Home/Catalog/ENLOGIC-PDU-MIB

ENLOGIC-PDU-MIB

This MIB describes the SNMP functions of the Enlogic PDU.
Main OID:
enlogic.1.3.6.1.4.1.38446
446
Objects
Active
Status
5
Dependencies

Imported Objects

Objects

446 total
Object Name
enlogicThis MIB describes the SNMP functions of the Enlogic PDU.
MODULE-IDENTITY
.1.3.6.1.4.1.38446
pdu
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1
pduNamePlate
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.1
pduNamePlateTableSizeThe total number of PDUsro
Integer32
.1.3.6.1.4.1.38446.1.1.1
pduNamePlateTableA table of PDU nameplate data
SEQUENCE OF PduNamePlateEntry
.1.3.6.1.4.1.38446.1.1.2
pduNamePlateEntryNameplate data from the PDU being queried. The numbers of entries equals the value of pduNamePlateTableSize.
PduNamePlateEntry
.1.3.6.1.4.1.38446.1.1.2.1
pduNamePlateIndexThe index of the PDU nameplate table entry
Integer32
.1.3.6.1.4.1.38446.1.1.2.1.1
pduNamePlateNameA user-defined string identifying the PDUro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.1.2.1.2
pduNamePlateLocationA user-defined string identifying the location of PDUro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.1.2.1.3
pduNamePlateInetAddressTypeThe type of address formatro
InetAddressType (INET-ADDRESS-MIB)
.1.3.6.1.4.1.38446.1.1.2.1.4
pduNamePlateIPAddressThe current IP address. A value of 0.0.0.0 indicates an error or an unset optionro
InetAddress (INET-ADDRESS-MIB)
.1.3.6.1.4.1.38446.1.1.2.1.5
pduNamePlateInetNetMaskThe current netmask. A value of 0.0.0.0 indiates an error or an unset optionro
InetAddress (INET-ADDRESS-MIB)
.1.3.6.1.4.1.38446.1.1.2.1.6
pduNamePlateInetGatewayThe current gateway. A value of 0.0.0.0 indicates an error or an unset optionro
InetAddress (INET-ADDRESS-MIB)
.1.3.6.1.4.1.38446.1.1.2.1.7
pduNamePlateMACAddressThe assigned MAC address for the PDUro
MacAddress (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.1.2.1.8
pduNamePlateUTCTimeOffsetThe difference in hours and minutes from Coordinated Universal Time(UTC) for the time used in a particular time zonero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.1.2.1.9
pduNamePlateModelNumberThe PDU model numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.1.2.1.10
pduNamePlateSerialNumberThe PDU serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.1.2.1.11
pduNamePlateDateofManufactureThe date the PDU was manufactured in mm/dd/yyyy formatro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.1.2.1.12
pduNamePlateFirmwareVersionThe PDU firmware versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.1.2.1.13
pduNamePlateFirmwareVersionTimeStampTimestamp of when the PDU firmware was last updatedro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.1.2.1.14
pduNamePlateTypeThe type of Unit, PDU or Inline Meterro
Enumeration
.1.3.6.1.4.1.38446.1.1.2.1.15
pduUnit
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.2
pduUnitTableSizeThe number of units.ro
Integer32
.1.3.6.1.4.1.38446.1.2.1
pduUnitConfigTableA table of PDU configuration data
SEQUENCE OF PduUnitConfigEntry
.1.3.6.1.4.1.38446.1.2.2
pduUnitConfigEntryConfiguration data from the PDU being queried. The number of entries equals the value of pduUnitTableSize
PduUnitConfigEntry
.1.3.6.1.4.1.38446.1.2.2.1
pduUnitConfigIndexThe index of the PDU Unit Config Entry
Integer32
.1.3.6.1.4.1.38446.1.2.2.1.1
pduUnitConfigNameA user-defined string identifying the PDUrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.2.1.2
pduUnitConfigLocationA user-defined string identifying the location of the PDUrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.2.1.3
pduUnitConfigDisplayOrientationIndicates the intended physical orientation of the oLED display displayNormal (1) indicates normal orientation. displayReverse (2) indicates upside down orientationrw
Enumeration
.1.3.6.1.4.1.38446.1.2.2.1.4
pduUnitConfigColdstartDelayThe amount of time, specified in seconds, between when power is provided to the PDU and when the PDU start providing basic master power to the outletsrw
Unsigned32
.1.3.6.1.4.1.38446.1.2.2.1.5
pduUnitConfigGlobalOutletStateOnStartupThe outlet state on device startup; applies to all outlets unless overridden at the outlet levelrw
Enumeration
.1.3.6.1.4.1.38446.1.2.2.1.6
pduUnitConfigLowerCriticalThresholdUser-defined lower critical unit active power alarm threshold measured in Wattsrw
Unsigned32
.1.3.6.1.4.1.38446.1.2.2.1.7
pduUnitConfigLowerWarningThresholdUser-defined lower non-critical (warning) unit active power alarm threshold measured in Wattsrw
Unsigned32
.1.3.6.1.4.1.38446.1.2.2.1.8
pduUnitConfigUpperCriticalThresholdUser-defined upper critical unit active power alarm threshold measured in Wattsrw
Unsigned32
.1.3.6.1.4.1.38446.1.2.2.1.9
pduUnitConfigUpperWarningThresholdUser-defined upper non-critical (warning) unit active power alarm threshold measured in Wattsrw
Unsigned32
.1.3.6.1.4.1.38446.1.2.2.1.10
pduUnitConfigAlarmResetThresholdThe hysteresis used for deassertions in Wattsrw
Unsigned32
.1.3.6.1.4.1.38446.1.2.2.1.11
pduUnitConfigAlarmStateChangeDelayThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.rw
Unsigned32
.1.3.6.1.4.1.38446.1.2.2.1.12
pduUnitConfigEnabledThresholdsA bit string indicating which alarm thresholds are enabledrw
Bits
.1.3.6.1.4.1.38446.1.2.2.1.13
pduUnitConfigPeakPowerResetSetting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and return the noOperation(1) value.rw
Enumeration
.1.3.6.1.4.1.38446.1.2.2.1.14
pduUnitConfigEnergyResetSetting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.rw
Enumeration
.1.3.6.1.4.1.38446.1.2.2.1.15
pduUnitConfigOutletPeakPowerResetSetting this OID to reset (2) will cause the outlet peak power meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.rw
Enumeration
.1.3.6.1.4.1.38446.1.2.2.1.16
pduUnitConfigOutletEnergyResetSetting this OID to reset (2) will cause the outlet energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.rw
Enumeration
.1.3.6.1.4.1.38446.1.2.2.1.17
pduUnitConfigUsbSetting this OID to off(0) will disable the USB port. Setting this OID to on(1) will enable the USB port.rw
Enumeration
.1.3.6.1.4.1.38446.1.2.2.1.18
pduUnitConfigSshSetting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection.rw
Enumeration
.1.3.6.1.4.1.38446.1.2.2.1.19
pduUnitConfigResetNetworkManagementCardGetting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC.rw
Enumeration
.1.3.6.1.4.1.38446.1.2.2.1.20
pduUnitConfigDaisyChainStateSetting this OID to daisychain(0) will enable daisychain mode.rw
Enumeration
.1.3.6.1.4.1.38446.1.2.2.1.21
pduUnitPropertiesTableA table of PDU properties
SEQUENCE OF PduUnitPropertiesEntry
.1.3.6.1.4.1.38446.1.2.3
pduUnitPropertiesEntryA unit properties entry containing objects for a particular unit.
