GE-SINGLEUPS
Detailed view of the defined objects, syntax rules, and hierarchical paths.
531
Objects
Active
Status
2
Dependencies
Imported Objects
Objects
531 total| Object Name |
|---|
upsAlarmUpsOffAsRequested-genThe entire UPS has shutdown as commanded. TRAP-TYPE .0.12 |
upsAlarmUpsOffAsRequestedRestored-genA entire UPS command has been restored. TRAP-TYPE .0.44 |
imv OBJECT IDENTIFIER .1.3.6.1.4.1.818 |
geHardware OBJECT IDENTIFIER .1.3.6.1.4.1.818.1 |
geUPS OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1 |
geDiscoveredUPSsMaskReading this variable returns bit mask indicating which
UPSs in a parallel system are alive. Management
software should poll only these UPSs on their snmp
branches 11-18 as follows:
1 FirstUPS alive
2 SecondUPS alive
4 ThirdUPS alive
8 FourthUPS alive
16 FifthUPS alive
32 SixthUPS alive
64 SeventhUPS alive
128 EigthUPS alive
Since the management software should always monitor
the GenericUPS branch (10), this value has no meaning
for single upses (which provide values on that snmp
branch), and should be set to zero in that case.ro Integer32 .1.3.6.1.4.1.818.1.1.1 |
geRequestPacketPut the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus.
This OID could be used for accede directly to the internally RS485 bus from a remote place.rw DisplayString .1.3.6.1.4.1.818.1.1.2 |
geReplyPacketContain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket.
Every time that a write command has be made at the OID ge RequestPacket, the value of this OID is erased.ro DisplayString .1.3.6.1.4.1.818.1.1.3 |
geGenericUPS OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10 |
upsIdent-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.1 |
upsIdentManufacturer-genThe name of the UPS manufacturer.(*)ro DisplayString .1.3.6.1.4.1.818.1.1.10.1.1 |
upsIdentModel-genThe UPS Model designation.(*)ro DisplayString .1.3.6.1.4.1.818.1.1.10.1.2 |
upsIdentUPSSoftwareVersion-genThe UPS firmware/software version(s). This variable
may or may not have the same value as
upsIdentAgentSoftwareVersion in some implementations.(*)ro DisplayString .1.3.6.1.4.1.818.1.1.10.1.3 |
upsIdentAgentSoftwareVersion-genThe UPS agent software version. This variable may or
may not have the same value as
upsIdentUPSSoftwareVersion in some implementations.(*)ro DisplayString .1.3.6.1.4.1.818.1.1.10.1.4 |
upsIdentName-genA string identifying the UPS. This object should be
set by the administrator.(*)rw DisplayString .1.3.6.1.4.1.818.1.1.10.1.5 |
upsIdentAttachedDevices-genA string identifying the devices attached to the
output(s) of the UPS. This object should be set by
the administrator.(*)rw DisplayString .1.3.6.1.4.1.818.1.1.10.1.6 |
upsIdentUPSSerialNumber-genThe UPS serial numberro DisplayString .1.3.6.1.4.1.818.1.1.10.1.7 |
upsIdentComProtVersion-genThe IMV communication protocol versionro DisplayString .1.3.6.1.4.1.818.1.1.10.1.8 |
upsIdentOperatingTime-genThe present value of the operating time.
total 'on' time since UPS manufacturedro NonNegativeInteger32 UNITS "seconds" .1.3.6.1.4.1.818.1.1.10.1.9 |
upsBattery-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.2 |
upsBatteryStatus-genThe indication of the capacity remaining in the UPS
system's batteries. A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output).(*)ro Integer32 { unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4) } .1.3.6.1.4.1.818.1.1.10.2.1 |
upsSecondsOnBattery-genIf the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. Zero shall be returned
if the unit is not on battery power.(*)ro NonNegativeInteger32 UNITS "seconds" .1.3.6.1.4.1.818.1.1.10.2.2 |
upsEstimatedMinutesRemaining-genAn estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off.(*)ro PositiveInteger32 UNITS "minutes" .1.3.6.1.4.1.818.1.1.10.2.3 |
upsEstimatedChargeRemaining-genAn estimate of the battery charge remaining expressed
as a percent of full charge.(*)ro Integer32 .1.3.6.1.4.1.818.1.1.10.2.4 |
upsBatteryVoltage-genThe magnitude of the present battery voltage.(*)ro NonNegativeInteger32 UNITS "0.1 Volt DC" .1.3.6.1.4.1.818.1.1.10.2.5 |
upsBatteryCurrent-genThe present battery current.(*)ro Integer32 UNITS "0.1 Amp DC" .1.3.6.1.4.1.818.1.1.10.2.6 |
upsBatteryTemperature-genThe ambient temperature at or near the UPS Battery
casing.(*)ro Integer32 UNITS "degrees Centigrade" .1.3.6.1.4.1.818.1.1.10.2.7 |
upsInput-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.3 |
upsInputLineBads-genA count of the number of times the input entered an
out-of-tolerance condition as defined by the
manufacturer. This count is incremented by one each
time the input transitions from zero out-of-tolerance
lines to one or more input lines out-of-tolerance.(*)ro Counter32 .1.3.6.1.4.1.818.1.1.10.3.1 |
upsInputNumLines-genThe number of input lines utilized in this device.
This variable indicates the number of rows in the
input table.(*)ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.3.2 |
upsInputTable-genA list of input table entries. The number of entries
is given by the value of upsInputNumLines.(*) SEQUENCE OF UpsInputEntry-gen .1.3.6.1.4.1.818.1.1.10.3.3 |
upsInputEntry-genAn entry containing information applicable to a
particular input line.(*) UpsInputEntry-gen .1.3.6.1.4.1.818.1.1.10.3.3.1 |
upsInputLineIndex-genThe input line identifier.(*) PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.3.3.1.1 |
upsInputFrequency-genThe present input frequency.(*)ro NonNegativeInteger32 UNITS "0.1 Hertz" .1.3.6.1.4.1.818.1.1.10.3.3.1.2 |
upsInputVoltage-genThe magnitude of the present input voltage.(*)ro NonNegativeInteger32 UNITS "RMS Volts" .1.3.6.1.4.1.818.1.1.10.3.3.1.3 |
upsInputCurrent-genThe magnitude of the present input current.(*)ro NonNegativeInteger32 UNITS "0.1 RMS Amp" .1.3.6.1.4.1.818.1.1.10.3.3.1.4 |
upsInputTruePower-genThe magnitude of the present input true power.(*)ro NonNegativeInteger32 UNITS "Watts" .1.3.6.1.4.1.818.1.1.10.3.3.1.5 |
upsInputVoltageMin-genThe lowest magnitude of the input voltage since last read out.ro NonNegativeInteger32 UNITS "RMS Volts" .1.3.6.1.4.1.818.1.1.10.3.3.1.6 |
upsInputVoltageMax-genThe highest magnitude of the input voltage since last read out.ro NonNegativeInteger32 UNITS "RMS Volts" .1.3.6.1.4.1.818.1.1.10.3.3.1.7 |
upsOutput-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.4 |
upsOutputSource-genThe present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.(*)ro Integer32 { other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7) } .1.3.6.1.4.1.818.1.1.10.4.1 |
upsOutputFrequency-genThe present output frequency.(*)ro NonNegativeInteger32 UNITS "0.1 Hertz" .1.3.6.1.4.1.818.1.1.10.4.2 |
upsOutputNumLines-genThe number of output lines utilized in this device.
This variable indicates the number of rows in the
output table.(*)ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.4.3 |
upsOutputTable-genA list of output table entries. The number of
entries is given by the value of upsOutputNumLines.(*) SEQUENCE OF UpsOutputEntry-gen .1.3.6.1.4.1.818.1.1.10.4.4 |
upsOutputEntry-genAn entry containing information applicable to a
particular output line.(*) UpsOutputEntry-gen .1.3.6.1.4.1.818.1.1.10.4.4.1 |
upsOutputLineIndex-genThe output line identifier.(*) PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.4.4.1.1 |
upsOutputVoltage-genThe present output voltage.(*)ro NonNegativeInteger32 UNITS "RMS Volts" .1.3.6.1.4.1.818.1.1.10.4.4.1.2 |
upsOutputCurrent-genThe present output current.(*)ro NonNegativeInteger32 UNITS "0.1 RMS Amp" .1.3.6.1.4.1.818.1.1.10.4.4.1.3 |
upsOutputPower-genThe present output true power.(*)ro NonNegativeInteger32 UNITS "Watts" .1.3.6.1.4.1.818.1.1.10.4.4.1.4 |
upsOutputPercentLoad-genThe percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA.(*)ro Integer32 .1.3.6.1.4.1.818.1.1.10.4.4.1.5 |
upsBypass-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.5 |
upsBypassFrequency-genThe present bypass frequency.(*)ro NonNegativeInteger32 UNITS "0.1 Hertz" .1.3.6.1.4.1.818.1.1.10.5.1 |
upsBypassNumLines-genThe number of bypass lines utilized in this device.
This entry indicates the number of rows in the bypass
table.(*)ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.5.2 |
upsBypassTable-genA list of bypass table entries. The number of
entries is given by the value of upsBypassNumLines.(*) SEQUENCE OF UpsBypassEntry-gen .1.3.6.1.4.1.818.1.1.10.5.3 |
upsBypassEntry-genAn entry containing information applicable to a
particular bypass input.(*) UpsBypassEntry-gen .1.3.6.1.4.1.818.1.1.10.5.3.1 |
upsBypassLineIndex-genThe bypass line identifier.(*) PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.5.3.1.1 |
upsBypassVoltage-genThe present bypass voltage.(*)ro NonNegativeInteger32 UNITS "RMS Volts" .1.3.6.1.4.1.818.1.1.10.5.3.1.2 |
upsBypassCurrent-genThe present bypass current.(*)ro NonNegativeInteger32 UNITS "0.1 RMS Amp" .1.3.6.1.4.1.818.1.1.10.5.3.1.3 |
upsBypassPower-genThe present true power conveyed by the bypass.(*)ro NonNegativeInteger32 UNITS "Watts" .1.3.6.1.4.1.818.1.1.10.5.3.1.4 |
upsAlarm-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.6 |
upsAlarmsPresent-genThe present number of active alarm conditions.(*)ro Gauge32 .1.3.6.1.4.1.818.1.1.10.6.1 |
upsAlarmTable-genA list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent.(*) SEQUENCE OF UpsAlarmEntry-gen .1.3.6.1.4.1.818.1.1.10.6.2 |
upsAlarmEntry-genAn entry containing information applicable to a
particular alarm.(*) UpsAlarmEntry-gen .1.3.6.1.4.1.818.1.1.10.6.2.1 |
upsAlarmId-genA unique identifier for an alarm condition. This
value must remain constant.(*) PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.6.2.1.1 |
upsAlarmDescr-genA reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition.(*)ro AutonomousType (SNMPv2-TC) .1.3.6.1.4.1.818.1.1.10.6.2.1.2 |
upsAlarmTime-genThe value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected at the
time of agent startup and presumably existed before
agent startup, the value of upsAlarmTime shall equal
0.(*)ro TimeStamp (SNMPv2-TC) .1.3.6.1.4.1.818.1.1.10.6.2.1.3 |
upsWellKnownAlarms-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.6.3 |
upsAlarmMaskA-genSpecifies which alarm can be handled by the UPS.
