SYNSO-UPSMIB
Detailed view of the defined objects, syntax rules, and hierarchical paths.
105
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
105 total| Object Name |
|---|
synso OBJECT IDENTIFIER .1.3.6.1.4.1.9557 |
synsoUpsSoftware OBJECT IDENTIFIER .1.3.6.1.4.1.9557.1 |
syupsBasicSetting OBJECT IDENTIFIER .1.3.6.1.4.1.9557.1.1 |
syupsPlatFormThe platform which the UPS software is running on.ro DisplayString .1.3.6.1.4.1.9557.1.1.1 |
syupsFeatureTableA table containing the supported features. SEQUENCE OF SyupsFeatureEntry .1.3.6.1.4.1.9557.1.1.2 |
syupsFeatureEntryAn entry representing the support information for a feature. SyupsFeatureEntry .1.3.6.1.4.1.9557.1.1.2.1 |
syupsFeatureThe string representing a feature.ro INTEGER .1.3.6.1.4.1.9557.1.1.2.1.1 |
syupsSupportInfoThe string containing the support information for a feature.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.1.2.1.2 |
syupsSystemStartTimeThe time that the UPS software starts. It is the number of seconds elapsed since 00:00:00, January 1, 1970.ro INTEGER .1.3.6.1.4.1.9557.1.1.3 |
syupsSignalTypeThe signaling method between the UPS and software. When the basicSignal used, the UPS changes the voltage level of some specific pins to notify the software of what critical event occurs. Usually, the UPS will inform software when a power failure or a low battery condition occurs. On the other hand, the software can change the voltage signal of a specific pin to ask the UPS to shut down (turn off). When the smartSignal used, the UPS asks like a standard communication device (such as mouse or modem). That means the UPS and software communicate with each other using a pre-defined protocol. The protocol should include at least the following commands: - query the power status of the UPS - query the power data of the UPS - command the UPS to shut downrw Enumeration .1.3.6.1.4.1.9557.1.1.4 |
syupsBasicSignalDefinitionThe signal definitions for the basic signaling UPS. The value can be the following bit combinations: SG_POWER_FAILURE_ENABLE 0x01 SG_BATTERY_LOW_ENABLE 0x02 SG_SHUTDOWN_ENABLE 0x04 SG_POWER_FAILURE_VOLTHIGH 0x10 SG_BATTERY_LOW_VOLTHIGH 0x20 SG_SHUTDOWN_VOLTHIGH 0x40 SG_POWER_FAILURE_ENABLE, SG_BATTERY_LOW_ENABLE, and SG_SHUTDOWN_ENABLE indicate whether the signals for a power failure , a low battery condition, and the UPS shutdown are enabled. SG_POWER_FAILURE_VOLTHIGH, SG_BATTERY_LOW_VOLTHIGH, and SG_SHUTDOWN_VOLTHIGH indicate whether the voltage level for these signals are high or low.ro INTEGER .1.3.6.1.4.1.9557.1.1.5 |
syupsUpsComPortThe serial port which the UPS software use to communicate with the UPS. The format varies from platform to platform. For DOS program, the format is 'portNo, portAddress, portIRQ' (e.g. '1, 0x2f8, 3' for COM2). For Windows program, it is 'portNo'. For NetWare program, it is 'portType, boardNo, portNo'. For UNIX, it is 'device name'.rw DisplayString .1.3.6.1.4.1.9557.1.1.6 |
syupsModemComPortThe serial port which the UPS software use to dial out when some particular events occur. The format varies from platform to platform. For DOS program, the format is 'portNo, portAddress, portIRQ' (e.g. '1, 0x2f8, 3' for COM2). For Windows program, it is 'portNo'. For NetWare program, it is 'portType, boardNo, portNo'. For UNIX, it is 'device name'.rw DisplayString .1.3.6.1.4.1.9557.1.1.7 |
syupsUpsExtension OBJECT IDENTIFIER .1.3.6.1.4.1.9557.1.2 |
syupsUpsAlarmIt is used internally. Each bit indicates a critical event, such as input bad, on battery, communications lost, ...,etc.ro INTEGER .1.3.6.1.4.1.9557.1.2.1 |
syupsSerialNoThe serial number of the UPS connected to the UPS software.ro DisplayString .1.3.6.1.4.1.9557.1.2.2 |
syupsConfigBatteryVoltageThe nominal battery voltage.ro INTEGER .1.3.6.1.4.1.9557.1.2.3 |
syupsBatteryReplaceDateThe last battery replacement date. It represents the number of days elapsed since January 1, 1901.rw INTEGER .1.3.6.1.4.1.9557.1.2.4 |
