Home/Catalog/NetBotz50-MIB

NetBotz50-MIB

AI MIB Summary

The NetBotz50-MIB facilitates SNMP-based monitoring and management of APC NetBotz 500 series environmental sensors and rack-mounted appliances, exposing real-time telemetry for temperature, humidity, airflow, door status, and intrusion detection events.

NetBotz5-APC BotzWare MIB
Main OID:
netBotz5_APC.1.3.6.1.4.1.52674.500.1
567
Objects
Active
Status
3
Dependencies

Imported Objects

Objects

567 total
Object Name
netBotzAPC
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674
netBotz5
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500
netBotz5_APCNetBotz5-APC BotzWare MIB
MODULE-IDENTITY
.1.3.6.1.4.1.52674.500.1
netBotzEnclosures
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.2
enclosureTableA list of enclosures (base enclosure and pods).
SEQUENCE OF EnclosureEntry
.1.3.6.1.4.1.52674.500.2.1
enclosureEntryEnclosure entry.
EnclosureEntry
.1.3.6.1.4.1.52674.500.2.1.1
enclosureIdThe id of the physical enclosure.ro
DisplayString
.1.3.6.1.4.1.52674.500.2.1.1.1
enclosureStatusThe operational status of the enclosure.ro
OperStatus
.1.3.6.1.4.1.52674.500.2.1.1.2
enclosureErrorStatusThe error status of the enclosure. If there are no error conditions reported for the enclosure, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the enclosure.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.2.1.1.3
enclosureLabelThe unique label assigned to the enclosure (or pod).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.2.1.1.4
enclosureParentEncIdThe id of the parent enclosure this enclosure is attached to.ro
DisplayString
.1.3.6.1.4.1.52674.500.2.1.1.5
enclosureSerialNumberThe serial number of this enclosure.ro
DisplayString
.1.3.6.1.4.1.52674.500.2.1.1.6
enclosureIndexThe index of the physical enclosure.ro
Counter32
.1.3.6.1.4.1.52674.500.2.1.1.7
netBotzSensorCounts
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.2.2
alinkSensorCountTableA count of alink-related sensors.
SEQUENCE OF AlinkSensorCountEntry
.1.3.6.1.4.1.52674.500.2.2.1
alinkSensorCountEntryA count-of-sensors entry.
AlinkSensorCountEntry
.1.3.6.1.4.1.52674.500.2.2.1.1
alinkSensorCountIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.2.2.1.1.1
alinkSensorCountValueThe number of known connected sensors.ro
Integer32
.1.3.6.1.4.1.52674.500.2.2.1.1.2
alinkSensorCountLabelThe unique label assigned to the sensor count.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.2.2.1.1.3
alinkSensorCountEncIdThe id of the physical enclosure represented by the sensor count.ro
DisplayString
.1.3.6.1.4.1.52674.500.2.2.1.1.4
alinkSensorCountValueStrThe sensor count value shown as a string.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.2.2.1.1.5
alinkSensorCountValueIntThe sensor count as integer value.ro
Integer32
.1.3.6.1.4.1.52674.500.2.2.1.1.6
alinkSensorCountIndexThe index of the sensor counter.ro
Counter32
.1.3.6.1.4.1.52674.500.2.2.1.1.7
netBotzPorts
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.3
otherPortTableA list of other port entries.
SEQUENCE OF OtherPortEntry
.1.3.6.1.4.1.52674.500.3.10
otherPortEntryOther port entry.
OtherPortEntry
.1.3.6.1.4.1.52674.500.3.10.1
otherPortIdThe unique id of the port.ro
DisplayString
.1.3.6.1.4.1.52674.500.3.10.1.1
otherPortStatusThe operational status of the port.ro
OperStatus
.1.3.6.1.4.1.52674.500.3.10.1.2
otherPortLabelThe unique label assigned to the port.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.3.10.1.3
otherPortEncIdThe id of the physical enclosure containing the port.ro
DisplayString
.1.3.6.1.4.1.52674.500.3.10.1.4
otherPortIndexThe index of the port.ro
Counter32
.1.3.6.1.4.1.52674.500.3.10.1.5
netBotzSensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.4
netBotzNumericSensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.4.1
tempSensorTableA list of temperature sensor entries.
SEQUENCE OF TempSensorEntry
.1.3.6.1.4.1.52674.500.4.1.1
tempSensorEntryA temperature sensor entry.
TempSensorEntry
.1.3.6.1.4.1.52674.500.4.1.1.1
tempSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.1.1.1
tempSensorValueThe temperature measured by the sensor in tenths of a degree Celsius.ro
Integer32 (-500..1000)
.1.3.6.1.4.1.52674.500.4.1.1.1.2
tempSensorErrorStatusThe error status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.1.1.1.3
tempSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.1.1.4
tempSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.1.1.5
tempSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.1.1.6
tempSensorValueStrThe temperature reading, in degrees Celsius, shown as a string (or empty string if it is not plugged into a port).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.1.1.7
tempSensorValueIntThe temperature measured by the sensor in degree Celsius.ro
Integer32 (-50..100)
.1.3.6.1.4.1.52674.500.4.1.1.1.8
tempSensorValueIntFThe temperature measured by the sensor in degree Fahrenheit.ro
Integer32 (-50..212)
.1.3.6.1.4.1.52674.500.4.1.1.1.9
tempSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.1.1.1.10
humiSensorTableA list of humidity sensor entries.
SEQUENCE OF HumiSensorEntry
.1.3.6.1.4.1.52674.500.4.1.2
humiSensorEntryA humidity sensor entry.
HumiSensorEntry
.1.3.6.1.4.1.52674.500.4.1.2.1
humiSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.2.1.1
humiSensorValueThe relative humidity measured by the sensor in tenths of a percent.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.2.1.2
humiSensorErrorStatusThe error status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.1.2.1.3
humiSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.2.1.4
humiSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.2.1.5
humiSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.2.1.6
humiSensorValueStrThe humidity reading, in percent, shown as a string (or empty string if it is not plugged into a port).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.2.1.7
humiSensorValueIntThe relative humidity measured by the sensor in percent.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.2.1.8
humiSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.1.2.1.9
dewPointSensorTableA list of dew point sensor entries.
