EXELTECH-XFERSW
AI MIB Summary
The EXELTECH-XFERSW MIB module provides SNMP management capabilities for Exeltech transfer switches, enabling the monitoring of port status, traffic statistics, and device health indicators. This module facilitates the collection of standard interface counters and operational state data required for network performance analysis and fault detection on Exeltech switching hardware.
The MIB module to describe exeltech's devices.
Main OID:
exeltechMIB.1.3.6.1.4.1.30320
52
Objects
Active
Status
1
Dependencies
Imported Objects
Objects
52 total| Object Name |
|---|
exeltechMIBThe MIB module to describe exeltech's
devices. MODULE-IDENTITY .1.3.6.1.4.1.30320 |
xferSw2 OBJECT IDENTIFIER .1.3.6.1.4.1.30320.1 |
objects OBJECT IDENTIFIER .1.3.6.1.4.1.30320.1.0 |
battery OBJECT IDENTIFIER .1.3.6.1.4.1.30320.1.0.0 |
batVThe present battery voltage. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.0.1 |
LowDC-trapBattery voltage low limit has been triggered. TRAP-TYPE .1.3.6.1.4.1.30320.1.0.0.1.0.1 |
HighDC-trapBattery voltage high limit has been triggered. TRAP-TYPE .1.3.6.1.4.1.30320.1.0.0.1.0.2 |
batIThe present battery current. Displayed in deciAmps. Divide by 10 to get amps.ro INTEGER .1.3.6.1.4.1.30320.1.0.0.2 |
aBusVThe present A bus DC voltage if present. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.0.3 |
bBusVThe present B bus DC voltage if present. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.0.4 |
source1 OBJECT IDENTIFIER .1.3.6.1.4.1.30320.1.0.1 |
voltage1aThe present RMS voltage of source 1a. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.1.1 |
current1aThe present RMS current of source 1a. Displayed in deciAmps. Divide by 10 to get amps.ro INTEGER .1.3.6.1.4.1.30320.1.0.1.2 |
freq1aThe present frequency of source 1a. Displayed in deciHertz. Divide by 10 to get hertz.ro INTEGER .1.3.6.1.4.1.30320.1.0.1.3 |
voltage1bThe present RMS voltage of source 1b. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.1.4 |
current1bThe present RMS current of source 1b. Displayed in deciAmps. Divide by 10 to get amps.ro INTEGER .1.3.6.1.4.1.30320.1.0.1.5 |
freq1bThe present frequency of source 1b. Displayed in deciHertz. Divide by 10 to get hertz.ro INTEGER .1.3.6.1.4.1.30320.1.0.1.6 |
ACVOut1The present RMS Output Voltage of source 1. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.1.7 |
SCRTemp1The present the SCR temperature of source 1. Displayed in Degrees C.ro INTEGER .1.3.6.1.4.1.30320.1.0.1.8 |
source2 OBJECT IDENTIFIER .1.3.6.1.4.1.30320.1.0.2 |
voltage2aThe present RMS voltage of source 2a. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.2.1 |
current2aThe present RMS current of source 2a. Displayed in deciAmps. Divide by 10 to get amps.ro INTEGER .1.3.6.1.4.1.30320.1.0.2.2 |
freq2aThe present frequency of source 2a. Displayed in deciHertz. Divide by 10 to get hertz.ro INTEGER .1.3.6.1.4.1.30320.1.0.2.3 |
voltage2bThe present RMS voltage of source 2b. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.2.4 |
current2bThe present RMS current of source 2b. Displayed in deciAmps. Divide by 10 to get amps.ro INTEGER .1.3.6.1.4.1.30320.1.0.2.5 |
freq2bThe present frequency of source 2b. Displayed in deciHertz. Divide by 10 to get hertz.ro INTEGER .1.3.6.1.4.1.30320.1.0.2.6 |
ACVOut2The present RMS Output Voltage of source 2. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.2.7 |
SCRTemp2The present the SCR temperature of source 2. Displayed in Degrees C.ro INTEGER .1.3.6.1.4.1.30320.1.0.2.8 |
source3 OBJECT IDENTIFIER .1.3.6.1.4.1.30320.1.0.3 |
voltage3aThe present RMS voltage of source 3a. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.3.1 |
current3aThe present RMS current of source 3a. Displayed in deciAmps. Divide by 10 to get amps.ro INTEGER .1.3.6.1.4.1.30320.1.0.3.2 |
freq3aThe present frequency of source 3a. Displayed in deciHertz. Divide by 10 to get hertz.ro INTEGER .1.3.6.1.4.1.30320.1.0.3.3 |
voltage3bThe present RMS voltage of source 3b. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.3.4 |
current3bThe present RMS current of source 3b. Displayed in deciAmps. Divide by 10 to get amps.ro INTEGER .1.3.6.1.4.1.30320.1.0.3.5 |
freq3bThe present frequency of source 3b. Displayed in deciHertz. Divide by 10 to get hertz.ro INTEGER .1.3.6.1.4.1.30320.1.0.3.6 |
ACVOut3The present RMS Output Voltage of source 3. Displayed in deciVolts. Divide by 10 to get voltage.ro INTEGER .1.3.6.1.4.1.30320.1.0.3.7 |
SCRTemp3The present the SCR temperature of source 3. Displayed in Degrees C.ro INTEGER .1.3.6.1.4.1.30320.1.0.3.8 |
Alarms OBJECT IDENTIFIER .1.3.6.1.4.1.30320.1.0.4 |
MinorAlarm-trapA minor alarm has been triggered. TRAP-TYPE .1.3.6.1.4.1.30320.1.0.4.0.3 |
MajorAlarm-trapA major alarm has been triggered. TRAP-TYPE .1.3.6.1.4.1.30320.1.0.4.0.4 |
source1AlarmsAlarms Status: This is a 2 byte and each bit represents an alarm.
