Home/Catalog/CPS-MIB

CPS-MIB

AI MIB Summary

Standard SNMP MIB module defining data structures for CPS-MIB.

973
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

973 total
Object Name
cps
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808
RFC1213-MIB
Unknown
.1.3.6.1.4.1.3808
communicationLostSEVERE: Communication with the UPS has been lost.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.1
upsOverloadSEVERE: The UPS has sensed an overload condition.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.2
upsDiagnosticsFailedSEVERE: The UPS battery test failed.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.3
upsDischargedSEVERE: The UPS has started a runtime calibration process.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.4
upsOnBatteryWARNING: Utility power failed, transfer to backup mode.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.5
upsBoostOnWARNING: The UPS has enabled boost, low utility voltage.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.6
lowBatterySEVERE: The UPS battery capacity is low than threshold, soon to be exhausted.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.7
communicationEstablishedINFORMATIONAL: Communication to the UPS has been established.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.8
powerRestoredINFORMATIONAL: Utility power restored, return from backup mode.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.9
upsDiagnosticsPassedINFORMATIONAL: The UPS battery test passed.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.10
returnFromLowBatteryINFORMATIONAL: The UPS has returned from a low battery condition.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.11
upsTurnedOffWARNING: The UPS has been turned off.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.12
upsSleepingWARNING: The UPS entered sleep mode. Output power will not be provided.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.13
upsWokeUpINFORMATION: The UPS woke up from sleep mode. Output power is being provided.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.14
upsRebootStartedWARNING: The UPS started reboot sequence.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.15
upsOverTempSEVERE: The UPS inner temperature is too high.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.16
returnFromOverTempINFORMATIONAL: The UPS over temperature condition cleared.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.17
upsBuckOnWARNING: The UPS has enabled buck, high utility voltage.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.18
returnFromOverLoadINFORMATIONAL: The UPS has returned from an overload condition.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.19
returnFromDischargedINFORMATIONAL: The UPS runtime calibration completed.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.20
upsScheduleShutdownWARNING: The UPS has started its schedule shutdown sequence.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.21
upsEnterSleepWARNING: The UPS started sleep sequence.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.22
upsChargerFailureWARNING: The battery charger is abnormal.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.23
returnFromChargerFailureINFORMATIONAL: The charger returned from a failure condition.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.24
upsTurnoffStartedWARNING: The UPS started turn off sequence.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.25
upsTurnedOnWARNING: The UPS has been turned on.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.26
upsRemoteCommandFailedWARNING: The UPS remote command failed.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.27
upsSignalClientShutdownSEVERE: The UPS has signaled clients to shutdown.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.29
nclBankOnINFORMATIONAL: Non-Critical bank has been turned on.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.31
nclBankOffINFORMATIONAL: Non-Critical bank has been turned off.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.32
upsCommandCancelINFORMATION: The cancel command has been executed.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.33
upsStartBatteryTestINFORMATION: The UPS has started a battery test process.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.34
upsRemainRuntimeLowThanThresholdWARNING: The UPS remaining runtime is lower than threshold.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.35
nclBankStartScheduleOffINFORMATION: Non-Critial bank has started its schedule off sequence.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.36
upsCalibrationAbortWARNING: The UPS runtime calibration aborted.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.37
upsHardwareFaultWARNING: The UPS hardware fault.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.38
upsBatteryNotPresentWARNING: Battery is not present.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.39
upsWiringFaultWARNING: The UPS wiring fault has been detected.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.40
upsWiringFaultClearedINFORMATION: The UPS wiring fault has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.41
upsEnterBypassModeWARNING: The UPS enters bypass mode.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.42
upsReturnFromBypassModeINFORMATION: The UPS leaves bypass mode.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.43
upsBypassOverloadWARNING: The UPS bypass overload.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.44
upsBypassOverloadClearedINFORMATION: The UPS bypass overload has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.45
upsEnterECOModeWARNING: The UPS enters ECO mode.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.46
upsReturnFromECOModeWARNING: The UPS leaves ECO mode.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.47
upsBatteryOverThreeYearWARNING: Battery has been 3 years from last Replacement.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.48
failAuthViaHTTPWARNING: Login authorization failure via HTTP.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.61
passwordChangeINFORMATION: The password has been changed.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.62
failAuthViaConsoleWARNING: Login authorization failure via Console.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.63