syupsNoOutletThe total number of controllable outlets.ro INTEGER .1.3.6.1.4.1.9557.1.2.5 |
syupsOutletParamterThis object is not used any more.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.2.6 |
syupsShutdownDependA string containing those who should perform their shutdown procedure before the UPS turns off. The agent will inform each one in the list to begin their shutdown procedure before it turns off the power of the UPS.rw DisplayString .1.3.6.1.4.1.9557.1.2.7 |
syupsEnableAutoSaveSetting it to 1, the agent will try to save all files opened by applications before shutting down the operation system. Setting it to 0 will disable the auto save feature.rw INTEGER .1.3.6.1.4.1.9557.1.2.8 |
syupsShutdownOsDelayThe delay time before shutting down the operation system. When it is necessary to shut down the operation system, the agent will run the specified command file and try to save all files opened by applications before shutting down the OS. This delay time is used to do such things.rw INTEGER .1.3.6.1.4.1.9557.1.2.9 |
syupsShutdownUpsDelayThe delay time before shutting down the UPS. Before shutting down the operation system, the agent will send a command to tell the UPS to shut down. This delay time is used to allow the agent to shut down the operation system safely.rw INTEGER .1.3.6.1.4.1.9557.1.2.10 |
syupsSaveConfigUsed to inform the agnet to save the configurations. Its value indicates which group to be saved. For example, a 1 indicates group 1 (syupsBasicSetting) to be saved, a 6 1 indicates group 6 (syupsCoworker) to be saved. You have to use it to save configurations after changing settings, or the settings may be lost.rw INTEGER .1.3.6.1.4.1.9557.1.2.11 |
syupsNoOutletsThe number of controllable outlets.ro INTEGER .1.3.6.1.4.1.9557.1.2.12 |
syupsOutletTableA list of outlet table entries. The number of entries is given by the value of syupsNoOutlets. SEQUENCE OF SyupsOutletEntry .1.3.6.1.4.1.9557.1.2.13 |
syupsOutletEntryAn entry containing information applicable to a particular controllable outlet. SyupsOutletEntry .1.3.6.1.4.1.9557.1.2.13.1 |
syupsOutletIndexThe outlet identifier. INTEGER .1.3.6.1.4.1.9557.1.2.13.1.1 |
syupsOutletDescriptionThe outlet description.rw DisplayString .1.3.6.1.4.1.9557.1.2.13.1.2 |
syupsOutletShutdownDelayThe delay time (in seconds) before turning off the outlet. Before turning off the outlet, the agent will send a shutdown command to anyone specified in the syupsOutletShutdownDepend, telling them to start their shutdown procedure. This delay time is used to allow those cmputers to be shut down safely.rw INTEGER .1.3.6.1.4.1.9557.1.2.13.1.3 |
syupsOutletShutdownDependA string containing those who should perform their shutdown procedure before the outlet turns off. The agent will inform each one in the list to begin their shutdown procedure before it turns off the power of the outlet.rw DisplayString .1.3.6.1.4.1.9557.1.2.13.1.4 |
syupsOutletOperatorThe operator is used to control the outlets. There are two commands: 1. 'SWITCH: OutletNo, OnOff'. The OutletNo specify the outlet. The OnOff can be 0 (off) or 1 (on). For example, 'SWITCH: 2, 1' means turning on (1) the outlet #2. 'SWITCH: 4, 0' means turning off (0) the outlet #4. 2. 'SET: OutletNo, Desc, DelayTime, Depend'. The OutletNo specify the outlet. The Desc specifies the outlet description. The DelayTime specifies the shutdown delay time for the outlet. The Depend specifies the shutdown dependent list for the outlet. For example, 'SET: 3, My Printer, 20, 192.168.1.9' means setting the description of outlet #3 to 'My Printer', the shutdown delay time to 20 seconds and the Shutdown Dependent to '192.168.1.9'.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.2.14 |
syupsEventAction OBJECT IDENTIFIER .1.3.6.1.4.1.9557.1.3 |
