Home/Catalog/MG-SNMP-UPS-MIB

MG-SNMP-UPS-MIB

AI MIB Summary

Standard SNMP MIB module defining data structures for MG-SNMP-UPS-MIB.

304
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

304 total
Object Name
merlinGerin
OBJECT IDENTIFIER
.1.3.6.1.4.1.705
RFC1213-MIB
Unknown
.1.3.6.1.4.1.705
upsmg
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1
upsmgIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.1
upsmgIdentFamilyNameThe UPS family name (e.g. `PULSAR', `COMET', `GALAXY', ...).rw
DisplayString
.1.3.6.1.4.1.705.1.1.1
upsmgIdentModelNameThe UPS model name (e.g. `PSX20', `SV9', ... ).rw
DisplayString
.1.3.6.1.4.1.705.1.1.2
upsmgIdentRevisionLevelThe UPS revision level.rw
DisplayString
.1.3.6.1.4.1.705.1.1.3
upsmgIdentFirmwareVersionThe UPS microprocessor firmware version number.rw
DisplayString
.1.3.6.1.4.1.705.1.1.4
upsmgIdentUserIDThe UPS user identification (set by administrator).rw
DisplayString
.1.3.6.1.4.1.705.1.1.5
upsmgIdentInstallationDateThe UPS installation date in dd/mm/yy format.rw
DisplayString
.1.3.6.1.4.1.705.1.1.6
upsmgIdentSerialNumberThe UPS manufacturing serial number.rw
DisplayString
.1.3.6.1.4.1.705.1.1.7
upsmgManagement
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.2
upsmgManagersNumThe number of managers that could manage the UPS.ro
INTEGER
.1.3.6.1.4.1.705.1.2.1
upsmgManagersTableThe table of managers.
SEQUENCE OF UpsmgManagersEntry
.1.3.6.1.4.1.705.1.2.2
upsmgManagersEntryThe description of a manager entry in the managers table.
UpsmgManagersEntry
.1.3.6.1.4.1.705.1.2.2.1
mgmanagerIndexA unique value for each manager. Its value ranges between 1 and the value of upsmgManagersNum.ro
INTEGER
.1.3.6.1.4.1.705.1.2.2.1.1
mgmanagerDeviceNumberThis object is the number of the manager device in the DevicesTable of the Config group. This means that the manager is powered by the UPS. If not the default value is 0.rw
INTEGER
.1.3.6.1.4.1.705.1.2.2.1.2
mgmanagerNMSTypeThe type of manager according to the NMS platform. We include in the manager class all systems which will be notified by the agent via receiving traps (e.g. basic to complex NMS software).rw
Enumeration
.1.3.6.1.4.1.705.1.2.2.1.3
mgmanagerCommTypeThe level of communication protocol for that manager. Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the upsmgManagersTable. It is an implementation-specific matter as to wether the agent removes an invalidated entry from the table. Accordingly, management stations must be prepared to receive tabular information from agents that corresponds to entry not currently in use. Proper interpretation of such entries requires examination of the relevant mgmanagerCommType object.rw
Enumeration
.1.3.6.1.4.1.705.1.2.2.1.4
mgmanagerDescrA textual string containing information about the manager. (manufacturer and version description).rw
DisplayString
.1.3.6.1.4.1.705.1.2.2.1.5
mgmanagerAddressThe IP address of the manager station receiving traps. The value of this object is meaningful if and only if the value of the relevant mgmanagerCommType object is snmp type.rw
IpAddress
.1.3.6.1.4.1.705.1.2.2.1.6
mgmanagerCommunityThe manager community string.rw
DisplayString
.1.3.6.1.4.1.705.1.2.2.1.7
mgmanagerSeverityLevelThe severity level of traps to be received by this manager.rw
INTEGER
.1.3.6.1.4.1.705.1.2.2.1.8
mgmanagerTrapAckThe manager Trap Acknowledgement status. Setting this object to mgnoack(2) or stdnomg(3) or cpqnoack(5) disables the trap acknowledgement from the related manager. The MG enterprise specific trap should then be sent only once by the agent to this manager in case of mgnoack(2), and should not be sent by the agent to this manager in case of stdnomg(3) or cpqnoack(5). mgack(1) allows a basic mecanism for acknowledged traps using upsmgAgentTrapAck object set by the manager to the enterprise specific number of the trap. mgacks(5) allows the enhanced mecanism using the upsmgAgentTrapSignature object set by the manager to the signature received within the trap var binding.rw
Enumeration
.1.3.6.1.4.1.705.1.2.2.1.9
upsmgReceptacle
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.3
upsmgReceptaclesNumThe total number of receptacles controlled by the UPS.ro
INTEGER
.1.3.6.1.4.1.705.1.3.1
upsmgReceptaclesTableThe table of receptacles that are controlled by the UPS.
SEQUENCE OF UpsmgReceptaclesEntry
.1.3.6.1.4.1.705.1.3.2
upsmgReceptaclesEntryThe description of a receptacle in the table.
