AI MIB Summary

The ADH3-NETCOM-MIB module defines the management interface for Environmental Technology Inc. SNMP devices, enabling the monitoring of environmental telemetry and system status metrics such as temperature, humidity, voltage, and fan speeds.

The Structure of Management Information for Environmental Technology Inc. SNMP devices
Main OID:
environmentalTechnology.1.3.6.1.4.1.32185
16
Objects
Active
Status
2
Dependencies

Imported Objects

Objects

16 total
Object Name
environmentalTechnology
MODULE-IDENTITY
.1.3.6.1.4.1.32185
netcom
OBJECT IDENTIFIER
.1.3.6.1.4.1.32185.2
statusInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.32185.2.1
allStatusesro
DisplayString
.1.3.6.1.4.1.32185.2.1.1
pressurePSIro
DisplayString
.1.3.6.1.4.1.32185.2.1.2
dutycyclero
DisplayString
.1.3.6.1.4.1.32185.2.1.3
statusVarsro
DisplayString
.1.3.6.1.4.1.32185.2.1.4
temperaturero
DisplayString
.1.3.6.1.4.1.32185.2.1.5
alarmsro
DisplayString
.1.3.6.1.4.1.32185.2.1.6
compressorHoursro
DisplayString
.1.3.6.1.4.1.32185.2.1.7
majorStaterw
Enumeration
.1.3.6.1.4.1.32185.2.1.8
paramsInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.32185.2.2
lowerLimitro
DisplayString
.1.3.6.1.4.1.32185.2.2.1
upperLimitro
DisplayString
.1.3.6.1.4.1.32185.2.2.2
lowerAlarmLimitro
DisplayString
.1.3.6.1.4.1.32185.2.2.3
upperAlarmLimitro
DisplayString
.1.3.6.1.4.1.32185.2.2.4

ADH3-NETCOM-MIB Technical Reference Overview

The ADH3-NETCOM-MIB SNMP MIB module published by Environmental Technology defines 16 managed OID objects, including 12 scalar/column metrics, 0 SNMP tables, and 0 trap/notification events anchored at base OID .1.3.6.1.4.1.32185.

Key OID Definitions in ADH3-NETCOM-MIB

environmentalTechnologyMODULE-IDENTITYnot-accessible
.1.3.6.1.4.1.32185

The Structure of Management Information for Environmental Technology Inc. SNMP devices

alarmsDisplayStringread-only
.1.3.6.1.4.1.32185.2.1.6

Current alarm conditions: is a list of them Each character has a - for no alarm, or an A or W if there is an alarm. A means alarm (serious), W means a warning (not so serious).

allStatusesDisplayStringread-only
.1.3.6.1.4.1.32185.2.1.1

Summary: same as objects 2-7, separated by semicolons

compressorHoursDisplayStringread-only
.1.3.6.1.4.1.32185.2.1.7

Number of hours that the compressor has been running; resolution is tenths of an hour.

dutycycleDisplayStringread-only
.1.3.6.1.4.1.32185.2.1.3

Current duty cycle, in percent; --- if none available

lowerAlarmLimitDisplayStringread-only
.1.3.6.1.4.1.32185.2.2.3

The pressure, in PSI, below which the unit declares a low pressure alarm

lowerLimitDisplayStringread-only
.1.3.6.1.4.1.32185.2.2.1

The pressure, in PSI, at which the unit starts to pump

majorStateINTEGERread-write
.1.3.6.1.4.1.32185.2.1.8

Major state of the dehydrator. Online: currently pressurizing. Standby: not pressurizing. Leaky: shut down because of inability to pressurize.

pressurePSIDisplayStringread-only
.1.3.6.1.4.1.32185.2.1.2

Pressure, in PSI

statusVarsDisplayStringread-only
.1.3.6.1.4.1.32185.2.1.4

Summary of the status of the unit. Is always 6 characters Character 1 is major state: N=normal, S=standby, L=leaky Character 2 is environment: N=normal, C=cold, H=hot Character 3 is canister 1 condition: O=OK (ie dry), F=full (wet), U=unknown, D=dead Character 4 is canister 1 usage: I=idle, U=in use, R=regenerating Character 5 is canister 2 condition, as in character 3 Character 5 is canister 2 usage, as in character 4

temperatureDisplayStringread-only
.1.3.6.1.4.1.32185.2.1.5

Current temperature, in degrees F

upperAlarmLimitDisplayStringread-only
.1.3.6.1.4.1.32185.2.2.4

The pressure, in PSI, above which the unit declares a high pressure alarm

upperLimitDisplayStringread-only
.1.3.6.1.4.1.32185.2.2.2

The pressure, in PSI, which the unit pressurizes to

netcomOBJECTnot-accessible
.1.3.6.1.4.1.32185.2

ADH-3 NETCOM

More MIBs from Environmental Technology