UPSMAN
AI MIB Summary
Standard SNMP MIB module defining data structures for UPSMAN.
55
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
55 total| Object Name |
|---|
upsman OBJECT IDENTIFIER .1.3.6.1.4.1.1356 |
RFC1213-MIB Unknown .1.3.6.1.4.1.1356 |
communicationLostSEVERE: Communication to the UPS has been lost. Check cable or network
connections, steps to reestablish communication are in progress. TRAP-TYPE .1.3.6.1.4.1.1356.0.1 |
upsOverloadSEVERE: The UPS has sensed a load greater than 100 percent
of its rated capcity. TRAP-TYPE .1.3.6.1.4.1.1356.0.2 |
upsTurnedOffWARNING: The UPS has been turned 'off' by the management station. TRAP-TYPE .1.3.6.1.4.1.1356.0.3 |
communicationEstablishedINFORMATION: Communication with the UPS has been established. TRAP-TYPE .1.3.6.1.4.1.1356.0.4 |
powerRestoredINFORMATION: Utility power has been restored. TRAP-TYPE .1.3.6.1.4.1.1356.0.5 |
upsOnBatteryWARNING: The UPS has switched to battery backup power. TRAP-TYPE .1.3.6.1.4.1.1356.0.6 |
testStartedINFORMATION: A UPS test was started. TRAP-TYPE .1.3.6.1.4.1.1356.0.7 |
testCompletedINFORMATION: A UPS test is completed. Now a test result should be
available in upsTest.lastTestResult. TRAP-TYPE .1.3.6.1.4.1.1356.0.8 |
upsBatteryLowWARNING: Battery Low. TRAP-TYPE .1.3.6.1.4.1.1356.0.9 |
upsShutdownImminentINFORMATION: Server Shutdown imminent. TRAP-TYPE .1.3.6.1.4.1.1356.0.10 |
upsmanStartedINFORMATION: The UpsMan service has been started. TRAP-TYPE .1.3.6.1.4.1.1356.0.11 |
upsmanTrapInputBadAn abnormal condition of input UPS has been detected. TRAP-TYPE .1.3.6.1.4.1.1356.0.12 |
upsmanTrapOutputOverloadRemovedThe UPS has returned from an overload situation to normal operation. TRAP-TYPE .1.3.6.1.4.1.1356.0.13 |
upsmanTrapBatteryBadAn abnormal condition of the UPS batteries has been detected. TRAP-TYPE .1.3.6.1.4.1.1356.0.14 |
upsmanTrapTempBadAn abnormal UPS temperature has been detected. TRAP-TYPE .1.3.6.1.4.1.1356.0.15 |
upsmanTrapTempBadRemovedThe abnormal UPS temperature is back to normal level. TRAP-TYPE .1.3.6.1.4.1.1356.0.16 |
upsmanTrapFatalFaultA fatal fault in the UPS has been detected. The UPS can not backup, contact your UPS
service team. TRAP-TYPE .1.3.6.1.4.1.1356.0.17 |
ups OBJECT IDENTIFIER .1.3.6.1.4.1.1356.1 |
upsIdent OBJECT IDENTIFIER .1.3.6.1.4.1.1356.1.1 |
upsIdentModelNameThe UPS model name (e.g. 'O1000S').ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.1356.1.1.1 |
upsIdentUpsIDNameAn ID string identifying the UPS. This object
can be set by the administrator.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.1356.1.1.2 |
upsBattery OBJECT IDENTIFIER .1.3.6.1.4.1.1356.1.2 |
upsBatteryStatusThe status of the UPS batteries. A batteryLow(3)
value indicates the UPS will be unable to sustain the
current load, and its services will be lost if power is
not restored.ro Enumeration .1.3.6.1.4.1.1356.1.2.1 |
upsBatteryCapacityThe remaining battery capacity expressed in
percent of full capacity.ro INTEGER .1.3.6.1.4.1.1356.1.2.2 |
upsBatteryVoltageThe current battery voltage expressed in VDC.ro INTEGER .1.3.6.1.4.1.1356.1.2.3 |
upsBatteryTemperatureThe current internal UPS temperature expressed in
Celsius.ro INTEGER .1.3.6.1.4.1.1356.1.2.4 |
upsBatteryRunTimeRemainingThe UPS battery run time remaining before battery
exhaustion, in seconds.ro INTEGER .1.3.6.1.4.1.1356.1.2.5 |
upsBatteryLifeTimeRemainingForecast of the battery lifetime, replacement recommended in x month. Format: monthro INTEGER .1.3.6.1.4.1.1356.1.2.6 |
