DeltaUPS-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for DeltaUPS-MIB.
194
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
194 total| Object Name |
|---|
delta OBJECT IDENTIFIER .1.3.6.1.4.1.2254 |
RFC1213-MIB Unknown .1.3.6.1.4.1.2254 |
ups OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2 |
upsv4 OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4 |
dupsIdent OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.1 |
dupsIdentManufacturerThe name of the UPS manufacturer.ro DisplayString .1.3.6.1.4.1.2254.2.4.1.1 |
dupsIdentModelThe UPS Model designation.ro DisplayString .1.3.6.1.4.1.2254.2.4.1.2 |
dupsIdentUPSSoftwareVersionThe UPS firmware/software version(s). This variable
may or may not has the same value as
upsIdentAgentSoftwareVersion in some implementations.ro DisplayString .1.3.6.1.4.1.2254.2.4.1.3 |
dupsIdentAgentSoftwareVersionThe UPS agent software version. This variable may or
may not has the same value as
upsIdentUPSSoftwareVersion in some implementations.ro DisplayString .1.3.6.1.4.1.2254.2.4.1.4 |
dupsIdentNameA string identifying the UPS. This object should be
set by the administrator.rw DisplayString .1.3.6.1.4.1.2254.2.4.1.5 |
dupsAttachedDevicesA string identifying the devices attached to the
output(s) of the UPS. This object should be set by
the administrator.rw DisplayString .1.3.6.1.4.1.2254.2.4.1.6 |
dupsRatingOutputVAThe magnitude of the nominal output VA rating.ro INTEGER .1.3.6.1.4.1.2254.2.4.1.7 |
dupsRatingOutputVoltageThe magnitude of the nominal output voltage rating.ro INTEGER .1.3.6.1.4.1.2254.2.4.1.8 |
dupsRatingOutputFrequencyThe magnitude of the nominal output frequency rating.ro INTEGER .1.3.6.1.4.1.2254.2.4.1.9 |
dupsRatingInputVoltageThe magnitude of the nominal input voltage rating.ro INTEGER .1.3.6.1.4.1.2254.2.4.1.10 |
dupsRatingInputFrequencyThe magnitude of the nominal input frequency rating.ro INTEGER .1.3.6.1.4.1.2254.2.4.1.11 |
dupsRatingBatteryVoltageThe magnitude of the nominal battery voltage rating.ro INTEGER .1.3.6.1.4.1.2254.2.4.1.12 |
dupsLowTransferVoltUpBoundThe minimum input line voltage upper bound allowed
before the UPS system transfers to battery backup.ro INTEGER UNITS "Volt" .1.3.6.1.4.1.2254.2.4.1.13 |
dupsLowTransferVoltLowBoundThe minimum input line voltage lower bound allowed
before the UPS system transfers to battery backup.ro INTEGER UNITS "Volt" .1.3.6.1.4.1.2254.2.4.1.14 |
dupsHighTransferVoltUpBoundThe maximum input line voltage upper bound allowed
before the UPS system transfers to battery backup.ro INTEGER UNITS "Volt" .1.3.6.1.4.1.2254.2.4.1.15 |
dupsHighTransferVoltLowBoundThe maximum input line voltage lower bound allowed
before the UPS system transfers to battery backup.ro INTEGER UNITS "Volt" .1.3.6.1.4.1.2254.2.4.1.16 |
dupsLowBattTimeMinutes, time from low battery to low battery shutdown.ro INTEGER .1.3.6.1.4.1.2254.2.4.1.17 |
dupsOutletRelaysNumber of outlet relay. If it is 0, the function is not
available for the UPS.ro INTEGER .1.3.6.1.4.1.2254.2.4.1.18 |
dupsTypeIndicate the UPS type.ro Enumeration .1.3.6.1.4.1.2254.2.4.1.19 |
dupsControl OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.2 |
dupsShutdownTypeThis object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
Setting this object to output(1) indicates that
shutdown requests should cause only the output of the
UPS to turn off. Setting this object to system(2)
indicates that shutdown requests will cause the entire
UPS system to turn off.rw Enumeration .1.3.6.1.4.1.2254.2.4.2.1 |
dupsAutoRebootIn backup mode, the UPS may shutdown normally by SDA command,
dry-contact remote shutdown signal or low battery shutdown.