The 'Mask' parameter is a Long Integer32. The meaning
of every bit is the same as for the 'upsAlarmGroupA'
command. A bit having value=1 indicates that the
corresponding alarm is handled by the UPS.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.6.4 |
upsTest-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.7 |
upsTestId-genThe test is named by an OBJECT IDENTIFIER which
allows a standard mechanism for the initiation of
tests, including the well known tests identified in
this document as well as those introduced by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device.
Setting this variable initiates the named test. Sets
to this variable require the presence of
upsTestSpinLock in the same SNMP message.
The set request will be rejected with an appropriate
error message if the requested test cannot be
performed, including attempts to start a test when
another test is already in progress. The status of
the current or last test is maintained in
upsTestResultsSummary. Tests in progress may be
aborted by setting the upsTestId variable to
upsTestAbortTestInProgress.
Read operations return the value of the name of the
test in progress if a test is in progress or the name
of the last test performed if no test is in progress,
unless no test has been run, in which case the well
known value upsTestNoTestsInitiated is returned.(*)rw OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.7.1 |
upsTestSpinLock-genA spin lock on the test subsystem. The spinlock is
used as follows.
Before starting a test, a manager-station should make
sure that a test is not in progress as follows:
try-again:
get (upsTestSpinLock)
while (upsTestResultsSummary == inProgress) {
/* loop while a test is running for another
manager */
short delay
get (upsTestSpinLock)
}
lock-value = upsTestSpinLock
/* no test in progress, start the test */
set (upsTestSpinLock = lock-value, upsTestId =
requested-test)
if (error-index == 1) { /* (upsTestSpinLock
failed) */
/* if problem is not access control, then
some other manager slipped in ahead of us
*/
goto try-again
}
if (error-index == 2) { /* (upsTestId) */
/* cannot perform the test */
give up
}
/* test started ok */
/* wait for test completion by polling
upsTestResultsSummary */
get (upsTestSpinLock, upsTestResultsSummary,
upsTestResultsDetail)
while (upsTestResultsSummary == inProgress) {
short delay
get (upsTestSpinLock, upsTestResultsSummary,
upsTestResultsDetail)
}
/* when test completes, retrieve any additional
test results */
/* if upsTestSpinLock == lock-value + 1, then
these are our test */
/* results (as opposed to another manager's */
The initial value of upsTestSpinLock at agent
initialization shall
be 1.(*)rw TestAndIncr (SNMPv2-TC) .1.3.6.1.4.1.818.1.1.10.7.2 |
upsTestResultsSummary-genThe results of the current or last UPS diagnostics
test performed. The values for donePass(1),
doneWarning(2), and doneError(3) indicate that the
test completed either successfully, with a warning, or
with an error, respectively. The value aborted(4) is
returned for tests which are aborted by setting the
value of upsTestId to upsTestAbortTestInProgress.
Tests which have not yet concluded are indicated by
inProgress(5). The value noTestsInitiated(6)
indicates that no previous test results are available,
such as is the case when no tests have been run since
the last reinitialization of the network management
subsystem and the system has no provision for non-
volatile storage of test results.(*)ro Integer32 { donePass(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestsInitiated(6) } .1.3.6.1.4.1.818.1.1.10.7.3 |
upsTestResultsDetail-genAdditional information about upsTestResultsSummary.
If no additional information available, a zero length
string is returned.(*)ro DisplayString .1.3.6.1.4.1.818.1.1.10.7.4 |
upsTestStartTime-genThe value of sysUpTime at the time the test in
progress was initiated, or, if no test is in progress,
the time the previous test was initiated. If the
value of upsTestResultsSummary is noTestsInitiated(6),
upsTestStartTime has the value 0.(*)ro TimeStamp (SNMPv2-TC) .1.3.6.1.4.1.818.1.1.10.7.5 |
upsTestElapsedTime-genThe amount of time, in TimeTicks, since the test in
progress was initiated, or, if no test is in progress,
the previous test took to complete. If the value of
upsTestResultsSummary is noTestsInitiated(6),
upsTestElapsedTime has the value 0.(*)ro TimeInterval (SNMPv2-TC) .1.3.6.1.4.1.818.1.1.10.7.6 |
upsWellKnownTests-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.7.7 |
upsTestNoTestsInitiated-genNo tests have been initiated and no test is in
progress.(*) OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.7.7.1 |
upsTestAbortTestInProgress-genThe test in progress is to be aborted / the test in
progress was aborted.(*) OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.7.7.2 |
upsTestGeneralSystemsTest-genThe manufacturer's standard test of UPS device
systems.(*) OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.7.7.3 |
upsTestQuickBatteryTest-genA test that is sufficient to determine if the battery
needs replacement.(*) OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.7.7.4 |
upsTestDeepBatteryCalibration-genThe system is placed on battery to a discharge level,
set by the manufacturer, sufficient to determine
battery replacement and battery run-time with a high
degree of confidence. WARNING: this test will leave
the battery in a low charge state and will require
time for recharging to a level sufficient to provide
normal battery duration for the protected load.(*) OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.7.7.5 |
upsControl-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.8 |
upsShutdownType-genThis object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
Setting this object to output(1) indicates that
shutdown requests should cause only the output of the
UPS to turn off. Setting this object to system(2)
indicates that shutdown requests will cause the entire
UPS system to turn off.(*)rw Integer32 { output(1), system(2) } .1.3.6.1.4.1.818.1.1.10.8.1 |
upsShutdownAfterDelay-genSetting this object will shutdown (i.e., turn off)
either the UPS output or the UPS system (as determined
by the value of upsShutdownType at the time of
shutdown) after the indicated number of seconds, or
less if the UPS batteries become depleted. Setting
this object to 0 will cause the shutdown to occur
immediately. Setting this object to -1 will abort the
countdown. If the system is already in the desired
state at the time the countdown reaches 0, then
nothing will happen. That is, there is no additional
action at that time if upsShutdownType = system and
the system is already off. Similarly, there is no
additional action at that time if upsShutdownType =
output and the output is already off. When read,
upsShutdownAfterDelay will return the number of
seconds remaining until shutdown, or -1 if no shutdown
countdown is in effect. On some systems, if the agent
is restarted while a shutdown countdown is in effect,
the countdown may be aborted. Sets to this object
override any upsShutdownAfterDelay already in effect.(*)rw Integer32 (-1..2147483648) UNITS "seconds" .1.3.6.1.4.1.818.1.1.10.8.2 |
upsStartupAfterDelay-genSetting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary. Setting this object to 0 will
cause the startup to occur immediately. Setting this
object to -1 will abort the countdown. If the output
is already on at the time the countdown reaches 0,
then nothing will happen. Sets to this object
override the effect of any upsStartupAfterDelay
countdown or upsRebootWithDuration countdown in
progress. When read, upsStartupAfterDelay will return
the number of seconds until startup, or -1 if no
startup countdown is in effect. If the countdown
expires during a utility failure, the startup shall
not occur until the utility power is restored. On
some systems, if the agent is restarted while a
startup countdown is in effect, the countdown is
aborted.(*)rw Integer32 (-1..2147483648) UNITS "seconds" .1.3.6.1.4.1.818.1.1.10.8.3 |
upsRebootWithDuration-genSetting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for a period equal to the indicated
number of seconds, after which time the output will be
started, including starting the UPS, if necessary. If
the number of seconds required to perform the request
is greater than the requested duration, then the
requested shutdown and startup cycle shall be
performed in the minimum time possible, but in no case
shall this require more than the requested duration
plus 60 seconds. When read, upsRebootWithDuration
shall return the number of seconds remaining in the
countdown, or -1 if no countdown is in progress. If
the startup should occur during a utility failure, the
startup shall not occur until the utility power is
restored.(*)rw Integer32 (-1..300) UNITS "seconds" .1.3.6.1.4.1.818.1.1.10.8.4 |
upsAutoRestart-genSetting this object to 'on' will cause the UPS system
to restart after a shutdown if the shutdown occurred
during a power loss as a result of either a
upsShutdownAfterDelay or an internal battery depleted
condition. Setting this object to 'off' will prevent
the UPS system from restarting after a shutdown until
an operator manually or remotely explicitly restarts
it. If the UPS is in a startup or reboot countdown,
then the UPS will not restart until that delay has
been satisfied.(*)rw Integer32 { on(1), off(2) } .1.3.6.1.4.1.818.1.1.10.8.5 |
upsReceptaclesNum-genThe number of receptacles utilized in this device.
This entry indicates the number of rows in the receptacle
table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.8.6 |
upsReceptacleTable-genA list of receptacle table entries. The number of
entries is given by the value of upsReceptacleNum. SEQUENCE OF UpsReceptacleEntry-gen .1.3.6.1.4.1.818.1.1.10.8.7 |
upsReceptacleEntry-genAn entry containing information applicable to a
particular receptacle. UpsReceptacleEntry-gen .1.3.6.1.4.1.818.1.1.10.8.7.1 |
upsReceptacleLineIndex-genThe receptacle line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.8.7.1.1 |
upsReceptacleOnOff-genThe present state of the receptacle. Setting this
object to 'on' will cause the receptacle to be turned
on. Setting this object to 'off' will turn the
receptacle off. If the receptacle is already in the
desired state nothing will happen. After an
autorestart (see upsAutoRestart) the receptacle will
be on.rw Integer32 { on(1), off(2) } .1.3.6.1.4.1.818.1.1.10.8.7.1.2 |
upsUPSMode-genThe operation mode off the UPS. Off-line indicates a
mode in which the input power is transferred to the
output directly or via a step-up or step-down
transformer. On-line mode indicates a mode in which
the output power is regenerated through some convertor.
the operating mode of the UPS may be fixed, or may be
selectable (e.g. an on-line UPS with ecomode)rw Integer32 { off-line(1), on-line(2), ecomode(3) } .1.3.6.1.4.1.818.1.1.10.8.8 |
upsRectifierOnOff-genThe present state of the rectifier. Setting this
object to 'on' will cause the rectifier to be turned
on. Setting this object to 'off' will turn the
rectifier off. If the rectifier is already in the
desired state nothing will happen.rw Integer32 { on(1), off(2) } .1.3.6.1.4.1.818.1.1.10.8.9 |
upsBatteryChargeMethod-genThe present state of the charge method. Setting this
object to 'Normal charge' will cause the battery to be
charged using the normal method. Setting this object to
'Boost charge' will charge the battery in boost mode.
If the charge method is already in the desired state
nothing will happen.rw Integer32 { normal-charge(1), boost-charge(2) } .1.3.6.1.4.1.818.1.1.10.8.10 |
upsInverterOnOff-genThe present state of the inverter. Setting this
object to 'on' will cause the inverter to be turned
on. Setting this object to 'off' will turn the
inverter off. If the inverter is already in the
desired state nothing will happen.rw Integer32 { on(1), off(2) } .1.3.6.1.4.1.818.1.1.10.8.11 |
upsBypassOnOff-genThe present state of the bypass. Setting this
object to 'on' will cause the bypass to be activated.
Setting this object to 'off' will deactivate the
bypass. If the UPS is already in the
desired state nothing will happen.rw Integer32 { on(1), off(2) } .1.3.6.1.4.1.818.1.1.10.8.12 |
upsLoadSource-genThe present source of the load. Setting this
object to 'On bypass' will cause the load to be
supplied by the bypass.