UpsmgReceptaclesEntry
.1.3.6.1.4.1.705.1.3.2.1
mgreceptacleIndexA unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum.ro
INTEGER
.1.3.6.1.4.1.705.1.3.2.1.1
mgreceptacleLevelThe level of receptacle. Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the upsmgReceptaclesTable. It is an implementation-specific matter as to wether the agent removes an invalidated entry from the table. Accordingly, management stations must be prepared to receive tabular information from agents that corresponds to entry not currently in use. Proper interpretation of such entries requires examination of the relevant receptacleLevel object. Values 1 and 4 are reserved, value 3 is used to identify a simple one-level receptacle, and values greater than 4 represent a group of equivalent receptacles.rw
INTEGER
.1.3.6.1.4.1.705.1.3.2.1.2
mgreceptacleTypeA textual string for the receptacle type.rw
DisplayString
.1.3.6.1.4.1.705.1.3.2.1.3
mgreceptacleIdentA textual string identification for the user.rw
DisplayString
.1.3.6.1.4.1.705.1.3.2.1.4
mgreceptacleStateThe ON/OFF status of the receptacle.ro
Enumeration
.1.3.6.1.4.1.705.1.3.2.1.5
mgreceptacleReceptacleThe receptacle number of the second level receptacle father. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the default value is 0.rw
INTEGER
.1.3.6.1.4.1.705.1.3.2.1.6
mgreceptaclePowerConsThe volt-ampere rating of the receptacle. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the default value is 0.rw
INTEGER
.1.3.6.1.4.1.705.1.3.2.1.7
mgreceptacleOverloadThe overload status of the receptacle. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the default value is 0.rw
INTEGER
.1.3.6.1.4.1.705.1.3.2.1.8
mgreceptacleAutonomyThe receptacle autonomy. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the default value is 0.rw
INTEGER
.1.3.6.1.4.1.705.1.3.2.1.9
upsmgConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.4
upsmgConfigBatteryInstalledThe battery installed status.rw
Enumeration
.1.3.6.1.4.1.705.1.4.1
upsmgConfigNominalBatteryVoltageThe nominal battery voltage.rw
INTEGER
.1.3.6.1.4.1.705.1.4.2
upsmgConfigNominalBatteryTimeThe full load battery autonomy time.rw
INTEGER
.1.3.6.1.4.1.705.1.4.3
upsmgConfigNominalRechargeTimeThe recharge time to go from low battery cut off to full charge at full load.rw
INTEGER
.1.3.6.1.4.1.705.1.4.4
upsmgConfigMinRechargeLevelThe minimum battery level required to supply power on the loads after low battery condition turn off and restart on main return.rw
INTEGER
.1.3.6.1.4.1.705.1.4.5
upsmgConfigMaxRechargeTimeThe maximum time delay of battery recharge before supply power to the loads.rw
INTEGER
.1.3.6.1.4.1.705.1.4.6
upsmgConfigLowBatteryTimeTo set remaining time value for low battery condition.rw
INTEGER
.1.3.6.1.4.1.705.1.4.7
upsmgConfigLowBatteryLevelTo set battery level value for low battery condition.rw
INTEGER
.1.3.6.1.4.1.705.1.4.8
upsmgConfigAutoRestartThe automatic restart enabling status.rw
Enumeration
.1.3.6.1.4.1.705.1.4.9
upsmgConfigShutdownTimerTo set ups shutdown timer from on battery condition.rw
INTEGER
.1.3.6.1.4.1.705.1.4.10
upsmgConfigSysShutDurationTo set ups shutdown delay (Sn delay).rw
INTEGER
.1.3.6.1.4.1.705.1.4.11
upsmgConfigVARatingThe UPS nominal VA rating.rw
INTEGER
.1.3.6.1.4.1.705.1.4.12
upsmgConfigLowTransferThe low voltage transfer point.rw
INTEGER
.1.3.6.1.4.1.705.1.4.13
upsmgConfigHighTransferThe high voltage transfer point.rw
INTEGER
.1.3.6.1.4.1.705.1.4.14
upsmgConfigOutputNominalVoltageThe nominal output voltage.rw
INTEGER
.1.3.6.1.4.1.705.1.4.15
upsmgConfigOutputNominalCurrentThe nominal output current.rw
INTEGER
.1.3.6.1.4.1.705.1.4.16
upsmgConfigOutputNomFrequencyThe nominal output frequency.rw
INTEGER
.1.3.6.1.4.1.705.1.4.17
upsmgConfigByPassTypeThe UPS by pass switch type.rw
Enumeration
.1.3.6.1.4.1.705.1.4.18
upsmgConfigAlarmAudibleTo set audible alarm status.rw
Enumeration
.1.3.6.1.4.1.705.1.4.19
upsmgConfigAlarmTimeDelayTo set audible alarm time delay.rw
INTEGER
.1.3.6.1.4.1.705.1.4.20
upsmgConfigDevicesNumThe number of devices that are powered by the UPS.rw
INTEGER
.1.3.6.1.4.1.705.1.4.21
upsmgConfigDevicesTableThe table of devices that are powered by the UPS.
SEQUENCE OF UpsmgConfigDevicesEntry
.1.3.6.1.4.1.705.1.4.22
upsmgConfigDevicesEntryThe description of a device entry in the devices table.