syupsNoEventActionEntriesThe number of event-action items. This variable indicates the number of rows in the event-action table.ro INTEGER .1.3.6.1.4.1.9557.1.3.1 |
syupsEventActionTableA list of event action entries. The number of entries is given by the value of syupsNoEventActionEntries. SEQUENCE OF SyupsEventActionEntry .1.3.6.1.4.1.9557.1.3.2 |
syupsEventActionEntryAn entry containing information applicable to a particular event action. SyupsEventActionEntry .1.3.6.1.4.1.9557.1.3.2.1 |
syupsEventIdThe event ID.ro INTEGER .1.3.6.1.4.1.9557.1.3.2.1.1 |
syupsLogEnableWhether to log the event in the log file when it occurs. A 1 indicates enable, a 0 indicates disable.rw Enumeration .1.3.6.1.4.1.9557.1.3.2.1.2 |
syupsNotifyEnableWhether to notify users when the event occurs. A 1 indicates enable, a 0 indicates disable.rw Enumeration .1.3.6.1.4.1.9557.1.3.2.1.3 |
syupsNotifyDelayHow long the event must last before notifying users.rw INTEGER .1.3.6.1.4.1.9557.1.3.2.1.4 |
syupsNotifyMessageThe message which will be sent when the event occurs.rw DisplayString .1.3.6.1.4.1.9557.1.3.2.1.5 |
syupsNotifyPeriodHow often (in seconds) to send the message. The -1 means once.rw INTEGER .1.3.6.1.4.1.9557.1.3.2.1.6 |
syupsNotifyUsersWho will receive the message when the event occurs.rw DisplayString .1.3.6.1.4.1.9557.1.3.2.1.7 |
syupsEmailEnableWhether to email users when the event occurs. A 1 indicates enable, a 0 indicates disable.rw Enumeration .1.3.6.1.4.1.9557.1.3.2.1.8 |
syupsEmailDelayHow long the event must last before emailing users.rw INTEGER .1.3.6.1.4.1.9557.1.3.2.1.9 |
syupsEmailMessageThe additional message which will be sent when the event occurs.rw DisplayString .1.3.6.1.4.1.9557.1.3.2.1.10 |
syupsEmailUsersWho will receive the mail when the event occurs.rw DisplayString .1.3.6.1.4.1.9557.1.3.2.1.11 |
syupsPageEnableWhether to page users when the event occurs. A 1 indicates enable, a 0 indicates disable.rw Enumeration .1.3.6.1.4.1.9557.1.3.2.1.12 |
syupsPageDelayHow long the event must last before paging users.rw INTEGER .1.3.6.1.4.1.9557.1.3.2.1.13 |
syupsPageMessageThe message which will be sent when the event occurs.rw DisplayString .1.3.6.1.4.1.9557.1.3.2.1.14 |
syupsPageUsersWho will receive the code when the event occurs.rw DisplayString .1.3.6.1.4.1.9557.1.3.2.1.15 |
syupsCommandEnableWhether to execute the external command file when the event occurs. A 1 indicates enable, a 0 indicates disable.rw Enumeration .1.3.6.1.4.1.9557.1.3.2.1.16 |
syupsCommandDelayHow long the event must last before executing the external command file.rw INTEGER .1.3.6.1.4.1.9557.1.3.2.1.17 |
syupsCommandFileThe external command file which will be executed when the event occurs.rw DisplayString .1.3.6.1.4.1.9557.1.3.2.1.18 |
syupsShutdownEnableWhether to shut down the system when the event occurs. A 1 indicates enable, a 0 indicates disable.rw Enumeration .1.3.6.1.4.1.9557.1.3.2.1.19 |
syupsShutdownDelayHow long the event must last before shutting down the system.rw INTEGER .1.3.6.1.4.1.9557.1.3.2.1.20 |
syupsHistory OBJECT IDENTIFIER .1.3.6.1.4.1.9557.1.4 |
syupsMaxEventFileLengthThe maximum length (in bytes) of the event log file. UPS software will cut the first half of the file whenever the file exceeds this maximum length.rw INTEGER .1.3.6.1.4.1.9557.1.4.1 |
syupsEventNumRecordsThe total number of records in the event log file.ro INTEGER .1.3.6.1.4.1.9557.1.4.2 |
syupsEventTableA list of event entries. Each entry represents a record in the event log file. SEQUENCE OF SyupsEventEntry .1.3.6.1.4.1.9557.1.4.3 |
syupsEventEntryAn entry representing a record in the event log file. SyupsEventEntry .1.3.6.1.4.1.9557.1.4.3.1 |
syupsEventIndexThe record number of an event entry.ro INTEGER .1.3.6.1.4.1.9557.1.4.3.1.1 |
syupsEventRecordThe string containing an event entry.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.4.3.1.2 |