Setting this object to 'On inverter' will cause the
load to be supplied by the inverter.
If the load is already supplied by the desired
source nothing will happen.rw Integer32 { on-bypass(1), on-Inverter(2), on-Detour(3), load-Off(4), other (5) } .1.3.6.1.4.1.818.1.1.10.8.13 |
upsConfig-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.9 |
upsConfigInputVoltage-genThe magnitude of the nominal input voltage. On those
systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1,
or inconsistentValue for SNMPv2.(*)rw NonNegativeInteger32 UNITS "RMS Volts" .1.3.6.1.4.1.818.1.1.10.9.1 |
upsConfigInputFreq-genThe nominal input frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw NonNegativeInteger32 UNITS "0.1 Hertz" .1.3.6.1.4.1.818.1.1.10.9.2 |
upsConfigOutputVoltage-genThe magnitude of the nominal output voltage. On
those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not supported, the request must be
rejected and the agent shall respond with an
appropriate error message, i.e., badValue for SNMPv1,
or inconsistentValue for SNMPv2.(*)rw NonNegativeInteger32 UNITS "RMS Volts" .1.3.6.1.4.1.818.1.1.10.9.3 |
upsConfigOutputFreq-genThe nominal output frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e.,
badValue for SNMPv1, or inconsistentValue for SNMPv2.(*)rw NonNegativeInteger32 UNITS "0.1 Hertz" .1.3.6.1.4.1.818.1.1.10.9.4 |
upsConfigOutputVA-genThe magnitude of the nominal Volt-Amp rating.(*)ro NonNegativeInteger32 UNITS "Volt-Amps" .1.3.6.1.4.1.818.1.1.10.9.5 |
upsConfigOutputPower-genThe magnitude of the nominal true power rating.(*)ro NonNegativeInteger32 UNITS "Watts" .1.3.6.1.4.1.818.1.1.10.9.6 |
upsConfigLowBattTime-genThe value of upsEstimatedMinutesRemaining at which a
lowBattery condition is declared. For agents which
support only discrete (discontinuous) values, then the
agent shall round up to the next supported value. If
the requested value is larger than the largest
supported value, then the largest supported value
shall be selected.(*)rw NonNegativeInteger32 UNITS "minutes" .1.3.6.1.4.1.818.1.1.10.9.7 |
upsConfigAudibleStatus-genThe requested state of the audible alarm. When in
the disabled state, the audible alarm should never
sound. The enabled state is self-describing. Setting
this object to muted(3) when the audible alarm is
sounding shall temporarily silence the alarm. It will
remain muted until it would normally stop sounding and
the value returned for read operations during this
period shall equal muted(3). At the end of this
period, the value shall revert to enabled(2). Writes
of the value muted(3) when the audible alarm is not
sounding shall be accepted but otherwise shall have no
effect.(*)rw Integer32 { disabled(1), enabled(2), muted(3) } .1.3.6.1.4.1.818.1.1.10.9.8 |
upsConfigLowVoltageTransferPoint-genThe minimum input line voltage allowed before the UPS
system transfers to battery backup.(*)rw NonNegativeInteger32 UNITS "RMS Volts" .1.3.6.1.4.1.818.1.1.10.9.9 |
upsConfigHighVoltageTransferPoint-genThe maximum line voltage allowed before the UPS
system transfers to battery backup.(*)rw NonNegativeInteger32 UNITS "RMS Volts" .1.3.6.1.4.1.818.1.1.10.9.10 |
upsConfigBatteryCapacity-genThe installed battery capacity. This value is the 'factory'-value,
not the value after calibration.rw NonNegativeInteger32 UNITS "Amps Hours" .1.3.6.1.4.1.818.1.1.10.9.11 |
upsConfigBatteryChargeCurrent-genThe maximum battery charge current, including external chargers.rw NonNegativeInteger32 UNITS "0.1 Amp DC" .1.3.6.1.4.1.818.1.1.10.9.12 |
upsConfigNoLoadShutdown-genDis- or enable 'no load' shutdown from the contact interface.rw Integer32 { disabled(1), enabled(2) } .1.3.6.1.4.1.818.1.1.10.9.13 |
upsConfigStartDelay-genMinimum required autonomy time before the UPS may perform an
autorestart.rw PositiveInteger32 UNITS "minutes" .1.3.6.1.4.1.818.1.1.10.9.14 |
upsGetSet-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.10 |
upsEventGetNext-genThe number of events to retreive from the UPS event buffer.
When this object is set the EventTable will be filled with the
requested number of entries. The value upsEventSetStartingTimeStamp
will be used as the start value of the table with the lowest index number.rw PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.10.1 |
upsEventGetPrevious-genThe number of events to retreive from the UPS event buffer.
When this object is set the EventTable will be filled with the
requested number of entries. The value upsEventLastTime will
be used as the last value of the table with the highest index number.
Returns SNMP-NOSUCHNAME for UPSs that don't support this command.rw PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.10.2 |
upsEventSetStartingTimeStamp-genThe timestamp which is used as starting point for downloading
events from the UPS event bufferrw NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.3 |
upsEventRetreiveCurrentTimeStamp-genThe current timestamp is retreived from the UPSro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.4 |
upsEventTableSize-genThe number of entries in the event table.
This object indicates the number of rows in the event table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.5 |
upsEventTable-genA list of event table entries. The number of entries is always
10, and the value of upsEventTableSize gives the number of valid
entries from the begging of the table. Invalid entries return 0.
To prevent problems with simultaneous queries from several agents,
these values MUST be accessed using several PDUs in the
same SNMP message (<number> is (1..10)):
PDU-SET upsSetStartingTimeStamp <time>
PDU-SET upsEventGetNext <number>
PDU-GET upsEventTableSize
PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
..
PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
The table is read up to requested number of events and the
management software afterwards decides which entries are
valid, as indicated by the upsEventTableSize. SEQUENCE OF UpsEventEntry-gen .1.3.6.1.4.1.818.1.1.10.10.6 |
upsEventEntry-genAn entry containing information applicable to a
particular event. UpsEventEntry-gen .1.3.6.1.4.1.818.1.1.10.10.6.1 |
upsEventLineIndex-genThe event line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.10.6.1.1 |
upsEventCode-genThe event code in numerical format.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.6.1.2 |
upsEventStatus-genThe status of the UPS at the moment that the event was generated.
The format is specified at the 'upsStatus' command.
If the UPS is not able to deliver status information, then
SNMP-NOSUCHNAME is returned.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.6.1.3 |
upsEventTime-genThe timestamp of the moment the event was generated.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.6.1.4 |
upsParametersRead-genThe number of parameters to retreive from the UPS.
When this object is set the ParameterTable will be filled with the
requested number of entries. The value upsParametersStartAddress
will be used as the start value of the table with the lowest index
number.rw PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.10.7 |
upsParametersWrite-genThe number of parameters to write to the UPS.
When this object is set the ParameterTable will be send to the ups.
The value upsParametersStartAddress will be used for the first value
of the table with the lowest index number.rw PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.10.8 |
upsParametersStartAddress-genThe address which is used as starting point for downloading
parameters from the UPSrw NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.9 |
upsParameterTableSize-genThe number of entries in the parameter table.
This object indicates the number of rows in the parameter table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.10 |
upsParameterTable-genA list of parameter entries. The number of entries is always
16, and the value of upsParameterTableSize gives the number of valid
entries from the begging of the table. Invalid entries return 0.
To prevent problems with simultaneous queries from several agents,
these values MUST be accessed using several PDUs in the
same SNMP message (<number> is (1..16)):
Read sequence:
PDU-SET upsSetStartingAddress <addr>
PDU-SET upsParametersRead <number>
PDU-GET upsParameterTableSize
PDU-GET upsParameterValue 1
PDU-GET upsParameterValue 2
..
PDU-GET upsParameterValue <number>
The table is read up to requested number of events and the
management software afterwards decides which entries are
valid, as indicated by the upsParameterTableSize.
Write sequence:
PDU-SET upsSetStartingAddress <addr>
PDU-SET upsParameterValue 1
PDU-SET upsParameterValue 2
..
PDU-SET upsParameterValue <number>
PDU-SET upsParametersWrite <number> SEQUENCE OF UpsParameterEntry-gen .1.3.6.1.4.1.818.1.1.10.10.11 |
upsParameterEntry-genAn entry containing information applicable to a
particular parameter. UpsParameterEntry-gen .1.3.6.1.4.1.818.1.1.10.10.11.1 |
upsParameterLineIndex-genThe parameter line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.1.10.10.11.1.1 |
upsParameterValue-genThe parameter value in numerical format.rw Integer32 .1.3.6.1.4.1.818.1.1.10.10.11.1.2 |
upsStatus-genThe global UPS status is returned. Every bit reflects a specific
status condition. Unused bits returns as 0. The status value can
also be found on other commands. The value SNMP-NOSUCHNAME means
'invalid status' or 'status value non available'.
Status 1 0001h upsStatusEcomodeIsOn
2 0002h upsStatusBatteryIsCharging
4 0004h upsStatusBatteryIsDischarging
8 0008h upsStatusAlarmIsActive
16 0010h upsStatusRectifierIsOn
32 0020h upsStatusLowBattery
64 0040h upsStatusOnBypass
128 0080h upsStatusMainsBypassOK
256 0100h upsStatusMainsRectifierOK
512 0200h upsStatusDetourIsOn
1024 0400h upsStatusAcousticAlarmIsOn
2048 0800h - (not used.)