UpsmgConfigDevicesEntry
.1.3.6.1.4.1.705.1.4.22.1
mgdeviceIndexA unique value for each device. Its value ranges between 1 and the value of upsmgDevicesNum.ro
INTEGER
.1.3.6.1.4.1.705.1.4.22.1.1
mgdeviceReceptacleNumThe receptacle number of the device plugged into the UPS. This value gives index entry in the ReceptaclesTable object of the Receptacle group. A value of 0 invalidates the entry in the DevicesTable.rw
INTEGER
.1.3.6.1.4.1.705.1.4.22.1.2
mgdeviceIdentA textual string for device user identification.rw
DisplayString
.1.3.6.1.4.1.705.1.4.22.1.3
mgdeviceVaRatingThe volt-ampere rating of the device plugged into the UPS.rw
INTEGER
.1.3.6.1.4.1.705.1.4.22.1.4
mgdeviceSequenceOffTo set the device position in the remote shutdown sequence.rw
INTEGER
.1.3.6.1.4.1.705.1.4.22.1.5
mgdeviceSequenceOnTo set the device position in the remote reboot sequence.rw
INTEGER
.1.3.6.1.4.1.705.1.4.22.1.6
mgdeviceShutdownDurationTo set the duration from start of computer shut-down to complete.rw
INTEGER
.1.3.6.1.4.1.705.1.4.22.1.7
mgdeviceBootUpDurationTo set the duration from start of computer boot-up to complete.rw
INTEGER
.1.3.6.1.4.1.705.1.4.22.1.8
upsmgConfigReceptaclesTableThe table of receptacles.
SEQUENCE OF UpsmgConfigReceptaclesEntry
.1.3.6.1.4.1.705.1.4.23
upsmgConfigReceptaclesEntryThe description of a receptacle entry in the table.
UpsmgConfigReceptaclesEntry
.1.3.6.1.4.1.705.1.4.23.1
mgreceptacleIndexbA unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum.ro
INTEGER
.1.3.6.1.4.1.705.1.4.23.1.1
mgreceptacleStateTurnOnDefault return state at turn on.rw
Enumeration
.1.3.6.1.4.1.705.1.4.23.1.2
mgreceptacleStateMainReturnDefault return state on main return.rw
Enumeration
.1.3.6.1.4.1.705.1.4.23.1.3
mgreceptacleStateDischargeDefault return state on main return from battery discharge.rw
Enumeration
.1.3.6.1.4.1.705.1.4.23.1.4
mgreceptacleShutoffLevelBattery level for starting shutoff sequence.rw
INTEGER
.1.3.6.1.4.1.705.1.4.23.1.5
mgreceptacleShutoffTimerTime delay from on battery for starting shutoff sequence.rw
INTEGER
.1.3.6.1.4.1.705.1.4.23.1.6
mgreceptacleRestartLevelBattery level for starting restart sequence.rw
INTEGER
.1.3.6.1.4.1.705.1.4.23.1.7
mgreceptacleRestartDelayTime delay for starting restart sequence.rw
INTEGER
.1.3.6.1.4.1.705.1.4.23.1.8
mgreceptacleShutdownDurationMaximum Shutdown Duration for systems powered by this plug.ro
INTEGER
.1.3.6.1.4.1.705.1.4.23.1.9
mgreceptacleBootUpDurationMaximum Reboot Duration for systems powered by this plug.ro
INTEGER
.1.3.6.1.4.1.705.1.4.23.1.10
upsmgConfigExtAlarmNumThe number of environ external alarm, value is between 8 and 32..ro
INTEGER
.1.3.6.1.4.1.705.1.4.24
upsmgConfigExtAlarmTableThe table of environmental external alarms.
SEQUENCE OF UpsmgConfigExtAlarmEntry
.1.3.6.1.4.1.705.1.4.25
upsmgConfigExtAlarmEntryThe description of an external alarm in the table.
UpsmgConfigExtAlarmEntry
.1.3.6.1.4.1.705.1.4.25.1
mgextAlarmIndexA unique value for each external alarm. Its value ranges between 1 and the value of upsmgConfigExtAlarmNum.ro
INTEGER
.1.3.6.1.4.1.705.1.4.25.1.1
mgextAlarmUIDA textual string for alarm state user identification.rw
DisplayString
.1.3.6.1.4.1.705.1.4.25.1.2
upsmgConfigEmergencyTestFailThe emergency condition status on Battery test fail.rw
Enumeration
.1.3.6.1.4.1.705.1.4.26
upsmgConfigEmergencyOnByPassThe emergency condition status on By Pass.rw
Enumeration
.1.3.6.1.4.1.705.1.4.27
upsmgConfigEmergencyOverloadThe emergency condition status on overload.rw
Enumeration
.1.3.6.1.4.1.705.1.4.28
upsmgConfigControlDayTableThe table of daily on/off time.
SEQUENCE OF UpsmgConfigControlDayEntry
.1.3.6.1.4.1.705.1.4.29
upsmgConfigControlDayEntryThe description of a daily on/off time schedule in the table.
UpsmgConfigControlDayEntry
.1.3.6.1.4.1.705.1.4.29.1
mgcontrolDayIndexThe day index. It is a number between 1 and 7, 1 for Sunday, 2 for Monday, ...ro
INTEGER
.1.3.6.1.4.1.705.1.4.29.1.1
mgcontrolDayOnTo set daily power on time. Any value greater than 86400 is to disable the Day On.rw
INTEGER
.1.3.6.1.4.1.705.1.4.29.1.2
mgcontrolDayOffTo set daily power off time. Any value greater than 86400 is to disable the Day Off.rw
INTEGER
.1.3.6.1.4.1.705.1.4.29.1.3
upsmgConfigLowBoosterTo set UPS booster low threshold.rw
INTEGER
.1.3.6.1.4.1.705.1.4.30
upsmgConfigHighBoosterTo set UPS booster high threshold.rw
INTEGER
.1.3.6.1.4.1.705.1.4.31
upsmgConfigLowFaderTo set UPS fader low threshold.rw
INTEGER
.1.3.6.1.4.1.705.1.4.32
upsmgConfigHighFaderTo set UPS fader high threshold.rw
INTEGER
.1.3.6.1.4.1.705.1.4.33
upsmgConfigEnvironmentTableThe table containing the configuration of the environment sensor.