syupsDataRecordIntervalThe number of minutes to wait between each recording to the data log file.rw INTEGER .1.3.6.1.4.1.9557.1.4.4 |
syupsMaxDataFileLengthThe maximum length (in bytes) of the data log file. UPS software will cut the first half of the file whenever the file exceeds this maximum length.rw INTEGER .1.3.6.1.4.1.9557.1.4.5 |
syupsDataNumRecordsThe total number of records in the data log file.ro INTEGER .1.3.6.1.4.1.9557.1.4.6 |
syupsDataTableA list of data entries. Each entry represents a record in the data log file. SEQUENCE OF SyupsDataEntry .1.3.6.1.4.1.9557.1.4.7 |
syupsDataEntryAn entry representing a record in the data log file. SyupsDataEntry .1.3.6.1.4.1.9557.1.4.7.1 |
syupsDataIndexThe record number of a data entry.ro INTEGER .1.3.6.1.4.1.9557.1.4.7.1.1 |
syupsDataRecordThe string containing a data entry.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.4.7.1.2 |
syupsHistoryOperatorThe operator which is used to operate on the history file. The command format is 'Command, File, Range'. So far, Command can be PURGE, File can be EVENT or DATA, and Range can be ALL or 'mm/dd/year..mm/dd/year'. For example, 'PURGE, EVENT, ALL' tells the UPS software to purge all entries in the event log file. And 'PURGE, DATA, 03/20/1995..07/02/1995' tells the UPS software to purge the entries which are recorded form 03/20/1995 to 07/20/1995 from the event log file.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.4.8 |
syupsScopeSettingsThe string contains the settings for UPS Scope Chart, including Value Original Point, Value Unit, Time Unit, Time Interval, and Display Items. The format for the settings string is '%d, %d, %d, %d, %d'. Display Items can be any one or any combination of the following items: SCOPE_INPUT_VOLT 0x0001 SCOPE_OUTPUT_VOLT 0x0010 SCOPE_INPUT_FREQ 0x0100 SCOPE_OUTPUT_FREQ 0x1000rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.4.9 |
syupsSchedule OBJECT IDENTIFIER .1.3.6.1.4.1.9557.1.5 |
syupsNoSchEntriesThe total number of schedule entries.ro INTEGER .1.3.6.1.4.1.9557.1.5.1 |
syupsSchOperatorThe operator which is used to operate on the schedule table. There are three commands: 1. 'ADD: action, mm/dd/yyyy, hh:mm:ss, week_day, repeat' indicates to add a new entry to the schedule list. 2. 'REPLACE: i, action, mm/dd/yyyy, hh:mm:ss, week_day, repeat' indicates to replace the i-th entry in the table with the new settings. 3. 'DELETE:n1, n2' indicates to delete the entries ranging from number n1 to number n2 from the schedule table. 'action' could be the following: General System Test (1) Quick Battery Test (2) Deep Battery Test (3) Turn On UPS (11) Turn Off UPS (21) Turn On Outlet (100+x) Turn Off Outlet (200+x) where x indicates the outlet number. 'mm/dd/year' and 'hh:mm:ss' specify the action's starting time. 'repeat' indicates the frequency of the action, it could be Once(1), Daily(2), Weekly(3) and Monthly(4). 'week_day' indicating the day of week is meaningful only when the repeat is set to Weekly, and it could be Sun(0), Mon(1), ..., and Sat(6). For example, '1, 07/08/1994, 15:30:00, 0, 4' indicates that the UPS will do a General System Test at 3:30 PM every month from July 8, 1994. '203, 06/20/1995, 07:00:00, 0, 1' indicates that the UPS will turn off outlet #3 at 7 o'clock on June 20, 1995 and do it only once.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.5.2 |
syupsSchTableA list of schedule entries. SEQUENCE OF SyupsSchEntry .1.3.6.1.4.1.9557.1.5.3 |
syupsSchEntryA schedule entry. SyupsSchEntry .1.3.6.1.4.1.9557.1.5.3.1 |
syupsSchIndexThe entry number of a schedule setting.ro INTEGER .1.3.6.1.4.1.9557.1.5.3.1.1 |
syupsSchStartDateThe starting date (mm/dd/yyyy) of the schedule entry.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.5.3.1.2 |
syupsSchStartTimeThe starting time (hh:mm:ss) of the schedule entry.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.5.3.1.3 |