4096 1000h upsStatusInverterIsOn
8192 2000h upsStatusNotInParallel (Q1 open)
16384 4000h upsStatusResetLoadOff
32768 8000h upsStatusLoadOffro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.12 |
upsMainsStatisticsMBfail-genCount of main bypass failures (>200 ms), since UPS installation.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.13 |
upsMainsStatisticsMRfail-genCount of mains rectifier failures (>200 ms), since UPS installation.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.14 |
upsMainsStatisticsB2-genCount of transients on the mains bypass (0..2 ms), during the last 7 days.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.15 |
upsMainsStatisticsB5-genCount of transients on the mains bypass (2..5 ms), during the last 7 days.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.16 |
upsMainsStatisticsB10-genCount of transients on the mains bypass (5..10 ms), during the last 7 days.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.17 |
upsMainsStatisticsB200-genCount of transients on the mains bypass (10..200 ms), during the last 7 days.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.18 |
upsMainsStatisticsBypRel-genBypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.19 |
upsTime-genThe current timestamp (or real-time) of the UPS. For the format,
see 'Timestamp' specifications. The write-command has to comply with the
correct timestamp format expected by the UPS (counter value or real-time-clock
value). Missing to doing so will result in a SNMP-genERROR,
meaning 'command not supported'. It is possible to know which is the timestamp
format supported by the UPS, by issuing a read-command or by reading events,
which includes timestamps.rw NonNegativeInteger32 .1.3.6.1.4.1.818.1.1.10.10.20 |
upsRequestPermission-genAn encrypted code is send to enable use of restricted write objects during
a limited period of time.rw DisplayString .1.3.6.1.4.1.818.1.1.10.10.21 |
upsEventGetCode-genThe code which is used as starting point to downloading the events from the
UPS event buffer.rw Integer32 .1.3.6.1.4.1.818.1.1.10.10.22 |
upsEventSpinLock-genA spin lock on the event subsystem.rw TestAndIncr (SNMPv2-TC) .1.3.6.1.4.1.818.1.1.10.10.23 |
upsParameterSpinLock-genA spin lock on the parameters subsystem.rw TestAndIncr (SNMPv2-TC) .1.3.6.1.4.1.818.1.1.10.10.24 |
geUPSTraps-gen OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.1.10.11 |
upsAlarmBatteryBad-genOne or more batteries have been determined to require
replacement. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.1 |
upsAlarmOnBattery-genAn On Battery condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.2 |
upsAlarmLowBattery-genThe remaining battery run-time is less than or equal
to upsConfigLowBattTime. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.3 |
upsAlarmDepletedBattery-genThe UPS will be unable to sustain the present load
when and if the utility power is lost) TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.4 |
upsAlarmTempBad-genA temperature is out of tolerance. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.5 |
upsAlarmInputBad-genAn input condition is out of tolerance. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.6 |
upsAlarmOutputBad-genAn output condition (other than OutputOverload) is
out of tolerance. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.7 |
upsAlarmOutputOverload-genThe output load exceeds the UPS output capacity. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.8 |
upsAlarmOnBypass-genThe Bypass is presently engaged on the UPS. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.9 |
upsAlarmBypassBad-genThe Bypass is out of tolerance. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.10 |
upsAlarmOutputOffAsRequested-genThe UPS has shutdown as requested, i.e., the output
is off. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.11 |
upsAlarmChargerFailed-genAn uncorrected problem has been detected within the
UPS charger subsystem. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.13 |
upsAlarmUpsOutputOff-genThe output of the UPS is in the off state. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.14 |
upsAlarmUpsSystemOff-genThe UPS system is in the off state. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.15 |
upsAlarmFanFailure-genThe failure of one or more fans in the UPS has been
detected. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.16 |
upsAlarmFuseFailure-genThe failure of one or more fuses has been detected. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.17 |
upsAlarmGeneralFault-genA general fault in the UPS has been detected. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.18 |
upsAlarmDiagnosticTestFailed-genThe result of the last diagnostic test indicates a
failure. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.19 |
upsAlarmCommunicationsLost-genA problem has been encountered in the communication
between the agent and the UPS. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.20 |
upsAlarmAwaitingPower-genThe UPS output is off and the UPS is awaiting the
return of the input power (*). TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.21 |
upsAlarmShutdownPending-genA upsShutdownAfterDelay countdown is underway. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.22 |
upsAlarmShutdownImminent-genThe UPS will turn off power to the load in less than
5 seconds; this may be either a timed shutdown or a
low battery shutdown. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.23 |
upsAlarmTestInProgress-genA test is in progress, as initiated and indicated by
the Test Group. Tests initiated via other
implementation-specific mechanisms can indicate the
presence of the testing in the alarm table, if
desired, via a OBJECT-IDENTITY macro in the MIB
document specific to that implementation and are
outside the scope of this OBJECT-IDENTITY. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.24 |
upsAlarmReceptacleOff-genA receptacle has been switched off. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.25 |
upsAlarmBatteryBadRestored-genA Battery bad condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.33 |
upsAlarmOnBatteryRestored-genThe UPS is drawing power from mains again. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.34 |
upsAlarmLowBatteryRestored-genA Low Battery condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.35 |
upsAlarmDepletedBatteryRestored-genA Depleted Battery condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.36 |
upsAlarmTempBadRestored-genA bad temperature condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.37 |
upsAlarmInputBadRestored-genAn input bad condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.38 |
upsAlarmOutputBadRestored-genAn output bad condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.39 |
upsAlarmOutputOverloadRestored-genAn output overload condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.40 |
upsAlarmOnBypassRestored-genAn On Bypass condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.41 |
upsAlarmBypassBadRestored-genA Bypass bad condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.42 |
upsAlarmOutputOffAsRequestedRestored-genA request shutdown has been restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.43 |
upsAlarmChargerFailedRestored-genA Charger Failer condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.45 |
upsAlarmUpsOutputOn-genThe output of the UPS switched in the on state. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.46 |
upsAlarmUpsSystemOn-genThe UPS system is switched in the on state. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.47 |
upsAlarmFanFailureRestored-genA Fan failure condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.48 |
upsAlarmFuseFailureRestored-genA Fuse failure condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.49 |
upsAlarmGeneralFaultRestored-genA general fault is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.50 |
upsAlarmDiagnosticTestFailedRestored-genA last diagnostic test indicates a failure is
restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.51 |
upsAlarmCommunicationsLostRestored-genA problem in the communication between the agent
and the UPS is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.52 |
upsAlarmAwaitingPowerRestored-genA awaiting power condition is restored (*). TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.53 |
upsAlarmShutdownPendingRestored-genA upsShutdownAfterDelay countdown is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.54 |
upsAlarmShutdownImminentRestored-genA shutdown imminent condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.55 |
upsAlarmTestInProgressRestored-genThe test is in progress is terminated. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.56 |
upsAlarmReceptacleOnA receptacle has been switched on. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.57 |
upsAlarmValueLow-genA measurement value reached a value below its low-level threshold. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.129 |
upsAlarmValueHigh-genA measurement value reached a value higher than its high-level threshold. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.130 |
upsAlarmValueLowRestored-genA ValueLow alarm condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.133 |
upsAlarmValueHighRestored-genA ValueHigh alarm condition is restored. TRAP-TYPE .1.3.6.1.4.1.818.1.1.10.11.0.134 |
geEnvironmental OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2 |
ioInterface-First OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.1 |
ioInterfaceInputLine-First OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.1.1 |
ioInterfaceNumInputs-FirstThe number of input lines utilized in this device.
This entry indicates the number of rows in the input
table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.1.1.1 |
ioInterfaceInputTable-FirstA list of input line table entries. The number of
entries is given by the value of ioInterfaceNumInputs. SEQUENCE OF IoInterfaceInputEntry-First .1.3.6.1.4.1.818.1.2.1.1.2 |
ioInterfaceInputEntry-FirstAn entry containing information applicable to a
particular input line. IoInterfaceInputEntry-First .1.3.6.1.4.1.818.1.2.1.1.2.1 |
ioInterfaceInputLineIndex-FirstThe input line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.1.1.2.1.1 |
ioInterfaceInputDescription-FirstA description of the alarm monitored by this input line.rw DisplayString .1.3.6.1.4.1.818.1.2.1.1.2.1.2 |
ioInterfaceInputStatus-FirstThe status of the input lines controlled by the device.
When a bit is high (1), the associated line is 'active'ro Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.1.1.2.1.3 |
ioInterfaceEdgeMode-FirstEdge mode for input lines.
This object specifies if the corresponding input line should be
recognised immediately as active (edge mode on), or only when the
state remains stable for at least the time specified by
ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful
when the object ioInterfaceAlarmMask is active.rw Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.1.2.1.1.2.1.4 |
ioInterfaceAlarmMask-FirstAlarm functionality for the input line can be set active or
inactive.rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.1.1.2.1.5 |
ioInterfaceAlarmDelay-FirstTime delay during which an active input line has to be stable, prior
to issue an alarm. Effective only when EdgeMode=off for the corresponding line.rw NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.1.1.3 |
ioInterfaceOutputLine-First OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.1.2 |
ioInterfaceNumOutput-FirstThe number of output lines utilized by this device.
This entry indicates the number of rows in the output
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.1.2.1 |
ioInterfaceOutputTable-FirstA list of output line table entries. The number of
entries is given by the value of ioInterfaceNumOutputs. SEQUENCE OF IoInterfaceOutputEntry-First .1.3.6.1.4.1.818.1.2.1.2.2 |
ioInterfaceOutputEntry-FirstAn entry containing information applicable to a
particular output line. IoInterfaceOutputEntry-First .1.3.6.1.4.1.818.1.2.1.2.2.1 |
ioInterfaceOutputLineIndex-FirstThe output line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.1.2.2.1.1 |
ioInterfaceOutputDescription-FirstA description of the alarm monitored by this output line.rw DisplayString .1.3.6.1.4.1.818.1.2.1.2.2.1.2 |
ioInterfaceOutputStatus-FirstThe status of the output lines controlled by the device.
When a bit is high (1), the associated line is 'active'rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.1.2.2.1.3 |
ioInterfaceAnalogueLine-First OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.1.3 |
ioInterfaceNumAnalogue-FirstThe number of analogue lines utilized by this device.
This entry indicates the number of rows in the analogue
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.1.3.1 |
ioInterfaceAnalogueTable-FirstA list of analogue line table entries. The number of
entries is given by the value of ioInterfaceNumAnalogue. SEQUENCE OF IoInterfaceAnalogueEntry-First .1.3.6.1.4.1.818.1.2.1.3.2 |
ioInterfaceAnalogueEntry-FirstAn entry containing information applicable to a
particular analogue line. IoInterfaceAnalogueEntry-First .1.3.6.1.4.1.818.1.2.1.3.2.1 |
ioInterfaceAnalogueLineIndex-FirstThe analogue line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.1.3.2.1.1 |
ioInterfaceAnalogueDescription-FirstA description of the alarm monitored by this analogue line.rw DisplayString .1.3.6.1.4.1.818.1.2.1.3.2.1.2 |
ioInterfaceAnalogueStatus-FirstRead analogue value 1, when the board support such functionalityro Integer32 .1.3.6.1.4.1.818.1.2.1.3.2.1.3 |
ioInterfaceAnalogueLowThreshold-FirstLow limit for the analogical value. When the analogical
measurement comes under this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.1.3.2.1.4 |
ioInterfaceAnalogueHighThreshold-FirstHigh limit for the analogical value. When the analogical
measurement comes higher than this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.1.3.2.1.5 |
ioInterfaceAnalogueResetLowThreshold-FirstAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the low alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.1.3.2.1.6 |
ioInterfaceAnalogueResetHighThreshold-FirstAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the high alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.1.3.2.1.7 |
ioInterfaceTraps-First OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.1.4 |
ioAlarmGenericChange-FirstAn generic change of a digital input/digital output/analog input has become active. TRAP-TYPE .1.3.6.1.4.1.818.1.2.1.4.0.1 |
ioInterface-Second OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.2 |
ioInterfaceInputLine-Second OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.2.1 |
ioInterfaceNumInputs-SecondThe number of input lines utilized in this device.
This entry indicates the number of rows in the input
table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.2.1.1 |
ioInterfaceInputTable-SecondA list of input line table entries. The number of
entries is given by the value of ioInterfaceNumInputs. SEQUENCE OF IoInterfaceInputEntry-Second .1.3.6.1.4.1.818.1.2.2.1.2 |
ioInterfaceInputEntry-SecondAn entry containing information applicable to a
particular input line. IoInterfaceInputEntry-Second .1.3.6.1.4.1.818.1.2.2.1.2.1 |
ioInterfaceInputLineIndex-SecondThe input line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.2.1.2.1.1 |
ioInterfaceInputDescription-SecondA description of the alarm monitored by this input line.rw DisplayString .1.3.6.1.4.1.818.1.2.2.1.2.1.2 |
ioInterfaceInputStatus-SecondThe status of the input lines controlled by the device.
When a bit is high (1), the associated line is 'active'ro Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.2.1.2.1.3 |
ioInterfaceEdgeMode-SecondEdge mode for input lines.
