Home/Catalog/SYNOLOGY-UPS-MIB

SYNOLOGY-UPS-MIB

AI MIB Summary

SYNOLOGY-UPS-MIB defines the SNMP objects for monitoring Synology NAS devices equipped with UPS modules, exposing real-time metrics such as battery charge percentage, remaining runtime, input/output voltage, and current UPS status states. This module enables centralized network management systems to track power supply health and trigger alerts for battery degradation or power loss events on Synology hardware.

Characteristics of the ups information
Main OID:
synoUPS.1.3.6.1.4.1.6574.4
159
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

159 total
Object Name
synology
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574
synoUPSCharacteristics of the ups information
MODULE-IDENTITY
.1.3.6.1.4.1.6574.4
upsDevice
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.1
upsDeviceModelDevice modelro
DisplayString
.1.3.6.1.4.1.6574.4.1.1
upsDeviceManufacturerDevice manufacturerro
DisplayString
.1.3.6.1.4.1.6574.4.1.2
upsDeviceSerialDevice serial number.ro
DisplayString
.1.3.6.1.4.1.6574.4.1.3
upsDeviceTypeDevice type (ups, pdu, scd, psu)ro
DisplayString
.1.3.6.1.4.1.6574.4.1.4
upsDeviceDescriptionDevice description.ro
DisplayString
.1.3.6.1.4.1.6574.4.1.5
upsDeviceContactDevice administrator name.ro
DisplayString
.1.3.6.1.4.1.6574.4.1.6
upsDeviceLocationDevice physical location.ro
DisplayString
.1.3.6.1.4.1.6574.4.1.7
upsDevicePartDevice part number.ro
DisplayString
.1.3.6.1.4.1.6574.4.1.8
upsDeviceMACAddrPhysical network address of the device.ro
DisplayString
.1.3.6.1.4.1.6574.4.1.9
upsInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.2
upsInfoStatusUPS status.ro
DisplayString
.1.3.6.1.4.1.6574.4.2.1
upsInfoAlarmUPS alarmsro
DisplayString
.1.3.6.1.4.1.6574.4.2.2
upsInfoTimeInternal UPS clock timero
DisplayString
.1.3.6.1.4.1.6574.4.2.3
upsInfoDateInternal UPS clock datero
DisplayString
.1.3.6.1.4.1.6574.4.2.4
upsInfoModelUPS modelro
DisplayString
.1.3.6.1.4.1.6574.4.2.5
upsInfoMfr
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.2.6
upsInfoMfrNameUPS manufacturerro
DisplayString
.1.3.6.1.4.1.6574.4.2.6.1
upsInfoMfrDateUPS manufacturing datero
DisplayString
.1.3.6.1.4.1.6574.4.2.6.2
upsInfoSerialUPS serial numberro
DisplayString
.1.3.6.1.4.1.6574.4.2.7
upsInfoVendorIDVendor ID for USB devicesro
DisplayString
.1.3.6.1.4.1.6574.4.2.8
upsInfoProductIDProduct ID for USB devicesro
DisplayString
.1.3.6.1.4.1.6574.4.2.9
upsInfoFirmware
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.2.10
upsInfoFirmwareNameUPS firmwarero
DisplayString
.1.3.6.1.4.1.6574.4.2.10.1
upsInfoFirmwareAuxAuxiliary device firmwarero
DisplayString
.1.3.6.1.4.1.6574.4.2.10.2
upsInfoTemperatureUPS temperature (degrees C)ro
Float UNITS "degree C"
.1.3.6.1.4.1.6574.4.2.11
upsInfoLoad
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.2.12
upsInfoLoadValueLoad on UPS (percent)ro
Float UNITS "percentage"
.1.3.6.1.4.1.6574.4.2.12.1
upsInfoLoadHighLoad when UPS switches to overload condition (OVER) (percent)ro
Float UNITS "percentage"
.1.3.6.1.4.1.6574.4.2.12.2
upsInfoIDUPS system identifierro
DisplayString
.1.3.6.1.4.1.6574.4.2.13
upsInfoDelay
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.2.14
upsInfoDelayStartInterval to wait before restarting the load (seconds)ro
NonNegativeInteger UNITS "seconds"
.1.3.6.1.4.1.6574.4.2.14.1
upsInfoDelayRebootInterval to wait before rebooting the UPS (seconds)ro
NonNegativeInteger UNITS "seconds"
.1.3.6.1.4.1.6574.4.2.14.2
upsInfoDelayShutdownInterval to wait after shutdown with delay command (seconds)ro
NonNegativeInteger UNITS "seconds"
.1.3.6.1.4.1.6574.4.2.14.3
upsInfoTimer
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.2.15
upsInfoTimerStartTime before the load will be started (seconds)ro
NonNegativeInteger UNITS "seconds"
.1.3.6.1.4.1.6574.4.2.15.1
upsInfoTimerRebootTime before the load will be rebooted (seconds)ro
NonNegativeInteger UNITS "seconds"
