MIB

AI MIB Summary

The SmartZone G5 iPDU MIB enables SNMP-based monitoring and management of Eaton SmartZone G5 Intelligent Power Distribution Units, providing access to real-time power metrics including voltage, current, power consumption, outlet status, and environmental sensor data.

SmartZone G5 iPDU
Main OID:
g5.1.3.6.1.4.1.19536.10
297
Objects
Active
Status
5
Dependencies

Imported Objects

Objects

297 total
Object Name
panduit
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536
g5SmartZone G5 iPDU
MODULE-IDENTITY
.1.3.6.1.4.1.19536.10
SNMPv2-CONFSmartZone G5 iPDU
NOTIFICATION-TYPE
.1.3.6.1.4.1.19536.10
pdug5
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1
pdug5Ident
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.1
pdug5NumberPDUThe number of PDUs detected (in its daisy chain).ro
Integer32
.1.3.6.1.4.1.19536.10.1.1.1
pdug5IdentTableAggregate Object with number of entries equal to pdug5NumberPDU .
SEQUENCE OF Pdug5IdentEntry
.1.3.6.1.4.1.19536.10.1.1.2
pdug5IdentEntryThe Identity table entry containing the name, model, manufacturer, firmware version, part number, etc.
Pdug5IdentEntry
.1.3.6.1.4.1.19536.10.1.1.2.1
pdug5IdentIndexIndex for the pdug5IdentEntry table.
Integer32
.1.3.6.1.4.1.19536.10.1.1.2.1.1
pdug5NameThe string identify the device in daisy chain. Example PDU A.rw
DisplayString
.1.3.6.1.4.1.19536.10.1.1.2.1.2
pdug5ModelThe Device Model.ro
DisplayString
.1.3.6.1.4.1.19536.10.1.1.2.1.3
pdug5ManufacturerThe Device Manufacturer Name.ro
DisplayString
.1.3.6.1.4.1.19536.10.1.1.2.1.4
pdug5FirmwareVersionThe firmware revision level of the device.ro
DisplayString
.1.3.6.1.4.1.19536.10.1.1.2.1.5
pdug5FirmwareVersionTimeStampTimestamp of when the PDU firmware was last updatedro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.1.2.1.6
pdug5PartNumberThe device part number. Example P36E09M.ro
DisplayString
.1.3.6.1.4.1.19536.10.1.1.2.1.7
pdug5SerialNumberThe device serial number, 10-digit.ro
DisplayString
.1.3.6.1.4.1.19536.10.1.1.2.1.8
pdug5StatusThe overall status of the device. A value of OK(2) indicates the device is operating normally. A value of degraded(3) indicates the device is operating with warning indicators. A value of failed(4) indicates the device is operating with critical indicators.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.1.2.1.9
pdug5ControllableThis object indicates whether or not the device is controllable.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.1.2.1.10
pdug5InputPhaseCountThe number of input phase on this pdu 1 or 3.ro
Integer32
.1.3.6.1.4.1.19536.10.1.1.2.1.11
pdug5GroupCountThe number of groups (breakers) on this pdu.ro
Integer32
.1.3.6.1.4.1.19536.10.1.1.2.1.12
pdug5OutletCountThe number of outlets in this PDU.ro
Integer32
.1.3.6.1.4.1.19536.10.1.1.2.1.13
pdug5MACAddressThe assigned MAC address for this PDU.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.1.2.1.14
pdug5IPv4AddressThe current IPv4 Address. A value of 0.0.0.0 indicates an error or an unset option.ro
IpAddress
.1.3.6.1.4.1.19536.10.1.1.2.1.15
pdug5IPv6AddressThe current IPv6 Address. A value of 0.0.0.0.0.0 indicates an error or an unset option.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.1.2.1.16
pdug5HWVersionThe current Hardware Version. 1.0 - G5 (STM) No Powershare, 1.5 - G5 (STM) with Powershare, 2.0 - G6 Processorro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.1.2.1.17
pdug5ConfigTableAggregate Object with number of entries equal to pdug5NumberPDU.
SEQUENCE OF Pdug5ConfigEntry
.1.3.6.1.4.1.19536.10.1.1.3
pdug5ConfigEntryRead Configuration data from the PDU being queried.
Pdug5ConfigEntry
.1.3.6.1.4.1.19536.10.1.1.3.1
pdug5ConfigIndexThe index of PDU configuration entry.
Integer32
.1.3.6.1.4.1.19536.10.1.1.3.1.1
pdug5ConfigSshSetting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection. iNC reboot will be required for the settings to take effect.rw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.3.1.2
pdug5ConfigFtpsSetting this OID to off(0) will disable the FTPS connection. Setting this OID to on(1) will enable the FTPS connection. iNC reboot will be required for the settings to take effectrw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.3.1.3
pdug5ConfigHttpSetting this OID to off(0) will disable the HTTP connection. Setting this OID to on(1) will enable the HTTP connection.iNC reboot will be required for the settings to take effectrw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.3.1.4
pdug5ConfigHttpsSetting this OID to off(0) will disable the HTTPS connection. Setting this OID to on(1) will enable the HTTPS connection.iNC reboot will be required for the settings to take effectrw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.3.1.5
pdug5ConfigIPv4IPv6SwitchSetting this OID to IPv4(1) will enable the IPv4 configuration. Setting this OID to IPv6(2) will enable the IPv6 configuration. Setting this OID to IPv4&IPv6(3) will enable both IPv4 and IPv6 configuration.iNC reboot will be required for the settings to take effectrw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.3.1.6
pdug5ConfigRedfishAPISetting this OID to off(0) will disable the Redfish API. Setting this OID to on(1) will enable the Redfish API.iNC reboot will be required for the settings to take effectrw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.3.1.7
pdug5ConfigOledDispalyOrientationIndicates the intended physical orientation of OLED display. displayNormal(1) indicates normal orientation. displayReverse(2) indicates upside down orientation.rw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.3.1.8
pdug5ConfigEnergyResetSetting this OID to reset(2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not supported this feature will respond to this OID with a value of notSupported(3). Attempts to set this OID in these models will fail.rw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.3.1.9
pdug5ConfigNetworkManagementCardResetGetting this OID will return noOperation(0). Getting this OID to reset(1) will reset iNC.rw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.3.1.10
pdug5ConfigDaisyChainStatusSetting this OID will change daisychain mode. 0:QNA,1:DNA.rw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.3.1.11
pdug5PowershareTableAggregate Object with number of entries equal to number of PDUs and Power share
SEQUENCE OF Pdug5PowershareEntry
.1.3.6.1.4.1.19536.10.1.1.4
pdug5PowershareEntryThe Power share entry containing the available, input, output etc.