PduUnitPropertiesEntry
.1.3.6.1.4.1.38446.1.2.3.1
pduUnitPropertiesIndexThe index of the PDU properties table entry
Integer32
.1.3.6.1.4.1.38446.1.2.3.1.1
pduUnitPropertiesNameA user-defined string identifying the PDUro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.3.1.2
pduUnitPropertiesOutletCountThe total number of outlets on the PDUro
Integer32
.1.3.6.1.4.1.38446.1.2.3.1.3
pduUnitPropertiesSwitchedOutletCountThe total number of switched outlets on the PDUro
Integer32
.1.3.6.1.4.1.38446.1.2.3.1.4
pduUnitPropertiesMeteredOutletCountThe total number of metered outlets on the PDUro
Integer32
.1.3.6.1.4.1.38446.1.2.3.1.5
pduUnitPropertiesInputPhaseCountThe total number of phases on the PDUro
Integer32
.1.3.6.1.4.1.38446.1.2.3.1.6
pduUnitPropertiesCircuitBreakerCountThe total number of circuit breaker on the PDUro
Integer32
.1.3.6.1.4.1.38446.1.2.3.1.7
pduUnitPropertiesMaxExternalSensorCountThe maximum number of external sensors that can be connected to the PDUro
Integer32
.1.3.6.1.4.1.38446.1.2.3.1.8
pduUnitPropertiesConnExternalSensorCountThe current number of external sensors connected to the PDUro
Integer32
.1.3.6.1.4.1.38446.1.2.3.1.9
pduUnitPropertiesRatedVoltageThe PDU voltage rating in Voltsro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.3.1.10
pduUnitPropertiesRatedMaxCurrentThe PDU current rating in Ampsro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.3.1.11
pduUnitPropertiesRatedFrequencyThe PDU frequency rating in Hzro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.3.1.12
pduUnitPropertiesRatedPowerThe PDU VA (VoltAmps) rating.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.3.1.13
pduUnitPropertiesOrientationThe PDU orientationro
Enumeration
.1.3.6.1.4.1.38446.1.2.3.1.14
pduUnitPropertiesOutletLayoutThe outlet layout for the PDU. Getting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... seqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... seqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... seqPhToPhGrouped(4) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-2, Group 2:2-3, Group 3:3-1. seqPhToNGrouped(5) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N. seqPToN1516PToPGrouped(6) indicates outlet layout as follows: This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2, Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1. seqPhToPh2xGrouped(7) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3, Group 4:2-3, Group 5:3-1, Group 6:3-1. seqPhToN2xGrouped(8) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N, Group 4:2-N, Group 5:3-N, Group 6:3-N. seqNotApplicable(9):ro
Enumeration
.1.3.6.1.4.1.38446.1.2.3.1.15
pduUnitPropertiesDaisyChainMemberTypeThe daisy-chain member typero
Enumeration
.1.3.6.1.4.1.38446.1.2.3.1.16
pduUnitPropertiesServerCountThe number of serversro
Integer32
.1.3.6.1.4.1.38446.1.2.3.1.17
pduUnitStatusTableA table of PDU status information
SEQUENCE OF PduUnitStatusEntry
.1.3.6.1.4.1.38446.1.2.4
pduUnitStatusEntryStatus information from the PDU being queried
PduUnitStatusEntry
.1.3.6.1.4.1.38446.1.2.4.1
pduUnitStatusIndexThe index of the PDU status table entry
Integer32
.1.3.6.1.4.1.38446.1.2.4.1.1
pduUnitStatusNameA user-defined string identifying the PDUro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.4.1.2
pduUnitStatusLoadStateReturns the present load status of the PDU based on Active Power.ro
Enumeration
.1.3.6.1.4.1.38446.1.2.4.1.3
pduUnitStatusActivePowerReturns power consumption, in Watts(W), of the PDU being queried.ro
Integer32
.1.3.6.1.4.1.38446.1.2.4.1.4
pduUnitStatusApparentPowerReturns power consumption, in Volt-Amps(VA) of the PDU load being queried.ro
Integer32
.1.3.6.1.4.1.38446.1.2.4.1.5
pduUnitStatusPeakPowerReturns peak power consumption, in Watts(W), of the PDU being queried.ro
Integer32
.1.3.6.1.4.1.38446.1.2.4.1.6
pduUnitStatusPeakPowerTimestampIndicates the date and time that peak power consumption occurredro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.4.1.7
pduUnitStatusPeakPowerStartTimeIndicates the date and time of the last device peak power resetro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.4.1.8
pduUnitStatusEnergyReturns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime.ro
Integer32
.1.3.6.1.4.1.38446.1.2.4.1.9
pduUnitStatusResettableEnergyA user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh).ro
Integer32
.1.3.6.1.4.1.38446.1.2.4.1.10
pduUnitStatusEnergyStartTimeIndicates the date and time of the last device energy meter resetro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.4.1.11
pduUnitStatusOutletsEnergyStartTimeIndicates the date and time of the last outlets energy meter resetro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.2.4.1.12
pduInputPhase
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.3
pduInputPhaseTableSizeThe number of PDU Input Phasesro
Integer32
.1.3.6.1.4.1.38446.1.3.1
pduInputPhaseConfigTableA table of PDU Input Phase configuration data
SEQUENCE OF PduInputPhaseConfigEntry
.1.3.6.1.4.1.38446.1.3.2
pduInputPhaseConfigEntryAn input phase entry containing objects for a particular input phase.
PduInputPhaseConfigEntry
.1.3.6.1.4.1.38446.1.3.2.1
pduInputPhaseConfigIndexThe index of the PDU Input Phase configuration table entry
Integer32
.1.3.6.1.4.1.38446.1.3.2.1.1
pduInputPhaseConfigCountThe total number of Input Phasesro
Integer32
.1.3.6.1.4.1.38446.1.3.2.1.2
pduInputPhaseConfigOverloadRestrictionThis OID controls the behavior of a Switched PDU Input Phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Input Phase to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.rw
Enumeration
.1.3.6.1.4.1.38446.1.3.2.1.3
pduInputPhaseConfigCurrentLowerCriticalThresholdUser-defined lower critical input phase current alarm threshold in hundredths of Amps(A).rw
Unsigned32
.1.3.6.1.4.1.38446.1.3.2.1.4
pduInputPhaseConfigCurrentLowerWarningThresholdUser-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A).rw
Unsigned32
.1.3.6.1.4.1.38446.1.3.2.1.5
pduInputPhaseConfigCurrentUpperCriticalThresholdUser-defined upper critical input phase current alarm threshold in hundredths of Amps(A).rw
Unsigned32
.1.3.6.1.4.1.38446.1.3.2.1.6
pduInputPhaseConfigCurrentUpperWarningThresholdUser-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A).rw
Unsigned32
.1.3.6.1.4.1.38446.1.3.2.1.7
pduInputPhaseConfigVoltageLowerCriticalThresholdUser-defined lower critical input phase voltage alarm threshold in Volts(V).rw
Unsigned32
.1.3.6.1.4.1.38446.1.3.2.1.8
pduInputPhaseConfigVoltageLowerWarningThresholdUser-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V).rw
Unsigned32
.1.3.6.1.4.1.38446.1.3.2.1.9
pduInputPhaseConfigVoltageUpperCriticalThresholdUser-defined upper critical input phase voltage alarm threshold in Volts(V).rw
Unsigned32
.1.3.6.1.4.1.38446.1.3.2.1.10
pduInputPhaseConfigVoltageUpperWarningThresholdUser-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V).rw
Unsigned32
.1.3.6.1.4.1.38446.1.3.2.1.11
pduInputPhaseConfigCurrentAlarmResetThresholdThe hysteresis used for current alarm deassertions in hundredths of Amps(A).rw
Unsigned32
.1.3.6.1.4.1.38446.1.3.2.1.12
pduInputPhaseConfigCurrentAlarmStateChangeDelayThe delay measured in samples before a current state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.rw
Integer32
.1.3.6.1.4.1.38446.1.3.2.1.13
pduInputPhaseConfigCurrentEnabledThresholdsA bit string indicating which current alarm thresholds are enabled.rw
Bits
.1.3.6.1.4.1.38446.1.3.2.1.14
pduInputPhaseConfigVoltageAlarmResetThresholdThe hysteresis used for voltage alarm deassertions in Volts(V).rw
Unsigned32
.1.3.6.1.4.1.38446.1.3.2.1.15
pduInputPhaseConfigVoltageAlarmStateChangeDelayThe delay measured in samples before a voltage state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.rw
Integer32
.1.3.6.1.4.1.38446.1.3.2.1.16
pduInputPhaseConfigVoltageEnabledThresholdsA bit string indicating which voltage alarm thresholds are enabled.rw
Bits
.1.3.6.1.4.1.38446.1.3.2.1.17
pduInputPhasePropertiesTableA table of PDU Input Phase properties
SEQUENCE OF PduInputPhasePropertiesEntry
.1.3.6.1.4.1.38446.1.3.3
pduInputPhasePropertiesEntryAn input phase properties entry containing objects for a particular input phase.