.1.3.6.1.4.1.6574.4.2.15.2
upsInfoTimerShutdownTime before the load will be shutdown (seconds)ro
NonNegativeInteger UNITS "seconds"
.1.3.6.1.4.1.6574.4.2.15.3
upsInfoTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.2.16
upsInfoTestIntervalInterval between self testsro
NonNegativeInteger UNITS "seconds"
.1.3.6.1.4.1.6574.4.2.16.1
upsInfoTestResultResults of last self testro
DisplayString
.1.3.6.1.4.1.6574.4.2.16.2
upsInfoDisplayLanguageLanguage to use on front panelro
DisplayString
.1.3.6.1.4.1.6574.4.2.17
upsInfoContactsUPS external contact sensorsro
DisplayString
.1.3.6.1.4.1.6574.4.2.18
upsInfoEffciencyEfficiency of the UPS (ratio of the output current on the input current) (percent)ro
NonNegativeInteger UNITS "percent"
.1.3.6.1.4.1.6574.4.2.19
upsInfoPower
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.2.20
upsInfoPowerValueCurrent value of apparent power (Volt-Amps)ro
Float UNITS "Volt-Amps"
.1.3.6.1.4.1.6574.4.2.20.1
upsInfoPowerNominalNominal value of apparent power (Volt-Amps)ro
Float UNITS "Volt-Amps"
.1.3.6.1.4.1.6574.4.2.20.2
upsInfoRealPower
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.2.21
upsInfoRealPowerValueCurrent value of real power (Watts)ro
Float UNITS "Watts"
.1.3.6.1.4.1.6574.4.2.21.1
upsInfoRealPowerNominalNominal value of real power (Watts)ro
Float UNITS "Watts"
.1.3.6.1.4.1.6574.4.2.21.2
upsInfoBeeperStatusUPS beeper status (enabled, disabled or muted)ro
DisplayString
.1.3.6.1.4.1.6574.4.2.22
upsInfoTypeUPS typero
DisplayString
.1.3.6.1.4.1.6574.4.2.23
upsInfoWatchdogStatusUPS watchdog status (enabled or disabled)ro
DisplayString
.1.3.6.1.4.1.6574.4.2.24
upsInfoStart
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.2.25
upsInfoStartAutoUPS starts when mains is (re)appliedro
DisplayString
.1.3.6.1.4.1.6574.4.2.25.1
upsInfoStartBatteryAllow to start UPS from batteryro
DisplayString
.1.3.6.1.4.1.6574.4.2.25.2
upsInfoStartRebootUPS coldstarts from battery (enabled or disabled)ro
DisplayString
.1.3.6.1.4.1.6574.4.2.25.3
upsBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.3
upsBatteryCharge
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.3.1
upsBatteryChargeValueBattery chargero
Float UNITS "Percent"
.1.3.6.1.4.1.6574.4.3.1.1
upsBatteryChargeLowRemaining battery level when UPS switches to LB (percent)ro
Float UNITS "Percent"
.1.3.6.1.4.1.6574.4.3.1.2
upsBatteryChargeRestartMinimum battery level for UPS restart after power-offro
Float UNITS "Percent"
.1.3.6.1.4.1.6574.4.3.1.3
upsBatteryChargeWarningBattery level when UPS switches to Warning state (percent)ro
Float UNITS "Percent"
.1.3.6.1.4.1.6574.4.3.1.4
upsBatteryVoltage
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.3.2
upsBatteryVoltageValueThe magnitude of the present battery voltage.ro
Float UNITS "Volt DC"
.1.3.6.1.4.1.6574.4.3.2.1
upsBatteryVoltageNominalNominal battery voltage.ro
Float UNITS "Volt DC"
.1.3.6.1.4.1.6574.4.3.2.2
upsBatteryVoltageLowMinimum battery voltage, that triggers FSD status .ro
Float UNITS "Volt DC"
.1.3.6.1.4.1.6574.4.3.2.3
upsBatteryVoltageHighMaximum battery voltage (Ie battery.charge = 100).ro
Float UNITS "Volt DC"
.1.3.6.1.4.1.6574.4.3.2.4
upsBatteryCapacityBattery capacity (Ah)ro
Float UNITS "A"
.1.3.6.1.4.1.6574.4.3.3
upsBatteryCurrentThe present battery current.ro
Float UNITS "Amp DC"
.1.3.6.1.4.1.6574.4.3.4
upsBatteryTemperatureThe ambient temperature at or near the UPS Battery casing.ro
Float UNITS "degrees Centigrade"
.1.3.6.1.4.1.6574.4.3.5
upsBatteryRuntime
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.3.6
upsBatteryRuntimeValueBattery runtime (seconds)ro
NonNegativeInteger UNITS "Seconds"
.1.3.6.1.4.1.6574.4.3.6.1
upsBatteryRuntimeLowRemaining battery runtime when UPS switches to LB (seconds)ro
NonNegativeInteger UNITS "Seconds"
.1.3.6.1.4.1.6574.4.3.6.2
upsBatteryRuntimeRestartMinimum battery runtime for UPS restart after power-off (seconds)ro
NonNegativeInteger UNITS "Seconds"