SEQUENCE OF DewPointSensorEntry
.1.3.6.1.4.1.52674.500.4.1.3
dewPointSensorEntryA dew point sensor entry.
DewPointSensorEntry
.1.3.6.1.4.1.52674.500.4.1.3.1
dewPointSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.3.1.1
dewPointSensorValueThe dew point value measured by the sensor in tenths of a degree Celsius.ro
Integer32 (-500..1000)
.1.3.6.1.4.1.52674.500.4.1.3.1.2
dewPointSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.1.3.1.3
dewPointSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.3.1.4
dewPointSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.3.1.5
dewPointSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.3.1.6
dewPointSensorValueStrThe dew point reading, in degrees Celsius, shown as a string (or empty string if it is not plugged into a port).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.3.1.7
dewPointSensorValueIntThe dew point value measured by the sensor in degrees Celsius.ro
Integer32 (-50..100)
.1.3.6.1.4.1.52674.500.4.1.3.1.8
dewPointSensorValueIntFThe dew point reading in degrees Fahrenheit, measured by the sensor.ro
Integer32 (-40..122)
.1.3.6.1.4.1.52674.500.4.1.3.1.9
dewPointSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.1.3.1.10
airFlowSensorTableA list of airflow sensor entries.
SEQUENCE OF AirFlowSensorEntry
.1.3.6.1.4.1.52674.500.4.1.5
airFlowSensorEntryAn air flow sensor entry.
AirFlowSensorEntry
.1.3.6.1.4.1.52674.500.4.1.5.1
airFlowSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.5.1.1
airFlowSensorValueThe air flow measured by the sensor in tenths of a meter per minute.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.5.1.2
airFlowSensorErrorStatusThe error status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.1.5.1.3
airFlowSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.5.1.4
airFlowSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.5.1.5
airFlowSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.5.1.6
airFlowSensorValueStrThe airflow reading, in meters per minute, shown as a string (or empty string if it is not plugged into a port).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.5.1.7
airFlowSensorValueIntThe air flow measured by the sensor in meters per minute.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.5.1.8
airFlowSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.1.5.1.9
ampDetectSensorTableA list of amp detect sensor entries.
SEQUENCE OF AmpDetectSensorEntry
.1.3.6.1.4.1.52674.500.4.1.6
ampDetectSensorEntryAn ampere sensor entry.
AmpDetectSensorEntry
.1.3.6.1.4.1.52674.500.4.1.6.1
ampDetectSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.6.1.1
ampDetectSensorValueThe value measured by the sensor in tenths of an ampere.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.6.1.2
ampDetectSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.1.6.1.3
ampDetectSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.6.1.4
ampDetectSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.6.1.5
ampDetectSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.6.1.6
ampDetectSensorValueStrThe amp detect reading, in amperes, shown as a string (or empty string if it is not plugged into a port).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.6.1.7
ampDetectSensorValueIntThe value measured by the sensor in amperes.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.6.1.8
ampDetectSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.1.6.1.9
otherNumericSensorTableA list of other numeric sensor entries.
SEQUENCE OF OtherNumericSensorEntry
.1.3.6.1.4.1.52674.500.4.1.10
otherNumericSensorEntryOther numeric sensor entry.
OtherNumericSensorEntry
.1.3.6.1.4.1.52674.500.4.1.10.1
otherNumericSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.10.1.1
otherNumericSensorValueThe value measured by the sensor in tenths of the unit of measure.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.10.1.2
otherNumericSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.1.10.1.3
otherNumericSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.10.1.4
otherNumericSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.10.1.5
otherNumericSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.10.1.6
otherNumericSensorValueStrThe sensor reading shown as a string (or empty string if it is not plugged into a port).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.10.1.7
otherNumericSensorValueIntThe value measured by the sensor in the unit of measure (1/10 of otherNumericSensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.10.1.8
otherNumericSensorUnitsThe unit of measure for the sensor value.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.10.1.9
otherNumericSensorValueIntX1000The value measured by the sensor in thousandths of the unit of measure (100 times otherNumericSensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.10.1.10
otherNumericSensorValueIntX1000000The value measured by the sensor in millionths of the unit of measure (100000 times otherNumericSensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.10.1.11
otherNumericSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.1.10.1.12
rssiSensorTableA list of wireless network RSSI entries.
SEQUENCE OF RssiSensorEntry
.1.3.6.1.4.1.52674.500.4.1.11
rssiSensorEntryRSSI sensor entry.
RssiSensorEntry
.1.3.6.1.4.1.52674.500.4.1.11.1
rssiSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.11.1.1
rssiSensorValueThe value measured by the sensor in tenths of the unit of measure.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.11.1.2
rssiSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.1.11.1.3
rssiSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.11.1.4
rssiSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.11.1.5
rssiSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.11.1.6
rssiSensorValueStrThe sensor reading shown as a string (or empty string if it is not plugged into a port).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.11.1.7
rssiSensorValueIntThe value measured by the sensor in the unit of measure (1/10 of rssiSensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.11.1.8
rssiSensorUnitsThe unit of measure for the sensor value.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.11.1.9
rssiSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.1.11.1.10
currentInputSensorTableA list of current input sensor entries.
SEQUENCE OF CurrentInputSensorEntry
.1.3.6.1.4.1.52674.500.4.1.12
currentInputSensorEntryCurrent Input sensor entry.