0x0001 - Power Module Overtemp
0x0002 - Power Module Fail
0x0004 - Control Card Fail
0x0008 - One Source has failed or are not phase locked
0x0010 - LvAlarm
0x0020 - Control Card Overtemp
0x0040 - SCRs are Warm
0x0080 - Low DCV
0x0200 - Popk alarm - System not redunant
0x0400 - Both sources are dead
0x0800 - Fan Failed or Hot Temperaturero INTEGER .1.3.6.1.4.1.30320.1.0.4.1 |
source2AlarmsAlarms Status: This is a 2 byte and each bit represents an alarm.
0x0001 - Power Module Overtemp
0x0002 - Power Module Fail
0x0004 - Control Card Fail
0x0008 - One Source has failed or are not phase locked
0x0010 - LvAlarm
0x0020 - Control Card Overtemp
0x0040 - SCRs are Warm
0x0080 - Low DCV
0x0200 - Popk alarm - System not redunant
0x0400 - Both sources are dead
0x0800 - Fan Failed or Hot Temperaturero INTEGER .1.3.6.1.4.1.30320.1.0.4.2 |
source3AlarmsAlarms Status: This is a 2 byte and each bit represents an alarm.
0x0001 - Power Module Overtemp
0x0002 - Power Module Fail
0x0004 - Control Card Fail
0x0008 - One Source has failed or are not phase locked
0x0010 - LvAlarm
0x0020 - Control Card Overtemp
0x0040 - SCRs are Warm
0x0080 - Low DCV
0x0200 - Popk alarm - System not redunant
0x0400 - Both sources are dead
0x0800 - Fan Failed or Hot Temperaturero INTEGER .1.3.6.1.4.1.30320.1.0.4.3 |
MinorAlarmAlarms Status: 0 is no Alarm, 1 is any Minor Alarm on any phase.ro INTEGER .1.3.6.1.4.1.30320.1.0.4.4 |
MajorAlarmAlarms Status: 0 is no Alarm, 1 is any Major Alarm on any phase.ro INTEGER .1.3.6.1.4.1.30320.1.0.4.5 |
Settings OBJECT IDENTIFIER .1.3.6.1.4.1.30320.1.0.5 |
DCVLowThis value is the low DC Voltage limit for sending traps. The voltage
needs to be set in deciVolts. Multiply the voltage by 10 and then send
that value.rw INTEGER .1.3.6.1.4.1.30320.1.0.5.1 |
DCVHighThis value is the high DC Voltage limit for sending traps. The voltage
needs to be set in deciVolts. Multiply the voltage by 10 and then send
that value.rw INTEGER .1.3.6.1.4.1.30320.1.0.5.2 |
TrapTragetIp1Ip address of the first target for traps. Set to zero to remove from targets.rw IpAddress .1.3.6.1.4.1.30320.1.0.5.3 |
IpAddressStaticStatic Ip address of the system. Set to zero to use DHCP to obtain an Ip
address. Changes will be applied after network chip is reset.rw IpAddress .1.3.6.1.4.1.30320.1.0.5.4 |
SubnetMaskStaticSubnet mask for the system when using a static Ip address. Changes will
be applied after network chip is reset.rw IpAddress .1.3.6.1.4.1.30320.1.0.5.5 |
DefaultGatewayStaticDefault gateway for the system when using a static Ip address. Changes
will be applied after network chip is reset.rw IpAddress .1.3.6.1.4.1.30320.1.0.5.6 |