PduInputPhasePropertiesEntry
.1.3.6.1.4.1.38446.1.3.3.1
pduInputPhasePropertiesIndexThe index of the PDU Input Phase status entry
Integer32
.1.3.6.1.4.1.38446.1.3.3.1.1
pduInputPhasePropertiesCountThe numeric Input Phase IDro
Integer32
.1.3.6.1.4.1.38446.1.3.3.1.2
pduInputPhaseStatusTableA table of PDU Input Phase status data
SEQUENCE OF PduInputPhaseStatusEntry
.1.3.6.1.4.1.38446.1.3.4
pduInputPhaseStatusEntryAn input phase status entry containing objects for a particular input phase.
PduInputPhaseStatusEntry
.1.3.6.1.4.1.38446.1.3.4.1
pduInputPhaseStatusIndexThe index of the PDU Input Phase status entry
Integer32
.1.3.6.1.4.1.38446.1.3.4.1.1
pduInputPhaseStatusCountThe numeric Input Phase IDro
Integer32
.1.3.6.1.4.1.38446.1.3.4.1.2
pduInputPhaseStatusCurrentStateIndicates the present current status of the PDU Phase in case of Y connection or PDU Line in case of Delta conneciton.ro
Enumeration
.1.3.6.1.4.1.38446.1.3.4.1.3
pduInputPhaseStatusVoltageStateIndicates the present voltage status of the PDU Input Phase being queriedro
Enumeration
.1.3.6.1.4.1.38446.1.3.4.1.4
pduInputPhaseStatusCurrentReturns the current draw, in hundredths of Amps(A), of the load on the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.ro
Integer32
.1.3.6.1.4.1.38446.1.3.4.1.5
pduInputPhaseStatusVoltageReturns the voltage, in Volts(V), of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.ro
Integer32
.1.3.6.1.4.1.38446.1.3.4.1.6
pduInputPhaseStatusActivePowerReturns power consumption, in Watts(W), consumed on the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.ro
Integer32
.1.3.6.1.4.1.38446.1.3.4.1.7
pduInputPhaseStatusApparentPowerReturns power consumption, in Volt-Amps(VA), of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.ro
Integer32
.1.3.6.1.4.1.38446.1.3.4.1.8
pduInputPhaseStatusPowerFactorReturns the ratio of active to apparent power of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values.ro
Integer32
.1.3.6.1.4.1.38446.1.3.4.1.9
pduCircuitBreaker
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.4
pduCircuitBreakerTableSizeThe number of PDU Circuit Breakersro
Integer32
.1.3.6.1.4.1.38446.1.4.1
pduCircuitBreakerConfigTableA table of PDU Circuit Breaker configuration data
SEQUENCE OF PduCircuitBreakerConfigEntry
.1.3.6.1.4.1.38446.1.4.2
pduCircuitBreakerConfigEntryA circuit breaker configuration entry containing objects for a particular circuit breaker.
PduCircuitBreakerConfigEntry
.1.3.6.1.4.1.38446.1.4.2.1
pduCircuitBreakerConfigIndexThe index of the PDU Circuit Breaker configuration table entry
Integer32
.1.3.6.1.4.1.38446.1.4.2.1.1
pduCircuitBreakerConfigCountThe number of circuit breakers on the PDUro
Integer32
.1.3.6.1.4.1.38446.1.4.2.1.2
pduCircuitBreakerNameThe label of the circuit breakerro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.4.2.1.3
pduCircuitBreakerConfigOverloadRestrictionThis OID controls the behavior of a Switched PDU Circuit Breaker when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Circuit Breaker to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.rw
Enumeration
.1.3.6.1.4.1.38446.1.4.2.1.4
pduCircuitBreakerConfigLowerCriticalThresholdUser-defined lower critical circuit breaker current alarm threshold in hundredths of Amps(A).rw
Unsigned32
.1.3.6.1.4.1.38446.1.4.2.1.5
pduCircuitBreakerConfigLowerWarningThresholdUser-defined lower non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A).rw
Unsigned32
.1.3.6.1.4.1.38446.1.4.2.1.6
pduCircuitBreakerConfigUpperCriticalThresholdUser-defined upper critical circuit breaker current alarm threshold in hundredths of Amps(A).rw
Unsigned32
.1.3.6.1.4.1.38446.1.4.2.1.7
pduCircuitBreakerConfigUpperWarningThresholdUser-defined upper non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A).rw
Unsigned32
.1.3.6.1.4.1.38446.1.4.2.1.8
pduCircuitBreakerConfigAlarmResetThresholdThe hysteresis used for deassertions in hundredths of Amps(A).rw
Unsigned32
.1.3.6.1.4.1.38446.1.4.2.1.9
pduCircuitBreakerConfigAlarmStateChangeDelayThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.rw
Unsigned32
.1.3.6.1.4.1.38446.1.4.2.1.10
pduCircuitBreakerConfigEnabledThresholdsA bit string indicating which alarm thresholds are enabled.rw
Bits
.1.3.6.1.4.1.38446.1.4.2.1.11
pduCircuitBreakerPropertiesTableA table of PDU circuit breaker properties
SEQUENCE OF PduCircuitBreakerPropertiesEntry
.1.3.6.1.4.1.38446.1.4.3
pduCircuitBreakerPropertiesEntryA circuit breaker properties entry containing objects for a particular circuit breaker.
PduCircuitBreakerPropertiesEntry
.1.3.6.1.4.1.38446.1.4.3.1
pduCircuitBreakerPropertiesIndexThe index of the PDU Circuit Breaker properties table entry
Integer32
.1.3.6.1.4.1.38446.1.4.3.1.1
pduCircuitBreakerPropertiesCountThe number of Circuit Breakersro
Integer32
.1.3.6.1.4.1.38446.1.4.3.1.2
pduCircuitBreakerPropertiesInputLayoutThis OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to circuit breaker are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to circuit breaker are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to circuit breaker are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to circuit breaker are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to circuit breaker are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to circuit breaker are connected from Phase 3 to Phase1.ro
Enumeration
.1.3.6.1.4.1.38446.1.4.3.1.3
pduCircuitBreakerStatusTableA table of PDU circuit breaker status data
SEQUENCE OF PduCircuitBreakerStatusEntry
.1.3.6.1.4.1.38446.1.4.4
pduCircuitBreakerStatusEntryA circuit breaker status entry containing objects for a particular circuit breaker.
PduCircuitBreakerStatusEntry
.1.3.6.1.4.1.38446.1.4.4.1
pduCircuitBreakerStatusIndexThe index of the PDU Circuit Breaker status table entry
Integer32
.1.3.6.1.4.1.38446.1.4.4.1.1
pduCircuitBreakerStatusCountThe number of Circuit Breakersro
Integer32
.1.3.6.1.4.1.38446.1.4.4.1.2
pduCircuitBreakerLabelThe label on the PDU identifying the circuit breakerro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.4.4.1.3
pduCircuitBreakerStatusLoadStateIndicates the present load status of the PDU Circuit Breaker being queriedro
Enumeration
.1.3.6.1.4.1.38446.1.4.4.1.4
pduCircuitBreakerStatusCurrentReturns the current draw, in hundredths of Amps(A), of the load on the PDU Circuit Breaker being queried.ro
Integer32
.1.3.6.1.4.1.38446.1.4.4.1.5
pduOutlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.5
pduOutletSwitchedTableSizeThe number of PDU Outletsro
Integer32
.1.3.6.1.4.1.38446.1.5.1
pduOutletSwitchedConfigTableA table of PDU Switched Outlet configuration data
SEQUENCE OF PduOutletSwitchedConfigEntry
.1.3.6.1.4.1.38446.1.5.2
pduOutletSwitchedConfigEntryAn outlet configuration entry containing objects for a particular outlet.
