Home/Catalog/RIELLOMDU-MIB

RIELLOMDU-MIB

Detailed view of the defined objects, syntax rules, and hierarchical paths.

43
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

43 total
Object Name
mduMIB
OBJECT IDENTIFIER
.1.3.6.1.4.1.5491.11
RFC1213-MIB
Unknown
.1.3.6.1.4.1.5491.11
mduIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.5491.11.1
mduIdentManufacturerThe name of the mdu manufacturer.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5491.11.1.1
mduIdentModelThe mdu Model designation.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5491.11.1.2
mduIdentSoftwareVersionThe mdu Software version.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.5491.11.1.3
mduIdentIOConfigurationThe mdu input/output configuration (1 for Mono/mono, 4 for Tri/tri).ro
INTEGER
.1.3.6.1.4.1.5491.11.1.4
mduIdentInputSocketsThe number of mdu input sockets.ro
INTEGER
.1.3.6.1.4.1.5491.11.1.5
mduIdentOutputSocketsThe number of mdu output sockets.ro
INTEGER
.1.3.6.1.4.1.5491.11.1.6
mduIdentNominalCurrentThe mdu nominal current (A).ro
INTEGER
.1.3.6.1.4.1.5491.11.1.7
mduIdentNominalVoltageThe mdu nominal voltage (V).ro
INTEGER
.1.3.6.1.4.1.5491.11.1.8
mduIdentNominalFrequencyThe mdu nominal frequency (0.1 Hz).ro
INTEGER
.1.3.6.1.4.1.5491.11.1.9
mduStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.5491.11.2
mduLineAFrequencyThe frequency of source A (0.1 Hz).ro
INTEGER
.1.3.6.1.4.1.5491.11.2.1
mduLineAVoltageThe voltage of source 1 (V).ro
INTEGER
.1.3.6.1.4.1.5491.11.2.2
mduLineACurrentThe current of line A (0.1 A).ro
INTEGER
.1.3.6.1.4.1.5491.11.2.3
mduOutputA list of output table entries.
SEQUENCE OF MduOutputSockets
.1.3.6.1.4.1.5491.11.2.4
mduOutputSocketsAn entry containing information applicable to a particular output line.
MduOutputSockets
.1.3.6.1.4.1.5491.11.2.4.1
mduOutputLineIndexThe line identifier.
INTEGER
.1.3.6.1.4.1.5491.11.2.4.1.1
mduOutputCurrentOutput current (0.1 A)ro
INTEGER
.1.3.6.1.4.1.5491.11.2.4.1.2
mduOutputDisabled1->line active, 2->line deactivatedro
Enumeration
.1.3.6.1.4.1.5491.11.2.4.1.3
mduOutputOverload1->line ok, 2->line deactivated for overloadro
INTEGER
.1.3.6.1.4.1.5491.11.2.4.1.4
mduOutputStatus0=OFF 1=ON 2= Shutdown active (when a CS or a CR command is received but shutdown is not yet been executed and the 'Imminent time' is not reached) 3= Shutdown imminent (S01 to S08 code) 4= Restore active (when after that a CR command is received and the shutdown has been acted but the restore delay time is not expired) 5= Overload alarm (F01 to F08 code) 6= Locked: OFF for overload (L01 to L08 code)ro
Enumeration
.1.3.6.1.4.1.5491.11.2.4.1.5
mduLowInputVoltage1= yes, 0= no.ro
INTEGER
.1.3.6.1.4.1.5491.11.2.5
mduHighInputVoltage1= yes, 0= no.ro
INTEGER
.1.3.6.1.4.1.5491.11.2.6
mduLowInputCurrent1= yes, 0= no.ro
INTEGER
.1.3.6.1.4.1.5491.11.2.7
mduHighInputCurrent1= yes, 0= no.ro
INTEGER
.1.3.6.1.4.1.5491.11.2.8
mduPowerFailAux11= yes, 0= no.ro
INTEGER
.1.3.6.1.4.1.5491.11.2.9
mduPowerFailAux21= yes, 0= no.ro
INTEGER
.1.3.6.1.4.1.5491.11.2.10
mduManualBypass1= on manual bypass, 0= no.ro
INTEGER
.1.3.6.1.4.1.5491.11.2.11
mduTemperatureThe temperature (oC).ro
INTEGER
.1.3.6.1.4.1.5491.11.2.12
mduCommand
OBJECT IDENTIFIER
.1.3.6.1.4.1.5491.11.3
mduCommandCodeThis object determines the nature of the action to be taken at the time when the countdown of the mduShutdownDelay and mduRestoreDelay objects reaches zero. Setting this object to shutdown(1) indicates that the specified sockets mduOutputSocketApplyCommand will yurn off. Setting this object to restore(2) indicates that the specified output sockets will turn on. command delete(3) will delete the applied command, test panel will perform a test of LCD panel and audible alarmrw
Enumeration
.1.3.6.1.4.1.5491.11.3.1
mduShutdownDelaySetting this object will shutdown (i.e., turn off) either the MDU output socket by the value of mduCommandCode at the time of shutdown after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediatelyrw
INTEGER
.1.3.6.1.4.1.5491.11.3.2
mduRestoreDelayThe restore delay.rw
INTEGER
.1.3.6.1.4.1.5491.11.3.3
mduOutputSocketApplyCommandSpecify the socket to apply the command, the value 0 apply to all sockets.rw
INTEGER
.1.3.6.1.4.1.5491.11.3.4
mduCommandResultThe command result, refer to the follow codes: 0+mduCommandCode Command in progress 256+mduCommandCode Wrong Command code 512+mduCommandCode Command is not handled 768+mduCommandCode Parameter out of range 3584+mduCommandCode Command sent to MDU 3840+mduCommandCode Command executedro
INTEGER
.1.3.6.1.4.1.5491.11.3.5
mduTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.5491.11.4
mduNormalThis trap is sent when MDU is on normal status
TRAP-TYPE
.1.3.6.1.4.1.5491.11.4.0.1
mduAnomalyThis trap is sent when MDU is has some anomaly and is resent every minute
TRAP-TYPE
.1.3.6.1.4.1.5491.11.4.0.2
mduFaultThis trap is sent when MDU is has some fault and is resent every minute
TRAP-TYPE
.1.3.6.1.4.1.5491.11.4.0.3
mduLockThis trap is sent when MDU is locked and is resent every minute
TRAP-TYPE
.1.3.6.1.4.1.5491.11.4.0.4
mduManualBypassEnabledThis trap is sent when MDU is on manual bypass and is resent every minute
TRAP-TYPE
.1.3.6.1.4.1.5491.11.4.0.5