.1.3.6.1.4.1.6574.4.3.6.3
upsBatteryAlarmThresholdBattery alarm thresholdro
DisplayString
.1.3.6.1.4.1.6574.4.3.7
upsBatteryDateBattery change datero
DisplayString
.1.3.6.1.4.1.6574.4.3.8
upsBatteryMfrDateBattery manufacturing datero
DisplayString
.1.3.6.1.4.1.6574.4.3.9
upsBatteryPacksNumber of battery packsro
NonNegativeInteger
.1.3.6.1.4.1.6574.4.3.10
upsBatteryPacksBadNumber of bad battery packsro
NonNegativeInteger
.1.3.6.1.4.1.6574.4.3.11
upsBatteryTypeBattery chemistryro
DisplayString
.1.3.6.1.4.1.6574.4.3.12
upsBatteryProtectionPrevent deep discharge of batteryro
DisplayString
.1.3.6.1.4.1.6574.4.3.13
upsBatteryEnergySaveSwitch off when running on battery and no/low loadro
DisplayString
.1.3.6.1.4.1.6574.4.3.14
upsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.4
upsInputVoltage
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.4.1
upsInputVoltageValueInput voltagero
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.1.1
upsInputVoltageMaxMaximum incoming voltage seenro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.1.2
upsInputVoltageMinMinimum incoming voltage seenro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.1.3
upsInputVoltageNominalNominal input voltagero
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.1.4
upsInputVoltageExtendExtended input voltage rangero
DisplayString
.1.3.6.1.4.1.6574.4.4.1.5
upsInputVoltageFaultInput voltage Faultro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.1.6
upsInputTransfer
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.4.2
upsInputTransferReasonReason for last transfer to batteryro
DisplayString
.1.3.6.1.4.1.6574.4.4.2.1
upsInputTransferLowLow voltage transfer pointro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.2.2
upsInputTransferHighHigh voltage transfer pointro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.2.3
upsInputTransferLowMinsmallest settable low voltage transfer pointro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.2.4
upsInputTransferLowMaxgreatest settable low voltage transfer pointro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.2.5
upsInputTransferHighMinsmallest settable high voltage transfer pointro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.2.6
upsInputTransferHighMaxgreatest settable high voltage transfer pointro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.2.7
upsInputTransferBoostLowLow voltage boosting transfer pointro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.2.8
upsInputTransferBoostHighHigh voltage boosting transfer pointro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.2.9
upsInputTransferTrimLowLow voltage trimming transfer pointro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.2.10
upsInputTransferTrimHighHigh voltage trimming transfer pointro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.4.2.11
upsInputSensitivityInput power sensitivityro
DisplayString
.1.3.6.1.4.1.6574.4.4.3
upsInputQualityInput power qualityro
DisplayString
.1.3.6.1.4.1.6574.4.4.4
upsInputCurrent
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.4.5
upsInputCurrentValueInput current (A)ro
Float UNITS "Amp"
.1.3.6.1.4.1.6574.4.4.5.1
upsInputCurrentNominalNominal input current (A)ro
Float UNITS "Amp"
.1.3.6.1.4.1.6574.4.4.5.2
upsInputFrequency
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.4.6
upsInputFrequencyValueInput line frequency (Hz)ro
Float UNITS "Hz"
.1.3.6.1.4.1.6574.4.4.6.1
upsInputFrequencyNominalNominal input line frequency (Hz)ro
Float UNITS "Hz"
.1.3.6.1.4.1.6574.4.4.6.2
upsInputFrequencyLowInput line frequency low (Hz)ro
Float UNITS "Hz"
.1.3.6.1.4.1.6574.4.4.6.3
upsInputFrequencyHighInput line frequency high (Hz)ro
Float UNITS "Hz"
.1.3.6.1.4.1.6574.4.4.6.4
upsInputFrequencyExtendExtended input frequency rangero
DisplayString
.1.3.6.1.4.1.6574.4.4.6.5
upsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.5
upsOutputVoltage