Pdug5PowershareEntry
.1.3.6.1.4.1.19536.10.1.1.4.1
pdug5PowershareIndexThe index of the PDU Power share table entry
Integer32
.1.3.6.1.4.1.19536.10.1.1.4.1.1
pdug5PowershareFunctionStatusPower share function status on PDU.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.1.4.1.2
pdug5PowershareFunctionUpstreamStatusPower share function status on upstream PDUro
Enumeration
.1.3.6.1.4.1.19536.10.1.1.4.1.3
pdug5PowershareOutputPower share output status.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.1.4.1.4
pdug5PowershareInputPower share input status.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.1.4.1.5
pdug5PowershareOptModePower share operation status of PDU. 0 meaning pdu is using powershare to power the NMC, 1 meaning pdu is using mains power to power the NMCro
Enumeration
.1.3.6.1.4.1.19536.10.1.1.4.1.6
pdug5PowershareFuncEnable/Disable Powershare function of PDU. Set 1 to enable powershare. Set 0 to disable powersharerw
Enumeration
.1.3.6.1.4.1.19536.10.1.1.4.1.7
pdug5Input
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.2
pdug5InputTableAggregate Object with number of entries equal to pdug5NumberPDU .
SEQUENCE OF Pdug5InputEntry
.1.3.6.1.4.1.19536.10.1.2.1
pdug5InputEntryThe ident table entry containing the VA, Watts, WH, etc.
Pdug5InputEntry
.1.3.6.1.4.1.19536.10.1.2.1.1
pdug5InputTypeType of input - single phase, split phase, three phase delta, or three phase wye.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.1.1.1
pdug5InputFrequencyThe measured input frequency from the PDU meters in tenths of Hz.ro
Integer32
.1.3.6.1.4.1.19536.10.1.2.1.1.2
pdug5InputFrequencyStatusStatus of the measured input frequency relative to the nominal frequency and the admitted tolerance.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.1.1.3
pdug5InputPowerVAA total input VA of all phases. Units are VA. A negative value indicates that this object is not available.ro
Integer32 -- Units in VA
.1.3.6.1.4.1.19536.10.1.2.1.1.4
pdug5InputPowerWattsA total input Watts of all phases. Units are Watts. A negative value indicates that this object is not available.ro
Integer32 -- Units in Watts
.1.3.6.1.4.1.19536.10.1.2.1.1.5
pdug5InputTotalEnergyA total input Watt-Hour value for all phases. Units are KWh. This value is accumulated since PDU in service. A negative value indicates that this object is not available.ro
Integer32 -- Units in KWh
.1.3.6.1.4.1.19536.10.1.2.1.1.6
pdug5InputPowerWattHourTimerA Timestamp of when the Total Input WH was last reset.ro
DisplayString
.1.3.6.1.4.1.19536.10.1.2.1.1.7
pdug5InputResettableEnergyA total input Watt-Hour value for all phases. Units are Wh. This value can be reset to 0 using GUI. In that case, the pdug5InputPowerWattHourTimer will be reset as well A negative value indicates that this object is not available.ro
Integer32 -- Units in Wh
.1.3.6.1.4.1.19536.10.1.2.1.1.8
pdug5InputPowerFactorAn input PF value. Units are in hundredths, for example a power factor of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available.ro
Integer32 -- Units 0.01
.1.3.6.1.4.1.19536.10.1.2.1.1.9
pdug5InputPowerVARAn input VAR value. Units are VAR. A negative value indicates that this object is not available.ro
Integer32 -- Units in VAR
.1.3.6.1.4.1.19536.10.1.2.1.1.10
pdug5InputTotalCurrentAll phases total current value. Units are 0.01 amps. For 3 phase, mathematically add totally 3 phase current together.ro
Integer32 -- Units are 0.01 A
.1.3.6.1.4.1.19536.10.1.2.1.1.11
pdug5InputPhaseTableAggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and number of input phase (pdug5InputPhaseCount).
SEQUENCE OF Pdug5InputPhaseEntry
.1.3.6.1.4.1.19536.10.1.2.2
pdug5InputPhaseEntryThe input table entry containing the voltage, current, frequency, power for each phase. Entries are given with number of pdu and number of input phase 1, 2, or 3.
Pdug5InputPhaseEntry
.1.3.6.1.4.1.19536.10.1.2.2.1
pdug5InputPhaseIndexIndex for the pdug5InputEntry table.
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.1
pdug5InputPhaseVoltageMeasTypeValue indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.2.1.2
pdug5InputPhaseVoltageAn input voltage measurement value. Values is in 0.1 V.ro
Integer32 -- UNITS RMS 0.1 V
.1.3.6.1.4.1.19536.10.1.2.2.1.3
pdug5InputPhaseVoltageThStatusStatus of the measured input voltage relative to the configured thresholds.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.2.1.4
pdug5InputPhaseVoltageThLowerWarningLower warning threshold. Units are 0.1 volts. A negative value indicates that this object is not available.rw
Integer32 (-1..500000) -- Units in 0.1 V
.1.3.6.1.4.1.19536.10.1.2.2.1.5
pdug5InputPhaseVoltageThLowerCriticalLower critical threshold. Units are 0.1 volts. A negative value indicates that this object is not available.rw
Integer32 (-1..500000) -- Units in 0.1 V
.1.3.6.1.4.1.19536.10.1.2.2.1.6
pdug5InputPhaseVoltageThUpperWarningUpper warning threshold. Units are 0.1 volts. A negative value indicates that this object is not available.rw
Integer32 (-1..500000) -- Units in 0.1 V
.1.3.6.1.4.1.19536.10.1.2.2.1.7
pdug5InputPhaseVoltageThUpperCriticalUpper critical threshold. Units are 0.1 volts. A negative value indicates that this object is not available.rw
Integer32 (-1..500000) -- Units in 0.1 V
.1.3.6.1.4.1.19536.10.1.2.2.1.8
pdug5InputPhaseCurrentMeasTypeWhich input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.2.1.9
pdug5InputPhaseCurrentRatingRated current capacity of the input. A negative value indicates that the hardware current capacity is unknown. Units are 0.01 amps.ro
Integer32 -- Units in 0.01 A
.1.3.6.1.4.1.19536.10.1.2.2.1.10
pdug5InputPhaseCurrentAn input current measurement value. Units are 0.01 amps.ro
Integer32 -- Units in 0.01 A
.1.3.6.1.4.1.19536.10.1.2.2.1.11
pdug5InputPhaseCurrentThStatusStatus of the measured input current relative to the configured thresholds.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.2.1.12
pdug5InputPhaseCurrentThLowerWarningLower warning threshold. Units are 0.01 amps. A negative value indicates that this object is not available.rw
Integer32 (-1..100000) -- Units in 0.01 A
.1.3.6.1.4.1.19536.10.1.2.2.1.13
pdug5InputPhaseCurrentThLowerCriticalLower critical threshold. Units are 0.01 amps. A negative value indicates that this object is not available.rw
Integer32 (-1..100000) -- Units in 0.01 A
.1.3.6.1.4.1.19536.10.1.2.2.1.14
pdug5InputPhaseCurrentThUpperWarningUpper warning threshold. Units are 0.01 amps. A negative value indicates that this object is not available.rw
Integer32 (-1..100000) -- Units in 0.01 A
.1.3.6.1.4.1.19536.10.1.2.2.1.15
pdug5InputPhaseCurrentThUpperCriticalUpper critical threshold. Units are 0.01 amps. A negative value indicates that this object is not available.rw
Integer32 (-1..100000) -- Units in 0.01 A
.1.3.6.1.4.1.19536.10.1.2.2.1.16
pdug5InputPhaseCurrentPercentLoadCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available.ro
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.17
pdug5InputPhasePowerMeasTypeWhich input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.2.1.18
pdug5InputPhasePowerVAAn input VA value. Units are VA. A negative value indicates that this object is not available.ro