PduOutletSwitchedConfigEntry
.1.3.6.1.4.1.38446.1.5.2.1
pduOutletSwitchedConfigIndexThe index of the PDU Switched Outlet configuration table entry
Integer32
.1.3.6.1.4.1.38446.1.5.2.1.1
pduOutletSwitchedNameThe user-defined name for the Switched Outletrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.5.2.1.2
pduOutletSwitchedStateOnStartupThe outlet state on device startup; overrides the global value pduUnitConfigGlobalOutletStateOnStartup.rw
Enumeration
.1.3.6.1.4.1.38446.1.5.2.1.3
pduOutletSwitchedConfigPowerOnTimeThe amount of delay, in seconds, between when power is provided to outlets the outlet and when this outlet starts providing powerrw
Integer32
.1.3.6.1.4.1.38446.1.5.2.1.4
pduOutletSwitchedConfigPowerOffTimeThe amount of time, in seconds, this outlet will delay powering offrw
Integer32
.1.3.6.1.4.1.38446.1.5.2.1.5
pduOutletSwitchedConfigRebootDurationThe amount of time, in seconds, this outlet will remain in powered off state before returning to power on state during a reboot action.rw
Integer32
.1.3.6.1.4.1.38446.1.5.2.1.6
pduOutletSwitchedPropertiesTableA table of PDU Switched Outlet properties
SEQUENCE OF PduOutletSwitchedPropertiesEntry
.1.3.6.1.4.1.38446.1.5.3
pduOutletSwitchedPropertiesEntryAn outlet properties entry containing objects for a particular outlet.
PduOutletSwitchedPropertiesEntry
.1.3.6.1.4.1.38446.1.5.3.1
pduOutletSwitchedPropertiesIndexThe index of the PDU Switched Outlet properties table entry
Integer32
.1.3.6.1.4.1.38446.1.5.3.1.1
pduOutletSwitchedPropertiesNumberThe numeric Switched Outlet IDro
Integer32
.1.3.6.1.4.1.38446.1.5.3.1.2
pduOutletSwitchedPropertiesNameThe user-defined switched outlet ID stringro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.5.3.1.3
pduOutletSwitchedPropertiesInputPhaseLayoutThis OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to Switched Outlet are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to Switched Outlet are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to Switched Outlet are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to Switched Outlet are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to Switched Outlet are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to Switched Outlet are connected from Phase 3 to Phase1.ro
Enumeration
.1.3.6.1.4.1.38446.1.5.3.1.4
pduOutletSwitchedPropertiesCircuitBreakerThe numeric Circuit Breaker IDro
Integer32
.1.3.6.1.4.1.38446.1.5.3.1.5
pduOutletSwitchedStatusTableA table of PDU Switched Outlet status data
SEQUENCE OF PduOutletSwitchedStatusEntry
.1.3.6.1.4.1.38446.1.5.4
pduOutletSwitchedStatusEntryStatus data from the PDU Switched Outlet being queried
PduOutletSwitchedStatusEntry
.1.3.6.1.4.1.38446.1.5.4.1
pduOutletSwitchedStatusIndexThe index of the PDU Switched Outlet status table entry
Integer32
.1.3.6.1.4.1.38446.1.5.4.1.1
pduOutletSwitchedStatusNumberThe numeric Switched Outlet IDro
Integer32
.1.3.6.1.4.1.38446.1.5.4.1.2
pduOutletSwitchedStatusNameThe user-defined switched outlet ID stringro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.5.4.1.3
pduOutletSwitchedStatusStateIndicates the present switch state of the PDU switched outlet being queriedro
Enumeration
.1.3.6.1.4.1.38446.1.5.4.1.4
pduOutletSwitchedControlTableA table of PDU Switched Outlet status data
SEQUENCE OF PduOutletSwitchedControlEntry
.1.3.6.1.4.1.38446.1.5.5
pduOutletSwitchedControlEntryStatus data from the PDU Switched Outlet being queried
PduOutletSwitchedControlEntry
.1.3.6.1.4.1.38446.1.5.5.1
pduOutletSwitchedControlIndexThe index to the PDU switched outlet control data table entry
Integer32
.1.3.6.1.4.1.38446.1.5.5.1.1
pduOutletSwitchedControlNumberThe numeric Switched Outlet IDro
Integer32
.1.3.6.1.4.1.38446.1.5.5.1.2
pduOutletSwitchedControlNameThe user-defined switched outlet ID stringro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.5.5.1.3
pduOutletSwitchedControlCommandGetting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (1) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (7) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (2) will immediately turn the outlet on. Setting this variable to immediateOff (1) will immediately turn the outlet off. Setting this variable to immediateReboot (5) will cause the Switched PDU to perform an immediateOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (4) will turn the outlet on after the pduOutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (3) will turn the outlet off after the pduOutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched PDU to perform a delayedOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command.rw
Enumeration
.1.3.6.1.4.1.38446.1.5.5.1.4
pduOutletMeteredTableSizeThe number of PDU Outletsro
Integer32
.1.3.6.1.4.1.38446.1.5.6
pduOutletMeteredConfigTableA table of PDU Metered Outlet configuration data
SEQUENCE OF PduOutletMeteredConfigEntry
.1.3.6.1.4.1.38446.1.5.7
pduOutletMeteredConfigEntryAn outlet configuration entry containing objects for a particular outlet.
PduOutletMeteredConfigEntry
.1.3.6.1.4.1.38446.1.5.7.1
pduOutletMeteredConfigIndexThe index of the PDU Metered Outlet configuration table entry
Integer32
.1.3.6.1.4.1.38446.1.5.7.1.1
pduOutletMeteredNameThe user-defined name for the Metered Outletrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.5.7.1.2
pduOutletMeteredConfigLowerCriticalThresholdUser-defined lower critical outlet active power alarm threshold in Watts(W).rw
Unsigned32
.1.3.6.1.4.1.38446.1.5.7.1.3
pduOutletMeteredConfigLowerWarningThresholdUser-defined lower non-critical (warning) outlet active power alarm threshold in Watts(W).rw
Unsigned32
.1.3.6.1.4.1.38446.1.5.7.1.4
pduOutletMeteredConfigUpperCriticalThresholdUser-defined upper critical outlet active power alarm threshold in Watts(W).rw
Unsigned32
.1.3.6.1.4.1.38446.1.5.7.1.5
pduOutletMeteredConfigUpperWarningThresholdUser-defined upper non-critical (warning) outlet active power alarm threshold in Watts(W).rw
Unsigned32
.1.3.6.1.4.1.38446.1.5.7.1.6
pduOutletMeteredConfigAlarmResetThresholdThe hysteresis used for deassertions in Watts(W).rw
Unsigned32
.1.3.6.1.4.1.38446.1.5.7.1.7
pduOutletMeteredConfigAlarmStateChangeDelayThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.rw
Unsigned32
.1.3.6.1.4.1.38446.1.5.7.1.8
pduOutletMeteredConfigEnabledThresholdsA bit string indicating which alarm thresholds are enabled.rw
Bits
.1.3.6.1.4.1.38446.1.5.7.1.9
pduOutletMeteredPropertiesTableA table of PDU Metered Outlet properties
SEQUENCE OF PduOutletMeteredPropertiesEntry
.1.3.6.1.4.1.38446.1.5.8
pduOutletMeteredPropertiesEntryConfiguration data from the PDU Metered Outlet being queried
PduOutletMeteredPropertiesEntry
.1.3.6.1.4.1.38446.1.5.8.1
pduOutletMeteredPropertiesIndexThe index of the PDU Metered Outlet properties table entry
Integer32
.1.3.6.1.4.1.38446.1.5.8.1.1
pduOutletMeteredPropertiesNumberThe numeric Metered Outlet IDro
Integer32
.1.3.6.1.4.1.38446.1.5.8.1.2
pduOutletMeteredPropertiesNameThe user-defined Metered outlet ID stringro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.5.8.1.3
pduOutletMeteredPropertiesInputPhaseLayoutThis OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to Metered Outlet are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to Metered Outlet are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to Metered Outlet are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to Metered Outlet are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to Metered Outlet are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to Metered Outlet are connected from Phase 3 to Phase1.ro
Enumeration
.1.3.6.1.4.1.38446.1.5.8.1.4
pduOutletMeteredPropertiesCircuitBreakerThe numeric Circuit Breaker IDro
Integer32
.1.3.6.1.4.1.38446.1.5.8.1.5
pduOutletMeteredPropertiesPowerRatingMaximum power rating of the PDU metered outletro
Integer32
.1.3.6.1.4.1.38446.1.5.8.1.6
pduOutletMeteredStatusTableA table of PDU Metered Outlet status data
SEQUENCE OF PduOutletMeteredStatusEntry
.1.3.6.1.4.1.38446.1.5.9
pduOutletMeteredStatusEntryStatus data from the PDU Metered Outlet being queried
PduOutletMeteredStatusEntry
.1.3.6.1.4.1.38446.1.5.9.1
pduOutletMeteredStatusIndexThe index of the PDU Metered Outlet status table entry
Integer32
.1.3.6.1.4.1.38446.1.5.9.1.1
pduOutletMeteredStatusNumberThe numeric Metered Outlet IDro
Integer32
.1.3.6.1.4.1.38446.1.5.9.1.2
pduOutletMeteredStatusNameThe user-defined Metered outlet ID stringro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.5.9.1.3
pduOutletMeteredStatusLoadStateReturns the present load status of the PDU metered outlet being queried.ro
Enumeration
.1.3.6.1.4.1.38446.1.5.9.1.4
pduOutletMeteredStatusCurrentReturns the current draw, in hundredths of Amps(A), of the load on the PDU outlet being queried.ro
Integer32
.1.3.6.1.4.1.38446.1.5.9.1.5
pduOutletMeteredStatusActivePowerReturns the power draw, in Watts(W), of the load on the PDU outlet being queried.ro
Integer32
.1.3.6.1.4.1.38446.1.5.9.1.6
pduOutletMeteredStatusPowerFactorReturns the ratio of active to apparent power of the PDU Outlet being queriedro
Integer32
.1.3.6.1.4.1.38446.1.5.9.1.7
pduOutletMeteredStatusPeakPowerReturns peak power consumption, in Watts(W), of the Rack PDU outlet being queried.ro
Integer32
.1.3.6.1.4.1.38446.1.5.9.1.8
pduOutletMeteredStatusPeakPowerTimeStampIndicates the date and time that this metered outlet's peak power consumption occurredro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.5.9.1.9
pduOutletMeteredStatusPeakPowerStartTimeIndicates the start date and time that this metered outlet began recording peak power observationsro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.5.9.1.10
pduOutletMeteredStatusResettableEnergyA user resettable energy meter measuring outlet load energy consumption in tenths of Kilowatt-Hours(kWh).ro
Integer32
.1.3.6.1.4.1.38446.1.5.9.1.11
pduExternalSensor
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.6
pduExternalSensorTableSizeThe total number of External Sensorsro
Integer32
.1.3.6.1.4.1.38446.1.6.1
pduExternalSensorNamePlateTableA table of PDU ExternalSensorNamePlate data
SEQUENCE OF PduExternalSensorNamePlateEntry
.1.3.6.1.4.1.38446.1.6.2
pduExternalSensorNamePlateEntryExternal Sensor Name Plate data from the external sensor being queried. The number of entries equals the value of pduExternalSensorNamePlateTableSize.