This object specifies if the corresponding input line should be
recognised immediately as active (edge mode on), or only when the
state remains stable for at least the time specified by
ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful
when the object ioInterfaceAlarmMask is active.rw Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.1.2.2.1.2.1.4 |
ioInterfaceAlarmMask-SecondAlarm functionality for the input line can be set active or
inactive.rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.2.1.2.1.5 |
ioInterfaceAlarmDelay-SecondTime delay during which an active input line has to be stable, prior
to issue an alarm. Effective only when EdgeMode=off for the corresponding line.rw NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.2.1.2.1.6 |
ioInterfaceOutputLine-Second OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.2.2 |
ioInterfaceNumOutput-SecondThe number of output lines utilized by this device.
This entry indicates the number of rows in the output
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.2.2.1 |
ioInterfaceOutputTable-SecondA list of output line table entries. The number of
entries is given by the value of ioInterfaceNumOutputs. SEQUENCE OF IoInterfaceOutputEntry-Second .1.3.6.1.4.1.818.1.2.2.2.2 |
ioInterfaceOutputEntry-SecondAn entry containing information applicable to a
particular output line. IoInterfaceOutputEntry-Second .1.3.6.1.4.1.818.1.2.2.2.2.1 |
ioInterfaceOutputLineIndex-SecondThe output line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.2.2.2.1.1 |
ioInterfaceOutputDescription-SecondA description of the alarm monitored by this output line.rw DisplayString .1.3.6.1.4.1.818.1.2.2.2.2.1.2 |
ioInterfaceOutputStatus-SecondThe status of the output lines controlled by the device.
When a bit is high (1), the associated line is 'active'rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.2.2.2.1.3 |
ioInterfaceAnalogueLine-Second OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.2.3 |
ioInterfaceNumAnalogue-SecondThe number of analogue lines utilized by this device.
This entry indicates the number of rows in the analogue
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.2.3.1 |
ioInterfaceAnalogueTable-SecondA list of analogue line table entries. The number of
entries is given by the value of ioInterfaceNumAnalogue. SEQUENCE OF IoInterfaceAnalogueEntry-Second .1.3.6.1.4.1.818.1.2.2.3.2 |
ioInterfaceAnalogueEntry-SecondAn entry containing information applicable to a
particular analogue line. IoInterfaceAnalogueEntry-Second .1.3.6.1.4.1.818.1.2.2.3.2.1 |
ioInterfaceAnalogueLineIndex-SecondThe analogue line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.2.3.2.1.1 |
ioInterfaceAnalogueDescription-SecondA description of the alarm monitored by this analogue line.rw DisplayString .1.3.6.1.4.1.818.1.2.2.3.2.1.2 |
ioInterfaceAnalogueStatus-SecondRead analogue value 1, when the board support such functionalityro Integer32 .1.3.6.1.4.1.818.1.2.2.3.2.1.3 |
ioInterfaceAnalogueLowThreshold-SecondLow limit for the analogical value. When the analogical
measurement comes under this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.2.3.2.1.4 |
ioInterfaceAnalogueHighThreshold-SecondHigh limit for the analogical value. When the analogical
measurement comes higher than this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.2.3.2.1.5 |
ioInterfaceAnalogueResetLowThreshold-SecondAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the low alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.2.3.2.1.6 |
ioInterfaceAnalogueResetHighThreshold-SecondAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the high alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.2.3.2.1.7 |
ioInterfaceTraps-Second OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.2.4 |
ioAlarmGenericChange-SecondAn generic change of a digital input/digital output/analog input has become active. TRAP-TYPE .1.3.6.1.4.1.818.1.2.2.4.0.1 |
ioInterface-Third OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.3 |
ioInterfaceInputLine-Third OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.3.1 |
ioInterfaceNumInputs-ThirdThe number of input lines utilized in this device.
This entry indicates the number of rows in the input
table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.3.1.1 |
ioInterfaceInputTable-ThirdA list of input line table entries. The number of
entries is given by the value of ioInterfaceNumInputs. SEQUENCE OF IoInterfaceInputEntry-Third .1.3.6.1.4.1.818.1.2.3.1.2 |
ioInterfaceInputEntry-ThirdAn entry containing information applicable to a
particular input line. IoInterfaceInputEntry-Third .1.3.6.1.4.1.818.1.2.3.1.2.1 |
ioInterfaceInputLineIndex-ThirdThe input line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.3.1.2.1.1 |
ioInterfaceInputDescription-ThirdA description of the alarm monitored by this input line.rw DisplayString .1.3.6.1.4.1.818.1.2.3.1.2.1.2 |
ioInterfaceInputStatus-ThirdThe status of the input lines controlled by the device.
When a bit is high (1), the associated line is 'active'ro Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.3.1.2.1.3 |
ioInterfaceEdgeMode-ThirdEdge mode for input lines.
This object specifies if the corresponding input line should be
recognised immediately as active (edge mode on), or only when the
state remains stable for at least the time specified by
ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful
when the object ioInterfaceAlarmMask is active.rw Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.1.2.3.1.2.1.4 |
ioInterfaceAlarmMask-ThirdAlarm functionality for the input line can be set active or
inactive.rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.3.1.2.1.5 |
ioInterfaceAlarmDelay-ThirdTime delay during which an active input line has to be stable, prior
to issue an alarm. Effective only when EdgeMode=off for the corresponding line.rw NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.3.1.2.1.6 |
ioInterfaceOutputLine-Third OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.3.2 |
ioInterfaceNumOutput-ThirdThe number of output lines utilized by this device.
This entry indicates the number of rows in the output
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.3.2.1 |
ioInterfaceOutputTable-ThirdA list of output line table entries. The number of
entries is given by the value of ioInterfaceNumOutputs. SEQUENCE OF IoInterfaceOutputEntry-Third .1.3.6.1.4.1.818.1.2.3.2.2 |
ioInterfaceOutputEntry-ThirdAn entry containing information applicable to a
particular output line. IoInterfaceOutputEntry-Third .1.3.6.1.4.1.818.1.2.3.2.2.1 |
ioInterfaceOutputLineIndex-ThirdThe output line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.3.2.2.1.1 |
ioInterfaceOutputDescription-ThirdA description of the alarm monitored by this output line.rw DisplayString .1.3.6.1.4.1.818.1.2.3.2.2.1.2 |
ioInterfaceOutputStatus-ThirdThe status of the output lines controlled by the device.
When a bit is high (1), the associated line is 'active'rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.3.2.2.1.3 |
ioInterfaceAnalogueLine-Third OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.3.3 |
ioInterfaceNumAnalogue-ThirdThe number of analogue lines utilized by this device.
This entry indicates the number of rows in the analogue
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.3.3.1 |
ioInterfaceAnalogueTable-ThirdA list of analogue line table entries. The number of
entries is given by the value of ioInterfaceNumAnalogue. SEQUENCE OF IoInterfaceAnalogueEntry-Third .1.3.6.1.4.1.818.1.2.3.3.2 |
ioInterfaceAnalogueEntry-ThirdAn entry containing information applicable to a
particular analogue line. IoInterfaceAnalogueEntry-Third .1.3.6.1.4.1.818.1.2.3.3.2.1 |
ioInterfaceAnalogueLineIndex-ThirdThe analogue line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.3.3.2.1.1 |
ioInterfaceAnalogueDescription-ThirdA description of the alarm monitored by this analogue line.rw DisplayString .1.3.6.1.4.1.818.1.2.3.3.2.1.2 |
ioInterfaceAnalogueStatus-ThirdRead analogue value 1, when the board support such functionalityro Integer32 .1.3.6.1.4.1.818.1.2.3.3.2.1.3 |
ioInterfaceAnalogueLowThreshold-ThirdLow limit for the analogical value. When the analogical
measurement comes under this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.3.3.2.1.4 |
ioInterfaceAnalogueHighThreshold-ThirdHigh limit for the analogical value. When the analogical
measurement comes higher than this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.3.3.2.1.5 |
ioInterfaceAnalogueResetLowThreshold-ThirdAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the low alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.3.3.2.1.6 |
ioInterfaceAnalogueResetHighThreshold-ThirdAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the high alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.3.3.2.1.7 |
ioInterfaceTraps-Third OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.3.4 |
ioAlarmGenericChange-ThirdAn generic change of a digital input/digital output/analog input has become active. TRAP-TYPE .1.3.6.1.4.1.818.1.2.3.4.0.1 |
ioInterface-Fourth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.4 |
ioInterfaceInputLine-Fourth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.4.1 |
ioInterfaceNumInputs-FourthThe number of input lines utilized in this device.
This entry indicates the number of rows in the input
table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.4.1.1 |
ioInterfaceInputTable-FourthA list of input line table entries. The number of
entries is given by the value of ioInterfaceNumInputs. SEQUENCE OF IoInterfaceInputEntry-Fourth .1.3.6.1.4.1.818.1.2.4.1.2 |
ioInterfaceInputEntry-FourthAn entry containing information applicable to a
particular input line. IoInterfaceInputEntry-Fourth .1.3.6.1.4.1.818.1.2.4.1.2.1 |
ioInterfaceInputLineIndex-FourthThe input line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.4.1.2.1.1 |
ioInterfaceInputDescription-FourthA description of the alarm monitored by this input line.rw DisplayString .1.3.6.1.4.1.818.1.2.4.1.2.1.2 |
ioInterfaceInputStatus-FourthThe status of the input lines controlled by the device.
When a bit is high (1), the associated line is 'active'ro Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.4.1.2.1.3 |
ioInterfaceEdgeMode-FourthEdge mode for input lines.
This object specifies if the corresponding input line should be
recognised immediately as active (edge mode on), or only when the
state remains stable for at least the time specified by
ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful
when the object ioInterfaceAlarmMask is active.rw Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.1.2.4.1.2.1.4 |
ioInterfaceAlarmMask-FourthAlarm functionality for the input line can be set active or
inactive.rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.4.1.2.1.5 |
ioInterfaceAlarmDelay-FourthTime delay during which an active input line has to be stable, prior
to issue an alarm. Effective only when EdgeMode=off for the corresponding line.rw NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.4.1.2.1.6 |
ioInterfaceOutputLine-Fourth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.4.2 |
ioInterfaceNumOutput-FourthThe number of output lines utilized by this device.
This entry indicates the number of rows in the output
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.4.2.1 |
ioInterfaceOutputTable-FourthA list of output line table entries. The number of
entries is given by the value of ioInterfaceNumOutputs. SEQUENCE OF IoInterfaceOutputEntry-Fourth .1.3.6.1.4.1.818.1.2.4.2.2 |
ioInterfaceOutputEntry-FourthAn entry containing information applicable to a
particular output line. IoInterfaceOutputEntry-Fourth .1.3.6.1.4.1.818.1.2.4.2.2.1 |
ioInterfaceOutputLineIndex-FourthThe output line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.4.2.2.1.1 |
ioInterfaceOutputDescription-FourthA description of the alarm monitored by this output line.rw DisplayString .1.3.6.1.4.1.818.1.2.4.2.2.1.2 |
ioInterfaceOutputStatus-FourthThe status of the output lines controlled by the device.
When a bit is high (1), the associated line is 'active'rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.4.2.2.1.3 |
ioInterfaceAnalogueLine-Fourth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.4.3 |
ioInterfaceNumAnalogue-FourthThe number of analogue lines utilized by this device.