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.19
pdug5InputPhasePowerWattsAn input Watts value. Units are Watts. A negative value indicates that this object is not available.ro
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.20
pdug5InputPhasePowerWattHourA Watt-Hour value for each Input phase. Units are WH. This value can be reset to 0 using GUI. In that case, the pdug5InputPhasePowerWattHourTimer will be reset as well A negative value indicates that this object is not available.ro
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.21
pdug5InputPhasePowerWattHourTimerTimestamp of when input Watt-hours (inputWh) was last reset.ro
DisplayString
.1.3.6.1.4.1.19536.10.1.2.2.1.22
pdug5InputPhasePowerFactorAn input PF value. Units are in hundredths, for example a power factor of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available.ro
Integer32 -- Units 0.01
.1.3.6.1.4.1.19536.10.1.2.2.1.23
pdug5InputPhasePowerVARAn input VAR value. Units are VAR. A negative value indicates that this object is not available.ro
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.24
pdug5InputPhaseVoltageThResetThldThe Reset threshold is the number of volts the reading needs to fall below the threshold setting for the condition to be cleared. Units are 0.1 volts.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.25
pdug5InputPhaseVoltageThChangeDelayThe number of consecutive sample that the condition is present before an alarm is raised.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.26
pdug5InputPhaseVoltageThCtrlInput phase voltage alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disablerw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.27
pdug5InputPhaseCurrentThResetThldThe Reset threshold is the number of amps the reading needs to fall below the threshold setting for the condition to be cleared. Units are 0.01 amps.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.28
pdug5InputPhaseCurrentThChangeDelayThe number of consecutive sample that the condition is present before an alarm is raised.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.29
pdug5InputPhaseCurrentThCtrlInput phase current alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disablerw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.30
pdug5InputPowerThresholdThLowerWarningLower warning Power threshold. Units are in Watts. A negative value indicates that this object is not available.rw
Integer32 (-1..500000) -- Units in W
.1.3.6.1.4.1.19536.10.1.2.2.1.31
pdug5InputPowerThresholdThLowerCriticalLower critical Power threshold. Units are in Watts. A negative value indicates that this object is not available.rw
Integer32 (-1..500000) -- Units in W
.1.3.6.1.4.1.19536.10.1.2.2.1.32
pdug5InputPowerThresholdThUpperWarningUpper warning Power threshold. Units are in Watts. A negative value indicates that this object is not available.rw
Integer32 (-1..500000) -- Units in W
.1.3.6.1.4.1.19536.10.1.2.2.1.33
pdug5InputPowerThresholdThUpperCriticalUpper critical Power threshold. Units are in Watts. A negative value indicates that this object is not available.rw
Integer32 (-1..500000) -- Units in W
.1.3.6.1.4.1.19536.10.1.2.2.1.34
pdug5InputPowerThresholdThResetThldThe Reset threshold is the number of watts the reading needs to fall below the threshold setting for the condition to be cleared. Units are watts.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.35
pdug5InputPowerThresholdThChangeDelayThe number of consecutive sample that the condition is present before an alarm is raised.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.36
pdug5InputPowerThresholdThCtrlPower alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disablerw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.37
pdug5InputEnergyThresholdThUpperWarningUpper warning Energy threshold. Units are in Watts. A negative value indicates that this object is not available.rw
Integer32 (-1..500000) -- Units in W
.1.3.6.1.4.1.19536.10.1.2.2.1.38
pdug5InputEnergyThresholdThUpperCriticalUpper critical Energy threshold. Units are in Watts. A negative value indicates that this object is not available.rw
Integer32 (-1..500000) -- Units in W
.1.3.6.1.4.1.19536.10.1.2.2.1.39
pdug5InputEnergyThresholdThResetThldThe Reset threshold is the number of watts the reading needs to fall below the threshold setting for the condition to be cleared. Units are watts.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.40
pdug5InputEnergyThresholdThChangeDelayThe number of consecutive sample that the condition is present before an alarm is raised.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.41
pdug5InputEnergyThresholdThCtrlEnergy alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disablerw
Integer32
.1.3.6.1.4.1.19536.10.1.2.2.1.42
pdug5InputPhasePowerThStatusStatus of the measured input current relative to the configured thresholds.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.2.1.43
pdug5InputRcmTableAggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and number of RCM modules per PDU.
SEQUENCE OF Pdug5InputRcmEntry
.1.3.6.1.4.1.19536.10.1.2.3
pdug5InputRcmEntryThe ident table entry containing the RCM Module status, RCM current, RCM module threshold settings, etc.
Pdug5InputRcmEntry
.1.3.6.1.4.1.19536.10.1.2.3.1
pdug5InputRcmEnabledRCM configuration value off(0) if the PDU doesn't have RCM, on(1) if the PDU has RCM.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.3.1.1
pdug5InputRcmModStatusRCM module status ok(2) if the PDU can communicate with the RCM module, failed(4) if the PDU cannot communicate with the RCM module, degraded(3) if the PDU can communicate with the RCM module and the last self-test failed.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.3.1.2
pdug5InputRcmThUpperWarningRCM Current Upper warning threshold. Units are 0.01 amps. A negative value indicates that this object is not available.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.3.1.3
pdug5InputRcmThUpperCriticalRCM Current Upper critical threshold. Units are 0.01 amps. A negative value indicates that this object is not available.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.3.1.4
pdug5InputRcmThResetThldThe Reset threshold is the number of amps the reading needs to fall below the threshold setting for the condition to be cleared. Units are 0.01 amps.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.3.1.5
pdug5InputRcmThChangeDelayThe number of consecutive sample that the condition is present before an alarm is raised.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.3.1.6
pdug5InputRcmThCtrlRcm current alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable.rw
Integer32
.1.3.6.1.4.1.19536.10.1.2.3.1.7
pdug5InputRcmThStatusStatus of the measured Rcm current relative to the configured thresholds.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.3.1.8
pdug5InputRcmCurrentRcm module current reading. Units are milliAmps.ro
Integer32 -- Units 0.01
.1.3.6.1.4.1.19536.10.1.2.3.1.9
pdug5InputRcmSelfTestTableAggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and number of Rcm modules per PDU.