SEQUENCE OF UpsmgConfigEnvironmentEntry
.1.3.6.1.4.1.705.1.4.34
upsmgConfigEnvironmentEntryThe description of an entry in the table.
UpsmgConfigEnvironmentEntry
.1.3.6.1.4.1.705.1.4.34.1
upsmgConfigSensorIndexThe sensor index, ranging from 1 to upsmgEnvironmentNum.ro
INTEGER
.1.3.6.1.4.1.705.1.4.34.1.1
upsmgConfigSensorNameThe sensor user-friendly name.rw
DisplayString
.1.3.6.1.4.1.705.1.4.34.1.2
upsmgConfigTemperatureLowThe low temperature threshold in unit 0.1 Cel.rw
INTEGER
.1.3.6.1.4.1.705.1.4.34.1.3
upsmgConfigTemperatureHighThe high temperature threshold in unit 0.1 Cel.rw
INTEGER
.1.3.6.1.4.1.705.1.4.34.1.4
upsmgConfigTemperatureHysteresisThe temperature hysteresys used for threshold test in unit 0.1 Cel.rw
INTEGER
.1.3.6.1.4.1.705.1.4.34.1.5
upsmgConfigHumidityLowThe low humidity threshold in unit 1 %.rw
INTEGER
.1.3.6.1.4.1.705.1.4.34.1.6
upsmgConfigHumidityHighThe high humidity threshold in unit 1 %.rw
INTEGER
.1.3.6.1.4.1.705.1.4.34.1.7
upsmgConfigHumidityHysteresisThe humidity hysteresys used for threshold test in unit 1 %.rw
INTEGER
.1.3.6.1.4.1.705.1.4.34.1.8
upsmgConfigInput1NameThe Input #1 user-friendly name.rw
DisplayString
.1.3.6.1.4.1.705.1.4.34.1.9
upsmgConfigInput1ClosedLabelThe Input #1 label for closed position.rw
DisplayString
.1.3.6.1.4.1.705.1.4.34.1.10
upsmgConfigInput1OpenLabelThe Input #1 label for open position.rw
DisplayString
.1.3.6.1.4.1.705.1.4.34.1.11
upsmgConfigInput2NameThe Input #2 user-friendly name.rw
DisplayString
.1.3.6.1.4.1.705.1.4.34.1.12
upsmgConfigInput2ClosedLabelThe Input #2 label for closed position.rw
DisplayString
.1.3.6.1.4.1.705.1.4.34.1.13
upsmgConfigInput2OpenLabelThe Input #2 label for open position.rw
DisplayString
.1.3.6.1.4.1.705.1.4.34.1.14
upsmgBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.5
upsmgBatteryRemainingTimeThe time remaining actual charge vs actual load (dynamic).ro
INTEGER
.1.3.6.1.4.1.705.1.5.1
upsmgBatteryLevelThe battery level as a percentage of charge.ro
INTEGER
.1.3.6.1.4.1.705.1.5.2
upsmgBatteryRechargeTimeThe actual operational battery recharge time to set point equal to upsmgConfigRechargeLevel. This value is computed from upsmgConfigRechargeLevel (level to reach), upsmgBatteryLevel (the actual reached level) and the UPS charge rate.ro
INTEGER
.1.3.6.1.4.1.705.1.5.3
upsmgBatteryRechargeLevelThe actual value of the battery recharge level that will be reached during the time delay necessary to restart after power returns. This value is computed from upsmgConfigRechargeTime (the delay), upsmgBatteryLevel (the actual level) and the UPS charge rate.ro
INTEGER
.1.3.6.1.4.1.705.1.5.4
upsmgBatteryVoltageThe actual battery voltage.ro
INTEGER
.1.3.6.1.4.1.705.1.5.5
upsmgBatteryCurrentThe actual battery current.ro
INTEGER
.1.3.6.1.4.1.705.1.5.6
upsmgBatteryTemperatureThe battery temperature.ro
INTEGER
.1.3.6.1.4.1.705.1.5.7
upsmgBatteryFullRechargeTimeThe battery full recharge time (from 0 to 100 percent) at current load.ro
INTEGER
.1.3.6.1.4.1.705.1.5.8
upsmgBatteryFaultBatteryThe battery fault status.ro
Enumeration
.1.3.6.1.4.1.705.1.5.9
upsmgBatteryNoBatteryThe UPS has no Battery status.ro
Enumeration
.1.3.6.1.4.1.705.1.5.10
upsmgBatteryReplacementThe UPS Battery to be replaced status.ro
Enumeration
.1.3.6.1.4.1.705.1.5.11
upsmgBatteryUnavailableBatteryThe UPS Battery is unavailable status.ro
Enumeration
.1.3.6.1.4.1.705.1.5.12
upsmgBatteryNotHighChargeThe UPS Battery quit high condition status.ro
Enumeration
.1.3.6.1.4.1.705.1.5.13
upsmgBatteryLowBatteryThe battery low status.ro
Enumeration
.1.3.6.1.4.1.705.1.5.14
upsmgBatteryChargerFaultThe UPS Battery is not charging status.ro
Enumeration
.1.3.6.1.4.1.705.1.5.15
upsmgBatteryLowConditionThe UPS is at low condition status.ro
Enumeration
.1.3.6.1.4.1.705.1.5.16
upsmgBatteryLowRechargeThe UPS Battery is not recharged status.ro
Enumeration
.1.3.6.1.4.1.705.1.5.17
upsmgInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.6
upsmgInputPhaseNumThe number of input phases.ro
INTEGER
.1.3.6.1.4.1.705.1.6.1
upsmgInputPhaseTableThe table of input phases.