This entry indicates the number of rows in the analogue
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.4.3.1 |
ioInterfaceAnalogueTable-FourthA list of analogue line table entries. The number of
entries is given by the value of ioInterfaceNumAnalogue. SEQUENCE OF IoInterfaceAnalogueEntry-Fourth .1.3.6.1.4.1.818.1.2.4.3.2 |
ioInterfaceAnalogueEntry-FourthAn entry containing information applicable to a
particular analogue line. IoInterfaceAnalogueEntry-Fourth .1.3.6.1.4.1.818.1.2.4.3.2.1 |
ioInterfaceAnalogueLineIndex-FourthThe analogue line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.4.3.2.1.1 |
ioInterfaceAnalogueDescription-FourthA description of the alarm monitored by this analogue line.rw DisplayString .1.3.6.1.4.1.818.1.2.4.3.2.1.2 |
ioInterfaceAnalogueStatus-FourthRead analogue value 1, when the board support such functionalityro Integer32 .1.3.6.1.4.1.818.1.2.4.3.2.1.3 |
ioInterfaceAnalogueLowThreshold-FourthLow limit for the analogical value. When the analogical
measurement comes under this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.4.3.2.1.4 |
ioInterfaceAnalogueHighThreshold-FourthHigh limit for the analogical value. When the analogical
measurement comes higher than this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.4.3.2.1.5 |
ioInterfaceAnalogueResetLowThreshold-FourthAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the low alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.4.3.2.1.6 |
ioInterfaceAnalogueResetHighThreshold-FourthAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the high alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.4.3.2.1.7 |
ioInterfaceTraps-Fourth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.4.4 |
ioAlarmGenericChange-FourthAn generic change of a digital input/digital output/analog input has become active. TRAP-TYPE .1.3.6.1.4.1.818.1.2.4.4.0.1 |
ioInterface-Fifth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.5 |
ioInterfaceInputLine-Fifth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.5.1 |
ioInterfaceNumInputs-FifthThe number of input lines utilized in this device.
This entry indicates the number of rows in the input
table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.5.1.1 |
ioInterfaceInputTable-FifthA list of input line table entries. The number of
entries is given by the value of ioInterfaceNumInputs. SEQUENCE OF IoInterfaceInputEntry-Fifth .1.3.6.1.4.1.818.1.2.5.1.2 |
ioInterfaceInputEntry-FifthAn entry containing information applicable to a
particular input line. IoInterfaceInputEntry-Fifth .1.3.6.1.4.1.818.1.2.5.1.2.1 |
ioInterfaceInputLineIndex-FifthThe input line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.5.1.2.1.1 |
ioInterfaceInputDescription-FifthA description of the alarm monitored by this input line.rw DisplayString .1.3.6.1.4.1.818.1.2.5.1.2.1.2 |
ioInterfaceInputStatus-FifthThe status of the input lines controlled by the device.
When a bit is high (1), the associated line is 'active'ro Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.5.1.2.1.3 |
ioInterfaceEdgeMode-FifthEdge mode for input lines.
This object specifies if the corresponding input line should be
recognised immediately as active (edge mode on), or only when the
state remains stable for at least the time specified by
ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful
when the object ioInterfaceAlarmMask is active.rw Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.1.2.5.1.2.1.4 |
ioInterfaceAlarmMask-FifthAlarm functionality for the input line can be set active or
inactive.rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.5.1.2.1.5 |
ioInterfaceAlarmDelay-FifthTime delay during which an active input line has to be stable, prior
to issue an alarm. Effective only when EdgeMode=off for the corresponding line.rw NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.5.1.2.1.6 |
ioInterfaceOutputLine-Fifth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.5.2 |
ioInterfaceNumOutput-FifthThe number of output lines utilized by this device.
This entry indicates the number of rows in the output
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.5.2.1 |
ioInterfaceOutputTable-FifthA list of output line table entries. The number of
entries is given by the value of ioInterfaceNumOutputs. SEQUENCE OF IoInterfaceOutputEntry-Fifth .1.3.6.1.4.1.818.1.2.5.2.2 |
ioInterfaceOutputEntry-FifthAn entry containing information applicable to a
particular output line. IoInterfaceOutputEntry-Fifth .1.3.6.1.4.1.818.1.2.5.2.2.1 |
ioInterfaceOutputLineIndex-FifthThe output line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.5.2.2.1.1 |
ioInterfaceOutputDescription-FifthA description of the alarm monitored by this output line.rw DisplayString .1.3.6.1.4.1.818.1.2.5.2.2.1.2 |
ioInterfaceOutputStatus-FifthThe status of the output lines controlled by the device.
When a bit is high (1), the associated line is 'active'rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.5.2.2.1.3 |
ioInterfaceAnalogueLine-Fifth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.5.3 |
ioInterfaceNumAnalogue-FifthThe number of analogue lines utilized by this device.
This entry indicates the number of rows in the analogue
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.5.3.1 |
ioInterfaceAnalogueTable-FifthA list of analogue line table entries. The number of
entries is given by the value of ioInterfaceNumAnalogue. SEQUENCE OF IoInterfaceAnalogueEntry-Fifth .1.3.6.1.4.1.818.1.2.5.3.2 |
ioInterfaceAnalogueEntry-FifthAn entry containing information applicable to a
particular analogue line. IoInterfaceAnalogueEntry-Fifth .1.3.6.1.4.1.818.1.2.5.3.2.1 |
ioInterfaceAnalogueLineIndex-FifthThe analogue line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.5.3.2.1.1 |
ioInterfaceAnalogueDescription-FifthA description of the alarm monitored by this analogue line.rw DisplayString .1.3.6.1.4.1.818.1.2.5.3.2.1.2 |
ioInterfaceAnalogueStatus-FifthRead analogue value 1, when the board support such functionalityro Integer32 .1.3.6.1.4.1.818.1.2.5.3.2.1.3 |
ioInterfaceAnalogueLowThreshold-FifthLow limit for the analogical value. When the analogical
measurement comes under this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.5.3.2.1.4 |
ioInterfaceAnalogueHighThreshold-FifthHigh limit for the analogical value. When the analogical
measurement comes higher than this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.5.3.2.1.5 |
ioInterfaceAnalogueResetLowThreshold-FifthAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the low alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.5.3.2.1.6 |
ioInterfaceAnalogueResetHighThreshold-FifthAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the high alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.5.3.2.1.7 |
ioInterfaceTraps-Fifth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.5.4 |
ioAlarmGenericChange-FifthAn generic change of a digital input/digital output/analog input has become active. TRAP-TYPE .1.3.6.1.4.1.818.1.2.5.4.0.1 |
ioInterface-Sixth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.6 |
ioInterfaceInputLine-Sixth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.6.1 |
ioInterfaceNumInputs-SixthThe number of input lines utilized in this device.
This entry indicates the number of rows in the input
table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.6.1.1 |
ioInterfaceInputTable-SixthA list of input line table entries. The number of
entries is given by the value of ioInterfaceNumInputs. SEQUENCE OF IoInterfaceInputEntry-Sixth .1.3.6.1.4.1.818.1.2.6.1.2 |
ioInterfaceInputEntry-SixthAn entry containing information applicable to a
particular input line. IoInterfaceInputEntry-Sixth .1.3.6.1.4.1.818.1.2.6.1.2.1 |
ioInterfaceInputLineIndex-SixthThe input line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.6.1.2.1.1 |
ioInterfaceInputDescription-SixthA description of the alarm monitored by this input line.rw DisplayString .1.3.6.1.4.1.818.1.2.6.1.2.1.2 |
ioInterfaceInputStatus-SixthThe status of the input lines controlled by the device.
When a bit is high (1), the associated line is 'active'ro Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.6.1.2.1.3 |
ioInterfaceEdgeMode-SixthEdge mode for input lines.
This object specifies if the corresponding input line should be
recognised immediately as active (edge mode on), or only when the
state remains stable for at least the time specified by
ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful
when the object ioInterfaceAlarmMask is active.rw Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.1.2.6.1.2.1.4 |
ioInterfaceAlarmMask-SixthAlarm functionality for the input line can be set active or
inactive.rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.6.1.2.1.5 |
ioInterfaceAlarmDelay-SixthTime delay during which an active input line has to be stable, prior
to issue an alarm. Effective only when EdgeMode=off for the corresponding line.rw NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.6.1.2.1.6 |
ioInterfaceOutputLine-Sixth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.6.2 |
ioInterfaceNumOutput-SixthThe number of output lines utilized by this device.
This entry indicates the number of rows in the output
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.6.2.1 |
ioInterfaceOutputTable-SixthA list of output line table entries. The number of
entries is given by the value of ioInterfaceNumOutputs. SEQUENCE OF IoInterfaceOutputEntry-Sixth .1.3.6.1.4.1.818.1.2.6.2.2 |
ioInterfaceOutputEntry-SixthAn entry containing information applicable to a
particular output line. IoInterfaceOutputEntry-Sixth .1.3.6.1.4.1.818.1.2.6.2.2.1 |
ioInterfaceOutputLineIndex-SixthThe output line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.6.2.2.1.1 |
ioInterfaceOutputDescription-SixthA description of the alarm monitored by this output line.rw DisplayString .1.3.6.1.4.1.818.1.2.6.2.2.1.2 |
ioInterfaceOutputStatus-SixthThe status of the output lines controlled by the device.
When a bit is high (1), the associated line is 'active'rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.6.2.2.1.3 |
ioInterfaceAnalogueLine-Sixth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.6.3 |
ioInterfaceNumAnalogue-SixthThe number of analogue lines utilized by this device.
This entry indicates the number of rows in the analogue
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.6.3.1 |
ioInterfaceAnalogueTable-SixthA list of analogue line table entries. The number of
entries is given by the value of ioInterfaceNumAnalogue. SEQUENCE OF IoInterfaceAnalogueEntry-Sixth .1.3.6.1.4.1.818.1.2.6.3.2 |
ioInterfaceAnalogueEntry-SixthAn entry containing information applicable to a
particular analogue line. IoInterfaceAnalogueEntry-Sixth .1.3.6.1.4.1.818.1.2.6.3.2.1 |
ioInterfaceAnalogueLineIndex-SixthThe analogue line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.6.3.2.1.1 |
ioInterfaceAnalogueDescription-SixthA description of the alarm monitored by this analogue line.rw DisplayString .1.3.6.1.4.1.818.1.2.6.3.2.1.2 |
ioInterfaceAnalogueStatus-SixthRead analogue value 1, when the board support such functionalityro Integer32 .1.3.6.1.4.1.818.1.2.6.3.2.1.3 |
ioInterfaceAnalogueLowThreshold-SixthLow limit for the analogical value. When the analogical
measurement comes under this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.6.3.2.1.4 |
ioInterfaceAnalogueHighThreshold-SixthHigh limit for the analogical value. When the analogical
measurement comes higher than this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.6.3.2.1.5 |
ioInterfaceAnalogueResetLowThreshold-SixthAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the low alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.6.3.2.1.6 |
ioInterfaceAnalogueResetHighThreshold-SixthAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the high alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.6.3.2.1.7 |
ioInterfaceTraps-Sixth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.6.4 |
ioAlarmGenericChange-SixthAn generic change of a digital input/digital output/analog input has become active. TRAP-TYPE .1.3.6.1.4.1.818.1.2.6.4.0.1 |
ioInterface-Seventh OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.7 |
ioInterfaceInputLine-Seventh OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.7.1 |
ioInterfaceNumInputs-SeventhThe number of input lines utilized in this device.