syupsSchWeekDayThe starting day of week for the schedule entry. It could be Sun(0), Mon(1), ..., and Sat(6). It is used when syupsSchRepeat is set to weekly.ro Enumeration .1.3.6.1.4.1.9557.1.5.3.1.4 |
syupsSchActionThe action of the schedule entry. It could be: General System Test (1) Quick Battery Test (2) Deep Battery Test (3) Turn On UPS (11) Turn Off UPS (21) Turn On Outlet (100+x) Turn Off Outlet (200+x) where x indicates the outlet number.ro INTEGER .1.3.6.1.4.1.9557.1.5.3.1.5 |
syupsSchRepeatIt indicates the frequency of the action, it could be Once(1), Daily(2), Weekly(3) and Monthly(4).ro Enumeration .1.3.6.1.4.1.9557.1.5.3.1.6 |
syupsCoworker OBJECT IDENTIFIER .1.3.6.1.4.1.9557.1.6 |
syupsNoAccessControlThe total number of access control entries.ro INTEGER .1.3.6.1.4.1.9557.1.6.1 |
syupsAccessControlOperatorThe operator which is used to operate on the access control table. There are three commands: 1. 'ADD: community' indicates to add a new entry to the access control list. 2. 'REPLACE: x, community' indicates to replace the x-th entry in the table with the new settings. 3. 'DELETE:n1, n2' indicates to delete the entries from number n1 to number n2 from the access control table.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.6.2 |
syupsAccessControlTableA list of access control entries. Only entries in this list can have access to the agent. SEQUENCE OF SyupsAccessControlEntry .1.3.6.1.4.1.9557.1.6.3 |
syupsAccessControlEntryAn access control entry. SyupsAccessControlEntry .1.3.6.1.4.1.9557.1.6.3.1 |
syupsAccessControlIndexThe entry number of a access control setting.ro INTEGER .1.3.6.1.4.1.9557.1.6.3.1.1 |
syupsAccessControlSettingA string containing the community name.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.6.3.1.2 |
syupsNoTrapReceiverThe total number of trap receiver entries.ro INTEGER .1.3.6.1.4.1.9557.1.6.4 |
syupsTrapReceiverOperatorThe operator which is used to operate on the trap receiver table. There are three commands: 1. 'ADD: ipAddress' indicates to add a new entry to the trap receiver list. 2. 'REPLACE: x, ipAddress' indicates to replace the x-th entry in the table with the new settings. 3. 'DELETE:n1, n2' indicates to delete the entries from number n1 to number n2 from the trap receiver table.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.6.5 |
syupsTrapReceiverTableA list of trap receiver entries. When an important event occurs, the agent will send traps to all the entries in the list. SEQUENCE OF SyupsTrapReceiverEntry .1.3.6.1.4.1.9557.1.6.6 |
syupsTrapReceiverEntryAn trap receiver entry. SyupsTrapReceiverEntry .1.3.6.1.4.1.9557.1.6.6.1 |
syupsTrapReceiverIndexThe entry number of a trap receiver setting.ro INTEGER .1.3.6.1.4.1.9557.1.6.6.1.1 |
syupsTrapReceiverSettingA string containing a trap receiver's IP address.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.9557.1.6.6.1.2 |
syupsTraps OBJECT IDENTIFIER .1.3.6.1.4.1.9557.1.7 |
syupsTrapOverTemperatureThe battery temperature is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. NOTIFICATION-TYPE .1.3.6.1.4.1.9557.1.7.1 |
syupsTrapOverCurrentThe current is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. NOTIFICATION-TYPE .1.3.6.1.4.1.9557.1.7.2 |
syupsTrapOverVoltageThe voltage is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. NOTIFICATION-TYPE .1.3.6.1.4.1.9557.1.7.3 |
syupsTrapUnderVoltageThe voltage is too low. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. NOTIFICATION-TYPE .1.3.6.1.4.1.9557.1.7.4 |
syupsOffFrequencyThe frequency is abnormal. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. NOTIFICATION-TYPE .1.3.6.1.4.1.9557.1.7.5 |
syupsLowBatteryThe battery is too low. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. NOTIFICATION-TYPE .1.3.6.1.4.1.9557.1.7.6 |
syupsBadBatteryThe battery is bad. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. NOTIFICATION-TYPE .1.3.6.1.4.1.9557.1.7.7 |