBatteryeighthThe UPS will be unable to sustain the present load when and if the utility power is lost)
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.4
upsTrapAlarmTempBadeighthA temperature is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.5
upsTrapAlarmInputBadeighthAn input condition is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.6
upsTrapAlarmOutputBadeighthAn output condition (other than OutputOverload) is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.7
upsTrapAlarmOutputOverloadeighthThe output load exceeds the UPS output capacity.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.8
upsTrapAlarmOnBypasseighthThe Bypass is presently engaged on the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.9
upsTrapAlarmBypassBadeighthThe Bypass is out of tolerance.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.10
upsTrapAlarmOutputOffAsRequestedeighthThe UPS has shutdown as requested, i.e., the output is off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.11
upsTrapAlarmUpsOffAsRequestedeighthThe entire UPS has shutdown as commanded.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.12
upsTrapAlarmChargerFailedeighthAn uncorrected problem has been detected within the UPS charger subsystem.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.13
upsTrapAlarmUpsOutputOffeighthThe output of the UPS is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.14
upsTrapAlarmUpsSystemOffeighthThe UPS system is in the off state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.15
upsTrapAlarmFanFailureeighthThe failure of one or more fans in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.16
upsTrapAlarmFuseFailureeighthThe failure of one or more fuses has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.17
upsTrapAlarmGeneralFaulteighthA general fault in the UPS has been detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.18
upsTrapAlarmDiagnosticTestFailedeighthThe result of the last diagnostic test indicates a failure.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.19
upsTrapAlarmCommunicationsLosteighthA problem has been encountered in the communication between the agent and the UPS.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.20
upsTrapAlarmAwaitingPowereighthThe UPS output is off and the UPS is awaiting the return of the input power (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.21
upsTrapAlarmShutdownPendingeighthA upsShutdownAfterDelay countdown is underway.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.22
upsTrapAlarmShutdownImminenteighthThe UPS will turn off power to the load in less than 5 eighths; this may be either a timed shutdown or a low battery shutdown.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.23
upsTrapAlarmTestInProgresseighthA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.24
upsTrapAlarmReceptacleOffeighthA receptacle has been switched off.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.25
upsTrapAlarmHighspeedBusFailureeighthA problem on the Highspeed Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.26
upsTrapAlarmHighspeedBusJACRCFailureeighthA CRC failure on the Highspeed Bus JA is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.27
upsTrapAlarmConnectivityBusFailureeighthA problem on the Connectivity Bus communication is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.28
upsTrapAlarmHighspeedBusJBCRCFailureeighthA CRC failure on the Highspeed Bus JB is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.29
upsTrapAlarmCurrentSharingFailureeighthAn high current sharing on the parallel system is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.30
upsTrapAlarmDCRippleFailureeighthAn high ripple voltage on his DC link is detected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.31
upsTrapAlarmBatteryBadRestoredeighthA Battery bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.33
upsTrapAlarmOnBatteryRestoredeighthThe UPS is drawing power from mains again.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.34
upsTrapAlarmLowBatteryRestoredeighthA Low Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.35
upsTrapAlarmDepletedBatteryRestoredeighthA Depleted Battery condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.36
upsTrapAlarmTempBadRestoredeighthA bad temperature condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.37
upsTrapAlarmInputBadRestoredeighthAn input bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.38
upsTrapAlarmOutputBadRestoredeighthAn output bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.39
upsTrapAlarmOutputOverloadRestoredeighthAn output overload condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.40
upsTrapAlarmOnBypassRestoredeighthAn On Bypass condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.41
upsTrapAlarmBypassBadRestoredeighthA Bypass bad condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.42
upsTrapAlarmOutputOffAsRequestedRestoredeighthA request shutdown has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.43
upsTrapAlarmUpsOffAsRequestedRestoredeighthA entire UPS command has been restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.44
upsTrapAlarmChargerFailedRestoredeighthA Charger Failer condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.45
upsTrapAlarmUpsOutputOneighthThe output of the UPS switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.46
upsTrapAlarmUpsSystemOneighthThe UPS system is switched in the on state.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.47
upsTrapAlarmFanFailureRestoredeighthA Fan failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.48
upsTrapAlarmFuseFailureRestoredeighthA Fuse failure condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.49
upsTrapAlarmGeneralFaultRestoredeighthA general fault is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.50
upsTrapAlarmDiagnosticTestFailedRestoredeighthA last diagnostic test indicates a failure is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.51
upsTrapAlarmCommunicationsLostRestoredeighthA problem in the communication between the agent and the UPS is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.52
upsTrapAlarmAwaitingPowerRestoredeighthA awaiting power condition is restored (*).
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.53
upsTrapAlarmShutdownPendingRestoredeighthA upsShutdownAfterDelay countdown is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.54
upsTrapAlarmShutdownImminentRestoredeighthA shutdown imminent condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.55
upsTrapAlarmTestInProgressRestoredeighthThe test is in progress is terminated.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.56
upsTrapAlarmReceptacleOneighthA receptacle has been switched on.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.57
upsTrapAlarmHighspeedBusRestoreeighthA problem on the Highspeed Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.58
upsTrapAlarmHighspeedBusJACRCRestoreeighthA CRC failure on the Highspeed Bus JA is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.59
upsTrapAlarmConnectivityBusRestoreeighthA problem on the Connectivity Bus communication is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.60
upsTrapAlarmHighspeedBusJBCRCRestoredeighthA CRC failure on the Highspeed Bus JB is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.61
upsTrapAlarmCurrentSharingRestoredeighthAn high current sharing on the parallel system is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.62
upsTrapAlarmDCRippleRestoredeighthAn high ripple voltage on his DC link is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.63
upsTrapAlarmValueLoweighthA measurement value reached a value below its low-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.129
upsTrapAlarmValueHigheighthA measurement value reached a value higher than its high-level threshold.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.130
upsTrapAlarmValueLowRestoredeighthA ValueLow alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.133
upsTrapAlarmValueHighRestoredeighthA ValueHigh alarm condition is restored.
NOTIFICATION-TYPE
.1.3.6.1.4.1.818.1.1.18.11.134
upsDiagnosticeighth
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.1.18.12
upsDiagnosticBusJACommunicationStatuseighthBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.18.12.1
upsDiagnosticBusJBCommunicationStatuseighthBit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.18.12.2
upsDiagnosticBatteryLifetimeeighthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.18.12.3
upsDiagnosticFansLifetimeeighthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.18.12.4
upsDiagnosticDCcapacitorsLifetimeeighthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.18.12.5
upsDiagnosticACcapacitorsLifetimeeighthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.18.12.6
upsDiagnosticGlobalServiceCheckeighthThe critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)ro
Integer32
.1.3.6.1.4.1.818.1.1.18.12.7
geDevices
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.100
geDevicesDescriptions
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.100.1
advSNMPWebIntCard
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.100.1.1
snmpWebIntCard
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.100.1.2
snmpWebIntBox
OBJECT IDENTIFIER
.1.3.6.1.4.1.818.1.100.1.3