This command is used to determine the unit should restart or
not next time when the power restoresrw Enumeration .1.3.6.1.4.1.2254.2.4.2.2 |
dupsShutdownActionIf the value is greater than 0 the UPS performs
shutdown action that defined by ShutdownType after
the seconds. 0, aborted.rw INTEGER -- UNITS "Second" .1.3.6.1.4.1.2254.2.4.2.3 |
dupsRestartActionUPS will restart after the indicated number of minutes.
-1, aborted.rw INTEGER -- UNITS "Minute" .1.3.6.1.4.1.2254.2.4.2.4 |
dupsSetOutletRelayIndicate which outlet relay, from 1,2,3... .rw INTEGER .1.3.6.1.4.1.2254.2.4.2.5 |
dupsRelayOffDelayTurn the relay off after the seconds. The relay was indicated
by SetOutletRelay.rw INTEGER -- UNITS "Second" .1.3.6.1.4.1.2254.2.4.2.6 |
dupsRelayOnDelayTurn the relay on after the seconds. The relay was indicated
by SetOutletRelay.rw INTEGER -- UNITS "Minute" .1.3.6.1.4.1.2254.2.4.2.7 |
dupsConfig OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.3 |
dupsConfigBuzzerAlarmUPS will keep silence but will alarm again when
next power event is occurredrw Enumeration .1.3.6.1.4.1.2254.2.4.3.1 |
dupsConfigBuzzerStateIf it is disabled then the UPS is always muted.rw Enumeration .1.3.6.1.4.1.2254.2.4.3.2 |
dupsConfigSensitivityThe seneitivity of the UPS to utility line
abnormalities or noises.rw Enumeration .1.3.6.1.4.1.2254.2.4.3.3 |
dupsConfigLowVoltageTransferPointThe minimum input line voltage allowed before the UPS
system transfers to battery backup.rw INTEGER UNITS "Volt" .1.3.6.1.4.1.2254.2.4.3.4 |
dupsConfigHighVoltageTransferPointThe maximum line voltage allowed before the UPS
system transfers to battery backup.rw INTEGER UNITS "Volt" .1.3.6.1.4.1.2254.2.4.3.5 |
dupsConfigShutdownOSDelayThe operating system shutdown delay time when the
input power fail. -1 will disable this option.rw INTEGER UNITS "Second" .1.3.6.1.4.1.2254.2.4.3.6 |
dupsConfigUPSBootDelayDelay the UPS startup after power restores. The power
quality may not stable when power restores, this
feature let the UPS wait a period of time to startup
the system.rw INTEGER UNITS "Second" .1.3.6.1.4.1.2254.2.4.3.7 |
dupsConfigExternalBatteryPackIndicate the number of external battery pack.rw INTEGER .1.3.6.1.4.1.2254.2.4.3.8 |
dupsInput OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.4 |
dupsInputNumLinesThe number of input lines utilized in this device.ro INTEGER .1.3.6.1.4.1.2254.2.4.4.1 |
dupsInputFrequency1The current input line 1 frequency to the UPS
system in 1/10 Hz.ro INTEGER .1.3.6.1.4.1.2254.2.4.4.2 |
dupsInputVoltage1The Input line 1 voltage of the UPS system in 1/10 V.ro INTEGER .1.3.6.1.4.1.2254.2.4.4.3 |
dupsInputCurrent1The Input line 1 current to the UPS system in 1/10 A.ro INTEGER .1.3.6.1.4.1.2254.2.4.4.4 |
dupsInputFrequency2The current input line 2 frequency to the UPS system
in 1/10 Hz.ro INTEGER .1.3.6.1.4.1.2254.2.4.4.5 |
dupsInputVoltage2The Input line 2 voltage of the UPS system in 1/10 V.ro INTEGER .1.3.6.1.4.1.2254.2.4.4.6 |
dupsInputCurrent2The Input line 2 current to the UPS system in 1/10 A.ro INTEGER .1.3.6.1.4.1.2254.2.4.4.7 |
dupsInputFrequency3The current input line 3 frequency to the UPS system
in 1/10 Hz.ro INTEGER .1.3.6.1.4.1.2254.2.4.4.8 |
dupsInputVoltage3The Input line 3 voltage of the UPS system in 1/10 V.ro INTEGER .1.3.6.1.4.1.2254.2.4.4.9 |
dupsInputCurrent3The Input line 3 current to the UPS system in 1/10 A.ro INTEGER .1.3.6.1.4.1.2254.2.4.4.10 |
dupsOutput OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.5 |
dupsOutputSourceThe present source of output power. The enumeration
none(7) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.ro Enumeration .1.3.6.1.4.1.2254.2.4.5.1 |
dupsOutputFrequencyThe present output frequency in 1/10 Hz.ro INTEGER UNITS "0.1 Hertz" .1.3.6.1.4.1.2254.2.4.5.2 |
dupsOutputNumLinesThe number of output lines utilized in this device.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.3 |
dupsOutputVoltage1The Output line 1 voltage of the UPS system in 1/10 V.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.4 |
dupsOutputCurrent1The Output line 1 current of the UPS system in 1/10 A.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.5 |