PduExternalSensorNamePlateEntry
.1.3.6.1.4.1.38446.1.6.2.1
pduExternalSensorNamePlateIndexThe index of the PDU External Sensor status table entry
Integer32
.1.3.6.1.4.1.38446.1.6.2.1.1
pduExternalSensorNamePlateNameA user-defined string identifying the external sensorrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.6.2.1.2
pduExternalSensorNamePlateDescriptionA user-defined description of the external sensorrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.6.2.1.3
pduExternalSensorNamePlateLocationA user-defined string identifying the location of the PDUrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.6.2.1.4
pduExternalSensorNamePlateSerialNumberThe serial number of the external sensor being queriedro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.6.2.1.5
pduExternalSensorNamePlateTypeThe type of external sensor.ro
Enumeration
.1.3.6.1.4.1.38446.1.6.2.1.6
pduExternalSensorNamePlateUnitsThe base units the external sensor is measured in. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.ro
Enumeration
.1.3.6.1.4.1.38446.1.6.2.1.7
pduExternalSensorNamePlateIdentifierUnique identifier of the external sensor.ro
Integer32
.1.3.6.1.4.1.38446.1.6.2.1.8
pduExternalSensorConfigTableA table of PDU External Sensor configuration data
SEQUENCE OF PduExternalSensorConfigEntry
.1.3.6.1.4.1.38446.1.6.3
pduExternalSensorConfigEntryConfiguration data from the PDU External Sensor being queried
PduExternalSensorConfigEntry
.1.3.6.1.4.1.38446.1.6.3.1
pduExternalSensorConfigIndexThe index of the PDU External Sensor configuration table entry
Integer32
.1.3.6.1.4.1.38446.1.6.3.1.1
pduExternalSensorConfigLowerCriticalThresholdUser-defined lower critical alarm threshold in pduExternalSensorNamePlateUnits.rw
Unsigned32
.1.3.6.1.4.1.38446.1.6.3.1.2
pduExternalSensorConfigLowerWarningThresholdUser-defined lower non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits.rw
Unsigned32
.1.3.6.1.4.1.38446.1.6.3.1.3
pduExternalSensorConfigUpperCriticalThresholdUser-defined upper critical alarm threshold in pduExternalSensorNamePlateUnits.rw
Unsigned32
.1.3.6.1.4.1.38446.1.6.3.1.4
pduExternalSensorConfigUpperWarningThresholdUser-defined upper non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits.rw
Unsigned32
.1.3.6.1.4.1.38446.1.6.3.1.5
pduExternalSensorConfigAlarmResetThresholdThe hysteresis used for deassertions.rw
Unsigned32
.1.3.6.1.4.1.38446.1.6.3.1.6
pduExternalSensorConfigAlarmStateChangeDelayThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported.rw
Unsigned32
.1.3.6.1.4.1.38446.1.6.3.1.7
pduExternalSensorConfigEnabledThresholdsA bit string indicating which alarm thresholds are enabled.rw
Bits
.1.3.6.1.4.1.38446.1.6.3.1.8
pduExternalSensorConfigAlarmStateUser defined alarm state of external sensorrw
Enumeration
.1.3.6.1.4.1.38446.1.6.3.1.9
pduExternalSensorStatusTableA table of PDU External Sensor status data
SEQUENCE OF PduExternalSensorStatusEntry
.1.3.6.1.4.1.38446.1.6.4
pduExternalSensorStatusEntryStatus data from the PDU External Sensor being queried
PduExternalSensorStatusEntry
.1.3.6.1.4.1.38446.1.6.4.1
pduExternalSensorStatusIndexThe index of the PDU External Sensor status table entry
Integer32
.1.3.6.1.4.1.38446.1.6.4.1.1
pduExternalSensorStatusNameThe user-defined name for the External Sensorro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.6.4.1.2
pduExternalSensorStatusAisleIndicates whether the external sensor is in a hot or cold aislerw
Enumeration
.1.3.6.1.4.1.38446.1.6.4.1.3
pduExternalSensorStatusCommStatusThe communications status of the sensorro
Enumeration
.1.3.6.1.4.1.38446.1.6.4.1.4
pduExternalSensorStatusStateThis OID reports the current state of the sensor. A notPresent (0) response indicates that no sensor is attached. An alarmed (1) response indicates that the sensor is present and its measured reading indicates alarmed. A normal (2) response indicates that the sensor is present and its measured reading lies within all thresholds. A belowLowerCritical (3) response indicates that the sensor is present and its measured reading lies below the lower critical threshold. A belowLowerWarning (4) response indicates that the sensor is present and its measured reading lies below the lower warning threshold. An aboveUpperWarning (5) response indicates that the sensor is present and its measured reading lies above the upper warning threshold. An aboveUpperCritical (6) response indicates that the sensor is present and its measured reading lies above the upper critical threshold.ro
Enumeration
.1.3.6.1.4.1.38446.1.6.4.1.5
pduExternalSensorStatusValueSensor reading in pduExternalSensorConfigUnits value.ro
Integer32
.1.3.6.1.4.1.38446.1.6.4.1.6
pduExternalSensorStatusTimeStampThe sensor reading timestamp.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.6.4.1.7
pduExternalSensorStatusHighPrecisionValueTemperature sensor reading in tenths of pduExternalSensorConfigUnits value. This OID is applied to temperature sensor onlyro
Integer32
.1.3.6.1.4.1.38446.1.6.4.1.8
pduServerPing
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.7
pduServerPingTableSizeThe total number of Serversro
Integer32
.1.3.6.1.4.1.38446.1.7.1
pduServerPingTableA table of Server Ping data
SEQUENCE OF PduServerPingEntry
.1.3.6.1.4.1.38446.1.7.2
pduServerPingEntryServer Ping data from the server being queried. The number of entries equals the value of pduServerPingTableSize.
