Home/Catalog/Sentry4-MIB

Sentry4-MIB

AI MIB Summary

The Sentry4-MIB enables SNMP-based monitoring and management of APC Smart and Switched CDU/PDU hardware (PRO1 and PRO2 series), providing granular access to electrical parameters such as voltage, current, power consumption, and outlet-level control states.

This is the MIB module for the fourth generation of the Sentry product family. This includes the PRO1 and PRO2 series of Smart and Switched Cabinet Distribution Unit (CDU) and Power Distribution Unit (PDU) products.
Main OID:
sentry4.1.3.6.1.4.1.1718.4
391
Objects
Active
Status
3
Dependencies

Imported Objects

Objects

391 total
Object Name
serverTech
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718
sentry4This is the MIB module for the fourth generation of the Sentry product family. This includes the PRO1 and PRO2 series of Smart and Switched Cabinet Distribution Unit (CDU) and Power Distribution Unit (PDU) products.
MODULE-IDENTITY
.1.3.6.1.4.1.1718.4
st4Objects
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1
st4System
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.1
st4SystemConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.1.1
st4SystemProductNameThe product name.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.1.1.1
st4SystemLocationThe location of the system.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.1.1.2
st4SystemFirmwareVersionThe firmware version.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.1.1.3
st4SystemFirmwareBuildInfoThe firmware build information.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.1.1.4
st4SystemNICSerialNumberThe serial number of the network interface card.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.1.1.5
st4SystemNICHardwareInfoHardware information about the network interface card.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.1.1.6
st4SystemProductSeriesThe product series.ro
Enumeration
.1.3.6.1.4.1.1718.4.1.1.1.7
st4SystemFeaturesThe key-activated features enabled in the system.ro
Bits
.1.3.6.1.4.1.1718.4.1.1.1.10
st4SystemFeatureKeyA valid feature key written to this object will enable a feature in the system. A valid feature key is in the form xxxx-xxxx-xxxx-xxxx. A read of this object returns an empty string.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.1.1.11
st4SystemConfigModifiedCountThe total number of times the system configuration has changed.ro
Integer32
.1.3.6.1.4.1.1718.4.1.1.1.20
st4SystemUnitCountThe number of units in the system.ro
Integer32
.1.3.6.1.4.1.1718.4.1.1.1.21
st4Units
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.2
st4UnitCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.2.1
st4UnitConfigTableUnit configuration table.
SEQUENCE OF St4UnitConfigEntry
.1.3.6.1.4.1.1718.4.1.2.2
st4UnitConfigEntryConfiguration objects for a particular unit.
St4UnitConfigEntry
.1.3.6.1.4.1.1718.4.1.2.2.1
st4UnitIndexUnit index. A=1, B=2, C=3, D=4, E=5, F=6.
Integer32
.1.3.6.1.4.1.1718.4.1.2.2.1.1
st4UnitIDThe internal ID of the unit. Format=A.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.2.2.1.2
st4UnitNameThe name of the unit.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.2.2.1.3
st4UnitProductSNThe product serial number of the unit.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.2.2.1.4
st4UnitModelThe model of the unit.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.2.2.1.5
st4UnitAssetTagThe asset tag of the unit.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.2.2.1.6
st4UnitTypeThe type of the unit.ro
Enumeration
.1.3.6.1.4.1.1718.4.1.2.2.1.7
st4UnitCapabilitiesThe capabilities of the unit.ro
Bits
.1.3.6.1.4.1.1718.4.1.2.2.1.8
st4UnitProductMfrDateThe product manufacture date in YYYY-MM-DD (ISO 8601 format).ro
DisplayString
.1.3.6.1.4.1.1718.4.1.2.2.1.9
st4UnitDisplayOrientationThe orientation of all displays in the unit.rw
Enumeration
.1.3.6.1.4.1.1718.4.1.2.2.1.20
st4UnitOutletSequenceOrderThe sequencing order of all outlets in the unit.rw
Enumeration
.1.3.6.1.4.1.1718.4.1.2.2.1.21
st4UnitInputCordCountThe number of power input cords into the unit.ro
Integer32
.1.3.6.1.4.1.1718.4.1.2.2.1.30
st4UnitTempSensorCountThe number of external temperature sensors supported by the unit.ro
Integer32
.1.3.6.1.4.1.1718.4.1.2.2.1.31
st4UnitHumidSensorCountThe number of external humidity sensors supported by the unit.ro
Integer32
.1.3.6.1.4.1.1718.4.1.2.2.1.32
st4UnitWaterSensorCountThe number of external water sensors supported by the unit.ro
Integer32
.1.3.6.1.4.1.1718.4.1.2.2.1.33
st4UnitCcSensorCountThe number of external contact closure sensors supported by the unit.ro
Integer32
.1.3.6.1.4.1.1718.4.1.2.2.1.34
st4UnitAdcSensorCountThe number of analog-to-digital converter sensors supported by the unit.ro
Integer32
.1.3.6.1.4.1.1718.4.1.2.2.1.35
st4UnitMonitorTableUnit monitor table.
SEQUENCE OF St4UnitMonitorEntry
.1.3.6.1.4.1.1718.4.1.2.3
st4UnitMonitorEntryObjects to monitor for a particular unit.
St4UnitMonitorEntry
.1.3.6.1.4.1.1718.4.1.2.3.1
st4UnitStatusThe status of the unit.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.2.3.1.1
st4UnitEventConfigTableUnit event configuration table.
SEQUENCE OF St4UnitEventConfigEntry
.1.3.6.1.4.1.1718.4.1.2.4
st4UnitEventConfigEntryEvent configuration objects for a particular unit.
St4UnitEventConfigEntry
.1.3.6.1.4.1.1718.4.1.2.4.1
st4UnitNotificationsThe notification methods enabled for unit events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.2.4.1.1
st4InputCords
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.3
st4InputCordCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.3.1
st4InputCordActivePowerHysteresisThe active power hysteresis of the input cord in Watts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.1.1
st4InputCordApparentPowerHysteresisThe apparent power hysteresis of the input cord in Volt-Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.1.2
st4InputCordPowerFactorHysteresisThe power factor hysteresis of the input cord in hundredths.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.1.3
st4InputCordOutOfBalanceHysteresisThe 3 phase out-of-balance hysteresis of the input cord in percent.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.1.4
st4InputCordConfigTableInput cord configuration table.
