DAMOCLES-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for DAMOCLES-MIB.
52
Objects
Active
Status
5
Dependencies
Imported Objects
Objects
52 total| Object Name |
|---|
hwgroup OBJECT IDENTIFIER .1.3.6.1.4.1.21796 |
IMPORTS Unknown .1.3.6.1.4.1.21796 |
charonII OBJECT IDENTIFIER .1.3.6.1.4.1.21796.3 |
damocles OBJECT IDENTIFIER .1.3.6.1.4.1.21796.3.4 |
inpChangeInput changed. TRAP-TYPE .1.3.6.1.4.1.21796.3.4.0.1 |
sensStateChangedSensor n changed its state. TRAP-TYPE .1.3.6.1.4.1.21796.3.4.0.2 |
tsTrapNewAlarmThis trap is sent each time an alarm is inserted
into to the alarm table. It is sent on the insertion
of all alarms except for powerFailure. TRAP-TYPE .1.3.6.1.4.1.21796.3.4.0.3 |
tsTrapAlarmEndThis trap is sent each time an alarm is removed
from the alarm table. It is sent on the removal
of all alarms. TRAP-TYPE .1.3.6.1.4.1.21796.3.4.0.4 |
inpTableA list of binary input entries. SEQUENCE OF InpEntry .1.3.6.1.4.1.21796.3.4.1 |
inpEntryAn entry containing information applicable
to a particular binary input. InpEntry .1.3.6.1.4.1.21796.3.4.1.1 |
inpIndexThe binary input index. PositiveInteger .1.3.6.1.4.1.21796.3.4.1.1.1 |
inpStateThe binary input state.ro OnOff .1.3.6.1.4.1.21796.3.4.1.1.2 |
inpNameThe binary input name.rw IOName .1.3.6.1.4.1.21796.3.4.1.1.3 |
inpAlarmSetupYou can enable alarm for this binary input.
Alarm can be inactive or active for ON/OFF state.rw InputAlarmSetup .1.3.6.1.4.1.21796.3.4.1.1.4 |
inpAlarmStateThe binary input alarm state.ro InputAlarmState .1.3.6.1.4.1.21796.3.4.1.1.5 |
inpCounterNumber of pulses on this input.
Entering edge is used to increment this counter.
Only pulses longer than sampling interval are counted.rw NonNegativeInteger .1.3.6.1.4.1.21796.3.4.1.1.6 |
outTableA list of binary output entries. SEQUENCE OF OutEntry .1.3.6.1.4.1.21796.3.4.2 |
outEntryAn entry containing information applicable
to a particular binary output. OutEntry .1.3.6.1.4.1.21796.3.4.2.1 |
outIndexThe binary output index. PositiveInteger .1.3.6.1.4.1.21796.3.4.2.1.1 |
outStateThe binary output state. 0 off(open), 1 on(close), 2 off if any alarm, 3 on if any alarmrw OnOff .1.3.6.1.4.1.21796.3.4.2.1.2 |
outNameThe binary output name.rw IOName .1.3.6.1.4.1.21796.3.4.2.1.3 |
outTypeThe binary output type. 0 relay (off, on), 1 rts (-10,+10v), 2 dtr (0,10v)ro OutputType .1.3.6.1.4.1.21796.3.4.2.1.4 |
sensTableA list of sensor table entries. The number
of entries corresponds with number of detected sensors. SEQUENCE OF SensEntry .1.3.6.1.4.1.21796.3.4.3 |
sensEntryAn entry containing information applicable to a
particular sensor. SensEntry .1.3.6.1.4.1.21796.3.4.3.1 |
sensIndexThe sensor index. PositiveInteger .1.3.6.1.4.1.21796.3.4.3.1.1 |
sensNameThe sensor name.ro SensorName .1.3.6.1.4.1.21796.3.4.3.1.2 |
sensStateThe sensor state.ro SensorState .1.3.6.1.4.1.21796.3.4.3.1.4 |
sensStringThe string representation of sensor value.ro SensorString .1.3.6.1.4.1.21796.3.4.3.1.5 |
sensValueThe integer (decimal * 10) representation
of sensor value.ro SensorValue .1.3.6.1.4.1.21796.3.4.3.1.6 |
sensValueRawThe original raw value of sensor
(it differs for each sensor type, especially
1-Wire sensors have different precisions).ro SensorValue .1.3.6.1.4.1.21796.3.4.3.1.7 |
sensIDThe sensor ID.ro SensorID .1.3.6.1.4.1.21796.3.4.3.1.8 |
sensUnitThe sensor unit.ro UnitType .1.3.6.1.4.1.21796.3.4.3.1.9 |
tsAlarm OBJECT IDENTIFIER .1.3.6.1.4.1.21796.3.4.50 |
tsAlarmsPresentThe present number of active alarm conditions.ro Gauge32 .1.3.6.1.4.1.21796.3.4.50.1 |
tsAlarmTableA list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
tsAlarmId equal to 1, and increments the value of
tsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of tsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
tsAlarmId might have wrapped.