upsInput OBJECT IDENTIFIER .1.3.6.1.4.1.1356.1.3 |
upsInputLineVoltageThe current utility line voltage in VAC.ro INTEGER .1.3.6.1.4.1.1356.1.3.1 |
upsInputLineFrequenceThe current utility line frequence in Hz.ro INTEGER .1.3.6.1.4.1.1356.1.3.2 |
upsOutput OBJECT IDENTIFIER .1.3.6.1.4.1.1356.1.4 |
upsOutputStatusThe current state of the UPS. If the UPS is unable
to determine the state of the UPS this variable is set
to unknown(1).ro Enumeration .1.3.6.1.4.1.1356.1.4.1 |
upsOutputLoadThe current UPS load expressed in percent
of rated capacity.ro INTEGER .1.3.6.1.4.1.1356.1.4.2 |
upsOutputFrequencyThe present output frequency, format: 0.1 Hertz.ro INTEGER .1.3.6.1.4.1.1356.1.4.3 |
upsOutputVoltageThe present output voltage, format: RMS Volts.ro INTEGER .1.3.6.1.4.1.1356.1.4.4 |
upsTest OBJECT IDENTIFIER .1.3.6.1.4.1.1356.1.5 |
upsRunTestSet this value to run a test. If this this variable is set
to NoTest(0) no test will be initiated.rw Enumeration .1.3.6.1.4.1.1356.1.5.1 |
upsLastTestPerformedThis value shows which last test was performed. If this value is
set to noTest(0) no test has been run since startup.ro Enumeration .1.3.6.1.4.1.1356.1.5.2 |
upsLastTestResultThe current UPS Test Result. If this value is undefined(0) no
test has been run since startup.ro Enumeration .1.3.6.1.4.1.1356.1.5.3 |
upsLastTestedBackupTimeThis value shows the last tested backup time in minutes.
To acquire a new value perform one of battery test's.ro INTEGER .1.3.6.1.4.1.1356.1.5.4 |
upsControl OBJECT IDENTIFIER .1.3.6.1.4.1.1356.1.6 |
upsRunShutdownRestoreSet this value to run a shutdown procedure. If this this variable is set
to (0) nothing happens.rw Enumeration .1.3.6.1.4.1.1356.1.6.1 |
upsShutdownSecsThis value indicates the time in seconds after which a ups
shutdown will be performed. If this value is (0) shutdown
executes immediately.rw INTEGER .1.3.6.1.4.1.1356.1.6.2 |
upsRestoreSecsThis value indicates the time in seconds after which a ups
restore will be performed. If this value is (0) restore
executes immediately.rw INTEGER .1.3.6.1.4.1.1356.1.6.3 |
upsAlarms OBJECT IDENTIFIER .1.3.6.1.4.1.1356.1.7 |
upsAlarmFatalFaultStatusCRITICAL ALARM : A fatal fault in the UPS has been detected. Detailed information by referring to UpsAlarmFatalFaultDetail
Possible causes: Fatal Fault none (-1), Abnormal output (1), main circuit failure (2), fuse blown (3), fan fault (4), abnormal control (5),
abnormal battery (6), others (7).ro Enumeration .1.3.6.1.4.1.1356.1.7.1 |
upsAlarmWarningStatusWARNING : The UPS has detect a minor fault, warning level. Detailed information by referring to UpsAlarmWarningDetail.ro Enumeration .1.3.6.1.4.1.1356.1.7.2 |
upsAlarmInputBadStatusAn abnormal condition of the input in the UPS has been detected. Detailed information by referring to UpsAlarmInputBadDetail.ro Enumeration .1.3.6.1.4.1.1356.1.7.3 |
upsAlarmOutputOverloadStatusAn abnormal output overload in the UPS has been detected.ro Enumeration .1.3.6.1.4.1.1356.1.7.4 |
upsAlarmBatteryBadStatusAn abnormal condition of the battery in the UPS has been detected. Detailed information by referring to UpsAlarmBatteryBadDetail.ro Enumeration .1.3.6.1.4.1.1356.1.7.5 |
upsAlarmTempBadStatusAn abnormal condition of the temperature in the UPS has been detected. Detailed information by referring to UpsAlarmTempBadDetail.ro Enumeration .1.3.6.1.4.1.1356.1.7.6 |
mgmt OBJECT IDENTIFIER .1.3.6.1.4.1.1356.2 |