dupsOutputPower1The Output line 1 real power of the UPS system in watts.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.6 |
dupsOutputLoad1The current UPS output line 1 load expressed in percent
of rated capacity.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.7 |
dupsOutputVoltage2The Output line 2 voltage of the UPS system in 1/10 V.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.8 |
dupsOutputCurrent2The Output line 2 current of the UPS system in 1/10 A.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.9 |
dupsOutputPower2The Output line 2 real power of the UPS system in watts.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.10 |
dupsOutputLoad2The current UPS output line 2 load expressed in percent
of rated capacity.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.11 |
dupsOutputVoltage3The Output line 3 voltage of the UPS system in 1/10 V.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.12 |
dupsOutputCurrent3The Output line 3 current of the UPS system in 1/10 A.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.13 |
dupsOutputPower3The Output line 3 real power of the UPS system in watts.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.14 |
dupsOutputLoad3The current UPS output line 3 load expressed in percent
of rated capacity.ro INTEGER .1.3.6.1.4.1.2254.2.4.5.15 |
dupsBypass OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.6 |
dupsBypassFrequencyThe present bypass frequency in 1/10 Hz.ro INTEGER UNITS "0.1 Hertz" .1.3.6.1.4.1.2254.2.4.6.1 |
dupsBypassNumLinesThe number of bypass lines utilized in this device.ro INTEGER .1.3.6.1.4.1.2254.2.4.6.2 |
dupsBypassVoltage1The bypass line 1 voltage of the UPS system in 1/10 V.ro INTEGER .1.3.6.1.4.1.2254.2.4.6.3 |
dupsBypassCurrent1The bypass line 1 current of the UPS system in 1/10 A.ro INTEGER .1.3.6.1.4.1.2254.2.4.6.4 |
dupsBypassPower1The bypass line 1 real power of the UPS system in watts.ro INTEGER .1.3.6.1.4.1.2254.2.4.6.5 |
dupsBypassVoltage2The bypass line 2 voltage of the UPS system in 1/10 V.ro INTEGER .1.3.6.1.4.1.2254.2.4.6.6 |
dupsBypassCurrent2The bypass line 2 current of the UPS system in 1/10 A.ro INTEGER .1.3.6.1.4.1.2254.2.4.6.7 |
dupsBypassPower2The bypass line 2 real power of the UPS system in watts.ro INTEGER .1.3.6.1.4.1.2254.2.4.6.8 |
dupsBypassVoltage3The bypass line 3 voltage of the UPS system in 1/10 V.ro INTEGER .1.3.6.1.4.1.2254.2.4.6.9 |
dupsBypassCurrent3The bypass line 3 current of the UPS system in 1/10 A.ro INTEGER .1.3.6.1.4.1.2254.2.4.6.10 |
dupsBypassPower3The bypass line 3 real power of the UPS system in watts.ro INTEGER .1.3.6.1.4.1.2254.2.4.6.11 |
dupsBattery OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.7 |
dupsBatteryCondictionThe indication of the capacity remaining in the UPS
system's batteries when AC normal.ro Enumeration .1.3.6.1.4.1.2254.2.4.7.1 |
dupsBatteryStatusThe indication of the capacity remaining in the UPS
system's batteries when AC failed. A value of ok
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of low indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
depleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output).ro Enumeration .1.3.6.1.4.1.2254.2.4.7.2 |
dupsBatteryChargero Enumeration .1.3.6.1.4.1.2254.2.4.7.3 |
dupsSecondsOnBatteryIf the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is less. Zero shall be returned
if the unit is not on battery power.ro INTEGER UNITS "seconds" .1.3.6.1.4.1.2254.2.4.7.4 |
dupsBatteryEstimatedTimeEstimated time from backup to low battery shutdown.ro INTEGER UNITS "minutes" .1.3.6.1.4.1.2254.2.4.7.5 |
dupsBatteryVoltageThe magnitude of the present battery voltage
in 1/10 V.ro INTEGER UNITS "0.1 Volt DC" .1.3.6.1.4.1.2254.2.4.7.6 |
dupsBatteryCurrentThe present battery current in 1/10 A.ro INTEGER UNITS "0.1 Amp DC" .1.3.6.1.4.1.2254.2.4.7.7 |
dupsBatteryCapacityAn estimate of the battery charge remaining expressed
as a percent of full charge.ro INTEGER .1.3.6.1.4.1.2254.2.4.7.8 |
dupsTemperatureThe ambient temperature at or near the UPS Battery