PduServerPingEntry
.1.3.6.1.4.1.38446.1.7.2.1
pduServerPingIndexThe index of the PDU pduServerPing table entry
Integer32
.1.3.6.1.4.1.38446.1.7.2.1.1
pduServerPingServerIPAddressThe IP Address/host name of the serverro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.7.2.1.2
pduServerPingEnabledIs ping enabled for this server?rw
Enumeration
.1.3.6.1.4.1.38446.1.7.2.1.3
pduSmartCabinet
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.8
pduUnitSmartCabinetTableSizeThe total number of Smart Cabinet Configurationro
Integer32
.1.3.6.1.4.1.38446.1.8.1
pduUnitSmartCabinetTableA table of Smart Cabinet information
SEQUENCE OF PduUnitSmartCabinetEntry
.1.3.6.1.4.1.38446.1.8.2
pduUnitSmartCabinetEntryInformation of Smart Cabinet
PduUnitSmartCabinetEntry
.1.3.6.1.4.1.38446.1.8.2.1
pduUnitSmartCabinetIndexThe index of the PDU Smart Cabinet table entry
Integer32
.1.3.6.1.4.1.38446.1.8.2.1.1
pduUnitSmartCabinetCardUserNameUser name of ID cardro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.8.2.1.2
pduUnitSmartCabinetCardIDCard ID.ro
Integer32
.1.3.6.1.4.1.38446.1.8.2.1.3
pduUnitSmartCabinetTimestampIndicates the date and time of information updatero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.8.2.1.4
pduUnitSmartCabinetDoorAisle of Smart Cabinet.ro
Enumeration
.1.3.6.1.4.1.38446.1.8.2.1.5
pduUnitSmartCabinetControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.8.3
pduUnitSmartCabinetControlUserNameUser name of ID cardrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.8.3.1
pduUnitSmartCabinetControlCardIDCard ID.rw
Integer32
.1.3.6.1.4.1.38446.1.8.3.2
pduUnitSmartCabinetControlTimestampIndicates the date and time of information updaterw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.8.3.3
pduUnitSmartCabinetControlDoorAisle of Smart Cabinet.rw
Enumeration
.1.3.6.1.4.1.38446.1.8.3.4
pduUnitSmartCabinetCardIDEditSmart Cabinet edit CardIDrw
Enumeration
.1.3.6.1.4.1.38446.1.8.3.5
pduUnitSmartCabinetColdAisleLockStateSmart Cabinet ColdAisle lock staterw
Enumeration
.1.3.6.1.4.1.38446.1.8.3.6
pduUnitSmartCabinetHotAisleLockStateSmart Cabinet HotAisle lock staterw
Enumeration
.1.3.6.1.4.1.38446.1.8.3.7
pduTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.9
trapsInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.1.9.1
trapsInfoTableA list of Trap Information entries. The number of entries are given by the value of pduUnitTableSize.
SEQUENCE OF TrapsInfoEntry
.1.3.6.1.4.1.38446.1.9.1.1
trapsInfoEntryAn entry containing objects used in traps
TrapsInfoEntry
.1.3.6.1.4.1.38446.1.9.1.1.1
trapsInfoIndexThe index of the traps table entry
Integer32
.1.3.6.1.4.1.38446.1.9.1.1.1.1
userNameThe user currently logged in.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.9.1.1.1.2
userUpdatedThe user added, deleted, or modified.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.9.1.1.1.3
firmwareVersionThe version of Firmware.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.9.1.1.1.4
roleUpdatedThe role added, deleted, or modified.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.9.1.1.1.5
smtpRecipientsComma separated list of SMTP recipientsro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.9.1.1.1.6
smtpServerThe IP address/host name of the SMTP serverro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.9.1.1.1.7
pduIndexA unique value for PDU. Its value ranges between 1 and the value of PDU countro
Integer32
.1.3.6.1.4.1.38446.1.9.1.2
externalSensorIndexA unique value for each sensor. Its value ranges between 1 and the value of external sensor count.ro
Integer32
.1.3.6.1.4.1.38446.1.9.1.3
serverPingWhether server ping has been enabled or disabled and whether the server is reachable or not reachablero
Enumeration
.1.3.6.1.4.1.38446.1.9.1.4
usbDeviceWhether a USB device has been connected or disconnectedro
Enumeration
.1.3.6.1.4.1.38446.1.9.1.5
errorDescriptionDescription of the Errorro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.1.9.1.6
daisyChainWhether a daisy chain member has been connected or disconnectedro
Enumeration
.1.3.6.1.4.1.38446.1.9.1.7
systemCommunicationWhether the Network management card has lost contact with daisy a chain member.ro
Enumeration
.1.3.6.1.4.1.38446.1.9.1.8
networkCardStartThe network card has started
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.2
networkCardResetThe network card was reset via the web or command line interface.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.3
userLoginA user logged in
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.4
userLogoffA user logged off
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.5
userAuthenticationFailedA user authentication attempt failed.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.6
userSessionTimeoutA user session timed out
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.7
userAddedA user account was added to system.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.8
userModifiedA user account was modified.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.9
userDeletedA user account was deleted.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.10
roleAddedA user role was added.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.11
roleModifiedA user role was modified.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.12
roleDeletedA user role was deleted.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.13
firmwareUpdateStartedA firmware update has started.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.14
firmwareUpdateCompletedThe firmware update has completed.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.15
userBlockedA user is blocked.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.16
outletControlOutlet control operation applied.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.17
userPasswordChangeA user password was changed.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.18
passwordSettingsChangeOne or more password policy settings were changed.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.19
logFileClearedThe log file has been cleared.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.21
pduConfigurationFileImportedPDU configuration file was imported.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.22
pduConfigurationFileExportedPDU configuration file was exported
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.23
pduUnitActivePowerStateChangePDU unit active power state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.24
pduInputphaseVoltageStateChangePDU input phase voltage state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.25
pduInputphaseCurrentStateChangePDU input phase Current state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.26
pduCircuitBreakerCurrentStateChangePDU Circuit Breaker Current state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.27
pduOutletActivePowerStateChangePDU Metered Outlet Active Power state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.28
pduExternalSensorStateChangePDU External Sensor state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.29
smtpTransmissionFailureSMTP message transmission failed.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.30
ldapErrorA LDAP error occurred
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.31
firmwareUpdateFailedA firmware update has failed.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.32
serverPingStateThe Ping feature has been enabled.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.33
bootloaderStateEnter into Bootloader mode
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.34
daisyChainStateA daisy chain member has been connected or disconnected.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.35
systemInternalCommunicationLostNetwork management card has lost contaction with internal boards.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.36
smartCabinetLockUnlockedThe Cabinet lock is unlocked.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.37
smartCabinetLockLockedThe Cabinet lock is locked
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.38
smartCabinetSwapCardCard is swapped
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.39
smartCabinetLockerLockDoorOpenLocker locked but door open
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.40
smartCabinetLockerUnlockDoorCloseLocker unlocked but door close
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.41
systemRebootSystem has rebooted
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.1.9.50
esp
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.2
espNamePlate
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.2.1
espNamePlateTableA table of es PDU nameplate data
SEQUENCE OF EspNamePlateEntry
.1.3.6.1.4.1.38446.2.1.2
espNamePlateEntryNameplate data from the PDU being queried. The numbers of entries equals the value of espNamePlateTableSize.
