UPSMAN

AI MIB Summary

Standard SNMP MIB module defining data structures for UPSMAN.

55
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

55 total
Object Name
upsman
OBJECT IDENTIFIER
.1.3.6.1.4.1.1356
RFC1213-MIB
Unknown
.1.3.6.1.4.1.1356
communicationLostSEVERE: Communication to the UPS has been lost. Check cable or network connections, steps to reestablish communication are in progress.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.1
upsOverloadSEVERE: The UPS has sensed a load greater than 100 percent of its rated capcity.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.2
upsTurnedOffWARNING: The UPS has been turned 'off' by the management station.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.3
communicationEstablishedINFORMATION: Communication with the UPS has been established.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.4
powerRestoredINFORMATION: Utility power has been restored.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.5
upsOnBatteryWARNING: The UPS has switched to battery backup power.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.6
testStartedINFORMATION: A UPS test was started.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.7
testCompletedINFORMATION: A UPS test is completed. Now a test result should be available in upsTest.lastTestResult.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.8
upsBatteryLowWARNING: Battery Low.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.9
upsShutdownImminentINFORMATION: Server Shutdown imminent.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.10
upsmanStartedINFORMATION: The UpsMan service has been started.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.11
upsmanTrapInputBadAn abnormal condition of input UPS has been detected.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.12
upsmanTrapOutputOverloadRemovedThe UPS has returned from an overload situation to normal operation.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.13
upsmanTrapBatteryBadAn abnormal condition of the UPS batteries has been detected.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.14
upsmanTrapTempBadAn abnormal UPS temperature has been detected.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.15
upsmanTrapTempBadRemovedThe abnormal UPS temperature is back to normal level.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.16
upsmanTrapFatalFaultA fatal fault in the UPS has been detected. The UPS can not backup, contact your UPS service team.
TRAP-TYPE
.1.3.6.1.4.1.1356.0.17
ups
OBJECT IDENTIFIER
.1.3.6.1.4.1.1356.1
upsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.1356.1.1
upsIdentModelNameThe UPS model name (e.g. 'O1000S').ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.1356.1.1.1
upsIdentUpsIDNameAn ID string identifying the UPS. This object can be set by the administrator.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.1356.1.1.2
upsBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.1356.1.2
upsBatteryStatusThe status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored.ro
Enumeration
.1.3.6.1.4.1.1356.1.2.1
upsBatteryCapacityThe remaining battery capacity expressed in percent of full capacity.ro
INTEGER
.1.3.6.1.4.1.1356.1.2.2
upsBatteryVoltageThe current battery voltage expressed in VDC.ro
INTEGER
.1.3.6.1.4.1.1356.1.2.3
upsBatteryTemperatureThe current internal UPS temperature expressed in Celsius.ro
INTEGER
.1.3.6.1.4.1.1356.1.2.4
upsBatteryRunTimeRemainingThe UPS battery run time remaining before battery exhaustion, in seconds.ro
INTEGER
.1.3.6.1.4.1.1356.1.2.5
upsBatteryLifeTimeRemainingForecast of the battery lifetime, replacement recommended in x month. Format: monthro
INTEGER
.1.3.6.1.4.1.1356.1.2.6
upsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.1356.1.3
upsInputLineVoltageThe current utility line voltage in VAC.ro
INTEGER
.1.3.6.1.4.1.1356.1.3.1
upsInputLineFrequenceThe current utility line frequence in Hz.ro
INTEGER
.1.3.6.1.4.1.1356.1.3.2
upsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.1356.1.4
upsOutputStatusThe current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1).ro
Enumeration
.1.3.6.1.4.1.1356.1.4.1
upsOutputLoadThe current UPS load expressed in percent of rated capacity.ro
INTEGER
.1.3.6.1.4.1.1356.1.4.2
upsOutputFrequencyThe present output frequency, format: 0.1 Hertz.ro
INTEGER
.1.3.6.1.4.1.1356.1.4.3
upsOutputVoltageThe present output voltage, format: RMS Volts.ro
INTEGER
.1.3.6.1.4.1.1356.1.4.4
upsTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.1356.1.5
upsRunTestSet this value to run a test. If this this variable is set to NoTest(0) no test will be initiated.rw
Enumeration
.1.3.6.1.4.1.1356.1.5.1
upsLastTestPerformedThis value shows which last test was performed. If this value is set to noTest(0) no test has been run since startup.ro
Enumeration
.1.3.6.1.4.1.1356.1.5.2
upsLastTestResultThe current UPS Test Result. If this value is undefined(0) no test has been run since startup.ro
Enumeration
.1.3.6.1.4.1.1356.1.5.3
upsLastTestedBackupTimeThis value shows the last tested backup time in minutes. To acquire a new value perform one of battery test's.ro
INTEGER
.1.3.6.1.4.1.1356.1.5.4
upsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.1356.1.6
upsRunShutdownRestoreSet this value to run a shutdown procedure. If this this variable is set to (0) nothing happens.rw
Enumeration
.1.3.6.1.4.1.1356.1.6.1
upsShutdownSecsThis value indicates the time in seconds after which a ups shutdown will be performed. If this value is (0) shutdown executes immediately.rw
INTEGER
.1.3.6.1.4.1.1356.1.6.2
upsRestoreSecsThis value indicates the time in seconds after which a ups restore will be performed. If this value is (0) restore executes immediately.rw
INTEGER
.1.3.6.1.4.1.1356.1.6.3
upsAlarms
OBJECT IDENTIFIER
.1.3.6.1.4.1.1356.1.7
upsAlarmFatalFaultStatusCRITICAL ALARM : A fatal fault in the UPS has been detected. Detailed information by referring to UpsAlarmFatalFaultDetail Possible causes: Fatal Fault none (-1), Abnormal output (1), main circuit failure (2), fuse blown (3), fan fault (4), abnormal control (5), abnormal battery (6), others (7).ro
Enumeration
.1.3.6.1.4.1.1356.1.7.1
upsAlarmWarningStatusWARNING : The UPS has detect a minor fault, warning level. Detailed information by referring to UpsAlarmWarningDetail.ro
Enumeration
.1.3.6.1.4.1.1356.1.7.2
upsAlarmInputBadStatusAn abnormal condition of the input in the UPS has been detected. Detailed information by referring to UpsAlarmInputBadDetail.ro
Enumeration
.1.3.6.1.4.1.1356.1.7.3
upsAlarmOutputOverloadStatusAn abnormal output overload in the UPS has been detected.ro
Enumeration
.1.3.6.1.4.1.1356.1.7.4
upsAlarmBatteryBadStatusAn abnormal condition of the battery in the UPS has been detected. Detailed information by referring to UpsAlarmBatteryBadDetail.ro
Enumeration
.1.3.6.1.4.1.1356.1.7.5
upsAlarmTempBadStatusAn abnormal condition of the temperature in the UPS has been detected. Detailed information by referring to UpsAlarmTempBadDetail.ro
Enumeration
.1.3.6.1.4.1.1356.1.7.6
mgmt
OBJECT IDENTIFIER
.1.3.6.1.4.1.1356.2