SEQUENCE OF Pdug5InputRcmSelfTestEntry
.1.3.6.1.4.1.19536.10.1.2.4
pdug5InputRcmSelfTestEntryThe ident table entry containing the Rcm Module Self Test Enable, Schedule, LastRunTime,LastRunStatus etc.
Pdug5InputRcmSelfTestEntry
.1.3.6.1.4.1.19536.10.1.2.4.1
pdug5InputRcmSelfTestEnableRcm Self Test configuration value Disable(0) if the self test is disabled on the PDU, Enable(1) if self test is enabled on the PDU .rw
Enumeration
.1.3.6.1.4.1.19536.10.1.2.4.1.1
pdug5InputRcmSelfTestFreqRcm module self test run frequency , the time for the test is set from Pdug5RcmSelfTestNextRunTime, the self test will be repeated based on the setting as Daily(1),Weekly(2),First Day Of Month(3),Yearly(4)rw
Enumeration
.1.3.6.1.4.1.19536.10.1.2.4.1.2
pdug5InputRcmSelfTestHourRcm module self test schedule hour setting,-1 means feature not availablerw
Integer32 (-1..23)
.1.3.6.1.4.1.19536.10.1.2.4.1.3
pdug5InputRcmSelfTestMinuteRcm module self test schedule minute setting,-1 means feature not availablerw
Integer32 (-1..59)
.1.3.6.1.4.1.19536.10.1.2.4.1.4
pdug5InputRcmSelfTestDayRcm module self test schedule day setting,-1 means feature not availablerw
Enumeration
.1.3.6.1.4.1.19536.10.1.2.4.1.5
pdug5InputRcmSelfTestMonthRcm module self test schedule month setting,-1 means feature not availablerw
Enumeration
.1.3.6.1.4.1.19536.10.1.2.4.1.6
pdug5InputRcmSelfTestNextRunTimenext run date and Time for self test.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.2.4.1.7
pdug5InputRcmSelfTestLastRunTimeDate and Time when the self test run previouslyro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.2.4.1.8
pdug5InputRcmSelfTestLastRunStatusStatus of the lastest self test runro
Enumeration
.1.3.6.1.4.1.19536.10.1.2.4.1.9
pdug5Group
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.3
pdug5GroupTableAggregate Object with number of entries equal to number of PDUs and number of breakers (pdug5GroupCount).
SEQUENCE OF Pdug5GroupEntry
.1.3.6.1.4.1.19536.10.1.3.1
pdug5GroupEntryThe input table entry containing the name, voltages, currents, power, etc.
Pdug5GroupEntry
.1.3.6.1.4.1.19536.10.1.3.1.1
pdug5GroupIndexIndex for the pdug5GroupEntry table.
Integer32
.1.3.6.1.4.1.19536.10.1.3.1.1.1
pdug5GroupNameA descriptive name for the group.rw
DisplayString
.1.3.6.1.4.1.19536.10.1.3.1.1.2
pdug5GroupTypeThe type of the group. (5) has no breakerro
Enumeration
.1.3.6.1.4.1.19536.10.1.3.1.1.3
pdug5GroupVoltageMeasTypeValue indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.3.1.1.4
pdug5GroupVoltageUnits are 0.1 volts.ro
Integer32 -- Units 0.1 V
.1.3.6.1.4.1.19536.10.1.3.1.1.5
pdug5GroupVoltageThStatusStatus of the measured group voltage relative to the configured thresholds.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.3.1.1.6
pdug5GroupVoltageThLowerWarningLower warning threshold. Units are 0.1 volts. A negative value indicates that this object is not available.ro
Integer32 (-1..500000) -- Units 0.1 V
.1.3.6.1.4.1.19536.10.1.3.1.1.7
pdug5GroupVoltageThLowerCriticalLower critical threshold. Units are 0.1 volts. A negative value indicates that this object is not available.ro
Integer32 (-1..500000) -- Units 0.1 V
.1.3.6.1.4.1.19536.10.1.3.1.1.8
pdug5GroupVoltageThUpperWarningUpper warning threshold. Units are 0.1 volts. A negative value indicates that this object is not available.ro
Integer32 (-1..500000) -- Units 0.1 V
.1.3.6.1.4.1.19536.10.1.3.1.1.9
pdug5GroupVoltageThUpperCriticalUpper critical threshold. Units are 0.1 volts. A negative value indicates that this object is not available.ro
Integer32 (-1..500000) -- Units 0.1 V
.1.3.6.1.4.1.19536.10.1.3.1.1.10
pdug5groupCurrentRatingRated current capacity of the group. Units are 0.01 amps. A negative value indicates that the hardware current capacity is unknown (it will always be unknown for custom groups).ro
Integer32 -- Units 0.01 A
.1.3.6.1.4.1.19536.10.1.3.1.1.11
pdug5GroupCurrentA group current measurement value. Units are 0.01 amps.ro
Integer32 -- Units 0.01 A
.1.3.6.1.4.1.19536.10.1.3.1.1.12
pdug5GroupCurrentThStatusStatus of the measured group current relative to the configured thresholds.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.3.1.1.13
pdug5GroupCurrentThLowerWarningLower warning threshold. Units are 0.01 amps. A negative value indicates that this object is not available.rw
Integer32 (-1..100000) -- Units 0.01 A
.1.3.6.1.4.1.19536.10.1.3.1.1.14
pdug5GroupCurrentThLowerCriticalLower critical threshold. Units are 0.01 amps. A negative value indicates that this object is not available.rw
Integer32 (-1..100000) -- Units 0.01 A
.1.3.6.1.4.1.19536.10.1.3.1.1.15
pdug5GroupCurrentThUpperWarningUpper warning threshold. Units are 0.01 amps. A negative value indicates that this object is not available.rw
Integer32 (-1..100000) -- Units 0.01 A
.1.3.6.1.4.1.19536.10.1.3.1.1.16
pdug5GroupCurrentThUpperCriticalUpper critical threshold. Units are 0.01 amps. A negative value indicates that this object is not available.rw
Integer32 (-1..100000) -- Units 0.01 A
.1.3.6.1.4.1.19536.10.1.3.1.1.17
pdug5GroupCurrentPercentLoadCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available.ro
Integer32
.1.3.6.1.4.1.19536.10.1.3.1.1.18
pdug5GroupPowerVAA group VA value. Units are VA. A negative value indicates that this object is not available.ro