This entry indicates the number of rows in the input
table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.7.1.1 |
ioInterfaceInputTable-SeventhA list of input line table entries. The number of
entries is given by the value of ioInterfaceNumInputs. SEQUENCE OF IoInterfaceInputEntry-Seventh .1.3.6.1.4.1.818.1.2.7.1.2 |
ioInterfaceInputEntry-SeventhAn entry containing information applicable to a
particular input line. IoInterfaceInputEntry-Seventh .1.3.6.1.4.1.818.1.2.7.1.2.1 |
ioInterfaceInputLineIndex-SeventhThe input line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.7.1.2.1.1 |
ioInterfaceInputDescription-SeventhA description of the alarm monitored by this input line.rw DisplayString .1.3.6.1.4.1.818.1.2.7.1.2.1.2 |
ioInterfaceInputStatus-SeventhThe status of the input lines controlled by the device.
When a bit is high (1), the associated line is 'active'ro Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.7.1.2.1.3 |
ioInterfaceEdgeMode-SeventhEdge mode for input lines.
This object specifies if the corresponding input line should be
recognised immediately as active (edge mode on), or only when the
state remains stable for at least the time specified by
ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful
when the object ioInterfaceAlarmMask is active.rw Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.1.2.7.1.2.1.4 |
ioInterfaceAlarmMask-SeventhAlarm functionality for the input line can be set active or
inactive.rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.7.1.2.1.5 |
ioInterfaceAlarmDelay-SeventhTime delay during which an active input line has to be stable, prior
to issue an alarm. Effective only when EdgeMode=off for the corresponding line.rw NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.7.1.2.1.6 |
ioInterfaceOutputLine-Seventh OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.7.2 |
ioInterfaceNumOutput-SeventhThe number of output lines utilized by this device.
This entry indicates the number of rows in the output
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.7.2.1 |
ioInterfaceOutputTable-SeventhA list of output line table entries. The number of
entries is given by the value of ioInterfaceNumOutputs. SEQUENCE OF IoInterfaceOutputEntry-Seventh .1.3.6.1.4.1.818.1.2.7.2.2 |
ioInterfaceOutputEntry-SeventhAn entry containing information applicable to a
particular output line. IoInterfaceOutputEntry-Seventh .1.3.6.1.4.1.818.1.2.7.2.2.1 |
ioInterfaceOutputLineIndex-SeventhThe output line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.7.2.2.1.1 |
ioInterfaceOutputDescription-SeventhA description of the alarm monitored by this output line.rw DisplayString .1.3.6.1.4.1.818.1.2.7.2.2.1.2 |
ioInterfaceOutputStatus-SeventhThe status of the output lines controlled by the device.
When a bit is high (1), the associated line is 'active'rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.7.2.2.1.3 |
ioInterfaceAnalogueLine-Seventh OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.7.3 |
ioInterfaceNumAnalogue-SeventhThe number of analogue lines utilized by this device.
This entry indicates the number of rows in the analogue
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.7.3.1 |
ioInterfaceAnalogueTable-SeventhA list of analogue line table entries. The number of
entries is given by the value of ioInterfaceNumAnalogue. SEQUENCE OF IoInterfaceAnalogueEntry-Seventh .1.3.6.1.4.1.818.1.2.7.3.2 |
ioInterfaceAnalogueEntry-SeventhAn entry containing information applicable to a
particular analogue line. IoInterfaceAnalogueEntry-Seventh .1.3.6.1.4.1.818.1.2.7.3.2.1 |
ioInterfaceAnalogueLineIndex-SeventhThe analogue line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.7.3.2.1.1 |
ioInterfaceAnalogueDescription-SeventhA description of the alarm monitored by this analogue line.rw DisplayString .1.3.6.1.4.1.818.1.2.7.3.2.1.2 |
ioInterfaceAnalogueStatus-SeventhRead analogue value 1, when the board support such functionalityro Integer32 .1.3.6.1.4.1.818.1.2.7.3.2.1.3 |
ioInterfaceAnalogueLowThreshold-SeventhLow limit for the analogical value. When the analogical
measurement comes under this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.7.3.2.1.4 |
ioInterfaceAnalogueHighThreshold-SeventhHigh limit for the analogical value. When the analogical
measurement comes higher than this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.7.3.2.1.5 |
ioInterfaceAnalogueResetLowThreshold-SeventhAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the low alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.7.3.2.1.6 |
ioInterfaceAnalogueResetHighThreshold-SeventhAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the high alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.7.3.2.1.7 |
ioInterfaceTraps-Seventh OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.7.4 |
ioAlarmGenericChange-SeventhAn generic change of a digital input/digital output/analog input has become active. TRAP-TYPE .1.3.6.1.4.1.818.1.2.7.4.0.1 |
ioInterface-Eighth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.8 |
ioInterfaceInputLine-Eighth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.8.1 |
ioInterfaceNumInputs-EighthThe number of input lines utilized in this device.
This entry indicates the number of rows in the input
table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.8.1.1 |
ioInterfaceInputTable-EighthA list of input line table entries. The number of
entries is given by the value of ioInterfaceNumInputs. SEQUENCE OF IoInterfaceInputEntry-Eighth .1.3.6.1.4.1.818.1.2.8.1.2 |
ioInterfaceInputEntry-EighthAn entry containing information applicable to a
particular input line. IoInterfaceInputEntry-Eighth .1.3.6.1.4.1.818.1.2.8.1.2.1 |
ioInterfaceInputLineIndex-EighthThe input line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.8.1.2.1.1 |
ioInterfaceInputDescription-EighthA description of the alarm monitored by this input line.rw DisplayString .1.3.6.1.4.1.818.1.2.8.1.2.1.2 |
ioInterfaceInputStatus-EighthThe status of the input lines controlled by the device.
When a bit is high (1), the associated line is 'active'ro Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.8.1.2.1.3 |
ioInterfaceEdgeMode-EighthEdge mode for input lines.
This object specifies if the corresponding input line should be
recognised immediately as active (edge mode on), or only when the
state remains stable for at least the time specified by
ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful
when the object ioInterfaceAlarmMask is active.rw Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.1.2.8.1.2.1.4 |
ioInterfaceAlarmMask-EighthAlarm functionality for the input line can be set active or
inactive.rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.8.1.2.1.5 |
ioInterfaceAlarmDelay-EighthTime delay during which an active input line has to be stable, prior
to issue an alarm. Effective only when EdgeMode=off for the corresponding line.rw NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.8.1.2.1.6 |
ioInterfaceOutputLine-Eighth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.8.2 |
ioInterfaceNumOutput-EighthThe number of output lines utilized by this device.
This entry indicates the number of rows in the output
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.8.2.1 |
ioInterfaceOutputTable-EighthA list of output line table entries. The number of
entries is given by the value of ioInterfaceNumOutputs. SEQUENCE OF IoInterfaceOutputEntry-Eighth .1.3.6.1.4.1.818.1.2.8.2.2 |
ioInterfaceOutputEntry-EighthAn entry containing information applicable to a
particular output line. IoInterfaceOutputEntry-Eighth .1.3.6.1.4.1.818.1.2.8.2.2.1 |
ioInterfaceOutputLineIndex-EighthThe output line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.8.2.2.1.1 |
ioInterfaceOutputDescription-EighthA description of the alarm monitored by this output line.rw DisplayString .1.3.6.1.4.1.818.1.2.8.2.2.1.2 |
ioInterfaceOutputStatus-EighthThe status of the output lines controlled by the device.
When a bit is high (1), the associated line is 'active'rw Integer32 { inactive(0), active(1) } .1.3.6.1.4.1.818.1.2.8.2.2.1.3 |
ioInterfaceAnalogueLine-Eighth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.8.3 |
ioInterfaceNumAnalogue-EighthThe number of analogue lines utilized by this device.
This entry indicates the number of rows in the analogue
line table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.2.8.3.1 |
ioInterfaceAnalogueTable-EighthA list of analogue line table entries. The number of
entries is given by the value of ioInterfaceNumAnalogue. SEQUENCE OF IoInterfaceAnalogueEntry-Eighth .1.3.6.1.4.1.818.1.2.8.3.2 |
ioInterfaceAnalogueEntry-EighthAn entry containing information applicable to a
particular analogue line. IoInterfaceAnalogueEntry-Eighth .1.3.6.1.4.1.818.1.2.8.3.2.1 |
ioInterfaceAnalogueLineIndex-EighthThe analogue line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.2.8.3.2.1.1 |
ioInterfaceAnalogueDescription-EighthA description of the alarm monitored by this analogue line.rw DisplayString .1.3.6.1.4.1.818.1.2.8.3.2.1.2 |
ioInterfaceAnalogueStatus-EighthRead analogue value 1, when the board support such functionalityro Integer32 .1.3.6.1.4.1.818.1.2.8.3.2.1.3 |
ioInterfaceAnalogueLowThreshold-EighthLow limit for the analogical value. When the analogical
measurement comes under this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.8.3.2.1.4 |
ioInterfaceAnalogueHighThreshold-EighthHigh limit for the analogical value. When the analogical
measurement comes higher than this limit, an alarm is issued. The limit
can be disabled specifying the special floating point value which
means 'not available'.rw Integer32 .1.3.6.1.4.1.818.1.2.8.3.2.1.5 |
ioInterfaceAnalogueResetLowThreshold-EighthAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the low alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.8.3.2.1.6 |
ioInterfaceAnalogueResetHighThreshold-EighthAfter an alarm, value which has to be crossed by the
analogue input, in order to remove the high alarm condition
(hysteresis)rw Integer32 .1.3.6.1.4.1.818.1.2.8.3.2.1.7 |
ioInterfaceTraps-Eighth OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.2.8.4 |
ioAlarmGenericChange-EighthAn generic change of a digital input/digital output/analog input has become active. TRAP-TYPE .1.3.6.1.4.1.818.1.2.8.4.0.1 |
geModem OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.3 |
geModemStatusThe status of the modem, controlled by the addressed device.
The status word is a collection of bits, as specified below. The SNMP value NOSUCHNAME means 'status not (yet) available'.
1 modemStatOnline. There is a valid online connection.
2 modemStatError. The last operation has failed. The device
will clear this bit when a new modem command is received.
4 unused (should be defined = 0).
8 unused (should be defined = 0).
16 modemStatDialling. The dialling procedure is pending.
32 modemStatBusy. The device is performing some operation,
and can not be accessed, temporarily.
64 unused (should be defined = 0).
128 modemStatNoModem. The modem is not connected or not responding.
256 modemStatDCD. The DCD line status signal is on.
512 modemStatRing. The RING line status signal is on.
1024 modemStatCTS. The CTS line status signal is on.
2048 modemStatDSR. The DSR line status signal is on.
4096 unused (should be defined = 0).
8192 unused (should be defined = 0).
16384 unused (should be defined = 0).
32768 unused (should be defined = 0).ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.3.1 |
geModemNumInitStringThe number of modem init strings utilized by this ups.