EspNamePlateEntry
.1.3.6.1.4.1.38446.2.1.2.1
espNamePlateIndexThe index of the es PDU nameplate table entry
Integer32
.1.3.6.1.4.1.38446.2.1.2.1.1
espNamePlateNameA user-defined string identifying the es PDUro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.1.2.1.2
espNamePlateLocationA user-defined string identifying the location of PDUro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.1.2.1.3
espNamePlateInetAddressTypeThe type of address formatro
InetAddressType (INET-ADDRESS-MIB)
.1.3.6.1.4.1.38446.2.1.2.1.4
espNamePlateIPAddressThe current IP address. A value of 0.0.0.0 indicates an error or an unset optionro
InetAddress (INET-ADDRESS-MIB)
.1.3.6.1.4.1.38446.2.1.2.1.5
espNamePlateInetNetMaskThe current netmask. A value of 0.0.0.0 indiates an error or an unset optionro
InetAddress (INET-ADDRESS-MIB)
.1.3.6.1.4.1.38446.2.1.2.1.6
espNamePlateInetGatewayThe current gateway. A value of 0.0.0.0 indicates an error or an unset optionro
InetAddress (INET-ADDRESS-MIB)
.1.3.6.1.4.1.38446.2.1.2.1.7
espNamePlateMACAddressThe assigned MAC address for the PDUro
MacAddress (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.1.2.1.8
espNamePlateUTCTimeOffsetThe difference in hours and minutes from Coordinated Universal Time(UTC) for the time used in a particular time zonero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.1.2.1.9
espNamePlateModelNumberThe PDU model numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.1.2.1.10
espNamePlateSerialNumberThe PDU serial numberro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.1.2.1.11
espNamePlateDateofManufactureThe date the PDU was manufactured in mm/dd/yyyy formatro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.1.2.1.12
espNamePlateFirmwareVersionThe PDU firmware versionro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.1.2.1.13
espNamePlateFirmwareVersionTimeStampTimestamp of when the PDU firmware was last updatedro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.1.2.1.14
espNamePlateTypeThe type of Unit, PDU or Inline Meterro
Enumeration
.1.3.6.1.4.1.38446.2.1.2.1.15
espUnit
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.2.2
espUnitConfigTableA table of PDU configuration data
SEQUENCE OF EspUnitConfigEntry
.1.3.6.1.4.1.38446.2.2.2
espUnitConfigEntryConfiguration data from the PDU being queried. The number of entries equals the value of espUnitTableSize
EspUnitConfigEntry
.1.3.6.1.4.1.38446.2.2.2.1
espUnitConfigIndexThe index of the PDU Unit Config Entry
Integer32
.1.3.6.1.4.1.38446.2.2.2.1.1
espUnitConfigNameA user-defined string identifying the PDUrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.2.2.1.2
espUnitConfigLocationA user-defined string identifying the location of the PDUrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.2.2.1.3
espUnitConfigEnergyResetSetting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.rw
Enumeration
.1.3.6.1.4.1.38446.2.2.2.1.15
espUnitConfigResetNetworkManagementCardGetting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC.rw
Enumeration
.1.3.6.1.4.1.38446.2.2.2.1.20
espUnitPropertiesTableA table of PDU properties
SEQUENCE OF EspUnitPropertiesEntry
.1.3.6.1.4.1.38446.2.2.3
espUnitPropertiesEntryA unit properties entry containing objects for a particular unit.
EspUnitPropertiesEntry
.1.3.6.1.4.1.38446.2.2.3.1
espUnitPropertiesIndexThe index of the PDU properties table entry
Integer32
.1.3.6.1.4.1.38446.2.2.3.1.1
espUnitPropertiesNameA user-defined string identifying the PDUro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.2.3.1.2
espUnitPropertiesOutletCountThe total number of outlets on the PDUro
Integer32
.1.3.6.1.4.1.38446.2.2.3.1.3
espUnitPropertiesSwitchedOutletCountThe total number of switched outlets on the PDUro
Integer32
.1.3.6.1.4.1.38446.2.2.3.1.4
espUnitPropertiesMeteredOutletCountThe total number of metered outlets on the PDUro
Integer32
.1.3.6.1.4.1.38446.2.2.3.1.5
espUnitPropertiesInputPhaseCountThe total number of phases on the PDUro
Integer32
.1.3.6.1.4.1.38446.2.2.3.1.6
espUnitPropertiesCircuitBreakerCountThe total number of circuit breaker on the PDUro
Integer32
.1.3.6.1.4.1.38446.2.2.3.1.7
espUnitPropertiesMaxExternalSensorCountThe maximum number of external sensors that can be connected to the PDUro
Integer32
.1.3.6.1.4.1.38446.2.2.3.1.8
espUnitPropertiesConnExternalSensorCountThe current number of external sensors connected to the PDUro
Integer32
.1.3.6.1.4.1.38446.2.2.3.1.9
espUnitPropertiesRatedVoltageThe PDU voltage rating in Voltsro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.2.3.1.10
espUnitPropertiesRatedMaxCurrentThe PDU current rating in Ampsro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.2.3.1.11
espUnitPropertiesRatedFrequencyThe PDU frequency rating in Hzro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.2.3.1.12
espUnitPropertiesRatedPowerThe PDU VA (VoltAmps) rating.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.2.3.1.13
espUnitStatusTableA table of PDU status information
SEQUENCE OF EspUnitStatusEntry
.1.3.6.1.4.1.38446.2.2.4
espUnitStatusEntryStatus information from the PDU being queried
EspUnitStatusEntry
.1.3.6.1.4.1.38446.2.2.4.1
espUnitStatusIndexThe index of the PDU status table entry
Integer32
.1.3.6.1.4.1.38446.2.2.4.1.1
espUnitStatusNameA user-defined string identifying the PDUro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.2.4.1.2
espUnitStatusLoadStateReturns the present load status of the PDU based on Active Power.ro
Enumeration
.1.3.6.1.4.1.38446.2.2.4.1.3
espUnitStatusActivePowerReturns power consumption, in Watts(W), of the PDU being queried.ro
Integer32
.1.3.6.1.4.1.38446.2.2.4.1.4
espUnitStatusApparentPowerReturns power consumption, in Volt-Amps(VA) of the PDU load being queried.ro
Integer32
.1.3.6.1.4.1.38446.2.2.4.1.5
espUnitStatusEnergyReturns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime.ro
Integer32
.1.3.6.1.4.1.38446.2.2.4.1.9
espUnitStatusResettableEnergyA user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh).ro
Integer32
.1.3.6.1.4.1.38446.2.2.4.1.10
espUnitStatusEnergyStartTimeIndicates the date and time of the last device energy meter resetro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.2.4.1.11
espInputPhase
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.2.3
espInputPhaseConfigTableA table of PDU Input Phase configuration data
SEQUENCE OF EspInputPhaseConfigEntry
.1.3.6.1.4.1.38446.2.3.2
espInputPhaseConfigEntryAn input phase entry containing objects for a particular input phase.
EspInputPhaseConfigEntry
.1.3.6.1.4.1.38446.2.3.2.1
espInputPhaseConfigIndexThe index of the PDU Input Phase configuration table entry
Integer32
.1.3.6.1.4.1.38446.2.3.2.1.1
espInputPhaseConfigCountThe total number of Input Phasesro
Integer32
.1.3.6.1.4.1.38446.2.3.2.1.2
espInputPhaseStatusTableA table of PDU Input Phase status data
SEQUENCE OF EspInputPhaseStatusEntry
.1.3.6.1.4.1.38446.2.3.4
espInputPhaseStatusEntryAn input phase status entry containing objects for a particular input phase.
EspInputPhaseStatusEntry
.1.3.6.1.4.1.38446.2.3.4.1
espInputPhaseStatusIndexThe index of the PDU Input Phase status entry
Integer32
.1.3.6.1.4.1.38446.2.3.4.1.1
espInputPhaseStatusCountThe numeric Input Phase IDro
Integer32
.1.3.6.1.4.1.38446.2.3.4.1.2
espInputPhaseStatusCurrentStateIndicates the present current status of the PDU Input Phase being queriedro
Enumeration
.1.3.6.1.4.1.38446.2.3.4.1.3
espInputPhaseStatusVoltageStateIndicates the present voltage status of the PDU Input Phase being queriedro
Enumeration
.1.3.6.1.4.1.38446.2.3.4.1.4
espInputPhaseStatusCurrentReturns the current draw, in hundredths of Amps(A), of the load on the PDU Input Phase being queried.ro
Integer32
.1.3.6.1.4.1.38446.2.3.4.1.5
espInputPhaseStatusVoltageReturns the voltage, in Volts(V), of the PDU Input Phase being queried.ro
Integer32
.1.3.6.1.4.1.38446.2.3.4.1.6
espInputPhaseStatusActivePowerReturns power consumption, in Watts(W), consumed on the PDU Input Phase being queried.ro
Integer32
.1.3.6.1.4.1.38446.2.3.4.1.7
espInputPhaseStatusApparentPowerReturns power consumption, in Volt-Amps(VA), of the PDU Input Phase being queried.ro
Integer32
.1.3.6.1.4.1.38446.2.3.4.1.8
espInputPhaseStatusPowerFactorReturns the ratio of active to apparent power of the PDU Input Phase being queried.ro
Integer32
.1.3.6.1.4.1.38446.2.3.4.1.9
espCircuitBreaker
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.2.4
espCircuitBreakerConfigTableA table of PDU Circuit Breaker configuration data
SEQUENCE OF EspCircuitBreakerConfigEntry
.1.3.6.1.4.1.38446.2.4.2
espCircuitBreakerConfigEntryA circuit breaker configuration entry containing objects for a particular circuit breaker.