Integer32 -- Units in VA
.1.3.6.1.4.1.19536.10.1.3.1.1.19
pdug5GroupPowerWattsA group power value. Units are Watts. A negative value indicates that this object is not available.ro
Integer32 -- Units in Watt
.1.3.6.1.4.1.19536.10.1.3.1.1.20
pdug5GroupPowerWattHourA Watt-Hour value for each section. Units are WH. This value can be reset to 0 using GUI. In that case, the pdug5GroupPowerWattHourTimer will be reset as well. A negative value indicates that this object is not available.ro
Integer32 -- Units in Watt-Hour
.1.3.6.1.4.1.19536.10.1.3.1.1.21
pdug5GroupPowerWattHourTimerTimestamp of when group Watt-hours (groupWh) was last reset.ro
DisplayString
.1.3.6.1.4.1.19536.10.1.3.1.1.22
pdug5GroupPowerFactorA group PF value. Units are in hundredths, for example a power factor of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available.ro
Integer32 -- Value is in 0.01
.1.3.6.1.4.1.19536.10.1.3.1.1.23
pdug5GroupPowerVARA group VAR value. Units are VAR. A negative value indicates that this object is not available.ro
Integer32 -- Units in VAR
.1.3.6.1.4.1.19536.10.1.3.1.1.24
pdug5GroupOutletCountThe number of outlets in each group (breaker).ro
Integer32
.1.3.6.1.4.1.19536.10.1.3.1.1.25
pdug5GroupBreakerStatusOnly applicable to groups with breaker. Indicates whether a breaker is turned off or on.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.3.1.1.26
pdug5GroupVoltageThCtrlCircuit Breaker voltage alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disablero
Integer32
.1.3.6.1.4.1.19536.10.1.3.1.1.27
pdug5GroupCurrentThCtrlCircuit Breaker current alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disablerw
Integer32
.1.3.6.1.4.1.19536.10.1.3.1.1.28
pdug5Environment
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.4
pdug5EnvProbeTableA list of environment probe (1 per PDU) for temperature, humidity, and contacts. The number of entries is given by number of PDUs in daisy chain.
SEQUENCE OF Pdug5EnvProbeEntry
.1.3.6.1.4.1.19536.10.1.4.1
pdug5EnvProbeEntryAggregate entries equal to number of PDUs.
Pdug5EnvProbeEntry
.1.3.6.1.4.1.19536.10.1.4.1.1
pdug5TemperatureScaleScale used to return temperature objects.rw
Enumeration
.1.3.6.1.4.1.19536.10.1.4.1.1.1
pdug5TemperatureCountThe number of temperature measurements.The MAX is 6 (1 per probe).ro
Integer32
.1.3.6.1.4.1.19536.10.1.4.1.1.2
pdug5HumidityCountThe number of humidity measurements.The MAX is 6(1 per probe).ro
Integer32
.1.3.6.1.4.1.19536.10.1.4.1.1.3
pdug5DoorCountThe number of door sensors.The MAX is 6(1 per probe).ro
Integer32
.1.3.6.1.4.1.19536.10.1.4.1.1.4
pdug5DryCountThe number of dry sensors.The MAX is 2(1 per probe).ro
Integer32
.1.3.6.1.4.1.19536.10.1.4.1.1.5
pdug5SpotCountThe number of spot sensors.The MAX is 2(1 per probe).ro
Integer32
.1.3.6.1.4.1.19536.10.1.4.1.1.6
pdug5RopeCountThe number of rope sensors.The MAX is 2(1 per probe).ro
Integer32
.1.3.6.1.4.1.19536.10.1.4.1.1.7
pdug5HidCountThe number of hid sensors. The MAX is 2(1 per probe).ro
Integer32
.1.3.6.1.4.1.19536.10.1.4.1.1.10
pdug5TemperatureTableA list of temperature probe measurements. The number of entries are given by number of pdu and pdug5TemperatureCount.
SEQUENCE OF Pdug5TemperatureEntry
.1.3.6.1.4.1.19536.10.1.4.2
pdug5TemperatureEntryAn entry for a temperature measurement.
Pdug5TemperatureEntry
.1.3.6.1.4.1.19536.10.1.4.2.1
pdug5TemperatureIndexA unique value for each temperature probe measurement. Its value ranges from 1 to temperatureCount.
Integer32
.1.3.6.1.4.1.19536.10.1.4.2.1.1
pdug5TemperatureNameA descriptive name for the temperature probe.rw
DisplayString
.1.3.6.1.4.1.19536.10.1.4.2.1.2
pdug5TemperatureProbeStatusIndicates whether a probe is connected or not.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.2.1.3
pdug5TemperatureValueUnits are degree(either Fahrenheit or Celsius).ro
Integer32 -- Fahrenheit or Celsius
.1.3.6.1.4.1.19536.10.1.4.2.1.4
pdug5TemperatureThStatusStatus of the measured temperature relative to the configured thresholds.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.2.1.5
pdug5TemperatureThLowerWarningLower warning threshold. Units are degrees. A negative value indicates that this object is not available.rw
Integer32 (-1..150000)
.1.3.6.1.4.1.19536.10.1.4.2.1.6
pdug5TemperatureThLowerCriticalLower critical threshold. Units are degrees. A negative value indicates that this object is not available.rw
Integer32 (-1..150000)
.1.3.6.1.4.1.19536.10.1.4.2.1.7
pdug5TemperatureThUpperWarningUpper warning threshold. Units are degrees. A negative value indicates that this object is not available.rw
Integer32 (-1..150000)
.1.3.6.1.4.1.19536.10.1.4.2.1.8
pdug5TemperatureThUpperCriticalUpper critical threshold. Units are degrees. A negative value indicates that this object is not available.rw
Integer32 (-1..150000)
.1.3.6.1.4.1.19536.10.1.4.2.1.9
pdug5TemperatureThCtrlTemperature alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disablerw
Integer32
.1.3.6.1.4.1.19536.10.1.4.2.1.10
pdug5HumidityTableA list of humidity probe measurements. The number of entries are given by number of pdu and pdug5HumidityCount.
SEQUENCE OF Pdug5HumidityEntry
.1.3.6.1.4.1.19536.10.1.4.3
pdug5HumidityEntryAn entry for a humidity measurement.