SEQUENCE OF St4InputCordConfigEntry
.1.3.6.1.4.1.1718.4.1.3.2
st4InputCordConfigEntryConfiguration objects for a particular input cord.
St4InputCordConfigEntry
.1.3.6.1.4.1.1718.4.1.3.2.1
st4InputCordIndexInput cord index. A=1, B=2, C=3, D=4.
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.1
st4InputCordIDThe internal ID of the input cord. Format=AA.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.3.2.1.2
st4InputCordNameThe name of the input cord.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.3.2.1.3
st4InputCordInletTypeThe type of plug on the input cord, or socket for the input cord.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.3.2.1.6
st4InputCordNominalVoltageThe user-configured nominal voltage of the input cord in tenth Volts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.7
st4InputCordNominalVoltageMinThe factory-set minimum allowed for the user-configured nominal voltage of the input cord in Volts.ro
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.8
st4InputCordNominalVoltageMaxThe factory-set maximum allowed for the user-configured nominal voltage of the input cord in Volts.ro
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.9
st4InputCordCurrentCapacityThe user-configured current capacity of the input cord in Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.10
st4InputCordCurrentCapacityMaxThe factory-set maximum allowed for the user-configured current capacity of the input cord in Amps.ro
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.11
st4InputCordPowerCapacityThe power capacity of the input cord in Volt-Amps. For DC products, this is identical to power capacity in Watts.ro
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.12
st4InputCordNominalPowerFactorThe user-configured estimated nominal power factor of the input cord in hundredths.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.13
st4InputCordLineCountThe number of current-carrying lines in the input cord.ro
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.20
st4InputCordPhaseCountThe number of active phases from the lines in the input cord.ro
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.21
st4InputCordOcpCountThe number of over-current protectors downstream from the input cord.ro
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.22
st4InputCordBranchCountThe number of branches downstream from the input cord.ro
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.23
st4InputCordOutletCountThe number of outlets powered from the input cord.ro
Integer32
.1.3.6.1.4.1.1718.4.1.3.2.1.24
st4InputCordMonitorTableInput cord monitor table.
SEQUENCE OF St4InputCordMonitorEntry
.1.3.6.1.4.1.1718.4.1.3.3
st4InputCordMonitorEntryObjects to monitor for a particular input cord.
St4InputCordMonitorEntry
.1.3.6.1.4.1.1718.4.1.3.3.1
st4InputCordStateThe on/off state of the input cord.ro
DeviceState
.1.3.6.1.4.1.1718.4.1.3.3.1.1
st4InputCordStatusThe status of the input cord.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.3.3.1.2
st4InputCordActivePowerThe measured active power of the input cord in Watts.ro
Integer32(-1..50000) UNITS "Watts"
.1.3.6.1.4.1.1718.4.1.3.3.1.3
st4InputCordActivePowerStatusThe status of the measured active power of the input cord.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.3.3.1.4
st4InputCordApparentPowerThe measured apparent power of the input cord in Volt-Amps.ro
Integer32(-1..50000) UNITS "Volt-Amps"
.1.3.6.1.4.1.1718.4.1.3.3.1.5
st4InputCordApparentPowerStatusThe status of the measured apparent power of the input cord.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.3.3.1.6
st4InputCordPowerUtilizedThe amount of the input cord power capacity used in tenth percent. For AC products, this is the ratio of the apparent power to the power capacity. For DC products, this is the ratio of the active power to the power capacity.ro
Integer32(-1..1200) UNITS "tenth percent"
.1.3.6.1.4.1.1718.4.1.3.3.1.7
st4InputCordPowerFactorThe measured power factor of the input cord in hundredths.ro
Integer32(-1..100) UNITS "hundredths"
.1.3.6.1.4.1.1718.4.1.3.3.1.8
st4InputCordPowerFactorStatusThe status of the measured power factor of the input cord.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.3.3.1.9
st4InputCordEnergyThe total energy consumption of loads through the input cord in tenth Kilowatt-Hours.ro
Integer32(-1..2147483647) UNITS "tenth Kilowatt-Hours"
.1.3.6.1.4.1.1718.4.1.3.3.1.10
st4InputCordFrequencyThe frequency of the input cord voltage in tenth Hertz.ro
Integer32(-1..1000) UNITS "tenth Hertz"
.1.3.6.1.4.1.1718.4.1.3.3.1.11
st4InputCordOutOfBalanceThe current imbalance on the lines of the input cord in tenth percent.ro
Integer32(-1..2000) UNITS "tenth percent"
.1.3.6.1.4.1.1718.4.1.3.3.1.12
st4InputCordOutOfBalanceStatusThe status of the current imbalance on the lines of the input cord.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.3.3.1.13
st4InputCordEventConfigTableInput cord event configuration table.
SEQUENCE OF St4InputCordEventConfigEntry
.1.3.6.1.4.1.1718.4.1.3.4
st4InputCordEventConfigEntryEvent configuration objects for a particular input cord.
St4InputCordEventConfigEntry
.1.3.6.1.4.1.1718.4.1.3.4.1
st4InputCordNotificationsThe notification methods enabled for input cord events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.3.4.1.1
st4InputCordActivePowerLowAlarmThe active power low alarm threshold of the input cord in Watts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.2
st4InputCordActivePowerLowWarningThe active power low warning threshold of the input cord in Watts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.3
st4InputCordActivePowerHighWarningThe active power high warning threshold of the input cord in Watts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.4
st4InputCordActivePowerHighAlarmThe active power high alarm threshold of the input cord in Watts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.5
st4InputCordApparentPowerLowAlarmThe apparent power low alarm threshold of the input cord in Volt-Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.6
st4InputCordApparentPowerLowWarningThe apparent power low warning threshold of the input cord in Volt-Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.7
st4InputCordApparentPowerHighWarningThe apparent power high warning threshold of the input cord in Volt-Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.8
st4InputCordApparentPowerHighAlarmThe apparent power high alarm threshold of the input cord in Volt-Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.9
st4InputCordPowerFactorLowAlarmThe power factor low alarm threshold of the input cord in hundredths.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.10
st4InputCordPowerFactorLowWarningThe power factor low warning threshold of the input cord in hundredths.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.11
st4InputCordOutOfBalanceHighWarningThe 3 phase out-of-balance high warning threshold of the input cord in percent.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.12
st4InputCordOutOfBalanceHighAlarmThe 3 phase out-of-balance high alarm threshold of the input cord in percent.rw
Integer32
.1.3.6.1.4.1.1718.4.1.3.4.1.13
st4Lines
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.4
st4LineCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.4.1
st4LineCurrentHysteresisThe current hysteresis of the line in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.4.1.1
st4LineConfigTableLine configuration table.