CurrentInputSensorEntry
.1.3.6.1.4.1.52674.500.4.1.12.1
currentInputSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.12.1.1
currentInputSensorValueThe value measured by the sensor in tenths of the unit of measure.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.12.1.2
currentInputSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.1.12.1.3
currentInputSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.12.1.4
currentInputSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.12.1.5
currentInputSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.12.1.6
currentInputSensorValueStrThe sensor reading shown as a string (or empty string if it is not plugged into a port).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.12.1.7
currentInputSensorValueIntThe value measured by the sensor in the unit of measure (1/10 of currentInputSensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.12.1.8
currentInputSensorUnitsThe unit of measure for the sensor value.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.12.1.9
currentInputSensorValueIntX1000The value measured by the sensor in thousandths of the unit of measure (100 times currentInputSensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.12.1.10
currentInputSensorValueIntX1000000The value measured by the sensor in millionths of the unit of measure (100000 times currentInputSensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.12.1.11
currentInputSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.1.12.1.12
voltageSensorTableA list of current input sensor entries.
SEQUENCE OF VoltageSensorEntry
.1.3.6.1.4.1.52674.500.4.1.13
voltageSensorEntryVoltage sensor entry.
VoltageSensorEntry
.1.3.6.1.4.1.52674.500.4.1.13.1
voltageSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.13.1.1
voltageSensorValueThe value measured by the sensor in tenths of the unit of measure.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.13.1.2
voltageSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.1.13.1.3
voltageSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.13.1.4
voltageSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.13.1.5
voltageSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.13.1.6
voltageSensorValueStrThe sensor reading shown as a string (or empty string if it is not plugged into a port).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.13.1.7
voltageSensorValueIntThe value measured by the sensor in the unit of measure (1/10 of voltageSensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.13.1.8
voltageSensorUnitsThe unit of measure for the sensor value.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.13.1.9
voltageSensorValueIntX1000The value measured by the sensor in thousandths of the unit of measure (100 times voltageSensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.13.1.10
voltageSensorValueIntX1000000The value measured by the sensor in millionths of the unit of measure (100000 times voltageSensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.13.1.11
voltageSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.1.13.1.12
batterySensorTableA list of current input sensor entries.
SEQUENCE OF BatterySensorEntry
.1.3.6.1.4.1.52674.500.4.1.14
batterySensorEntryBattery sensor entry.
BatterySensorEntry
.1.3.6.1.4.1.52674.500.4.1.14.1
batterySensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.14.1.1
batterySensorValueThe value measured by the sensor in tenths of the unit of measure.ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.14.1.2
batterySensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.1.14.1.3
batterySensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.14.1.4
batterySensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.14.1.5
batterySensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.1.14.1.6
batterySensorValueStrThe sensor reading shown as a string (or empty string if it is not plugged into a port).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.14.1.7
batterySensorValueIntThe value measured by the sensor in the unit of measure (1/10 of batterySensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.14.1.8
batterySensorUnitsThe unit of measure for the sensor value.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.1.14.1.9
batterySensorValueIntX1000The value measured by the sensor in thousandths of the unit of measure (100 times batterySensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.14.1.10
batterySensorValueIntX1000000The value measured by the sensor in millionths of the unit of measure (100000 times batterySensorValue)ro
Integer32
.1.3.6.1.4.1.52674.500.4.1.14.1.11
batterySensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.1.14.1.12
netBotzStateSensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.4.2
dryContactSensorTableA list of dry contact sensor entries.
SEQUENCE OF DryContactSensorEntry
.1.3.6.1.4.1.52674.500.4.2.1
dryContactSensorEntryDry contact sensor entry.
DryContactSensorEntry
.1.3.6.1.4.1.52674.500.4.2.1.1
dryContactSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.1.1.1
dryContactSensorValueWhether the dry sensor contact is open or closed.ro
Enumeration
.1.3.6.1.4.1.52674.500.4.2.1.1.2
dryContactSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.1.1.3
dryContactSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.1.1.4
dryContactSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.1.1.5
dryContactSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.1.1.6
dryContactSensorValueStrThe enum value label for the state reported by the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.1.1.7
dryContactSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.1.1.8
doorSwitchSensorTableA list of door switch sensor entries.
SEQUENCE OF DoorSwitchSensorEntry
.1.3.6.1.4.1.52674.500.4.2.2
doorSwitchSensorEntryDoor switch sensor entry.
DoorSwitchSensorEntry
.1.3.6.1.4.1.52674.500.4.2.2.1
doorSwitchSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.2.1.1
doorSwitchSensorValueWhether the door is open or closed.ro
Enumeration
.1.3.6.1.4.1.52674.500.4.2.2.1.2
doorSwitchSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.2.1.3
doorSwitchSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.2.1.4
doorSwitchSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.2.1.5
doorSwitchSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.2.1.6
doorSwitchSensorValueStrThe enum value label for the state reported by the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.2.1.7
doorSwitchSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.2.1.8
cameraMotionSensorTableA list of camera motion sensor entries.
SEQUENCE OF CameraMotionSensorEntry
.1.3.6.1.4.1.52674.500.4.2.3
cameraMotionSensorEntryCamera motion sensor entry.
CameraMotionSensorEntry
.1.3.6.1.4.1.52674.500.4.2.3.1
cameraMotionSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.3.1.1
cameraMotionSensorValueWhether motion is detected by the camera sensor.ro
Enumeration
.1.3.6.1.4.1.52674.500.4.2.3.1.2
cameraMotionSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.3.1.3
cameraMotionSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.3.1.4
cameraMotionSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.3.1.5
cameraMotionSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.3.1.6
cameraMotionSensorValueStrThe enum value label for the state reported by the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.3.1.7
cameraMotionSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.3.1.8
otherStateSensorTableA list of other state sensor entries.
SEQUENCE OF OtherStateSensorEntry
.1.3.6.1.4.1.52674.500.4.2.10
otherStateSensorEntryOther state sensor entry.