Pdug5HumidityEntry
.1.3.6.1.4.1.19536.10.1.4.3.1
pdug5HumidityIndexA unique value for each humidity probe measurement. Its value ranges from 1 to pdug5HumidityCount per PDU.
Integer32
.1.3.6.1.4.1.19536.10.1.4.3.1.1
pdug5HumidityNameA descriptive name for the humidity probe.rw
DisplayString
.1.3.6.1.4.1.19536.10.1.4.3.1.2
pdug5HumidityProbeStatusIndicates whether a probe is connected or not.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.3.1.3
pdug5HumidityValueUnits are %RH.ro
Integer32
.1.3.6.1.4.1.19536.10.1.4.3.1.4
pdug5HumidityThStatusStatus of the measured humidity relative to the configured thresholds.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.3.1.5
pdug5HumidityThLowerWarningLower warning threshold. Units are %RH. A negative value indicates that this object is not available.rw
Integer32 (-1..1000)
.1.3.6.1.4.1.19536.10.1.4.3.1.6
pdug5HumidityThLowerCriticalLower critical threshold. Units are %RH. A negative value indicates that this object is not available.rw
Integer32 (-1..1000)
.1.3.6.1.4.1.19536.10.1.4.3.1.7
pdug5HumidityThUpperWarningUpper warning threshold. Units are %RH. A negative value indicates that this object is not available.rw
Integer32 (-1..1000)
.1.3.6.1.4.1.19536.10.1.4.3.1.8
pdug5HumidityThUpperCriticalUpper critical threshold. Units are %RH. A negative value indicates that this object is not available.rw
Integer32 (-1..1000)
.1.3.6.1.4.1.19536.10.1.4.3.1.9
pdug5HumidityThCtrlHumidity alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disablerw
Integer32
.1.3.6.1.4.1.19536.10.1.4.3.1.10
pdug5DoorTableA list of door sensors. The number of entries are given by number of PDU and pdug5DoorCount.
SEQUENCE OF Pdug5DoorEntry
.1.3.6.1.4.1.19536.10.1.4.4
pdug5DoorEntryAn entry for a door sensor
Pdug5DoorEntry
.1.3.6.1.4.1.19536.10.1.4.4.1
pdug5DoorIndexA unique value for each door sensor. Its value ranges from 1 to doorCount.
Integer32
.1.3.6.1.4.1.19536.10.1.4.4.1.1
pdug5DoorNameA descriptive name for the door sensor.rw
DisplayString
.1.3.6.1.4.1.19536.10.1.4.4.1.2
pdug5DoorProbeStatusIndicates whether a probe is connected or not. Will not be returned if the door sensor is internal to the ePDU, in that case only doorState should be read.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.4.1.3
pdug5DoorStateThe state of the door sensor.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.4.1.4
pdug5DryTableA list of dry sensors. The number of entries are given by number of pdu and pdug5DryCount.
SEQUENCE OF Pdug5DryEntry
.1.3.6.1.4.1.19536.10.1.4.5
pdug5DryEntryAn entry for a contact sensor
Pdug5DryEntry
.1.3.6.1.4.1.19536.10.1.4.5.1
pdug5DryIndexA unique value for each dry sensor. Its value ranges from 1 to dryCount.
Integer32
.1.3.6.1.4.1.19536.10.1.4.5.1.1
pdug5DryNameA descriptive name for the dry sensor.rw
DisplayString
.1.3.6.1.4.1.19536.10.1.4.5.1.2
pdug5DryProbeStatusIndicates whether a probe is connected or not.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.5.1.3
pdug5DryStateThe state of the dry sensor.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.5.1.4
pdug5SpotTableA list of contact sensors. The number of entries are given by number of pdu and pdug5SpotCount.
SEQUENCE OF Pdug5SpotEntry
.1.3.6.1.4.1.19536.10.1.4.6
pdug5SpotEntryAn entry for a contact sensor
Pdug5SpotEntry
.1.3.6.1.4.1.19536.10.1.4.6.1
pdug5SpotIndexA unique value for each spot sensor. Its value ranges from 1 to spotCount.
Integer32
.1.3.6.1.4.1.19536.10.1.4.6.1.1
pdug5SpotNameA descriptive name for the spot sensor.rw
DisplayString
.1.3.6.1.4.1.19536.10.1.4.6.1.2
pdug5SpotProbeStatusIndicates whether a probe is connected or not.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.6.1.3
pdug5SpotStateThe state of the spot sensor.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.6.1.4
pdug5RopeTableA list of rope sensors. The number of entries are given by number of pdu and pdug5RopeCount.
SEQUENCE OF Pdug5RopeEntry
.1.3.6.1.4.1.19536.10.1.4.7
pdug5RopeEntryAn entry for a contact sensor
Pdug5RopeEntry
.1.3.6.1.4.1.19536.10.1.4.7.1
pdug5RopeIndexA unique value for each rope sensor. Its value ranges from 1 to ropeCount.
Integer32
.1.3.6.1.4.1.19536.10.1.4.7.1.1
pdug5RopeNameA descriptive name for the rope sensor.rw
DisplayString
.1.3.6.1.4.1.19536.10.1.4.7.1.2
pdug5RopeProbeStatusIndicates whether a probe is connected or not.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.7.1.3
pdug5RopeStateThe state of the rope sensor.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.7.1.4
pdug5EnvHID
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.4.10
pdug5EnvHidTableA list of contact sensors. The number of entries are given by number of pdu and pdug5HidCount.