SEQUENCE OF UpsmgInputPhaseEntry
.1.3.6.1.4.1.705.1.6.2
upsmgInputPhaseEntryThe description of an input phase.
UpsmgInputPhaseEntry
.1.3.6.1.4.1.705.1.6.2.1
mginputIndexThe input phase voltage index. It is a number between 1 and upsmgInputPhaseNum.ro
INTEGER
.1.3.6.1.4.1.705.1.6.2.1.1
mginputVoltageThe input phase voltage.ro
INTEGER
.1.3.6.1.4.1.705.1.6.2.1.2
mginputFrequencyThe input phase frequency.ro
INTEGER
.1.3.6.1.4.1.705.1.6.2.1.3
mginputMinimumVoltageThe input phase minimum voltage over the last minute.ro
INTEGER
.1.3.6.1.4.1.705.1.6.2.1.4
mginputMaximumVoltageThe input phase maximum voltage over the last minute.ro
INTEGER
.1.3.6.1.4.1.705.1.6.2.1.5
mginputCurrentThe input phase current.ro
INTEGER
.1.3.6.1.4.1.705.1.6.2.1.6
upsmgInputBadStatusThe utility power bad voltage or bad frequency status.ro
Enumeration
.1.3.6.1.4.1.705.1.6.3
upsmgInputLineFailCauseThe utility power failure cause: no(1) is for no utility failure, outoftolvolt(2) is for voltage out of tolerance, outoftolfreq(3) is for frequency out of tolerance, utilityoff(4) is for no voltage at all.ro
Enumeration
.1.3.6.1.4.1.705.1.6.4
upsmgOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.7
upsmgOutputPhaseNumThe number of output phases.ro
INTEGER
.1.3.6.1.4.1.705.1.7.1
upsmgOutputPhaseTableThe table of output phases.
SEQUENCE OF UpsmgOutputPhaseEntry
.1.3.6.1.4.1.705.1.7.2
upsmgOutputPhaseEntryThe description of an output phase.
UpsmgOutputPhaseEntry
.1.3.6.1.4.1.705.1.7.2.1
mgoutputPhaseIndexThe output phase voltage index. It is a number between 1 and upsmgOutputPhaseNum.ro
INTEGER
.1.3.6.1.4.1.705.1.7.2.1.1
mgoutputVoltageThe output phase voltage.ro
INTEGER
.1.3.6.1.4.1.705.1.7.2.1.2
mgoutputFrequencyThe output phase frequency.ro
INTEGER
.1.3.6.1.4.1.705.1.7.2.1.3
mgoutputLoadPerPhaseThe output load per phase.ro
INTEGER
.1.3.6.1.4.1.705.1.7.2.1.4
mgoutputCurrentThe output phase current.ro
INTEGER
.1.3.6.1.4.1.705.1.7.2.1.5
upsmgOutputOnBatteryThe UPS on battery / on main status.ro
Enumeration
.1.3.6.1.4.1.705.1.7.3
upsmgOutputOnByPassThe UPS on bypass status.ro
Enumeration
.1.3.6.1.4.1.705.1.7.4
upsmgOutputUnavailableByPassThe by pass unavailable status.ro
Enumeration
.1.3.6.1.4.1.705.1.7.5
upsmgOutputNoByPassThe UPS bypass installed status.ro
Enumeration
.1.3.6.1.4.1.705.1.7.6
upsmgOutputUtilityOffThe UPS utility off status.ro
Enumeration
.1.3.6.1.4.1.705.1.7.7
upsmgOutputOnBoostThe UPS on booster status.ro
Enumeration
.1.3.6.1.4.1.705.1.7.8
upsmgOutputInverterOffThe UPS Inverter on / off status.ro
Enumeration
.1.3.6.1.4.1.705.1.7.9
upsmgOutputOverLoadThe output over load status.ro
Enumeration
.1.3.6.1.4.1.705.1.7.10
upsmgOutputOverTempThe ups over temperature status.ro
Enumeration
.1.3.6.1.4.1.705.1.7.11
upsmgOutputOnBuckThe UPS on fader status.ro
INTEGER
.1.3.6.1.4.1.705.1.7.12
upsmgEnviron
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.8
upsmgEnvironAmbientTempThe ambient temperature.ro
INTEGER
.1.3.6.1.4.1.705.1.8.1
upsmgEnvironAmbientHumidityThe ambient humidity.ro
INTEGER
.1.3.6.1.4.1.705.1.8.2
upsmgEnvironExtAlarmTableThe table of external alarms.
SEQUENCE OF UpsmgEnvironExtAlarmEntry
.1.3.6.1.4.1.705.1.8.3
upsmgEnvironExtAlarmEntryThe description of an external alarm.
UpsmgEnvironExtAlarmEntry
.1.3.6.1.4.1.705.1.8.3.1
mgalarmNumThe external alarm number. A number between 1 and upsmgConfigExtAlarmNum.ro
INTEGER
.1.3.6.1.4.1.705.1.8.3.1.1
mgalarmStateThe external alarm state (active or inactive).ro
Enumeration
.1.3.6.1.4.1.705.1.8.3.1.2
upsmgEnvironSensorNumThe sensor unit number (0 to 4).ro
INTEGER
.1.3.6.1.4.1.705.1.8.4
upsmgEnvironSensorTableThe table of sensor units.