OtherStateSensorEntry
.1.3.6.1.4.1.52674.500.4.2.10.1
otherStateSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.10.1.1
otherStateSensorValueState value reported by the sensor.ro
Integer32
.1.3.6.1.4.1.52674.500.4.2.10.1.2
otherStateSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.10.1.3
otherStateSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.10.1.4
otherStateSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.10.1.5
otherStateSensorPortIdThe id of port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.10.1.6
otherStateSensorValueStrThe enum value label for the state reported by the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.10.1.7
otherStateSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.10.1.8
vibrationSensorTableA list of vibration sensor entries.
SEQUENCE OF VibrationSensorEntry
.1.3.6.1.4.1.52674.500.4.2.11
vibrationSensorEntryVibration sensor entry.
VibrationSensorEntry
.1.3.6.1.4.1.52674.500.4.2.11.1
vibrationSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.11.1.1
vibrationSensorValueWhether vibration is detected.ro
Enumeration
.1.3.6.1.4.1.52674.500.4.2.11.1.2
vibrationSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.11.1.3
vibrationSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.11.1.4
vibrationSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.11.1.5
vibrationSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.11.1.6
vibrationSensorValueStrThe enum value label for the state reported by the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.11.1.7
vibrationSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.11.1.8
smokeSensorTableA list of smoke sensor entries.
SEQUENCE OF SmokeSensorEntry
.1.3.6.1.4.1.52674.500.4.2.12
smokeSensorEntrySmoke sensor entry.
SmokeSensorEntry
.1.3.6.1.4.1.52674.500.4.2.12.1
smokeSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.12.1.1
smokeSensorValueWhether smoke is detected.ro
Enumeration
.1.3.6.1.4.1.52674.500.4.2.12.1.2
smokeSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.12.1.3
smokeSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.12.1.4
smokeSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.12.1.5
smokeSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.12.1.6
smokeSensorValueStrThe enum value label for the state reported by the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.12.1.7
smokeSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.12.1.8
leakSensorTableA list of leak sensor entries.
SEQUENCE OF LeakSensorEntry
.1.3.6.1.4.1.52674.500.4.2.13
leakSensorEntryLeak sensor entry.
LeakSensorEntry
.1.3.6.1.4.1.52674.500.4.2.13.1
leakSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.13.1.1
leakSensorValueWhether a leak is detected.ro
Enumeration
.1.3.6.1.4.1.52674.500.4.2.13.1.2
leakSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.13.1.3
leakSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.13.1.4
leakSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.13.1.5
leakSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.13.1.6
leakSensorValueStrThe enum value label for the state reported by the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.13.1.7
leakSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.13.1.8
beaconTableA list of beacon entries.
SEQUENCE OF BeaconEntry
.1.3.6.1.4.1.52674.500.4.2.14
beaconEntryBeacon entry.
BeaconEntry
.1.3.6.1.4.1.52674.500.4.2.14.1
beaconIdThe unique id of the beacon.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.14.1.1
beaconValueWhether the beacon is flashing.ro
Enumeration
.1.3.6.1.4.1.52674.500.4.2.14.1.2
beaconErrorStatusThe operational status of the beacon. If there are no error conditions reported for the beacon, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the beacon.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.14.1.3
beaconLabelThe unique label assigned to the beacon.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.14.1.4
beaconEncIdThe id of the physical enclosure containing the beacon.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.14.1.5
beaconPortIdThe id of the port the beacon is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.14.1.6
beaconValueStrThe enum value label for the state reported by the beacon.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.14.1.7
beaconIndexThe index of the beacon.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.14.1.8
switchedOutletTableA list of switched outlet entries.
SEQUENCE OF SwitchedOutletEntry
.1.3.6.1.4.1.52674.500.4.2.15
switchedOutletEntrySwitched outlet entry.
SwitchedOutletEntry
.1.3.6.1.4.1.52674.500.4.2.15.1
switchedOutletIdThe unique id of the switched outlet.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.15.1.1
switchedOutletValueWhether the switched outlet is on or off.ro
Enumeration
.1.3.6.1.4.1.52674.500.4.2.15.1.2
switchedOutletErrorStatusThe operational status of the switched outlet. If there are no error conditions reported for the switched outlet, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the switched outlet.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.15.1.3
switchedOutletLabelThe unique label assigned to the switched outlet.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.15.1.4
switchedOutletEncIdThe id of the physical enclosure containing the switched outlet.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.15.1.5
switchedOutletPortIdThe id of the port the switched outlet is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.15.1.6
switchedOutletValueStrThe enum value label for the state reported by the switchedOutlet.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.15.1.7
switchedOutletIndexThe index of the switched outlet.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.15.1.8
doorLockSensorTableA list of door lock sensor entries.
SEQUENCE OF DoorLockSensorEntry
.1.3.6.1.4.1.52674.500.4.2.16
doorLockSensorEntryDoor lock sensor entry.
DoorLockSensorEntry
.1.3.6.1.4.1.52674.500.4.2.16.1
doorLockSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.16.1.1
doorLockSensorValueWhen setting this object only unlocked(0) or locked(1) is valid.rw
Enumeration
.1.3.6.1.4.1.52674.500.4.2.16.1.2
doorLockSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.16.1.3
doorLockSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.16.1.4
doorLockSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.16.1.5
doorLockSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.16.1.6
doorLockSensorValueStrThe enum value label for the state reported by the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.16.1.7
doorLockSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.16.1.8
rackHandleSensorTableA list of rack handle sensor entries.
SEQUENCE OF RackHandleSensorEntry
.1.3.6.1.4.1.52674.500.4.2.17
rackHandleSensorEntryRack door handle sensor entry.
RackHandleSensorEntry
.1.3.6.1.4.1.52674.500.4.2.17.1
rackHandleSensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.17.1.1
rackHandleSensorValueWhether the door is open or closed.ro
Enumeration
.1.3.6.1.4.1.52674.500.4.2.17.1.2
rackHandleSensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.17.1.3
rackHandleSensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.17.1.4
rackHandleSensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.17.1.5
rackHandleSensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.17.1.6
rackHandleSensorValueStrThe enum value label for the state reported by the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.17.1.7
rackHandleSensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.17.1.8
outputRelaySensorTableA list of output relay entries.