SEQUENCE OF Pdug5EnvHidEntry
.1.3.6.1.4.1.19536.10.1.4.10.1
pdug5EnvHidEntryAn entry for a contact sensor
Pdug5EnvHidEntry
.1.3.6.1.4.1.19536.10.1.4.10.1.1
pdug5HIDIndexThe index of the PDU HID table entry
Integer32
.1.3.6.1.4.1.19536.10.1.4.10.1.1.1
pdug5HidAisleAisle of HID handle.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.10.1.1.2
pdug5HidHandleOperationHID handle control operationsrw
Enumeration
.1.3.6.1.4.1.19536.10.1.4.10.1.1.3
pduHIDVerThe firmware revision level of the HIDro
DisplayString
.1.3.6.1.4.1.19536.10.1.4.10.1.1.4
pdug5MechanicalLockHID Mechanical operationsro
Enumeration
.1.3.6.1.4.1.19536.10.1.4.10.1.1.5
pduHIDSerialThe Serial Number of the HIDro
DisplayString
.1.3.6.1.4.1.19536.10.1.4.10.1.1.6
pduHIDHwVerThe hardware revision level of the HIDro
DisplayString
.1.3.6.1.4.1.19536.10.1.4.10.1.1.7
pdug5HIDAutoLockTimeHID Electronic Latch Autolock Time in seconds, Value ranges (0-999)rw
Integer32
.1.3.6.1.4.1.19536.10.1.4.10.1.1.8
pdug5HIDDoorOpenTimeHID Door Open Time in seconds, Value ranges (0-999)rw
Integer32
.1.3.6.1.4.1.19536.10.1.4.10.1.1.9
pdug5HIDMaxDoorOpenTimeHID Max Door Open Time in seconds, Value ranges (0-32400), critical alarm will be raised if door is left open past this timerw
Integer32
.1.3.6.1.4.1.19536.10.1.4.10.1.1.10
pdug5HIDUserPinLengthRack Access User minimum PIN Length, value ranges(0-16)rw
Integer32
.1.3.6.1.4.1.19536.10.1.4.10.1.1.11
pdug5HIDUserPinModeRack Access User PIN mode settingrw
Enumeration
.1.3.6.1.4.1.19536.10.1.4.10.1.1.12
pdug5HIDAisleControlRack Access Aisle Control setting, when set to standalone each aisle will controlled separately, when set to combined opposite aisle can be controlled with authenticated control action on either aislerw
Enumeration
.1.3.6.1.4.1.19536.10.1.4.10.1.1.13
pdug5HIDBeaconFuncControlBeacon Function Controlrw
Enumeration
.1.3.6.1.4.1.19536.10.1.4.10.1.1.14
pdug5HidBeaconColorControlBeacon Color Controlrw
Enumeration
.1.3.6.1.4.1.19536.10.1.4.10.1.1.15
pdug5EnvHidControlTableA list of smartcard. The number of entries are given by number of pdu and pdug5HidCount.
SEQUENCE OF Pdug5EnvHidControlEntry
.1.3.6.1.4.1.19536.10.1.4.10.2
pdug5EnvHidControlEntryThe smart card table entry containing the username, cardid, cardaisle etc.
Pdug5EnvHidControlEntry
.1.3.6.1.4.1.19536.10.1.4.10.2.1
pdug5HidControlIndexThe index of the PDU smartcard table entry
Integer32
.1.3.6.1.4.1.19536.10.1.4.10.2.1.1
pdug5HidControlUserNameUser name of smartcard. Use #delete# to delete the HID userrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.4.10.2.1.2
pdug5HidControlCardIDHID smartcard ID.rw
Integer32
.1.3.6.1.4.1.19536.10.1.4.10.2.1.3
pdug5HidControlTimestampIndicates the date and time of accessingro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.4.10.2.1.4
pdug5HidControlCardAisleAisle of authorized cardrw
Enumeration
.1.3.6.1.4.1.19536.10.1.4.10.2.1.5
pdug5HidControlStartTimeIndicates the start date and time Rack access user is given accessrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.4.10.2.1.6
pdug5HidControlExpireTimeIndicates the date and time when the access of user card will expire, To set expire time first set user as temporary userrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.4.10.2.1.7
pdug5HidControlTempUserIndicates if the card user has temporary accessrw
Enumeration
.1.3.6.1.4.1.19536.10.1.4.10.2.1.8
pdug5HidControlPinRack access control entry keypad PINrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.4.10.2.1.9
pdug5HidControlCardIdStrSmartrack Access Card ID Stringrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.19536.10.1.4.10.2.1.10
pdug5Outlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.5
pdug5OutletTableAggregate Object with number of entries equal to Number of PDU (pdug5IdentIndex) and Number of outlet per PDU (pdug5OutletIndex).
SEQUENCE OF Pdug5OutletEntry
.1.3.6.1.4.1.19536.10.1.5.1
pdug5OutletEntryThe Outlet table entry containing the type, voltage, current etc.
Pdug5OutletEntry
.1.3.6.1.4.1.19536.10.1.5.1.1
pdug5OutletIndexIndex for each outlet, value from 1 to the number of outlets per PDU.
Integer32
.1.3.6.1.4.1.19536.10.1.5.1.1.1
pdug5OutletNameA descriptive name for the outlet.rw
DisplayString
.1.3.6.1.4.1.19536.10.1.5.1.1.2
pdug5OutletTypeType of this outlet - C13, C19, 5-20R, iecC13/C15 COMBO, iecC13/C15/C19 COMBO...ro
Enumeration
.1.3.6.1.4.1.19536.10.1.5.1.1.3
pdug5OutletCurrentRatingRated current capacity of this outlet. Units are 0.01 amps. A negative value indicates that the hardware current capacity is unknown.ro
Integer32 -- Units 0.01 A
.1.3.6.1.4.1.19536.10.1.5.1.1.4
pdug5OutletCurrentA outlet current measurement value. Units are 0.01 amps.ro
Integer32 -- Units 0.01 A
.1.3.6.1.4.1.19536.10.1.5.1.1.5
pdug5OutletActivePowerThStatusStatus of the measured outlet active power relative to the configured thresholds.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.5.1.1.6
pdug5OutletActivePowerThLowerWarningLower warning threshold. Units are Watts(W). A negative value indicates that this object is not available.rw
Integer32 (-1..10000)
.1.3.6.1.4.1.19536.10.1.5.1.1.7
pdug5OutletActivePowerThLowerCriticalLower critical threshold. Units are Watts(W). A negative value indicates that this object is not available.rw
Integer32 (-1..10000)
.1.3.6.1.4.1.19536.10.1.5.1.1.8
pdug5OutletActivePowerThUpperWarningUpper warning threshold. Units are Watts(W). A negative value indicates that this object is not available.rw
Integer32 (-1..10000)
.1.3.6.1.4.1.19536.10.1.5.1.1.9
pdug5OutletActivePowerThUpperCriticalUpper critical threshold. Units are Watts(W). A negative value indicates that this object is not available.rw
Integer32 (-1..10000)
.1.3.6.1.4.1.19536.10.1.5.1.1.10
pdug5OutletCurrentPercentLoadCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available.ro
Integer32 -- Unit in percentage
.1.3.6.1.4.1.19536.10.1.5.1.1.11
pdug5OutletVAA outlet VA value. Units are VA. A negative value indicates that this object is not available.ro
Integer32 -- Units in VA
.1.3.6.1.4.1.19536.10.1.5.1.1.12
pdug5OutletWattsA outlet Watts value. Units are Watts. A negative value indicates that this object is not available.ro
Integer32 -- Units in Watt
.1.3.6.1.4.1.19536.10.1.5.1.1.13
pdug5OutletWhA Watt-Hour value for each outlet. Units are WH. This object is writable so that it can be reset to 0. When it is written to, the pdug5OutletWhTimer will be reset updated as well A negative value indicates that this object is not available.ro
Integer32 -- Units in Watt-Hour
.1.3.6.1.4.1.19536.10.1.5.1.1.14
pdug5OutletWhTimerTimestamp (date and time) of outlet Watt-hours was last reset.ro
DisplayString
.1.3.6.1.4.1.19536.10.1.5.1.1.15
pdug5OutletPowerFactorAn outlet PF value. Units are in hundredths, for example a power factor of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available.ro
Integer32 -- Units are in 0.01
.1.3.6.1.4.1.19536.10.1.5.1.1.16
pdug5OutletVARAn outlet VAR value. Units are VAR. A negative value indicates that this object is not available.ro
Integer32 -- Units in VAR
.1.3.6.1.4.1.19536.10.1.5.1.1.17
pdug5OutletBranchThe branch number outlet located.ro
Integer32 -- Units in VAR
.1.3.6.1.4.1.19536.10.1.5.1.1.18
pdug5OutletActivePowerThResetThldThe Reset threshold is the number of watss the reading needs to fall below the threshold setting for the condition to be cleared. Units are watts.rw
Integer32 (-1..10000)
.1.3.6.1.4.1.19536.10.1.5.1.1.19
pdug5OutletActivePowerThChangeDelayThe number of consecutive sample that the condition is present before an alarm is raised.rw
Integer32
.1.3.6.1.4.1.19536.10.1.5.1.1.20
pdug5OutletActivePowerThCtrlOutlet Active Power alarm threshold control: bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 - disable bit 3: low critical alarm control bit, 0 - enable, 1 - disablerw
Integer32
.1.3.6.1.4.1.19536.10.1.5.1.1.21
pdug5OutletControlTableAggregate Object with number of entries equal to Number of PDU (pdug5IdentIndex) and Number of outlets per PDU (pdug5OutletIndex).