SEQUENCE OF St4LineConfigEntry
.1.3.6.1.4.1.1718.4.1.4.2
st4LineConfigEntryConfiguration objects for a particular line.
St4LineConfigEntry
.1.3.6.1.4.1.1718.4.1.4.2.1
st4LineIndexLine index. L1=1, L2=2, L3=3, N=4.
Integer32
.1.3.6.1.4.1.1718.4.1.4.2.1.1
st4LineIDThe internal ID of the line. Format=AAN.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.4.2.1.2
st4LineLabelThe system label assigned to the line for identification.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.4.2.1.4
st4LineCurrentCapacityThe current capacity of the line in Amps.ro
Integer32
.1.3.6.1.4.1.1718.4.1.4.2.1.6
st4LineMonitorTableLine monitor table.
SEQUENCE OF St4LineMonitorEntry
.1.3.6.1.4.1.1718.4.1.4.3
st4LineMonitorEntryObjects to monitor for a particular line.
St4LineMonitorEntry
.1.3.6.1.4.1.1718.4.1.4.3.1
st4LineStateThe on/off state of the line.ro
DeviceState
.1.3.6.1.4.1.1718.4.1.4.3.1.1
st4LineStatusThe status of the line.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.4.3.1.2
st4LineCurrentThe measured current on the line in hundredth Amps.ro
Integer32(-1..60000) UNITS "hundredth Amps"
.1.3.6.1.4.1.1718.4.1.4.3.1.3
st4LineCurrentStatusThe status of the measured current on the line.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.4.3.1.4
st4LineCurrentUtilizedThe amount of the line current capacity used in tenth percent.ro
Integer32(-1..1200) UNITS "tenth percent"
.1.3.6.1.4.1.1718.4.1.4.3.1.5
st4LineEventConfigTableLine event configuration table.
SEQUENCE OF St4LineEventConfigEntry
.1.3.6.1.4.1.1718.4.1.4.4
st4LineEventConfigEntryEvent configuration objects for a particular line.
St4LineEventConfigEntry
.1.3.6.1.4.1.1718.4.1.4.4.1
st4LineNotificationsThe notification methods enabled for line events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.4.4.1.1
st4LineCurrentLowAlarmThe current low alarm threshold of the line in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.4.4.1.2
st4LineCurrentLowWarningThe current low warning threshold of the line in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.4.4.1.3
st4LineCurrentHighWarningThe current high warning threshold of the line in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.4.4.1.4
st4LineCurrentHighAlarmThe current high alarm threshold of the line in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.4.4.1.5
st4Phases
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.5
st4PhaseCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.5.1
st4PhaseVoltageHysteresisThe voltage hysteresis of the phase in tenth Volts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.5.1.1
st4PhasePowerFactorHysteresisThe power factor hysteresis of the phase in hundredths.rw
Integer32
.1.3.6.1.4.1.1718.4.1.5.1.2
st4PhaseConfigTablePhase configuration table.
SEQUENCE OF St4PhaseConfigEntry
.1.3.6.1.4.1.1718.4.1.5.2
st4PhaseConfigEntryConfiguration objects for a particular phase.
St4PhaseConfigEntry
.1.3.6.1.4.1.1718.4.1.5.2.1
st4PhaseIndexPhase index. Three-phase AC Wye: L1-N=1, L2-N=2, L3-N=3; Three-phase AC Delta: L1-L2=1, L2-L3=2, L3-L1=3; Single Phase: L1-R=1; DC: L1-R=1; Three-phase AC Wye & Delta: L1-N=1, L2-N=2, L3-N=3, L1-L2=4, L2-L3=5; L3-L1=6.
Integer32
.1.3.6.1.4.1.1718.4.1.5.2.1.1
st4PhaseIDThe internal ID of the phase. Format=AAN.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.5.2.1.2
st4PhaseLabelThe system label assigned to the phase for identification.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.5.2.1.4
st4PhaseNominalVoltageThe nominal voltage of the phase in tenth Volts.ro
Integer32
.1.3.6.1.4.1.1718.4.1.5.2.1.6
st4PhaseBranchCountThe number of branches downstream from the phase.ro
Integer32
.1.3.6.1.4.1.1718.4.1.5.2.1.20
st4PhaseOutletCountThe number of outlets powered from the phase.ro
Integer32
.1.3.6.1.4.1.1718.4.1.5.2.1.21
st4PhaseMonitorTablePhase monitor table.
SEQUENCE OF St4PhaseMonitorEntry
.1.3.6.1.4.1.1718.4.1.5.3
st4PhaseMonitorEntryObjects to monitor for a particular phase.
St4PhaseMonitorEntry
.1.3.6.1.4.1.1718.4.1.5.3.1
st4PhaseStateThe on/off state of the phase.ro
DeviceState
.1.3.6.1.4.1.1718.4.1.5.3.1.1
st4PhaseStatusThe status of the phase.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.5.3.1.2
st4PhaseVoltageThe measured voltage on the phase in tenth Volts.ro
Integer32(-1..6000) UNITS "tenth Volts"
.1.3.6.1.4.1.1718.4.1.5.3.1.3
st4PhaseVoltageStatusThe status of the measured voltage on the phase.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.5.3.1.4
st4PhaseVoltageDeviationThe deviation from the nominal voltage on the phase in tenth percent.ro
Integer32(-1000..1000) UNITS "tenth percent"
.1.3.6.1.4.1.1718.4.1.5.3.1.5
st4PhaseCurrentThe measured current on the phase in hundredth Amps.ro
Integer32(-1..30000) UNITS "hundredth Amps"
.1.3.6.1.4.1.1718.4.1.5.3.1.6
st4PhaseCurrentCrestFactorThe measured crest factor of the current waveform on the phase in tenths.ro
Integer32(-1..250) UNITS "tenths"
.1.3.6.1.4.1.1718.4.1.5.3.1.7
st4PhaseActivePowerThe measured active power on the phase in Watts.ro
Integer32(-1..25000) UNITS "Watts"
.1.3.6.1.4.1.1718.4.1.5.3.1.8
st4PhaseApparentPowerThe measured apparent power on the phase in Volt-Amps.ro
Integer32(-1..25000) UNITS "Volt-Amps"
.1.3.6.1.4.1.1718.4.1.5.3.1.9
st4PhasePowerFactorThe measured power factor on the phase in hundredths.ro
Integer32(-1..100) UNITS "hundredths"
.1.3.6.1.4.1.1718.4.1.5.3.1.10
st4PhasePowerFactorStatusThe status of the measured power factor on the phase.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.5.3.1.11
st4PhaseReactanceThe status of the measured reactance of the phase.ro
Enumeration
.1.3.6.1.4.1.1718.4.1.5.3.1.12
st4PhaseEnergyThe total energy consumption of loads through the phase in tenth Kilowatt-Hours.ro
Integer32(-1..2147483647) UNITS "tenth Kilowatt-Hours"
.1.3.6.1.4.1.1718.4.1.5.3.1.13
st4PhaseEventConfigTablePhase event configuration table.