casing.ro INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.2254.2.4.7.9 |
dupsLastReplaceDateThe last battery replacement date. The format is YYYYMMDD.ro DisplayString .1.3.6.1.4.1.2254.2.4.7.10 |
dupsNextReplaceDateThe next battery replacement date. The format is YYYYMMDD.ro DisplayString .1.3.6.1.4.1.2254.2.4.7.11 |
dupsTest OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.8 |
dupsTestTypePerform the UPS Test procedure.rw Enumeration .1.3.6.1.4.1.2254.2.4.8.1 |
dupsTestResultsSummaryThe results of the current or last UPS diagnostics
test performed. The values for donePass(1),
generalTestFail(3), and batteryTestFail(4) indicate that the
test completed either successfully, with a warning, or
with an error, respectively.Tests which have not yet
concluded are indicated by inProgress(2). The value
noTestsInitiated(0) indicates that no previous test
results are available.ro Enumeration .1.3.6.1.4.1.2254.2.4.8.2 |
dupsTestResultsDetailAdditional information about upsTestResultsSummary.
If no additional information available, a zero length
string is returned.ro DisplayString .1.3.6.1.4.1.2254.2.4.8.3 |
dupsAlarm OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.9 |
dupsAlarmDisconnectDoes the UPS disconnect?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.1 |
dupsAlarmPowerFailDoes the input power fail?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.2 |
dupsAlarmBatteryLowAre the UPS batteries low?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.3 |
dupsAlarmLoadWarningDoes the UPS load percent over the load warning value?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.4 |
dupsAlarmLoadSeverityDoes the UPS load percent over the load severity value?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.5 |
dupsAlarmLoadOnBypassDoes the UPS load on bypass?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.6 |
dupsAlarmUPSFaultDoes the UPS general fail?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.7 |
dupsAlarmBatteryGroundFaultDoes the UPS battery ground fault?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.8 |
dupsAlarmTestInProgressDoes the UPS test in progress?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.9 |
dupsAlarmBatteryTestFailDoes the UPS test fail?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.10 |
dupsAlarmFuseFailureDoes the UPS fuse failure?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.11 |
dupsAlarmOutputOverloadDoes the UPS output overload?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.12 |
dupsAlarmOutputOverCurrentDoes the UPS output overcurrent?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.13 |
dupsAlarmInverterAbnormalDoes the UPS inverter abnormal?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.14 |
dupsAlarmRectifierAbnormalDoes the UPS rectifier abnormal?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.15 |
dupsAlarmReserveAbnormalDoes the UPS reserve abnormal?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.16 |
dupsAlarmLoadOnReserveDoes the UPS load on reserve?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.17 |
dupsAlarmOverTemperatureDoes the UPS over heat?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.18 |
dupsAlarmOutputBadIs the UPS output abnormal?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.19 |
dupsAlarmBypassBadIs the UPS bypass bad?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.20 |
dupsAlarmUPSOffIs the UPS in standby mode?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.21 |
dupsAlarmChargerFailDoes the UPS charger fail?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.22 |
dupsAlarmFanFailDoes the UPS fan fail?ro Enumeration .1.3.6.1.4.1.2254.2.4.9.23 |
dupsAlarmEconomicModeIndicates whether the UPS is in the economic mode.ro Enumeration .1.3.6.1.4.1.2254.2.4.9.24 |
dupsAlarmOutputOffIndicates whether the UPS output is turned off or not.ro Enumeration .1.3.6.1.4.1.2254.2.4.9.25 |
dupsAlarmSmartShutdownIndicates whether the Smart Shutdown is in progress.ro Enumeration .1.3.6.1.4.1.2254.2.4.9.26 |
dupsAlarmEmergencyPowerOffUPS emergency power off.ro Enumeration .1.3.6.1.4.1.2254.2.4.9.27 |