SEQUENCE OF Pdug5OutletControlEntry
.1.3.6.1.4.1.19536.10.1.5.2
pdug5OutletControlEntryThe Outlet table entry containing the type, voltage, current etc.
Pdug5OutletControlEntry
.1.3.6.1.4.1.19536.10.1.5.2.1
pdug5OutletControlStatuscurrent state of a control outlet.ro
Enumeration
.1.3.6.1.4.1.19536.10.1.5.2.1.1
pdug5OutletControlOffCmdWhen write, once issued, the outlet will turn Off immediately. 0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.rw
Integer32 (-1..99999)
.1.3.6.1.4.1.19536.10.1.5.2.1.2
pdug5OutletControlOnCmdWhen write, once issued, the outlet will turn On immediately. 0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet On command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.rw
Integer32 (-1..99999)
.1.3.6.1.4.1.19536.10.1.5.2.1.3
pdug5OutletControlRebootCmdWhen write, for outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn back On. For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime seconds from when the command is issued. 0-n : Time in seconds until the Reboot command is issued -1 : Cancel a pending outlet Reboot command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.rw
Integer32 (-1..99999)
.1.3.6.1.4.1.19536.10.1.5.2.1.4
pdug5OutletControlPowerOnStateDetermines the outlet state when power is applied to the unit. 1 : not restart at device startup 2 : should sequence back ON in line with outletControlSequenceTime 3 : should take the state the outlet had when power was lost. If the state was ON, should sequence back ON in line with outletControlSequenceTime.rw
Enumeration
.1.3.6.1.4.1.19536.10.1.5.2.1.5
pdug5OutletControlSequenceDelayTime delay in seconds from when a Global Sequence On command is issued to when the command is executed on this outlet. This delay is also used as a power-on delay.rw
Integer32 (-1..7200)
.1.3.6.1.4.1.19536.10.1.5.2.1.6
pdug5OutletControlRebootOffTimeTime delay in seconds that the outlet should remain in the Off state when executing a Reboot command.rw
Integer32
.1.3.6.1.4.1.19536.10.1.5.2.1.7
pdug5OutletControlSwitchableDetermines the outlet capability to be controlled On/Off from the communication channels. 1 : control On/Off enabled 2 : control On/Off disabled.rw
Enumeration
.1.3.6.1.4.1.19536.10.1.5.2.1.8
pdug5OutletControlShutoffDelayTime delay in seconds that could be taken in account before shutting of the outlet. An application which need to shutoff properly an outlet will read this parameter first then write it to the command pdug5OutletControlOffCmd.rw
Integer32 (-1..7200)
.1.3.6.1.4.1.19536.10.1.5.2.1.9
pdug5OutletControlCommandGetting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (1) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (7) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (2) will immediately turn the outlet on. Setting this variable to immediateOff (1) will immediately turn the outlet off. Setting this variable to immediateReboot (5) will cause the Switched PDU to perform an immediateOff command, wait the pdug5OutletControlRebootOffTime OID time, and then perform an immediateOn command. Setting this variable to delayedOn (4) will turn the outlet on after the pdug5OutletControlSequenceDelay OID time has elapsed. Setting this variable to delayedOff (3) will turn the outlet off after the pdug5OutletControlShutoffDelay OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched PDU to perform a delayedOff command, wait the pdug5OutletControlRebootOffTime OID time, and then perform a delayedOn command.rw
Enumeration
.1.3.6.1.4.1.19536.10.1.5.2.1.10
pdug5Traps
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.6
trapCriticalA critical alarm has occurred.
NOTIFICATION-TYPE
.1.3.6.1.4.1.19536.10.1.6.1
trapWarningA warning alarm has occurred.
NOTIFICATION-TYPE
.1.3.6.1.4.1.19536.10.1.6.2
trapInformationAn informational alarm has occurred.
NOTIFICATION-TYPE
.1.3.6.1.4.1.19536.10.1.6.3
trapClearedAn alarm has cleared.
NOTIFICATION-TYPE
.1.3.6.1.4.1.19536.10.1.6.4
trapTestTest trap sent to a trap receiver to check proper reception of traps
NOTIFICATION-TYPE
.1.3.6.1.4.1.19536.10.1.6.5
pdug5TrapInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.7
pdug5TrapInfoEntry
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.7.1
trapCodeA number identifying the event for the trap that was sent.ro
Integer32
.1.3.6.1.4.1.19536.10.1.7.1.1
trapDescriptionA string identifying the event for that last trap that was sent.ro
DisplayString
.1.3.6.1.4.1.19536.10.1.7.1.2
pdug5Conformance
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.8
pdug5Compliances
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.8.1
pdug5Groups
OBJECT IDENTIFIER
.1.3.6.1.4.1.19536.10.1.8.2
MIB - SNMP MIB Reference | MIBs Explorer