SEQUENCE OF OutputRelaySensorEntry
.1.3.6.1.4.1.52674.500.4.2.18
outputRelaySensorEntryOutput relay sensor entry.
OutputRelaySensorEntry
.1.3.6.1.4.1.52674.500.4.2.18.1
outputRelaySensorIdThe unique id of the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.18.1.1
outputRelaySensorValueWhether the relay is open or closed.ro
Enumeration
.1.3.6.1.4.1.52674.500.4.2.18.1.2
outputRelaySensorErrorStatusThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the sensor.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.4.2.18.1.3
outputRelaySensorLabelThe unique label assigned to the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.18.1.4
outputRelaySensorEncIdThe id of the physical enclosure containing the sensor.ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.18.1.5
outputRelaySensorPortIdThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.4.2.18.1.6
outputRelaySensorValueStrThe enum value label for the state reported by the sensor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.4.2.18.1.7
outputRelaySensorIndexThe index of the sensor.ro
Counter32
.1.3.6.1.4.1.52674.500.4.2.18.1.8
netBotzErrors
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.5
errorCondTableA list of active and resolved error conditions.
SEQUENCE OF ErrorCondEntry
.1.3.6.1.4.1.52674.500.5.1
errorCondEntryError condition entry.
ErrorCondEntry
.1.3.6.1.4.1.52674.500.5.1.1
errorCondIdThe unique id of the error condition.ro
DisplayString
.1.3.6.1.4.1.52674.500.5.1.1.1
errorCondSeverityThe relative severity of the error condition.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.5.1.1.2
errorCondTypeIdThe error type id reported for the error condition.ro
DisplayString
.1.3.6.1.4.1.52674.500.5.1.1.3
errorCondStartTimeThe start time of the error condition, in msec since 1/1/1970.ro
DateAndTime (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.5.1.1.4
errorCondStartTimeStrThe start time of the error condition, as ISO date-time formatted string (UTC).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.5.1.1.5
errorCondResolvedWhether the error condition was resolved.ro
BoolValue
.1.3.6.1.4.1.52674.500.5.1.1.6
errorCondResolvedTimeThe time the error condition was resolved (if it was resolved), in msec since 1/1/1970.ro
DateAndTime (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.5.1.1.7
errorCondResolvedTimeStrThe time the error condition was resolved (if it was resolved), as ISO date-time formatted string (UTC).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.5.1.1.8
errorCondEncIdThe id of the physical enclosure associated with the error.ro
DisplayString
.1.3.6.1.4.1.52674.500.5.1.1.9
errorCondPortIdThe id of the port associated with the error (or empty string if the error is not associated with a port).ro
DisplayString
.1.3.6.1.4.1.52674.500.5.1.1.10
errorCondSensorIdThe id of the sensor associated with the error (or empty string if the error is not associated with a sensor.)ro
DisplayString
.1.3.6.1.4.1.52674.500.5.1.1.11
errorCondIndexThe index of the error condition.ro
Counter32
.1.3.6.1.4.1.52674.500.5.1.1.12
netBotzCameras
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.6
cameraTableA list of configured camera's.
SEQUENCE OF CameraEntry
.1.3.6.1.4.1.52674.500.6.1
cameraEntryCamera entry.
CameraEntry
.1.3.6.1.4.1.52674.500.6.1.1
cameraIdThe id of the camera.ro
DisplayString
.1.3.6.1.4.1.52674.500.6.1.1.1
cameraVendorThe vendor of the camera.ro
DisplayString
.1.3.6.1.4.1.52674.500.6.1.1.2
cameraModelThe model of the camera.ro
DisplayString
.1.3.6.1.4.1.52674.500.6.1.1.3
cameraConnectionStatusThe operational status of the camera.ro
OperStatus
.1.3.6.1.4.1.52674.500.6.1.1.4
cameraErrorStatusThe error status of the camera. If there are no error conditions reported for the camera, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the camera.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.6.1.1.5
cameraLabelThe unique label assigned to the camera.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.6.1.1.6
cameraAddressThe address or host name of the camera.ro
DisplayString
.1.3.6.1.4.1.52674.500.6.1.1.7
cameraIndexThe index of the physical enclosure.ro
Counter32
.1.3.6.1.4.1.52674.500.6.1.1.8
netBotzFirmware
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.7
firmwareTableA list of firmware versions contained in the NetBotz distribution.
SEQUENCE OF FirmwareEntry
.1.3.6.1.4.1.52674.500.7.1
firmwareEntryFirmware entry.