SEQUENCE OF St4PhaseEventConfigEntry
.1.3.6.1.4.1.1718.4.1.5.4
st4PhaseEventConfigEntryEvent configuration objects for a particular phase.
St4PhaseEventConfigEntry
.1.3.6.1.4.1.1718.4.1.5.4.1
st4PhaseNotificationsThe notification methods enabled for phase events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.5.4.1.1
st4PhaseVoltageLowAlarmThe current low alarm threshold of the phase in tenth Volts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.5.4.1.2
st4PhaseVoltageLowWarningThe current low warning threshold of the phase in tenth Volts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.5.4.1.3
st4PhaseVoltageHighWarningThe current high warning threshold of the phase in tenth Volts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.5.4.1.4
st4PhaseVoltageHighAlarmThe current high alarm threshold of the phase in tenth Volts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.5.4.1.5
st4PhasePowerFactorLowAlarmThe low power factor alarm threshold of the phase in hundredths.rw
Integer32
.1.3.6.1.4.1.1718.4.1.5.4.1.6
st4PhasePowerFactorLowWarningThe low power factor warning threshold of the phase in hundredths.rw
Integer32
.1.3.6.1.4.1.1718.4.1.5.4.1.7
st4OverCurrentProtectors
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.6
st4OcpCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.6.1
st4OcpConfigTableOver-current protector configuration table.
SEQUENCE OF St4OcpConfigEntry
.1.3.6.1.4.1.1718.4.1.6.2
st4OcpConfigEntryConfiguration objects for a particular over-current protector.
St4OcpConfigEntry
.1.3.6.1.4.1.1718.4.1.6.2.1
st4OcpIndexOver-current protector index.
Integer32
.1.3.6.1.4.1.1718.4.1.6.2.1.1
st4OcpIDThe internal ID of the over-current protector. Format=AAN[N].ro
DisplayString
.1.3.6.1.4.1.1718.4.1.6.2.1.2
st4OcpLabelThe system label assigned to the over-current protector for identification.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.6.2.1.4
st4OcpTypeThe type of over-current protector.ro
Enumeration
.1.3.6.1.4.1.1718.4.1.6.2.1.6
st4OcpCurrentCapacityThe user-configured current capacity of the over-current protector in Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.6.2.1.7
st4OcpCurrentCapacityMaxThe factory-set maximum allowed for the user-configured current capacity of the over-current protector in Amps.ro
Integer32
.1.3.6.1.4.1.1718.4.1.6.2.1.8
st4OcpBranchCountThe number of branches downstream from the over-current protector.ro
Integer32
.1.3.6.1.4.1.1718.4.1.6.2.1.20
st4OcpOutletCountThe number of outlets powered from the over-current protector.ro
Integer32
.1.3.6.1.4.1.1718.4.1.6.2.1.21
st4OcpMonitorTableOver-current protector monitor table.
SEQUENCE OF St4OcpMonitorEntry
.1.3.6.1.4.1.1718.4.1.6.3
st4OcpMonitorEntryObjects to monitor for a particular over-current protector.
St4OcpMonitorEntry
.1.3.6.1.4.1.1718.4.1.6.3.1
st4OcpStatusThe status of the over-current protector.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.6.3.1.1
st4OcpEventConfigTableOver-current protector event configuration table.
SEQUENCE OF St4OcpEventConfigEntry
.1.3.6.1.4.1.1718.4.1.6.4
st4OcpEventConfigEntryEvent configuration objects for a particular over-current protector.
St4OcpEventConfigEntry
.1.3.6.1.4.1.1718.4.1.6.4.1
st4OcpNotificationsThe notification methods enabled for over-current protector events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.6.4.1.1
st4Branches
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.7
st4BranchCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.7.1
st4BranchCurrentHysteresisThe current hysteresis of the branch in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.7.1.1
st4BranchConfigTableBranch configuration table.
SEQUENCE OF St4BranchConfigEntry
.1.3.6.1.4.1.1718.4.1.7.2
st4BranchConfigEntryConfiguration objects for a particular branch.
St4BranchConfigEntry
.1.3.6.1.4.1.1718.4.1.7.2.1
st4BranchIndexBranch index.
Integer32
.1.3.6.1.4.1.1718.4.1.7.2.1.1
st4BranchIDThe internal ID of the branch. Format=AAN[N].ro
DisplayString
.1.3.6.1.4.1.1718.4.1.7.2.1.2
st4BranchLabelThe system label assigned to the branch for identification.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.7.2.1.4
st4BranchCurrentCapacityThe current capacity of the branch in Amps.ro
Integer32
.1.3.6.1.4.1.1718.4.1.7.2.1.6
st4BranchPhaseIDThe internal ID of the phase powering this branch. Format=AAN.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.7.2.1.20
st4BranchOcpIDThe internal ID of the over-current protector powering this outlet. Format=AAN[N].ro
DisplayString
.1.3.6.1.4.1.1718.4.1.7.2.1.21
st4BranchOutletCountThe number of outlets powered from the branch.ro
Integer32
.1.3.6.1.4.1.1718.4.1.7.2.1.30
st4BranchMonitorTableBranch monitor table.
SEQUENCE OF St4BranchMonitorEntry
.1.3.6.1.4.1.1718.4.1.7.3
st4BranchMonitorEntryObjects to monitor for a particular branch.