The number of rows in the table at any given time is
reflected by the value of tsAlarmsPresent. SEQUENCE OF TsAlarmEntry .1.3.6.1.4.1.21796.3.4.50.2 |
tsAlarmEntryAn entry containing information applicable
to a particular alarm. TsAlarmEntry .1.3.6.1.4.1.21796.3.4.50.2.1 |
tsAlarmIdxAn index to alarm table. PositiveInteger .1.3.6.1.4.1.21796.3.4.50.2.1.1 |
tsAlarmIdA unique identifier for an alarm condition.
This value must remain constant.ro PositiveInteger .1.3.6.1.4.1.21796.3.4.50.2.1.2 |
tsAlarmDescrDescription of the alarm condition.ro Enumeration .1.3.6.1.4.1.21796.3.4.50.2.1.3 |
tsAlarmSensNameName of sensor with alarm condition.ro SensorName .1.3.6.1.4.1.21796.3.4.50.2.1.4 |
tsAlarmTimeThe value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected
at the time of agent startup and presumably existed
before agent startup, the value of tsAlarmTime shall equal 0.ro TimeStamp (SNMPv2-TC) .1.3.6.1.4.1.21796.3.4.50.2.1.5 |
setup OBJECT IDENTIFIER .1.3.6.1.4.1.21796.3.4.99 |
sensSetup OBJECT IDENTIFIER .1.3.6.1.4.1.21796.3.4.99.1 |
unitTypeUnits for displayed values.
All setup values are fixed in Celsiusrw UnitType .1.3.6.1.4.1.21796.3.4.99.1.1 |
sensSetupTableA list of sensor table setup entries. The number
of entries corresponds with number of detected sensors. SEQUENCE OF SensSetupEntry .1.3.6.1.4.1.21796.3.4.99.1.2 |
sensSetupEntryAn entry containing setup information
for a particular sensor. SensSetupEntry .1.3.6.1.4.1.21796.3.4.99.1.2.1 |
sensSetupIndexThe sensor setup table index. PositiveInteger .1.3.6.1.4.1.21796.3.4.99.1.2.1.1 |
sensSetupNameThe sensor name.rw SensorName .1.3.6.1.4.1.21796.3.4.99.1.2.1.2 |
sensFlagsThe behaviour of sensor
- 0x01: range or level detection
- 0x02: enable trap sending
- 0x08: sensor enabled
- 0x10: enable SMS sending
- 0x20: enable email sending.rw SensorFlags .1.3.6.1.4.1.21796.3.4.99.1.2.1.5 |
sensLimitMinThe sensor low limit.rw SensorValue .1.3.6.1.4.1.21796.3.4.99.1.2.1.6 |
sensLimitMaxThe sensor high limit.rw SensorValue .1.3.6.1.4.1.21796.3.4.99.1.2.1.7 |
sensHysteresisThe sensor hysteresis.rw SensorValue .1.3.6.1.4.1.21796.3.4.99.1.2.1.8 |