FirmwareEntry
.1.3.6.1.4.1.52674.500.7.1.1
firmwareDescriptionName of of the firmware product.ro
DisplayString
.1.3.6.1.4.1.52674.500.7.1.1.1
firmwareVersionVersion of of the firmware product.ro
DisplayString
.1.3.6.1.4.1.52674.500.7.1.1.2
firmwareIndexThe index of the firmware.ro
Counter32
.1.3.6.1.4.1.52674.500.7.1.1.3
netBotzTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10
netBotzSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1
netBotzTempSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.1
netBotzTempSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.1.0
netBotzTempErrorTemperature sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.1.0.1
netBotzTempTooHighTemperature sensor value too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.1.0.2
netBotzTempTooLowTemperature sensor value too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.1.0.3
netBotzTempUnpluggedTemperature sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.1.0.6
netBotzTempErrorRTNTemperature sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.1.0.101
netBotzTempTooHighRTNTemperature sensor value is no longer too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.1.0.102
netBotzTempTooLowRTNTemperature sensor value is no longer too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.1.0.103
netBotzTempRepluggedTemperature sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.1.0.106
netBotzHumiditySensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.2
netBotzHumiditySensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.2.0
netBotzHumidityErrorHumidity sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.2.0.1
netBotzHumidityTooHighHumidity sensor value too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.2.0.2
netBotzHumidityTooLowHumidity sensor value too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.2.0.3
netBotzHumidityUnpluggedHumidity sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.2.0.6
netBotzHumidityErrorRTNHumidity sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.2.0.101
netBotzHumidityTooHighRTNHumidity sensor value is no longer too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.2.0.102
netBotzHumidityTooLowRTNHumidity sensor value is no longer too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.2.0.103
netBotzHumidityRepluggedHumidity sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.2.0.106
netBotzDewPointSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.3
netBotzDewPointSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.3.0
netBotzDewPointErrorDewPoint sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.3.0.1
netBotzDewPointTooHighDewPoint sensor value too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.3.0.2
netBotzDewPointTooLowDewPoint sensor value too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.3.0.3
netBotzDewPointUnpluggedDewPoint sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.3.0.6
netBotzDewPointErrorRTNDewPoint sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.3.0.101
netBotzDewPointTooHighRTNDewPoint sensor value is no longer too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.3.0.102
netBotzDewPointTooLowRTNDewPoint sensor value is no longer too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.3.0.103
netBotzDewPointRepluggedDewPoint sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.3.0.106
netBotzAirFlowSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.4
netBotzAirFlowSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.4.0
netBotzAirFlowErrorAirFlow sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.4.0.1
netBotzAirFlowTooHighAirFlow sensor value too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.4.0.2
netBotzAirFlowTooLowAirFlow sensor value too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.4.0.3
netBotzAirFlowUnpluggedAirFlow sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.4.0.6
netBotzAirFlowErrorRTNAirFlow sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.4.0.101
netBotzAirFlowTooHighRTNAirFlow sensor value is no longer too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.4.0.102
netBotzAirFlowTooLowRTNAirFlow sensor value is no longer too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.4.0.103
netBotzAirFlowRepluggedAirFlow sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.4.0.106
netBotzAmpDetectSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.5
netBotzAmpDetectSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.5.0
netBotzAmpDetectErrorAmp Detectsensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.5.0.1
netBotzAmpDetectTooHighAmp Detectsensor value too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.5.0.2
netBotzAmpDetectTooLowAmp Detectsensor value too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.5.0.3
netBotzAmpDetectUnpluggedAmp Detectsensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.5.0.6
netBotzAmpDetectErrorRTNAmp Detectsensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.5.0.101
netBotzAmpDetectTooHighRTNAmp Detectsensor value is no longer too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.5.0.102
netBotzAmpDetectTooLowRTNAmp Detectsensor value is no longer too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.5.0.103
netBotzAmpDetectRepluggedAmp Detectsensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.5.0.106
netBotzDryContactSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.6
netBotzDryContactSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.6.0
netBotzDryContactErrorDry Contact sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.6.0.1
netBotzDryContactUnpluggedDry Contact sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.6.0.6
netBotzDryContactValueErrorDry Contact sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.6.0.10
netBotzDryContactErrorRTNDry Contact sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.6.0.101
netBotzDryContactRepluggedDry Contact sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.6.0.106
netBotzDryContactValueErrorRTNDry Contact sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.6.0.110
netBotzCameraMotionSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.7
netBotzCameraMotionSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.7.0
netBotzCameraMotionSensorErrorCamera Motion Sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.7.0.1
netBotzCameraMotionSensorUnpluggedCamera Motion Sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.7.0.6
netBotzCameraMotionSensorValueErrorCamera Motion Sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.7.0.10
netBotzCameraMotionSensorErrorRTNCamera Motion Sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.7.0.101
netBotzCameraMotionSensorRepluggedCamera Motion Sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.7.0.106
netBotzCameraMotionSensorValueErrorRTNCamera Motion Sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.7.0.110
netBotzDoorSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.8
netBotzDoorSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.8.0
netBotzDoorSensorErrorDoor Sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.8.0.1
netBotzDoorSensorUnpluggedDoor Sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.8.0.6
netBotzDoorSensorValueErrorDoor Sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.8.0.10
netBotzDoorSensorErrorRTNDoor Sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.8.0.101
netBotzDoorSensorRepluggedDoor Sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.8.0.106
netBotzDoorSensorValueErrorRTNDoor Sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.8.0.110
netBotzWirelessStatusSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.9
netBotzWirelessStatusSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.9.0
netBotzWirelessStatusSensorErrorWireless Status Sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.9.0.1
netBotzWirelessStatusSensorUnpluggedWireless Status Sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.9.0.6
netBotzWirelessStatusSensorValueErrorWireless Status Sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.9.0.10
netBotzWirelessStatusSensorErrorRTNWireless Status Sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.9.0.101
netBotzWirelessStatusSensorRepluggedWireless Status Sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.9.0.106
netBotzWirelessStatusSensorValueErrorRTNWireless Status Sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.9.0.110
netBotzOutputControlSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.10
netBotzOutputControlSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.10.0
netBotzOutputControlSensorErrorOutput Control Sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.10.0.1