dupsAlarmUPSShutdownUPS shutdown.ro Enumeration .1.3.6.1.4.1.2254.2.4.9.28 |
dupsEnvironment OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.10 |
dupsEnvTemperatureThe ambient environmental temperature.ro INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.2254.2.4.10.1 |
dupsEnvHumidityThe environmental humidity.ro INTEGER UNITS "percentage" .1.3.6.1.4.1.2254.2.4.10.2 |
dupsEnvSetTemperatureLimitAlarm dupsAlarmOverTemperature on when the environmental
temperature over the value.rw INTEGER UNITS "degrees Centigrade" .1.3.6.1.4.1.2254.2.4.10.3 |
dupsEnvSetHumidityLimitAlarm dupsAlarmOverHumidity on when the environmental
humidity over the value.rw INTEGER UNITS "percentage" .1.3.6.1.4.1.2254.2.4.10.4 |
dupsEnvSetEnvRelay1rw Enumeration .1.3.6.1.4.1.2254.2.4.10.5 |
dupsEnvSetEnvRelay2rw Enumeration .1.3.6.1.4.1.2254.2.4.10.6 |
dupsEnvSetEnvRelay3rw Enumeration .1.3.6.1.4.1.2254.2.4.10.7 |
dupsEnvSetEnvRelay4rw Enumeration .1.3.6.1.4.1.2254.2.4.10.8 |
dupsAlarmOverEnvTemperatureDoes the environment over temperature?ro Enumeration .1.3.6.1.4.1.2254.2.4.10.9 |
dupsAlarmOverEnvHumidityDoes the environment over humidity?ro Enumeration .1.3.6.1.4.1.2254.2.4.10.10 |
dupsAlarmEnvRelay1ro Enumeration .1.3.6.1.4.1.2254.2.4.10.11 |
dupsAlarmEnvRelay2ro Enumeration .1.3.6.1.4.1.2254.2.4.10.12 |
dupsAlarmEnvRelay3ro Enumeration .1.3.6.1.4.1.2254.2.4.10.13 |
dupsAlarmEnvRelay4ro Enumeration .1.3.6.1.4.1.2254.2.4.10.14 |
dupsTraps OBJECT IDENTIFIER .1.3.6.1.4.1.2254.2.4.20 |
dupsCommunicationLostSEVER: Communication with the UPS failed. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.1 |
dupsCommunicationEstablishedINFORMATION: Communication with the UPS reestablished. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.2 |
dupsPowerFailWARNING: Power failed! The UPS is operating on battery power. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.3 |
dupsPowerRestoredINFORMATION: Power restored! The utility power restored. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.4 |
dupsLowBatterySEVER: The UPS batteries are low and will soon be exhausted. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.5 |
dupsReturnFromLowBatteryINFORMATION: The UPS has returned from a low battery condition. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.6 |
dupsLoadWarningINFORMATION: Loading percent of the UPS over the Load Warning value. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.7 |
dupsNoLongerLoadWarningINFORMATION: Returnd from Load Warning condition. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.8 |
dupsLoadSeverityWarning: Loading percent of the UPS over the Load Severity value. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.9 |
dupsNoLongerLoadSeverityINFORMATION: Returned from Load Severity condition. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.10 |
dupsLoadOnBypassSEVER: The UPS loads on bypass. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.11 |
dupsNoLongerLoadOnBypassINFORMATION: The UPS is not on bypass mode. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.12 |
dupsUPSFaultSEVER: A general fault caused in the UPS. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.13 |
dupsReturnFromUPSFaultINFORMATION: The UPS is returned from general fault. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.14 |
dupsBatteryGroundFaultSEVER: The UPS battery ground fault. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.15 |
dupsNoLongerBatteryFaultINFORMATION: The UPS recovered from battery ground fault. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.16 |
dupsTestInProgressINFORMATION: The UPS test in progress. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.17 |
dupsBatteryTestFailSEVER: The UPS test fail. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.18 |
dupsFuseFailureSEVER: The UPS fuse failed. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.19 |
dupsFuseRecoveredINFORMATION: The UPS fuse recovered. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.20 |
dupsOutputOverloadSEVER: The UPS overload!. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.21 |