SEQUENCE OF UpsmgEnvironSensorEntry
.1.3.6.1.4.1.705.1.8.5
upsmgEnvironSensorEntryThe description of a sensor unit.
UpsmgEnvironSensorEntry
.1.3.6.1.4.1.705.1.8.5.1
mgsensorNumThe unit number. A number between 1 and 4.ro
INTEGER
.1.3.6.1.4.1.705.1.8.5.1.1
mgsensorTempThe measured temperature of the unit.ro
INTEGER
.1.3.6.1.4.1.705.1.8.5.1.2
mgsensorHumidityThe measured humidity of the unit.ro
INTEGER
.1.3.6.1.4.1.705.1.8.5.1.3
upsmgEnvironmentNumNumber of Environment sensor connected.ro
INTEGER
.1.3.6.1.4.1.705.1.8.6
upsmgEnvironmentSensorTableThe table containing the measurements and alarms made by Environment sensor units.
SEQUENCE OF UpsmgEnvironmentSensorEntry
.1.3.6.1.4.1.705.1.8.7
upsmgEnvironmentSensorEntryThe description of an entry in the measurement table.
UpsmgEnvironmentSensorEntry
.1.3.6.1.4.1.705.1.8.7.1
upsmgEnvironmentIndexThe sensor index, ranging from 1 to upsmgEnvironmentNum.ro
INTEGER
.1.3.6.1.4.1.705.1.8.7.1.1
upsmgEnvironmentComFailureThe sensor communication failure : yes(1), no(2).ro
Enumeration
.1.3.6.1.4.1.705.1.8.7.1.2
upsmgEnvironmentTemperatureThe temperature measurement in unit 0.1 Cel.ro
INTEGER
.1.3.6.1.4.1.705.1.8.7.1.3
upsmgEnvironmentTemperatureLowTemperature is below low theshold : yes(1), no(2).ro
Enumeration
.1.3.6.1.4.1.705.1.8.7.1.4
upsmgEnvironmentTemperatureHighTemperature is above high threshold : yes(1), no(2).ro
Enumeration
.1.3.6.1.4.1.705.1.8.7.1.5
upsmgEnvironmentHumidityThe humidity measurement in unit 0.1 %.ro
INTEGER
.1.3.6.1.4.1.705.1.8.7.1.6
upsmgEnvironmentHumidityLowHumidity is below low threshold : yes(1), no(2).ro
Enumeration
.1.3.6.1.4.1.705.1.8.7.1.7
upsmgEnvironmentHumidityHighHumidity is above high threshold : yes(1), no(2).ro
Enumeration
.1.3.6.1.4.1.705.1.8.7.1.8
upsmgEnvironmentInput1StateState of Input#1 : closed(1), open(2).ro
Enumeration
.1.3.6.1.4.1.705.1.8.7.1.9
upsmgEnvironmentInput2StateState of Input#2 : closed(1), open(2).ro
Enumeration
.1.3.6.1.4.1.705.1.8.7.1.10
upsmgControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.9
upsmgControlReceptaclesTableThe table of receptacles.
SEQUENCE OF UpsmgControlReceptaclesEntry
.1.3.6.1.4.1.705.1.9.1
upsmgControlReceptaclesEntryThe description of a receptacle entry in the table.
UpsmgControlReceptaclesEntry
.1.3.6.1.4.1.705.1.9.1.1
mgreceptacleIndexcA unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum.ro
INTEGER
.1.3.6.1.4.1.705.1.9.1.1.1
mgreceptacleOnDelayTurn on UPS receptacle w/delay=?.rw
INTEGER
.1.3.6.1.4.1.705.1.9.1.1.2
mgreceptacleOnCtrlThe receptacle control on action.rw
Enumeration
.1.3.6.1.4.1.705.1.9.1.1.3
mgreceptacleOnStatusThe receptacle control on status.ro
Enumeration
.1.3.6.1.4.1.705.1.9.1.1.4
mgreceptacleOffDelayTurn off UPS receptacle w/delay=?.rw
INTEGER
.1.3.6.1.4.1.705.1.9.1.1.5
mgreceptacleOffCtrlThe receptacle control off action.rw
Enumeration
.1.3.6.1.4.1.705.1.9.1.1.6
mgreceptacleOffStatusThe receptacle control off status.ro
Enumeration
.1.3.6.1.4.1.705.1.9.1.1.7
mgreceptacleToggleDelayTurn off then on UPS receptacle w/delay=?.rw
INTEGER
.1.3.6.1.4.1.705.1.9.1.1.8
mgreceptacleToggleCtrlThe receptacle control toggle action.rw
Enumeration
.1.3.6.1.4.1.705.1.9.1.1.9
mgreceptacleToggleStatusThe receptacle control toggle status.ro
Enumeration
.1.3.6.1.4.1.705.1.9.1.1.10
mgreceptacleToggleDurationTurn off then on UPS receptacle w/duration=?.rw
INTEGER
.1.3.6.1.4.1.705.1.9.1.1.11
upsmgControlDayOffThe schedule off control object. Default value is none(8). Value 1 means to start scheduled off on Sunday, value 2 to start scheduled off on Monday, and so on.rw
Enumeration
.1.3.6.1.4.1.705.1.9.2
upsmgControlDayOnThe schedule on control object. Default value is none(8). Value 1 means to start scheduled on on Sunday, value 2 to start scheduled on on Monday, and so on. This object is meaningfull only for those agent that do not include internal clock. In such a case the object is set by a manager to start the schedule on sequence.rw
Enumeration
.1.3.6.1.4.1.705.1.9.3
upsmgTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.10
upsmgTestBatteryScheduleThe automatic battery test schedule.rw
Enumeration
.1.3.6.1.4.1.705.1.10.1
upsmgTestDiagnosticsTo run self test diagnostics.rw
Enumeration
.1.3.6.1.4.1.705.1.10.2
upsmgTestDiagResultThe automatic test diagnostic result.ro
Enumeration
.1.3.6.1.4.1.705.1.10.3
upsmgTestBatteryCalibrationTo run battery test calibration.rw
Enumeration
.1.3.6.1.4.1.705.1.10.4
upsmgTestLastCalibrationThe last battery calibration test date.ro
INTEGER
.1.3.6.1.4.1.705.1.10.5
upsmgTestIndicatorsTo run UPS indicators test.rw
INTEGER
.1.3.6.1.4.1.705.1.10.6
upsmgTestCommandLineTo send ASCII command line to UPS.rw
DisplayString
.1.3.6.1.4.1.705.1.10.7
upsmgTestCommandReadyTo advise UPS that command line has been prepared.rw
Enumeration
.1.3.6.1.4.1.705.1.10.8
upsmgTestResponseLineTo get ASCII protocol response from UPS.ro
DisplayString
.1.3.6.1.4.1.705.1.10.9
upsmgTestResponseReadyTo advise agent that response line has been received.ro
Enumeration
.1.3.6.1.4.1.705.1.10.10
upsmgTestBatteryResultThe test battery result: msuccess(1) is for manual battery test success, ssuccess(3) is for scheduled battery test success, mfailed(2) is for manual battery test failed, sfailed(4) is for scheduled battery test failed.ro
Enumeration
.1.3.6.1.4.1.705.1.10.11
upsmgTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.11
upsmgBatteryFaultTrap UPS Battery entering Fault status.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.1
upsmgBatteryOKTrap UPS Battery returned to OK status.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.2
upsmgBatteryReplacementIndicatedTrap UPS battery need to be replaced.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.3
upsmgBatteryReplaceNotIndicatedTrap UPS battery does not need to be replaced.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.4
upsmgAtLowBatteryTrap UPS battery reached low condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.5
upsmgFromLowBatteryTrap UPS battery returned from low condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.6
upsmgChargerFaultTrap UPS battery charger is not active.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.7