St4BranchMonitorEntry
.1.3.6.1.4.1.1718.4.1.7.3.1
st4BranchStateThe on/off state of the branch.ro
DeviceState
.1.3.6.1.4.1.1718.4.1.7.3.1.1
st4BranchStatusThe status of the branch.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.7.3.1.2
st4BranchCurrentThe measured current on the branch in hundredth Amps.ro
Integer32(-1..12500) UNITS "hundredth Amps"
.1.3.6.1.4.1.1718.4.1.7.3.1.3
st4BranchCurrentStatusThe status of the measured current on the branch.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.7.3.1.4
st4BranchCurrentUtilizedThe amount of the branch current capacity used in tenth percent.ro
Integer32(-1..1200) UNITS "tenth percent"
.1.3.6.1.4.1.1718.4.1.7.3.1.5
st4BranchEventConfigTableBranch event configuration table.
SEQUENCE OF St4BranchEventConfigEntry
.1.3.6.1.4.1.1718.4.1.7.4
st4BranchEventConfigEntryEvent configuration objects for a particular branch.
St4BranchEventConfigEntry
.1.3.6.1.4.1.1718.4.1.7.4.1
st4BranchNotificationsThe notification methods enabled for branch events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.7.4.1.1
st4BranchCurrentLowAlarmThe current low alarm threshold of the branch in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.7.4.1.2
st4BranchCurrentLowWarningThe current low warning threshold of the branch in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.7.4.1.3
st4BranchCurrentHighWarningThe current high warning threshold of the branch in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.7.4.1.4
st4BranchCurrentHighAlarmThe current high alarm threshold of the branch in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.7.4.1.5
st4Outlets
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.8
st4OutletCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.8.1
st4OutletCurrentHysteresisThe current hysteresis of the outlet in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.1.1
st4OutletActivePowerHysteresisThe power hysteresis of the outlet in Watts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.1.2
st4OutletPowerFactorHysteresisThe power factor hysteresis of the outlet in hundredths.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.1.3
st4OutletSequenceIntervalThe power-on sequencing interval for all outlets in seconds.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.1.10
st4OutletRebootDelayThe reboot delay for all outlets in seconds.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.1.11
st4OutletStateChangeLoggingEnables or disables informational Outlet State Change event logging.rw
Enumeration
.1.3.6.1.4.1.1718.4.1.8.1.12
st4OutletConfigTableOutlet configuration table.
SEQUENCE OF St4OutletConfigEntry
.1.3.6.1.4.1.1718.4.1.8.2
st4OutletConfigEntryConfiguration objects for a particular outlet.
St4OutletConfigEntry
.1.3.6.1.4.1.1718.4.1.8.2.1
st4OutletIndexOutlet index.
Integer32
.1.3.6.1.4.1.1718.4.1.8.2.1.1
st4OutletIDThe internal ID of the outlet. Format=AAN[N[N]].ro
DisplayString
.1.3.6.1.4.1.1718.4.1.8.2.1.2
st4OutletNameThe name of the outlet.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.8.2.1.3
st4OutletCapabilitiesThe capabilities of the outlet.ro
Bits
.1.3.6.1.4.1.1718.4.1.8.2.1.5
st4OutletSocketTypeThe socket type of the outlet.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.8.2.1.6
st4OutletCurrentCapacityThe current capacity of the outlet in Amps.ro
Integer32
.1.3.6.1.4.1.1718.4.1.8.2.1.7
st4OutletPowerCapacityThe power capacity of the outlet in Volt-Amps. For DC products, this is identical to power capacity in Watts.ro
Integer32
.1.3.6.1.4.1.1718.4.1.8.2.1.8
st4OutletWakeupStateThe wakeup state of the outlet.rw
Enumeration
.1.3.6.1.4.1.1718.4.1.8.2.1.20
st4OutletPostOnDelayThe post-on delay of the outlet in seconds.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.2.1.21
st4OutletPhaseIDThe internal ID of the phase powering this outlet. Format=AAN.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.8.2.1.30
st4OutletOcpIDThe internal ID of the over-current protector powering this outlet. Format=AAN[N].ro
DisplayString
.1.3.6.1.4.1.1718.4.1.8.2.1.31
st4OutletBranchIDThe internal ID of the branch powering this outlet. Format=AAN[N].ro
DisplayString
.1.3.6.1.4.1.1718.4.1.8.2.1.32
st4OutletMonitorTableOutlet monitor table.
SEQUENCE OF St4OutletMonitorEntry
.1.3.6.1.4.1.1718.4.1.8.3
st4OutletMonitorEntryObjects to monitor for a particular outlet.
St4OutletMonitorEntry
.1.3.6.1.4.1.1718.4.1.8.3.1
st4OutletStateThe on/off state of the outlet.ro
DeviceState
.1.3.6.1.4.1.1718.4.1.8.3.1.1
st4OutletStatusThe status of the outlet.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.8.3.1.2
st4OutletCurrentThe measured current on the outlet in hundredth Amps.ro
Integer32(-1..12500) UNITS "hundredth Amps"
.1.3.6.1.4.1.1718.4.1.8.3.1.3
st4OutletCurrentStatusThe status of the measured current on the outlet.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.8.3.1.4
st4OutletCurrentUtilizedThe amount of the outlet current capacity used in tenth percent.ro
Integer32(-1..1200) UNITS "tenth percent"
.1.3.6.1.4.1.1718.4.1.8.3.1.5
st4OutletVoltageThe measured voltage of the outlet in tenth Volts.ro
Integer32(-1..6000) UNITS "tenth Volts"
.1.3.6.1.4.1.1718.4.1.8.3.1.6
st4OutletActivePowerThe measured active power of the outlet in Watts.ro
Integer32(-1..10000) UNITS "Watts"
.1.3.6.1.4.1.1718.4.1.8.3.1.7
st4OutletActivePowerStatusThe status of the measured active power of the outlet.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.8.3.1.8
st4OutletApparentPowerThe measured apparent power of the outlet in Volt-Amps.ro
Integer32(-1..10000) UNITS "Volt-Amps"
.1.3.6.1.4.1.1718.4.1.8.3.1.9
st4OutletPowerFactorThe measured power factor of the outlet in hundredths.ro
Integer32(-1..100) UNITS "hundredths"
.1.3.6.1.4.1.1718.4.1.8.3.1.10
st4OutletPowerFactorStatusThe status of the measured power factor of the outlet.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.8.3.1.11
st4OutletCurrentCrestFactorThe measured crest factor of the outlet in tenths.ro
Integer32(-1..250) UNITS "tenths"
.1.3.6.1.4.1.1718.4.1.8.3.1.12
st4OutletReactanceThe status of the measured reactance of the outlet.ro
Enumeration
.1.3.6.1.4.1.1718.4.1.8.3.1.13
st4OutletEnergyThe total energy consumption of the device plugged into the outlet in Watt-Hours.ro
Integer32(-1..2147483647) UNITS "Watt-Hours"
.1.3.6.1.4.1.1718.4.1.8.3.1.14
st4OutletEventConfigTableOutlet event configuration table.