EspCircuitBreakerConfigEntry
.1.3.6.1.4.1.38446.2.4.2.1
espCircuitBreakerConfigIndexThe index of the PDU Circuit Breaker configuration table entry
Integer32
.1.3.6.1.4.1.38446.2.4.2.1.1
espCircuitBreakerConfigCountThe number of circuit breakers on the PDUro
Integer32
.1.3.6.1.4.1.38446.2.4.2.1.2
espCircuitBreakerNameThe label of the circuit breakerro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.4.2.1.3
espCircuitBreakerPropertiesTableA table of PDU circuit breaker properties
SEQUENCE OF EspCircuitBreakerPropertiesEntry
.1.3.6.1.4.1.38446.2.4.3
espCircuitBreakerPropertiesEntryA circuit breaker properties entry containing objects for a particular circuit breaker.
EspCircuitBreakerPropertiesEntry
.1.3.6.1.4.1.38446.2.4.3.1
espCircuitBreakerPropertiesIndexThe index of the PDU Circuit Breaker properties table entry
Integer32
.1.3.6.1.4.1.38446.2.4.3.1.1
espCircuitBreakerPropertiesCountThe number of Circuit Breakersro
Integer32
.1.3.6.1.4.1.38446.2.4.3.1.2
espCircuitBreakerPropertiesInputLayoutThis OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to circuit breaker are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to circuit breaker are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to circuit breaker are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to circuit breaker are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to circuit breaker are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to circuit breaker are connected from Phase 3 to Phase1.ro
Enumeration
.1.3.6.1.4.1.38446.2.4.3.1.3
espCircuitBreakerStatusTableA table of PDU circuit breaker status data
SEQUENCE OF EspCircuitBreakerStatusEntry
.1.3.6.1.4.1.38446.2.4.4
espCircuitBreakerStatusEntryA circuit breaker status entry containing objects for a particular circuit breaker.
EspCircuitBreakerStatusEntry
.1.3.6.1.4.1.38446.2.4.4.1
espCircuitBreakerStatusIndexThe index of the PDU Circuit Breaker status table entry
Integer32
.1.3.6.1.4.1.38446.2.4.4.1.1
espCircuitBreakerStatusCountThe number of Circuit Breakersro
Integer32
.1.3.6.1.4.1.38446.2.4.4.1.2
espCircuitBreakerLabelThe label on the PDU identifying the circuit breakerro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.4.4.1.3
espCircuitBreakerStatusLoadStateIndicates the present load status of the PDU Circuit Breaker being queriedro
Enumeration
.1.3.6.1.4.1.38446.2.4.4.1.4
espCircuitBreakerStatusCurrentReturns the current draw, in hundredths of Amps(A), of the load on the PDU Circuit Breaker being queried.ro
Integer32
.1.3.6.1.4.1.38446.2.4.4.1.5
espExternalSensor
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.2.6
espExternalSensorNamePlateTableA table of PDU ExternalSensorNamePlate data
SEQUENCE OF EspExternalSensorNamePlateEntry
.1.3.6.1.4.1.38446.2.6.2
espExternalSensorNamePlateEntryExternal Sensor Name Plate data from the external sensor being queried. The number of entries equals the value of espExternalSensorNamePlateTableSize.
EspExternalSensorNamePlateEntry
.1.3.6.1.4.1.38446.2.6.2.1
espExternalSensorNamePlateIndexThe index of the PDU External Sensor status table entry
Integer32
.1.3.6.1.4.1.38446.2.6.2.1.1
espExternalSensorNamePlateNameA user-defined string identifying the external sensorro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.6.2.1.2
espExternalSensorNamePlateSerialNumberThe serial number of the external sensor being queriedro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.6.2.1.5
espExternalSensorNamePlateTypeThe type of external sensor.ro
Enumeration
.1.3.6.1.4.1.38446.2.6.2.1.6
espExternalSensorNamePlateUnitsThe base units the external sensor is measured in. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.ro
Enumeration
.1.3.6.1.4.1.38446.2.6.2.1.7
espExternalSensorConfigTableA table of PDU External Sensor configuration data
SEQUENCE OF EspExternalSensorConfigEntry
.1.3.6.1.4.1.38446.2.6.3
espExternalSensorConfigEntryConfiguration data from the PDU External Sensor being queried
EspExternalSensorConfigEntry
.1.3.6.1.4.1.38446.2.6.3.1
espExternalSensorConfigIndexThe index of the PDU External Sensor configuration table entry
Integer32
.1.3.6.1.4.1.38446.2.6.3.1.1
espExternalSensorConfigAlarmStateUser defined alarm state of external sensorrw
Enumeration
.1.3.6.1.4.1.38446.2.6.3.1.9
espExternalSensorStatusTableA table of PDU External Sensor status data
SEQUENCE OF EspExternalSensorStatusEntry
.1.3.6.1.4.1.38446.2.6.4
espExternalSensorStatusEntryStatus data from the PDU External Sensor being queried
EspExternalSensorStatusEntry
.1.3.6.1.4.1.38446.2.6.4.1
espExternalSensorStatusIndexThe index of the PDU External Sensor status table entry
Integer32
.1.3.6.1.4.1.38446.2.6.4.1.1
espExternalSensorStatusNameThe user-defined name for the External Sensorro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.6.4.1.2
espExternalSensorStatusAisleIndicates whether the external sensor is in a hot or cold aislerw
Enumeration
.1.3.6.1.4.1.38446.2.6.4.1.3
espExternalSensorStatusCommStatusThe communications status of the sensorro
Enumeration
.1.3.6.1.4.1.38446.2.6.4.1.4
espExternalSensorStatusStateThis OID reports the current state of the sensor. A notPresent (0) response indicates that no sensor is attached. An alarmed (1) response indicates that the sensor is present and its measured reading indicates alarmed. A normal (2) response indicates that the sensor is present and its measured reading lies within all thresholds. A belowLowerCritical (3) response indicates that the sensor is present and its measured reading lies below the lower critical threshold. A belowLowerWarning (4) response indicates that the sensor is present and its measured reading lies below the lower warning threshold. An aboveUpperWarning (5) response indicates that the sensor is present and its measured reading lies above the upper warning threshold. An aboveUpperCritical (6) response indicates that the sensor is present and its measured reading lies above the upper critical threshold.ro
Enumeration
.1.3.6.1.4.1.38446.2.6.4.1.5
espExternalSensorStatusValueSensor reading in espExternalSensorConfigUnits value.ro
Integer32
.1.3.6.1.4.1.38446.2.6.4.1.6
espExternalSensorStatusHighPrecisionValueTemperature sensor reading in tenths of espExternalSensorConfigUnits value. This OID is applied to temperature sensor onlyro
Integer32
.1.3.6.1.4.1.38446.2.6.4.1.8
espTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.38446.2.9
espTrapsInfoIndexThe index of the traps table entry
Integer32
.1.3.6.1.4.1.38446.2.9.1
espUserNameThe user currently logged in.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.9.2
espFirmwareVersionThe version of Firmware.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.9.4
espIndexA unique value for PDU. Its value ranges between 1 and the value of PDU countro
Integer32
.1.3.6.1.4.1.38446.2.9.5
espExternalSensorIndexA unique value for each sensor. Its value ranges between 1 and the value of external sensor count.ro
Integer32
.1.3.6.1.4.1.38446.2.9.6
espErrorDescriptionDescription of the Errorro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.38446.2.9.7
espNetworkCardStartThe network card has started
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.8
espNetworkCardResetThe network card was reset via the web or command line interface.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.9
espFirmwareUpdateCompletedThe firmware update has completed.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.10
espUserPasswordChangeA user password was changed.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.11
espLogFileClearedThe log file has been cleared.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.12
espConfigurationFileExportedPDU configuration file was exported
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.13
espUnitActivePowerStateChangePDU unit active power state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.14
espInputphaseVoltageStateChangePDU input phase voltage state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.15
espInputphaseCurrentStateChangePDU input phase Current state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.16
espCircuitBreakerCurrentStateChangePDU Circuit Breaker Current state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.17
espExternalSensorStateChangePDU External Sensor state changes.
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.18
espConfigurationFileImportedPDU configuration file was imported
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.19
espNetworkUpPDU Network is up
NOTIFICATION-TYPE
.1.3.6.1.4.1.38446.2.9.20
ENLOGIC-PDU-MIB - SNMP MIB Reference | MIBs Explorer