upsmgChargerOKTrap UPS battery charger is active.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.8
upsmgAtLowConditionTrap UPS entering low condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.9
upsmgFromLowConditionTrap UPS exiting low condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.10
upsmgOnBatteryTrap UPS is on Battery.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.11
upsmgReturnFromBatteryTrap UPS returned from battery.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.12
upsmgOnByPassTrap UPS is on by pass.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.13
upsmgReturnFromByPassTrap UPS return from by pass.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.14
upsmgByPassUnavailableTrap UPS by pass unavailable.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.15
upsmgByPassAvailableTrap UPS by pass available.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.16
upsmgUtilityFailureTrap UPS utility power failed.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.17
upsmgUtilityRestoredTrap UPS utility power restored.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.18
upsmgOnBoostTrap UPS is on boost.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.19
upsmgReturnFromBoostTrap UPS has returned from boost.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.20
upsmgOverLoadTrap UPS has overload condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.21
upsmgLoadOKTrap UPS quit overload condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.22
upsmgOverTemperatureTrap UPS has overtemperature condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.23
upsmgTemperatureOKTrap UPS quit overtemperature condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.24
upsmgOnToStartTrap UPS on sequence started.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.25
upsmgOnAbortTrap UPS on sequence cancelled.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.26
upsmgOnInProgressTrap UPS on sequence in progress in ups.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.27
upsmgOnCompleteTrap UPS on sequence completed.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.28
upsmgOffToStartTrap UPS off sequence started.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.29
upsmgOffAbortTrap UPS off sequence cancelled.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.30
upsmgOffInProgressTrap UPS off sequence in progress in ups.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.31
upsmgOffCompleteTrap UPS off sequence completed.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.32
upsmgToggleToStartTrap UPS toggle (off/on) sequence started.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.33
upsmgToggleAbortTrap UPS toggle (off/on) sequence cancelled.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.34
upsmgToggleInProgressTrap UPS toggle (off/on) sequence in progress in ups.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.35
upsmgToggleCompleteTrap UPS toggle (off/on) sequence completed.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.36
upsmgCommunicationFailureTrap UPS serial communication failed.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.37
upsmgCommunicationRestoredTrap UPS serial communication restored.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.38
upsmgInputBadTrap UPS input has bad condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.39
upsmgInputOKTrap UPS input quit bad condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.40
upsmgBatteryUnavailableTrap UPS battery is unavailable.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.41
upsmgBatteryAvailableTrap UPS battery return from unavailable condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.42
upsmgAtLowRechargeTrap UPS waiting for battery charging condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.43
upsmgFromLowRechargeTrap UPS reached battery charging condition.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.44
upsmgDiagnosticTestFailTrap UPS self test failed.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.45
upsmgDiagnosticTestOKTrap UPS self test succeeded.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.46
upsmgBatteryTestOKTrap UPS passed battery test.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.47
upsmgBatteryTestFailTrap UPS failed battery test.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.48
upsmgExternalAlarmActiveTrap UPS enter environment external alarm.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.49
upsmgExternalAlarmInactiveTrap UPS exit environment external alarm.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.50
upsmgOnBuckTrap UPS is on buck.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.51
upsmgReturnFromBuckTrap UPS has returned from buck.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.52
upsmgEnvironComFailureEnvironment Probe communication failure.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.53
upsmgEnvironComOKEnvironment Probe communication restored.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.54
upsmgEnvironTemperatureLowTemperature is below low threshold.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.55
upsmgEnvironTemperatureHighTemperature is above high threshold.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.56
upsmgEnvironTemperatureOKTemperature is in normal range.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.57
upsmgEnvironHumidityLowHumidity is below low threshold.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.58
upsmgEnvironHumidityHighHumidity is above high threshold.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.59
upsmgEnvironHumidityOKHumidity is in normal range.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.60
upsmgEnvironInput1ClosedInput #1 is Closed.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.61
upsmgEnvironInput1OpenInput #1 is Open.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.62
upsmgEnvironInput2ClosedInput #2 is Closed.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.63
upsmgEnvironInput2OpenInput #2 is Open.
