ADH3-NETCOM-MIB
The ADH3-NETCOM-MIB module defines the management interface for Environmental Technology Inc. SNMP devices, enabling the monitoring of environmental telemetry and system status metrics such as temperature, humidity, voltage, and fan speeds.
Imported Objects
Objects
16 total| Object Name |
|---|
environmentalTechnology MODULE-IDENTITY .1.3.6.1.4.1.32185 |
netcom OBJECT IDENTIFIER .1.3.6.1.4.1.32185.2 |
statusInfo OBJECT IDENTIFIER .1.3.6.1.4.1.32185.2.1 |
allStatusesro DisplayString .1.3.6.1.4.1.32185.2.1.1 |
pressurePSIro DisplayString .1.3.6.1.4.1.32185.2.1.2 |
dutycyclero DisplayString .1.3.6.1.4.1.32185.2.1.3 |
statusVarsro DisplayString .1.3.6.1.4.1.32185.2.1.4 |
temperaturero DisplayString .1.3.6.1.4.1.32185.2.1.5 |
alarmsro DisplayString .1.3.6.1.4.1.32185.2.1.6 |
compressorHoursro DisplayString .1.3.6.1.4.1.32185.2.1.7 |
majorStaterw Enumeration .1.3.6.1.4.1.32185.2.1.8 |
paramsInfo OBJECT IDENTIFIER .1.3.6.1.4.1.32185.2.2 |
lowerLimitro DisplayString .1.3.6.1.4.1.32185.2.2.1 |
upperLimitro DisplayString .1.3.6.1.4.1.32185.2.2.2 |
lowerAlarmLimitro DisplayString .1.3.6.1.4.1.32185.2.2.3 |
upperAlarmLimitro DisplayString .1.3.6.1.4.1.32185.2.2.4 |
ADH3-NETCOM-MIB Technical Reference Overview
The ADH3-NETCOM-MIB SNMP MIB module published by Environmental Technology defines 16 managed OID objects, including 12 scalar/column metrics, 0 SNMP tables, and 0 trap/notification events anchored at base OID .1.3.6.1.4.1.32185.
Key OID Definitions in ADH3-NETCOM-MIB
.1.3.6.1.4.1.32185The Structure of Management Information for Environmental Technology Inc. SNMP devices
.1.3.6.1.4.1.32185.2.1.6Current alarm conditions: is a list of them Each character has a - for no alarm, or an A or W if there is an alarm. A means alarm (serious), W means a warning (not so serious).
.1.3.6.1.4.1.32185.2.1.1Summary: same as objects 2-7, separated by semicolons
.1.3.6.1.4.1.32185.2.1.7Number of hours that the compressor has been running; resolution is tenths of an hour.
.1.3.6.1.4.1.32185.2.1.3Current duty cycle, in percent; --- if none available
.1.3.6.1.4.1.32185.2.2.3The pressure, in PSI, below which the unit declares a low pressure alarm
.1.3.6.1.4.1.32185.2.2.1The pressure, in PSI, at which the unit starts to pump
.1.3.6.1.4.1.32185.2.1.8Major state of the dehydrator. Online: currently pressurizing. Standby: not pressurizing. Leaky: shut down because of inability to pressurize.
.1.3.6.1.4.1.32185.2.1.2Pressure, in PSI
.1.3.6.1.4.1.32185.2.1.4Summary of the status of the unit. Is always 6 characters Character 1 is major state: N=normal, S=standby, L=leaky Character 2 is environment: N=normal, C=cold, H=hot Character 3 is canister 1 condition: O=OK (ie dry), F=full (wet), U=unknown, D=dead Character 4 is canister 1 usage: I=idle, U=in use, R=regenerating Character 5 is canister 2 condition, as in character 3 Character 5 is canister 2 usage, as in character 4
.1.3.6.1.4.1.32185.2.1.5Current temperature, in degrees F
.1.3.6.1.4.1.32185.2.2.4The pressure, in PSI, above which the unit declares a high pressure alarm
.1.3.6.1.4.1.32185.2.2.2The pressure, in PSI, which the unit pressurizes to
.1.3.6.1.4.1.32185.2ADH-3 NETCOM