dupsNoLongerOverloadINFORMATION: Recovered from UPS overload. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.22 |
dupsOutputOverCurrentSEVER: The UPS output overcurrent. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.23 |
dupsNoLongerOutputOverCurrentINFORMATION: Recovered from UPS overcurrent. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.24 |
dupsInverterAbnormalSEVER: The UPS inverter abnormal. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.25 |
dupsInverterRecoveredINFORMATION: Recovered from UPS inverter abnormal. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.26 |
dupsRectifierAbnormalSEVER: The UPS rectifier abnormal. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.27 |
dupsRectifierRecoveredINFORMATION: The UPS recovered from rectifier abnormal. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.28 |
dupsReserveAbnormalSEVER: The UPS rectifier abnormal. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.29 |
dupsReserveRecoveredINFORMATION: The UPS rectifier abnormal. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.30 |
dupsLoadOnReserveSEVER: The UPS load on reserve. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.31 |
dupsNoLongerLoadOnReserveINFORMATION: The UPS no longer load on reserve. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.32 |
dupsEnvOverTemperatureWARNING: The environment overtemperature. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.33 |
dupsNoLongerEnvOverTemperatureINFORMATION: The environment recovered from overtemperature. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.34 |
dupsEnvOverHumidityWARNING: The environment overhumidity. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.35 |
dupsNoLongerEnvOverHumidityINFORMATION: The environment recovered from overhumidity. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.36 |
dupsEnvRelay1AlarmINFORMATION: The environment relay1 is not in normal state. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.37 |
dupsEnvRelay1NormalINFORMATION: The environment relay1 is in normal state. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.38 |
dupsEnvRelay2AlarmINFORMATION: The environment relay2 is not in normal state. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.39 |
dupsEnvRelay2NormalINFORMATION: The environment relay2 is in normal state. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.40 |
dupsEnvRelay3AlarmINFORMATION: The environment relay3 is not in normal state. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.41 |
dupsEnvRelay3NormalINFORMATION: The environment relay3 is in normal state. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.42 |
dupsEnvRelay4AlarmINFORMATION: The environment relay4 is not in normal state. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.43 |
dupsEnvRelay4NormalINFORMATION: The environment relay4 is in normal state. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.44 |
dupsSmartShutdownSEVER: Smart Shutdown is initiated. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.45 |
dupsCancelShutdownINFORMATION: Cancel UPS Shutdown. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.46 |
dupsTestCompletedINFORMATION: This trap is sent upon completion of a UPS diagnostic test. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.47 |
dupsEPOONINFORMATION: This trap is sent when emergency power off is on. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.48 |
dupsEPOOFFINFORMATION: This trap is sent when UPS recover from emergency power off. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.49 |
dupsOverTemperatureSEVER: This trap is sent when the UPS is over heat. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.50 |
dupsNormalTemperatureINFORMATION: This trap is sent when UPS recover from over heat. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.51 |
dupsBattReplaceWARNING: The battery needs to be replaced. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.52 |
dupsReturnFromBattReplaceINFORMATION: The UPS recovered from battery replacement. TRAP-TYPE .1.3.6.1.4.1.2254.2.4.20.0.53 |