TRAP-TYPE
.1.3.6.1.4.1.705.1.11.0.64
upsmgAgent
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.12
upsmgAgentIpaddressThe ip address that NMS can identify the managed devicerw
IpAddress
.1.3.6.1.4.1.705.1.12.1
upsmgAgentSubnetMaskInternet address subnet maskrw
IpAddress
.1.3.6.1.4.1.705.1.12.2
upsmgAgentDefGatewayThe default gateway that allow device managed through routersrw
IpAddress
.1.3.6.1.4.1.705.1.12.3
upsmgAgentBaudRatethe serial port communication speed. only 2400, 4800, and 9600 allowedrw
INTEGER
.1.3.6.1.4.1.705.1.12.4
upsmgAgentPollRateThe frequency that proxy agent polls the connected UPS in ASCII protocol. (unit : second)rw
INTEGER
.1.3.6.1.4.1.705.1.12.5
upsmgAgentTypeThe type of agent.rw
Enumeration
.1.3.6.1.4.1.705.1.12.6
upsmgAgentTrapAlarmDelayThe interval for the Trap packet retransmission, while the TRAP Acknowledge is implemented and the ack is received within the interval.rw
INTEGER
.1.3.6.1.4.1.705.1.12.7
upsmgAgentTrapAlarmRetryThe retry count for retransmitting Trap packet while the TRAP acknowledge is implemented.rw
INTEGER
.1.3.6.1.4.1.705.1.12.8
upsmgAgentResetThe variable initiates reset operation in agent software, ie. warm start. write reset(1) to any one of UPS MIB array, will result in the same reset operation.rw
Enumeration
.1.3.6.1.4.1.705.1.12.9
upsmgAgentFactResetThe variable initiates reset operation in agent software, ie. warm start, and load default data (Factory setting) to EEPROM and to runtime parameters associated with the UPS.rw
Enumeration
.1.3.6.1.4.1.705.1.12.10
upsmgAgentMibVersionThe version of the MIB implemented in agent.ro
INTEGER
.1.3.6.1.4.1.705.1.12.11
upsmgAgentFirmwareVersionThe agent firmware version.ro
DisplayString
.1.3.6.1.4.1.705.1.12.12
upsmgAgentCommUPSThe status of communication between agent and ups. Even value means no communication, and odd value means a certain level of communication with devices daisy-chained on the serial port. The value is the following: 1000*NSE + 100*NSW + 10*UPSW + UPST with UPST is UPS type: 5 if no UPS; 3 if PI (Protocol Interface) 1 if U-Talk UPS; UPSW is the number of switchable plugs of the UPS; NSW is the number of UM-Switch devices; NSE is the number of UM-Sensor devices.ro
INTEGER
.1.3.6.1.4.1.705.1.12.13
upsmgAgentTrapAckThe last Trap number that has been received by UM-View.rw
INTEGER
.1.3.6.1.4.1.705.1.12.14
upsmgAgentAutoLearningThe enabled/disabled configuration of the Auto Learning process of the agent, default value is yes(1) e.g. enabled.rw
Enumeration
.1.3.6.1.4.1.705.1.12.15
upsmgAgentBootPThe enabled/disabled configuration of the BootP process, default value is yes(1) e.g. enabled.rw
Enumeration
.1.3.6.1.4.1.705.1.12.16
upsmgAgentTFTPThe enabled/disabled configuration of the TFTP process, default value is no(2) e.g. disabled.rw
Enumeration
.1.3.6.1.4.1.705.1.12.17
upsmgAgentTrapSignatureThe signature of the trap acknowledged by a manager.ro
INTEGER
.1.3.6.1.4.1.705.1.12.18
upsmgRemote
OBJECT IDENTIFIER
.1.3.6.1.4.1.705.1.13
upsmgRemoteOnBatteryAn object to inform an ups-less agent that the remote UPS is on autonomy. This object could be set by a management application.rw
INTEGER
.1.3.6.1.4.1.705.1.13.1
upsmgRemoteIpAddressAn object to give the IP address of the agent managing the remote UPS. This object could be read by managers to perform management of receptacle dependencies between two different agents.rw
IpAddress
.1.3.6.1.4.1.705.1.13.2
MG-SNMP-UPS-MIB - SNMP MIB Reference | MIBs Explorer