SEQUENCE OF St4OutletEventConfigEntry
.1.3.6.1.4.1.1718.4.1.8.4
st4OutletEventConfigEntryEvent configuration objects for a particular outlet.
St4OutletEventConfigEntry
.1.3.6.1.4.1.1718.4.1.8.4.1
st4OutletNotificationsThe notification methods enabled for outlet events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.8.4.1.1
st4OutletCurrentLowAlarmThe current low alarm threshold of the outlet in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.4.1.2
st4OutletCurrentLowWarningThe current low warning threshold of the outlet in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.4.1.3
st4OutletCurrentHighWarningThe current high warning threshold of the outlet in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.4.1.4
st4OutletCurrentHighAlarmThe current high alarm threshold of the outlet in tenth Amps.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.4.1.5
st4OutletActivePowerLowAlarmThe active power low alarm threshold of the outlet in Watts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.4.1.6
st4OutletActivePowerLowWarningThe active power low warning threshold of the outlet in Watts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.4.1.7
st4OutletActivePowerHighWarningThe active power high warning threshold of the outlet in Watts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.4.1.8
st4OutletActivePowerHighAlarmThe active power high alarm threshold of the outlet in Watts.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.4.1.9
st4OutletPowerFactorLowAlarmThe low power factor alarm threshold of the outlet in hundredths.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.4.1.10
st4OutletPowerFactorLowWarningThe low power factor warning threshold of the outlet in hundredths.rw
Integer32
.1.3.6.1.4.1.1718.4.1.8.4.1.11
st4OutletControlTableOutlet control table.
SEQUENCE OF St4OutletControlEntry
.1.3.6.1.4.1.1718.4.1.8.5
st4OutletControlEntryObjects for control of a particular outlet.
St4OutletControlEntry
.1.3.6.1.4.1.1718.4.1.8.5.1
st4OutletControlStateThe control state of the outlet.ro
Enumeration
.1.3.6.1.4.1.1718.4.1.8.5.1.1
st4OutletControlActionAn action to change the control state of the outlet, or to queue an action.rw
Enumeration
.1.3.6.1.4.1.1718.4.1.8.5.1.2
st4OutletCommonControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.8.6
st4OutletQueueControlAn action to clear or commit queued outlet control actions. A read of this object returns clear(0) if queue is empty, and commit(1) if the queue is not empty.rw
Enumeration
.1.3.6.1.4.1.1718.4.1.8.6.1
st4TemperatureSensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.9
st4TempSensorCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.9.1
st4TempSensorHysteresisThe temperature hysteresis of the sensor in degrees, using the scale selected by st4TempSensorScale.rw
Integer32
.1.3.6.1.4.1.1718.4.1.9.1.1
st4TempSensorScaleThe current scale used for all temperature values.rw
Enumeration
.1.3.6.1.4.1.1718.4.1.9.1.10
st4TempSensorConfigTableTemperature sensor configuration table.
SEQUENCE OF St4TempSensorConfigEntry
.1.3.6.1.4.1.1718.4.1.9.2
st4TempSensorConfigEntryConfiguration objects for a particular temperature sensor.
St4TempSensorConfigEntry
.1.3.6.1.4.1.1718.4.1.9.2.1
st4TempSensorIndexTemperature sensor index.
Integer32
.1.3.6.1.4.1.1718.4.1.9.2.1.1
st4TempSensorIDThe internal ID of the temperature sensor. Format=AN.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.9.2.1.2
st4TempSensorNameThe name of the temperature sensor.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.9.2.1.3
st4TempSensorValueMinThe minimum temperature limit of the sensor in degrees, using the scale selected by st4TempSensorScale.ro
Integer32(-40..253) UNITS "degrees"
.1.3.6.1.4.1.1718.4.1.9.2.1.4
st4TempSensorValueMaxThe maximum temperature limit of the sensor in degrees, using the scale selected by st4TempSensorScale.ro
Integer32(-40..253) UNITS "degrees"
.1.3.6.1.4.1.1718.4.1.9.2.1.5
st4TempSensorMonitorTableTemperature sensor monitor table.
SEQUENCE OF St4TempSensorMonitorEntry
.1.3.6.1.4.1.1718.4.1.9.3
st4TempSensorMonitorEntryObjects to monitor for a particular temperature sensor.
St4TempSensorMonitorEntry
.1.3.6.1.4.1.1718.4.1.9.3.1
st4TempSensorValueThe measured temperature on the sensor in tenth degrees using the scale selected by st4TempSensorScale. -410 means the temperature reading is invalid.ro
Integer32(-410..2540) UNITS "tenth degrees"
.1.3.6.1.4.1.1718.4.1.9.3.1.1
st4TempSensorStatusThe status of the temperature sensor.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.9.3.1.2
st4TempSensorEventConfigTableTemperature sensor event configuration table.
SEQUENCE OF St4TempSensorEventConfigEntry
.1.3.6.1.4.1.1718.4.1.9.4
st4TempSensorEventConfigEntryEvent configuration objects for a particular temperature sensor.
St4TempSensorEventConfigEntry
.1.3.6.1.4.1.1718.4.1.9.4.1
st4TempSensorNotificationsThe notification methods enabled for temperature sensor events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.9.4.1.1
st4TempSensorLowAlarmThe low alarm threshold of the temperature sensor in degrees.rw
Integer32(-40..253) UNITS "degrees"
.1.3.6.1.4.1.1718.4.1.9.4.1.2
st4TempSensorLowWarningThe low warning threshold of the temperature sensor in degrees.rw
Integer32(-40..253) UNITS "degrees"
.1.3.6.1.4.1.1718.4.1.9.4.1.3
st4TempSensorHighWarningThe high warning threshold of the temperature sensor in degrees.rw
Integer32(-40..253) UNITS "degrees"
.1.3.6.1.4.1.1718.4.1.9.4.1.4
st4TempSensorHighAlarmThe high alarm threshold of the temperature sensor in degrees.rw
Integer32(-40..253) UNITS "degrees"
.1.3.6.1.4.1.1718.4.1.9.4.1.5
st4HumiditySensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.10
st4HumidSensorCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.10.1
st4HumidSensorHysteresisThe humidity hysteresis of the sensor in percent relative humidity.rw
Integer32
.1.3.6.1.4.1.1718.4.1.10.1.1
st4HumidSensorConfigTableHumidity sensor configuration table.