netBotzOutputControlSensorUnpluggedOutput Control Sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.10.0.6
netBotzOutputControlSensorValueErrorOutput Control Sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.10.0.10
netBotzOutputControlSensorErrorRTNOutput Control Sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.10.0.101
netBotzOutputControlSensorRepluggedOutput Control Sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.10.0.106
netBotzOutputControlSensorValueErrorRTNOutput Control Sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.10.0.110
netBotzLoopVoltageSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.11
netBotzLoopVoltageSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.11.0
netBotzLoopVoltageErrorLoop Voltage sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.11.0.1
netBotzLoopVoltageTooHighLoop Voltage sensor value too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.11.0.2
netBotzLoopVoltageTooLowLoop Voltage sensor value too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.11.0.3
netBotzLoopVoltageUnpluggedLoop Voltage sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.11.0.6
netBotzLoopVoltageErrorRTNLoop Voltage sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.11.0.101
netBotzLoopVoltageTooHighRTNLoop Voltage sensor value is no longer too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.11.0.102
netBotzLoopVoltageTooLowRTNLoop Voltage sensor value is no longer too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.11.0.103
netBotzLoopVoltageRepluggedLoop Voltage sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.11.0.106
netBotzSpotLeakSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.12
netBotzSpotLeakSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.12.0
netBotzSpotLeakSensorErrorSpot Leak sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.12.0.1
netBotzSpotLeakSensorUnpluggedSpot Leak Sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.12.0.6
netBotzSpotLeakSensorValueErrorSpot Leak sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.12.0.10
netBotzSpotLeakSensorErrorRTNSpot Leak sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.12.0.101
netBotzSpotLeakSensorRepluggedSpot Leak sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.12.0.106
netBotzSpotLeakSensorValueErrorRTNSpot Leak sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.12.0.110
netBotzRopeLeakSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.13
netBotzRopeLeakSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.13.0
netBotzRopeLeakSensorErrorRope Leak Sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.13.0.1
netBotzRopeLeakSensorUnpluggedRope Leak Sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.13.0.6
netBotzRopeLeakSensorValueErrorRope Leak Sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.13.0.10
netBotzRopeLeakSensorErrorRTNRope Leak Sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.13.0.101
netBotzRopeLeakSensorRepluggedRope Leak Sensor no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.13.0.106
netBotzRopeLeakSensorValueErrorRTNRope Leak Sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.13.0.110
netBotzRSSISensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.14
netBotzRSSISensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.14.0
netBotzRSSITooLowRSSI sensor value too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.14.0.3
netBotzRSSISensorValueErrorRSSI sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.14.0.10
netBotzRSSITooLowRTNRSSI sensor value is no longer too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.14.0.103
netBotzRSSISensorValueErrorRTNRSSI sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.14.0.110
netBotzBatterySensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.15
netBotzBatterySensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.15.0
netBotzBatterySensorErrorBattery sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.15.0.1
netBotzBatteryTooLowBattery sensor value too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.15.0.3
netBotzBatterySensorValueErrorBattery sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.15.0.10
netBotzBatterySensorErrorRTNBattery sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.15.0.101
netBotzBatteryTooLowRTNBattery sensor value is no longer too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.15.0.103
netBotzBatterySensorValueErrorRTNBattery sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.15.0.110
netBotzOutletSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.16
netBotzOutletSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.16.0
netBotzOutletSensorErrorOutlet sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.16.0.1
netBotzOutletSensorValueErrorOutlet sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.16.0.10
netBotzOutletSensorErrorRTNOutlet sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.16.0.101
netBotzOutletSensorValueErrorRTNOutlet sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.16.0.110
netBotzBeaconTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.17
netBotzBeaconPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.17.0
netBotzBeaconErrorBeacon error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.17.0.1
netBotzBeaconUnpluggedBeacon unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.17.0.6
netBotzBeaconValueErrorBeacon value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.17.0.10
netBotzBeaconErrorRTNBeacon error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.17.0.101
netBotzBeaconRepluggedBeacon no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.17.0.106
netBotzBeaconValueErrorRTNBeacon value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.17.0.110
netBotzSmokeSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.18
netBotzSmokeSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.18.0
netBotzSmokeSensorErrorSmoke sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.18.0.1
netBotzSmokeSensorUnpluggedSmoke sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.18.0.6
netBotzSmokeSensorValueErrorSmoke sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.18.0.10
netBotzSmokeSensorErrorRTNSmoke sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.18.0.101
netBotzSmokeSensorRepluggedSmoke sensor replugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.18.0.106
netBotzSmokeSensorValueErrorRTNSmoke sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.18.0.110
netBotzVibrationSensorTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.19
netBotzVibrationSensorPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.19.0
netBotzVibrationSensorErrorVibration sensor error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.19.0.1
netBotzVibrationSensorUnpluggedVibration sensor unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.19.0.6
netBotzVibrationSensorValueErrorVibration sensor value error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.19.0.10
netBotzVibrationSensorErrorRTNVibration sensor error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.19.0.101
netBotzVibrationSensorRepluggedVibration sensor replugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.19.0.106
netBotzVibrationSensorValueErrorRTNVibration sensor value error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.19.0.110
netBotzRackAccessTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.20
netBotzRackAccessPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.20.0
netBotzDoorSensorForcedEntryErrorDoor sensor forced entry detected. TrapErrorTypeLabel indicates rack access user label
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.10
netBotzRackHandleSensorOpenErrorRack handle sensor open error. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.11
netBotzCardReaderLocalAuthorizationErrorCard reader local authorization failure. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.12
netBotzCardReaderLdapAuthorizationErrorCard reader LDAP authorization failure. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.13
netBotzCardReaderUnpluggedCard reader unplugged. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.14
netBotzCardReaderRepluggedCard reader replugged. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.15
netBotzCardReaderErrorCard reader error. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.16
netBotzCardReaderErrorRTNCard reader error resolved. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.17
netBotzCardReaderValueErrorCard reader value error. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.18
netBotzCardReaderValueErrorRTNCard reader value error resolved. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.19
netBotzRackHandleSensorUnpluggedRack handle sensor unplugged. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.20