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.5.1
upsOutputVoltageValueOutput voltage (V)ro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.5.1.1
upsOutputVoltageNominalNominal output voltage (V)ro
Float UNITS "Volts"
.1.3.6.1.4.1.6574.4.5.1.2
upsOutputFrequency
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.5.2
upsOutputFrequencyValueOutput frequency (Hz)ro
Float UNITS "Hz"
.1.3.6.1.4.1.6574.4.5.2.1
upsOutputFrequencyNominalNominal output frequency (Hz)ro
Float UNITS "Hz"
.1.3.6.1.4.1.6574.4.5.2.2
upsOutputCurrent
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.5.3
upsOutputCurrentValueOutput current (A)ro
Float UNITS "Amp"
.1.3.6.1.4.1.6574.4.5.3.1
upsOutputCurrentNominalNominal output current (A)ro
Float UNITS "Amp"
.1.3.6.1.4.1.6574.4.5.3.2
upsAmbient
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.6
upsAmbientTemperature
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.6.1
upsAmbientTemperatureValueAmbient temperature (degrees C)ro
Float UNITS "degrees Centigrade"
.1.3.6.1.4.1.6574.4.6.1.1
upsAmbientTemperatureAlarmTemperature alarm (enabled/disabled)ro
DisplayString
.1.3.6.1.4.1.6574.4.6.1.2
upsAmbientTemperatureHighTemperature threshold high (degrees C)ro
Float UNITS "degrees Centigrade"
.1.3.6.1.4.1.6574.4.6.1.3
upsAmbientTemperatureLowTemperature threshold low (degrees C)ro
Float UNITS "degrees Centigrade"
.1.3.6.1.4.1.6574.4.6.1.4
upsAmbientTemperatureMaxMaximum temperature seen (degrees C)ro
Float UNITS "degrees Centigrade"
.1.3.6.1.4.1.6574.4.6.1.5
upsAmbientTemperatureMinMinimum temperature seen (degrees C)ro
Float UNITS "degrees Centigrade"
.1.3.6.1.4.1.6574.4.6.1.6
upsAmbientHumidity
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.6.2
upsAmbientHumidityValueAmbient relative humidity (percent)ro
Float UNITS "percent"
.1.3.6.1.4.1.6574.4.6.2.1
upsAmbientHumidityAlarmRelative humidity alarm (enabled/disabled)ro
DisplayString
.1.3.6.1.4.1.6574.4.6.2.2
upsAmbientHumidityHighRelative humidity threshold high (percent)ro
Float UNITS "percent"
.1.3.6.1.4.1.6574.4.6.2.3
upsAmbientHumidityLowRelative humidity threshold low (percent)ro
Float UNITS "percent"
.1.3.6.1.4.1.6574.4.6.2.4
upsAmbientHumidityMaxMaximum relative humidity seen (percent)ro
Float UNITS "percent"
.1.3.6.1.4.1.6574.4.6.2.5
upsAmbientHumidityMinMinimum relative humidity seen (percent)ro
Float UNITS "percent"
.1.3.6.1.4.1.6574.4.6.2.6
upsDriver
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.7
upsDriverNameDriver namero
DisplayString
.1.3.6.1.4.1.6574.4.7.1
upsDriverVersionDriver version (NUT release)ro
DisplayString
.1.3.6.1.4.1.6574.4.7.2
upsDriverVersionDataDriver version dataro
DisplayString
.1.3.6.1.4.1.6574.4.7.3
upsDriverVersionInternalInternal driver version (if tracked separately)ro
DisplayString
.1.3.6.1.4.1.6574.4.7.4
upsDriverPollIntervalPoll interval setup in configuration filero
Integer32 UNITS "second"
.1.3.6.1.4.1.6574.4.7.5
upsDriverPortPort setup in configuration filero
DisplayString
.1.3.6.1.4.1.6574.4.7.6
upsDriverPollFrequencyPoll frequencyro
Integer32
.1.3.6.1.4.1.6574.4.7.7
upsDriverProductIDProduct IDro
DisplayString
.1.3.6.1.4.1.6574.4.7.8
upsDriverSnmpVersionSnmp versionro
DisplayString
.1.3.6.1.4.1.6574.4.7.9
upsServer
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.8
upsServerInfoServer informationro
DisplayString
.1.3.6.1.4.1.6574.4.8.1
upsServerVersionServer versionro
DisplayString
.1.3.6.1.4.1.6574.4.8.2
upsConformance
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.9
upsCompliances
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.9.1
upsComplianceThe compliance statement for synoSystem entities which implement the SYNOLOGY SYSTEM MIB.
Unknown
.1.3.6.1.4.1.6574.4.9.1.1
upsGroups
OBJECT IDENTIFIER
.1.3.6.1.4.1.6574.4.9.2
upsGroupA collection of objects providing basic information of an synology ups entity.
Unknown
.1.3.6.1.4.1.6574.4.9.2.1
SYNOLOGY-UPS-MIB - SNMP MIB Reference | MIBs Explorer