ADH-NETCOM-MIB
AI MIB Summary
The ADH-NETCOM-MIB defines the management interface for Environmental Technology Inc. SNMP agents, enabling the monitoring of device-specific environmental parameters and operational status metrics. This module facilitates the collection of telemetry data required for infrastructure health assessment and fault detection on supported hardware platforms.
The Structure of Management Information for Environmental Technology Inc. SNMP devices
Main OID:
environmentalTechnology.1.3.6.1.4.1.32185
17
Objects
Active
Status
2
Dependencies
Imported Objects
Objects
17 total| Object Name |
|---|
environmentalTechnologyThe Structure of Management Information for Environmental Technology Inc. SNMP devices MODULE-IDENTITY .1.3.6.1.4.1.32185 |
netcomADH NETCOM OBJECT IDENTIFIER .1.3.6.1.4.1.32185.2 |
statusInfo OBJECT IDENTIFIER .1.3.6.1.4.1.32185.2.1 |
allStatusesSummary: same as objects 2-7, separated by semicolonsro DisplayString .1.3.6.1.4.1.32185.2.1.1 |
pressurePSIPressure, in PSI or mbarro DisplayString .1.3.6.1.4.1.32185.2.1.2 |
dutycycleCurrent duty cycle, in percent; --- if none availablero DisplayString .1.3.6.1.4.1.32185.2.1.3 |
statusVarsSummary of the status of the unit. Is always 7 characters Character 1 is super-state: govering whole system, if this unit is a master S=slave (not a master) M=master; N=master but system off line D=director; D=director but system off line master: for redundant systems director: for increasing pumping capability Character 2 is major state: N=normal, S=standby, L=leaky Character 3 is environment: N=normal, C=cold, H=hot Character 4 is canister 1 condition: O=OK (ie dry), F=full (wet), U=unknown, D=dead Character 5 is canister 1 usage: I=idle, U=in use, R=regenerating Character 6 is canister 2 condition, as in character 4 Character 7 is canister 2 usage, as in character 5ro DisplayString .1.3.6.1.4.1.32185.2.1.4 |
temperatureCurrent temperature, in degrees F or Cro DisplayString .1.3.6.1.4.1.32185.2.1.5 |
alarmsCurrent alarm conditions: is a list of them Each character has a - for no alarm, or an A or W if there is an alarm. A means alarm (serious), W means a warning (not so serious). Severity levels may later change. List of alarms: (later versions may add more): A1: Low pressure A2: High pressure W3: High duty cycle W4: High temperature W5: Low temperature W6: Unused A7: Canister 1 won't heat A8: Canister 1 won't cool A9: Canister 2 won't heat A10: Canister 2 won't cool A11: Unable to pressurize A12: Dew point alarm W13: Compressor timeout (for future use) W14: Communications error A15: Canister 1 thermistor bad A16: Canister 2 thermistor bad A17: Ambient thermistor bad A18: Overpressure A19: Bad calibrations in EEPROM A20: Bad limits in EEPROM A21: Short cycling A22: Pump shut down due to error conditionro DisplayString .1.3.6.1.4.1.32185.2.1.6 |
compressorHoursNumber of hours that the compressor has been running; resolution is tenths of an hour.ro DisplayString .1.3.6.1.4.1.32185.2.1.7 |
majorStateMajor state of the dehydrator. Online: currently pressurizing. Standby: not pressurizing. Leaky: shut down because of inability to pressurize.rw Enumeration .1.3.6.1.4.1.32185.2.1.8 |
cycleTimeTime of last duty cycle in seconds; 0.0 means none availablero DisplayString .1.3.6.1.4.1.32185.2.1.9 |
paramsInfo OBJECT IDENTIFIER .1.3.6.1.4.1.32185.2.2 |
lowerLimitThe pressure, in PSI or mbar, at which the unit starts to pumpro DisplayString .1.3.6.1.4.1.32185.2.2.1 |
upperLimitThe pressure, in PSI or mbar, which the unit pressurizes toro DisplayString .1.3.6.1.4.1.32185.2.2.2 |
lowerAlarmLimitThe pressure, in PSI or mbar, below which the unit declares a low pressure alarmro DisplayString .1.3.6.1.4.1.32185.2.2.3 |
upperAlarmLimitThe pressure, in PSI or mbar, above which the unit declares a high pressure alarmro DisplayString .1.3.6.1.4.1.32185.2.2.4 |