This entry indicates the number of rows in the init
string table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.3.2 |
geModemInitStringTableA list of init string table entries. The number of
entries is given by the value of geModemNumInitString. SEQUENCE OF GeModemInitStringEntry .1.3.6.1.4.1.818.1.3.3 |
geModemInitStringEntryAn entry containing information applicable to a
particular Init string. GeModemInitStringEntry .1.3.6.1.4.1.818.1.3.3.1 |
geModemInitStringLineIndexThe Init string line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.3.3.1.1 |
geModemInitstringA modem Init string.rw DisplayString .1.3.6.1.4.1.818.1.3.3.1.2 |
geModemNumPhoneNumberThe number of modem phone numbers utilized by this ups.
This entry indicates the number of rows in the table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.1.3.4 |
geModemPhoneNumberTableA list of phone number table entries. The number of
entries is given by the value of geModemNumPhoneNumber. SEQUENCE OF GeModemPhoneNumberEntry .1.3.6.1.4.1.818.1.3.5 |
geModemPhoneNumberEntryAn entry containing information applicable to a
particular phone number. GeModemPhoneNumberEntry .1.3.6.1.4.1.818.1.3.5.1 |
geModemPhoneNumberLineIndexThe phone number line identifier. PositiveInteger32 .1.3.6.1.4.1.818.1.3.5.1.1 |
geModemPhoneNumberA phone number.rw DisplayString .1.3.6.1.4.1.818.1.3.5.1.2 |
geDevices OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.100 |
geDevicesDescriptions OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.100.1 |
advSNMPWebIntCard OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.100.1.1 |
snmpWebIntCard OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.100.1.2 |
snmpWebIntBox OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.100.1.3 |
snmpSWPFAgent OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.100.1.4 |
snmpSWJUMPAgent OBJECT IDENTIFIER .1.3.6.1.4.1.818.1.100.1.5 |
geSoftware OBJECT IDENTIFIER .1.3.6.1.4.1.818.2 |
geClient OBJECT IDENTIFIER .1.3.6.1.4.1.818.2.1 |
geClientProcessorThe processor used by the clients machine.ro DisplayString .1.3.6.1.4.1.818.2.1.1 |
geClientOperatingSystemOperating system on which the client runs.ro DisplayString .1.3.6.1.4.1.818.2.1.2 |
geClientJavaRuntimeVersionJavaRuntimeVersion of the client machine.ro DisplayString .1.3.6.1.4.1.818.2.1.3 |
geClientMaxSizeOfLogfilesThe max. size of the logfiles in Kb.rw NonNegativeInteger32 .1.3.6.1.4.1.818.2.1.4 |
geClientLanguageSelectionShows the currently activated language of the client.ro DisplayString .1.3.6.1.4.1.818.2.1.5 |
geClientInternalCommunicationPortUDP port used between server and client part.rw NonNegativeInteger32 .1.3.6.1.4.1.818.2.1.6 |
geClientRebootsetting this object causes the protection client to reboot
and activate new settings.rw Integer32 { reboot(1) } .1.3.6.1.4.1.818.2.1.7 |
geClientNumUPSThe number of UPSs utilized by this client.
This entry indicates the number of rows in the table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.2.1.8 |
geClientUPSTableA list of UPS table entries. The number of
entries is given by the value of geClientNumUPS. SEQUENCE OF GeClientUPSEntry .1.3.6.1.4.1.818.2.1.9 |
geClientUPSEntryAn entry containing information applicable to a
particular UPS. GeClientUPSEntry .1.3.6.1.4.1.818.2.1.9.1 |
geClientUPSLineIndexThe UPS line identifier. PositiveInteger32 .1.3.6.1.4.1.818.2.1.9.1.1 |
geClientUPSNameThe administrative name of the UPS.rw DisplayString .1.3.6.1.4.1.818.2.1.9.1.2 |
geClientUPSCommunicationTypeThe method of communication.rw Integer32 { serial(0), snmp(1) } .1.3.6.1.4.1.818.2.1.9.1.3 |
geClientUPSCommunicationPortThe communication port.rw DisplayString .1.3.6.1.4.1.818.2.1.9.1.4 |
geClientUPSReadCommNameThe Read community string. Used when communication
method is SNMP.rw DisplayString .1.3.6.1.4.1.818.2.1.9.1.5 |
geClientUPSWriteCommNameThe Write community string. Used when communication
method is SNMP.rw DisplayString .1.3.6.1.4.1.818.2.1.9.1.6 |
geClientUPSCommRetriesNumber of retries in case an answer times out.
When the max. number of retries is reached a
lost communication alarm will be raised.rw NonNegativeInteger32 .1.3.6.1.4.1.818.2.1.9.1.7 |
geClientAlarmManagementAlarm Management enabled or disabled.rw Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.2.1.9.1.8 |
geClientPreDelayThe number of second an alarm needs to be active
before action is taken.ro NonNegativeInteger32 .1.3.6.1.4.1.818.2.1.9.1.9 |
geClientSystemShutdownSpecifies whether the client should shutdown the machine
when an alarm situation occurs.ro Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.2.1.9.1.10 |
geClientRuntimeThe user defined preferable runtime.ro NonNegativeInteger32 .1.3.6.1.4.1.818.2.1.9.1.11 |
geClientUPSShutdownDefines whether the UPS will be shut down after an
Operating System shutdown.ro Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.2.1.9.1.12 |
geClientMaxScriptExecutionTimeThe max. number of seconds the script file is allowed to run.ro NonNegativeInteger32 .1.3.6.1.4.1.818.2.1.9.1.13 |
geClientGraceperiodThe time between start of the Operating System shutdown
and the UPS shutdown.ro NonNegativeInteger32 .1.3.6.1.4.1.818.2.1.9.1.14 |
geClientNumTestsThe number of scheduled tests.
This entry indicates the number of rows in the table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.2.1.20 |
geClientTestTableA list of test table entries. The number of
entries is given by the value of geClientNumTests. SEQUENCE OF GeClientTestEntry .1.3.6.1.4.1.818.2.1.21 |
geClientTestEntryAn entry containing information applicable to a
particular Test. GeClientTestEntry .1.3.6.1.4.1.818.2.1.21.1 |
geClientTestLineIndexThe test line identifier. PositiveInteger32 .1.3.6.1.4.1.818.2.1.21.1.1 |
geClientTestIdThe test Id.rw Integer32 .1.3.6.1.4.1.818.2.1.21.1.2 |
geClientTestDayTimeThe time on which the test is due to be performed.rw Integer32 .1.3.6.1.4.1.818.2.1.21.1.3 |
geClientTestWeekDayThe day in the week on which the test will be performed.rw Integer32 .1.3.6.1.4.1.818.2.1.21.1.4 |
geClientTestMonthDayThe month day on which the test will be performed.rw Integer32 .1.3.6.1.4.1.818.2.1.21.1.5 |
geClientNumShutdownsThe number of scheduled Shutdowns.
This entry indicates the number of rows in the table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.2.1.30 |
geClientShutdownTableA list of Shutdown table entries. The number of
entries is given by the value of geClientNumShutdowns. SEQUENCE OF GeClientShutdownEntry .1.3.6.1.4.1.818.2.1.31 |
geClientShutdownEntryAn entry containing information applicable to a
particular Shutdown. GeClientShutdownEntry .1.3.6.1.4.1.818.2.1.31.1 |
geClientShutdownLineIndexThe Shutdown line identifier. PositiveInteger32 .1.3.6.1.4.1.818.2.1.31.1.1 |
geClientShutdownDelayThe delay before start of the Shutdown.rw Integer32 .1.3.6.1.4.1.818.2.1.31.1.2 |
geClientShutdownDurationThe duration of the Shutdown.rw Integer32 .1.3.6.1.4.1.818.2.1.31.1.3 |
geClientShutdownDayTimeThe time on which the Shutdown is due to be performed.rw Integer32 .1.3.6.1.4.1.818.2.1.31.1.4 |
geClientShutdownWeekDayThe day in the week on which the Shutdown will be performed.rw Integer32 .1.3.6.1.4.1.818.2.1.31.1.5 |
geClientShutdownMonthDayThe month day on which the Shutdown will be performed.rw Integer32 .1.3.6.1.4.1.818.2.1.31.1.6 |
geClientShutdownPreWarnTimeThe number of seconds before start of the shutdown a pre
warning will be raised.rw Integer32 .1.3.6.1.4.1.818.2.1.31.1.7 |
geAgent OBJECT IDENTIFIER .1.3.6.1.4.1.818.3 |
geAgentConfig OBJECT IDENTIFIER .1.3.6.1.4.1.818.3.1 |
geAgentUDPPortThe UDP port number used by agent.rw NonNegativeInteger32 .1.3.6.1.4.1.818.3.1.1 |
geAgentWebServerPortThe UDP port number used by the HTTP server.rw NonNegativeInteger32 .1.3.6.1.4.1.818.3.1.2 |
geAgentComPortThe COM port used by the agent.rw DisplayString .1.3.6.1.4.1.818.3.1.3 |
geAgentComTimeoutThe Timeout delay in seconds of the serial communication.rw NonNegativeInteger32 .1.3.6.1.4.1.818.3.1.4 |
geAgentComRetriesThe number of retries when serial communication fails.rw NonNegativeInteger32 .1.3.6.1.4.1.818.3.1.5 |
geAgentReadCommunityThe read community string of the agent.rw DisplayString .1.3.6.1.4.1.818.3.1.6 |
geAgentWriteCommunityThe write community string of the agent.rw DisplayString .1.3.6.1.4.1.818.3.1.7 |
geAgentResponsibleEmailAddressThe email address of the responsible person for this agent.rw DisplayString .1.3.6.1.4.1.818.3.1.8 |
geRFCTrapsToSendThis object defines whether RFC traps need to be send.
The bit value 1 indicates that the traps needs to be send, while
value 0 does not result in a trap to send.rw Integer32 { off(0), on(1) } .1.3.6.1.4.1.818.3.1.9 |
geIMVTrapsToSendThis object defines for which device(s) IMV traps need to be send.
The bit value 1 indicates that the trap needs to be send, while
value 0 does not result in a trap to send.
The value presents the devices as a mask:
1 GenericUPS
2 FirstUPS
4 SecondUPS
8 ThirdUPS
16 FourthUPS
32 FifthUPS
64 SixthUPS
128 SeventhUPS
256 EigthUPS
512 IOInterfacerw NonNegativeInteger32 .1.3.6.1.4.1.818.3.1.10 |
geAgentTraps OBJECT IDENTIFIER .1.3.6.1.4.1.818.3.2 |
geAgentNumTrapsThe number of configured traps.
This entry indicates the number of rows in the table.ro NonNegativeInteger32 .1.3.6.1.4.1.818.3.2.1 |
geAgentTrapTableA list of trap table entries. The number of
entries is given by the value of geAgentNumTraps. SEQUENCE OF GeAgentTrapEntry .1.3.6.1.4.1.818.3.2.2 |
geAgentTrapEntryAn entry containing information applicable to a
particular trap target. GeAgentTrapEntry .1.3.6.1.4.1.818.3.2.2.1 |
geAgentTrapLineIndexThe Trap line identifier. PositiveInteger32 .1.3.6.1.4.1.818.3.2.2.1.1 |
geAgentTrapAddressThe destination IP-address of the trap.rw DisplayString .1.3.6.1.4.1.818.3.2.2.1.2 |
geAgentTrapCommunityThe communication string used by the trap.rw DisplayString .1.3.6.1.4.1.818.3.2.2.1.3 |
geAgentTrapPortThe UDP port on the receiving side.rw Integer32 .1.3.6.1.4.1.818.3.2.2.1.4 |