SEQUENCE OF St4HumidSensorConfigEntry
.1.3.6.1.4.1.1718.4.1.10.2
st4HumidSensorConfigEntryConfiguration objects for a particular humidity sensor.
St4HumidSensorConfigEntry
.1.3.6.1.4.1.1718.4.1.10.2.1
st4HumidSensorIndexHumidity sensor index.
Integer32
.1.3.6.1.4.1.1718.4.1.10.2.1.1
st4HumidSensorIDThe internal ID of the humidity sensor. Format=AN.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.10.2.1.2
st4HumidSensorNameThe name of the humidity sensor.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.10.2.1.3
st4HumidSensorMonitorTableHumidity sensor monitor table.
SEQUENCE OF St4HumidSensorMonitorEntry
.1.3.6.1.4.1.1718.4.1.10.3
st4HumidSensorMonitorEntryObjects to monitor for a particular humidity sensor.
St4HumidSensorMonitorEntry
.1.3.6.1.4.1.1718.4.1.10.3.1
st4HumidSensorValueThe measured humidity on the sensor in percentage relative humidity.ro
Integer32(-1..100) UNITS "percentage relative humidity"
.1.3.6.1.4.1.1718.4.1.10.3.1.1
st4HumidSensorStatusThe status of the humidity sensor.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.10.3.1.2
st4HumidSensorEventConfigTableHumidity sensor event configuration table.
SEQUENCE OF St4HumidSensorEventConfigEntry
.1.3.6.1.4.1.1718.4.1.10.4
st4HumidSensorEventConfigEntryEvent configuration objects for a particular humidity sensor.
St4HumidSensorEventConfigEntry
.1.3.6.1.4.1.1718.4.1.10.4.1
st4HumidSensorNotificationsThe notification methods enabled for humidity sensor events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.10.4.1.1
st4HumidSensorLowAlarmThe low alarm threshold of the humidity sensor in percentage relative humidity.rw
Integer32
.1.3.6.1.4.1.1718.4.1.10.4.1.2
st4HumidSensorLowWarningThe low warning threshold of the humidity sensor in percentage relative humidity.rw
Integer32
.1.3.6.1.4.1.1718.4.1.10.4.1.3
st4HumidSensorHighWarningThe high warning threshold of the humidity sensor in percentage relative humidity.rw
Integer32
.1.3.6.1.4.1.1718.4.1.10.4.1.4
st4HumidSensorHighAlarmThe high alarm threshold of the humidity sensor in percentage relative humidity.rw
Integer32
.1.3.6.1.4.1.1718.4.1.10.4.1.5
st4WaterSensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.11
st4WaterSensorCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.11.1
st4WaterSensorConfigTableWater sensor configuration table.
SEQUENCE OF St4WaterSensorConfigEntry
.1.3.6.1.4.1.1718.4.1.11.2
st4WaterSensorConfigEntryConfiguration objects for a particular water sensor.
St4WaterSensorConfigEntry
.1.3.6.1.4.1.1718.4.1.11.2.1
st4WaterSensorIndexWater sensor index.
Integer32
.1.3.6.1.4.1.1718.4.1.11.2.1.1
st4WaterSensorIDThe internal ID of the water sensor. Format=AN.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.11.2.1.2
st4WaterSensorNameThe name of the water sensor.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.11.2.1.3
st4WaterSensorMonitorTableWater sensor monitor table.
SEQUENCE OF St4WaterSensorMonitorEntry
.1.3.6.1.4.1.1718.4.1.11.3
st4WaterSensorMonitorEntryObjects to monitor for a particular water sensor.
St4WaterSensorMonitorEntry
.1.3.6.1.4.1.1718.4.1.11.3.1
st4WaterSensorStatusThe status of the water sensor.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.11.3.1.1
st4WaterSensorEventConfigTableWater sensor event configuration table.
SEQUENCE OF St4WaterSensorEventConfigEntry
.1.3.6.1.4.1.1718.4.1.11.4
st4WaterSensorEventConfigEntryEvent configuration objects for a particular water sensor.
St4WaterSensorEventConfigEntry
.1.3.6.1.4.1.1718.4.1.11.4.1
st4WaterSensorNotificationsThe notification methods enabled for water sensor events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.11.4.1.1
st4ContactClosureSensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.12
st4CcSensorCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.12.1
st4CcSensorConfigTableContact closure sensor configuration table.
SEQUENCE OF St4CcSensorConfigEntry
.1.3.6.1.4.1.1718.4.1.12.2
st4CcSensorConfigEntryConfiguration objects for a particular contact closure sensor.
St4CcSensorConfigEntry
.1.3.6.1.4.1.1718.4.1.12.2.1
st4CcSensorIndexContact closure sensor index.
Integer32
.1.3.6.1.4.1.1718.4.1.12.2.1.1
st4CcSensorIDThe internal ID of the contact closure sensor. Format=AN.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.12.2.1.2
st4CcSensorNameThe name of the contact closure sensor.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.12.2.1.3
st4CcSensorMonitorTableContact closure sensor monitor table.
SEQUENCE OF St4CcSensorMonitorEntry
.1.3.6.1.4.1.1718.4.1.12.3
st4CcSensorMonitorEntryObjects to monitor for a particular contact closure sensor.
St4CcSensorMonitorEntry
.1.3.6.1.4.1.1718.4.1.12.3.1
st4CcSensorStatusThe status of the contact closure.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.12.3.1.1
st4CcSensorEventConfigTableContact closure sensor event configuration table.
SEQUENCE OF St4CcSensorEventConfigEntry
.1.3.6.1.4.1.1718.4.1.12.4
st4CcSensorEventConfigEntryEvent configuration objects for a particular contact closure sensor.
St4CcSensorEventConfigEntry
.1.3.6.1.4.1.1718.4.1.12.4.1
st4CcSensorNotificationsThe notification methods enabled for contact closure sensor events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.12.4.1.1
st4AnalogToDigitalConvSensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.13
st4AdcSensorCommonConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.13.1
st4AdcSensorHysteresisThe 8-bit count hysteresis of the analog-to-digital converter sensor.rw
Integer32
.1.3.6.1.4.1.1718.4.1.13.1.1
st4AdcSensorConfigTableAnalog-to-digital converter sensor configuration table.