netBotzRackHandleSensorRepluggedRack handle sensor replugged. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.21
netBotzRackHandleSensorErrorRack handle sensor error. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.22
netBotzRackHandleSensorErrorRTNRack handle sensor error resolved. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.23
netBotzRackHandleSensorValueErrorRack handle sensor value error. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.24
netBotzRackHandleSensorValueErrorRTNRack handle sensor value error resolved. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.25
netBotzLockSensorUnpluggedLock sensor unplugged. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.26
netBotzLockSensorRepluggedLock sensor replugged. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.27
netBotzLockSensorErrorLock sensor error. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.28
netBotzLockSensorErrorRTNLock sensor error resolved. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.29
netBotzLockSensorValueErrorLock sensor value error. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.30
netBotzLockSensorValueErrorRTNLock sensor value error resolved. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.31
netBotzDoorSensorForcedEntryErrorRTNDoor sensor forced entry returned to normal. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.110
netBotzRackHandleSensorOpenErrorRTNRack handle sensor open returned to normal. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.111
netBotzCardReaderLocalAuthorizationErrorRTNCard reader local authorization succeeded. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.112
netBotzCardReaderLdapAuthorizationErrorRTNCard reader LDAP authorization succeeded. TrapErrorTypeLabel indicates rack access user label.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.20.0.113
netBotzTestTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.99
netBotzTestPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.1.99.0
netBotzTestNotificationDiagnostic Test Trap.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.1.99.0.1
netBotzPodTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.2
netBotzPodPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.2.0
netBotzPodUnpluggedPod unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.0.7
netBotzLogonErrorMultiple failed logon attempts.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.0.11
netBotzRmtLinkErrorConfigured remote link has failed.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.0.13
netBotzPodRepluggedPod no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.0.107
netBotzLogonErrorResolvedFailed logon attempts stopped, or logon succeeded.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.0.111
netBotzRmtLinkErrorResolvedConfigured remote link has returned to normal.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.0.113
netBotzSensorPodTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.2.1
netBotzSensorPodPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.2.1.0
netBotzSensorPodUnpluggedSensor Pod unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.1.0.7
netBotzSensorPodRepluggedSensor Pod no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.1.0.107
netBotzCameraTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.2.2
netBotzCameraPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.2.2.0
netBotzCameraUnpluggedCamera Pod unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.2.0.7
netBotzCameraRepluggedCamera Pod no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.2.0.107
netBotz4to20mAPodTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.2.3
netBotz4to20mAPodPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.2.3.0
netBotzFourToTwentymAPodError4-20mA Pod error.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.3.0.1
netBotzFourToTwentymAPodTooHigh4-20mA Pod value too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.3.0.3
netBotzFourToTwentymAPodUnplugged4-20mA Pod unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.3.0.7
netBotzFourToTwentymAPodTooLow4-20mA Pod value too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.3.0.10
netBotzFourToTwentymAPodErrorRTN4-20mA Pod error resolved.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.3.0.101
netBotzFourToTwentymAPodTooHighRTN4-20mA Pod value is no longer too high.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.3.0.103
netBotzFourToTwentymAPodReplugged4-20mA Pod no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.3.0.107
netBotzFourToTwentymAPodTooLowRTN4-20mA Pod value is no longer too low.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.2.3.0.110
netBotzRpduTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.3
netBotzRpduPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.3.0
netBotzRpduUnpluggedRPDU unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.3.0.101
netBotzRpduRepluggedRPDU no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.3.0.102
netBotzUpsTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.4
netBotzUpsPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.4.0
netBotzUpsUnpluggedUPS unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.4.0.103
netBotzUpsRepluggedUPS no longer unplugged.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.4.0.104
netBotzGenericTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.5
netBotzGenericPrefix
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.10.5.0
netBotzGenericNotificationGeneric Trap.
NOTIFICATION-TYPE
.1.3.6.1.4.1.52674.500.10.5.0.1
netBotzTrapParms
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.11
netBotzTrapErrorIDUnique ID of error condition that produced the trapro
DisplayString
.1.3.6.1.4.1.52674.500.11.1
netBotzTrapErrorTypeSymbolic ID of error typero
DisplayString
.1.3.6.1.4.1.52674.500.11.2
netBotzTrapErrorTypeLabelLabel for error typero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.11.3
netBotzTrapSensorIDID of sensor associated with error condition that produced the trapro
DisplayString
.1.3.6.1.4.1.52674.500.11.4
netBotzTrapSensorLabelLabel of sensor associated with error condition that produced the trapro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.11.5
netBotzTrapContainerIDID of container associated with error condition that produced the trapro
DisplayString
.1.3.6.1.4.1.52674.500.11.6
netBotzTrapContainerLabelLabel of container associated with error condition that produced the trapro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.11.7
netBotzTrapPortIDID of port associated with error condition that produced the trapro
DisplayString
.1.3.6.1.4.1.52674.500.11.8
netBotzTrapPortLabelLabel of port associated with error condition that produced the trapro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.11.9
netBotzTrapStartTimeStart time (in UTC seconds) for error that produced the trapro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.11.10
netBotzTrapNotifyTimeNotification time (in UTC seconds) for error that produced the trapro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.11.11
netBotzTrapResolveTimeResolve time (in UTC seconds) for error that produced the trapro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.11.12
netBotzTrapSeveritySeverity of error that produced the trapro
Enumeration
.1.3.6.1.4.1.52674.500.11.13
netBotzTrapSensorValueString presentation of value of sensorro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.11.14
netBotzTrapSensorValueIntWhole integer representation of value of sensor (without decimal portion)ro
Integer32
.1.3.6.1.4.1.52674.500.11.15
netBotzTrapSensorValueFractionFractional portion of value of sensor (multiplied by 1000000)ro
Integer32
.1.3.6.1.4.1.52674.500.11.16
netBotzTrapDataGeneral Purpose Test Trap Data String Fieldro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.52674.500.11.17
netBotzProducts
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.20
netBotzBotz
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.20.10
netBotz750Rack
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.20.10.3000
netBotz755Wall
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.20.10.3001
netbotzBotzGroups
OBJECT IDENTIFIER
.1.3.6.1.4.1.52674.500.30
netbotzObjectGroupA collection of netbotz stuff
Unknown
.1.3.6.1.4.1.52674.500.30.1
netbotzNotificationGroupA collection of netbotz stuff
Unknown
.1.3.6.1.4.1.52674.500.30.2
netBotzErrorStatusThe error status of the appliance. If there are no error conditions reported for the appliance, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is not resolved for the appliance.ro
ErrorStatus
.1.3.6.1.4.1.52674.500.100
NetBotz50-MIB - SNMP MIB Reference | MIBs Explorer