SEQUENCE OF St4AdcSensorConfigEntry
.1.3.6.1.4.1.1718.4.1.13.2
st4AdcSensorConfigEntryConfiguration objects for a particular analog-to-digital converter sensor.
St4AdcSensorConfigEntry
.1.3.6.1.4.1.1718.4.1.13.2.1
st4AdcSensorIndexAnalog-to-digital converter sensor index.
Integer32
.1.3.6.1.4.1.1718.4.1.13.2.1.1
st4AdcSensorIDThe internal ID of the analog-to-digital converter sensor. Format=AN.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.13.2.1.2
st4AdcSensorNameThe name of the analog-to-digital converter sensor.rw
DisplayString
.1.3.6.1.4.1.1718.4.1.13.2.1.3
st4AdcSensorMonitorTableAnalog-to-digital converter sensor monitor table.
SEQUENCE OF St4AdcSensorMonitorEntry
.1.3.6.1.4.1.1718.4.1.13.3
st4AdcSensorMonitorEntryObjects to monitor for a particular analog-to-digital converter sensor.
St4AdcSensorMonitorEntry
.1.3.6.1.4.1.1718.4.1.13.3.1
st4AdcSensorValueThe 8-bit value from the analog-to-digital converter sensor.ro
Integer32(-1..255)
.1.3.6.1.4.1.1718.4.1.13.3.1.1
st4AdcSensorStatusThe status of the analog-to-digital converter sensor.ro
DeviceStatus
.1.3.6.1.4.1.1718.4.1.13.3.1.2
st4AdcSensorEventConfigTableAnalog-to-digital converter sensor event configuration table.
SEQUENCE OF St4AdcSensorEventConfigEntry
.1.3.6.1.4.1.1718.4.1.13.4
st4AdcSensorEventConfigEntryEvent configuration objects for a particular analog-to-digital converter sensor.
St4AdcSensorEventConfigEntry
.1.3.6.1.4.1.1718.4.1.13.4.1
st4AdcSensorNotificationsThe notification methods enabled for analog-to-digital converter sensor events.rw
EventNotificationMethods
.1.3.6.1.4.1.1718.4.1.13.4.1.1
st4AdcSensorLowAlarmThe 8-bit value for the low alarm threshold of the analog-to-digital converter sensor.rw
Integer32
.1.3.6.1.4.1.1718.4.1.13.4.1.2
st4AdcSensorLowWarningThe 8-bit value for the low warning threshold of the analog-to-digital converter sensor.rw
Integer32
.1.3.6.1.4.1.1718.4.1.13.4.1.3
st4AdcSensorHighWarningThe 8-bit value for the high warning threshold of the analog-to-digital converter sensor.rw
Integer32
.1.3.6.1.4.1.1718.4.1.13.4.1.4
st4AdcSensorHighAlarmThe 8-bit value for the high alarm threshold of the analog-to-digital converter sensor.rw
Integer32
.1.3.6.1.4.1.1718.4.1.13.4.1.5
st4EventInformation
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.1.99
st4EventStatusTextThe text representation of the enumerated integer value of the most-relevant status or state object included in a trap. The value of this object is set only when sent with a trap. A read of this object will return a NULL string.ro
DisplayString
.1.3.6.1.4.1.1718.4.1.99.1
st4EventStatusConditionThe condition of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A read of this object will return zero.ro
Enumeration
.1.3.6.1.4.1.1718.4.1.99.2
st4Notifications
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.100
st4Events
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.100.0
st4UnitStatusEventUnit status event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.1
st4InputCordStatusEventInput cord status event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.2
st4InputCordActivePowerEventInput cord active power event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.3
st4InputCordApparentPowerEventInput cord apparent power event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.4
st4InputCordPowerFactorEventInput cord power factor event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.5
st4InputCordOutOfBalanceEventInput cord out-of-balance event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.6
st4LineStatusEventLine status event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.7
st4LineCurrentEventLine current event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.8
st4PhaseStatusEventPhase status event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.9
st4PhaseVoltageEventPhase voltage event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.10
st4PhasePowerFactorEventPhase voltage event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.11
st4OcpStatusEventOver-current protector status event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.12
st4BranchStatusEventBranch status event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.13
st4BranchCurrentEventBranch current event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.14
st4OutletStatusEventOutlet status event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.15
st4OutletStateChangeEventOutlet state change event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.16
st4OutletCurrentEventOutlet current event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.17
st4OutletActivePowerEventOutlet active power event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.18
st4OutletPowerFactorEventOutlet power factor event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.19
st4TempSensorEventTemperature sensor event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.20
st4HumidSensorEventHumidity sensor event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.21
st4WaterSensorStatusEventWater sensor status event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.22
st4CcSensorStatusEventContact closure sensor status event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.23
st4AdcSensorEventAnalog-to-digital converter sensor event.
NOTIFICATION-TYPE
.1.3.6.1.4.1.1718.4.100.0.24
st4Conformance
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.200
st4Groups
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.200.1
st4SystemObjectsGroupSystem objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.1
st4UnitObjectsGroupUnit objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.2
st4InputCordObjectsGroupInput cord objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.3
st4LineObjectsGroupLine objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.4
st4PhaseObjectsGroupPhase objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.5
st4OcpObjectsGroupOver-current protector objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.6
st4BranchObjectsGroupBranch objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.7
st4OutletObjectsGroupOutlet objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.8
st4TempSensorObjectsGroupTemperature sensor objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.9
st4HumidSensorObjectsGroupHumidity sensor objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.10
st4WaterSensorObjectsGroupWater sensor objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.11
st4CcSensorObjectsGroupContact closure sensor objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.12
st4AdcSensorObjectsGroupAnalog-to-digital converter sensor objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.13
st4EventInfoObjectsGroupEvent information objects group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.99
st4EventNotificationsGroupEvent notifications group.
Unknown
.1.3.6.1.4.1.1718.4.200.1.100
st4Compliances
OBJECT IDENTIFIER
.1.3.6.1.4.1.1718.4.200.2
st4ModuleCompliancesThe requirements for conformance to the Sentry4-MIB.
Unknown
.1.3.6.1.4.1.1718.4.200.2.1
Sentry4-MIB - SNMP MIB Reference | MIBs Explorer