configFileUploadINFORMATION: Configuration file uploaded.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.64
adminLoginInfoINFORMATION: Administrator login.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.65
adminLogoutInfoINFORMATION: Administrator logout.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.66
deviceLoginInfoINFORMATION: Device login.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.67
deviceLogoutInfoINFORMATION: Device logout.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.68
configurationChangedINFORMATION: Configuration has been changed.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.69
clientRegisteredInformation: PowerPanel client has been registered.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.70
clientRemovedInformation: PowerPanel client has been removed.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.71
testEventInformation: Test Event.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.72
outletUserLoginInfoInformation: Outlet User login.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.73
outletUserLogoutInfoInformation: Outlet User logout.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.74
ePDUCommunicationEstablishedINFORMATIONAL: Communication with a Rack PDU has been established. The first argument is the serial number. The second argument is the device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.100
ePDUCommunicationLostSEVERE: Communication with a Rack PDU has been lost. The first argument is the serial number. The second argument is the device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.101
ePDUOutletOnINFORMATIONAL: An outlet on a Switched Rack PDU has turned on. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.102
ePDUOutletOffINFORMATIONAL: An outlet on a Switched Rack PDU has turned off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.103
ePDUDeviceConfigChangeINFORMATIONAL: A device configuration change has been made on a Rack PDU. The first argument is the serial number. The second argument is the device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.104
ePDUOutletConfigChangeINFORMATIONAL: An outlet configuration change has been made on a Switched Rack PDU. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.105
ePDULowLoadWARNING: A Rack PDU has violated the low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.106
ePDULowLoadClearedINFORMATIONAL: The low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.107
ePDUNearOverloadWARNING: A Rack PDU is near an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.108
ePDUNearOverloadClearedINFORMATIONAL: The near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.109
ePDUOverloadSEVERE: A Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.110
ePDUOverloadClearedINFORMATIONAL: The overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.111
ePDUDelayOutletOnCommandINFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to turn on. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.112
ePDUDelayOutletOffCommandINFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to turn off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.113
ePDUDelayOutletRebootCommandINFORMATIONAL: An outlet on a Switched Rack PDU has been assigned to reboot. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.114
ePDUCancelPendingCommandINFORMATIONAL: A cancel pending command has been made on a Switched Rack PDU. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number (0 indicates all outlets). The fourth argument is the outlet name (or device name if all outlets).
TRAP-TYPE
.1.3.6.1.4.1.3808.0.115
ePDULineUndervoltageSEVERE: Utility Line Undervoltage The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.116
ePDULineUndervoltageClearedINFORMATIONAL: Utility Line Undervoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.117
ePDULineOvervoltageSEVERE: Utility Line Overvoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.118
ePDULineOvervoltageClearedINFORMATIONAL: Utility Line Overvoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.119
ePDUPowerSupply1FailSEVERE: Power Supply 1 on Rack PDU is in FAIL state. The first argument is the serial number. The second argument is the device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.120
ePDUPowerSupply1OkINFORMATIONAL: Power Supply 1 on Rack PDU is operating normally. The first argument is the serial number. The second argument is the device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.121
ePDUPowerSupply2FailSEVERE: Power Supply 2 on Rack PDU is in FAIL state. The first argument is the serial number. The second argument is the device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.122
ePDUPowerSupply2OkINFORMATIONAL: Power Supply 2 on Rack PDU is operating normally. The first argument is the serial number. The second argument is the device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.123
ePDUBankLowLoadWARNING: A Rack PDU bank has violated the low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is the bank number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.124
ePDUBankLowLoadClearedINFORMATIONAL: The low load condition on a Rack PDU bank has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the bank number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.125
ePDUBankNearOverloadWARNING: A Rack PDU bank is near an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the bank number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.126
ePDUBankNearOverloadClearedINFORMATIONAL: The near overload condition on a Rack PDU bank has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase/bank number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.127
ePDUBankOverloadSEVERE: A Rack PDU bank is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the bank number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.128
ePDUBankOverloadClearedINFORMATIONAL: The overload condition on a Rack PDU bank has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the bank number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.129
ePDUComponentCommunicationEstablishedINFORMATIONAL: Component communication lost has been cleared. The first argument is the serial number. The second argument is the device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.130
ePDUComponentCommunicationLostSEVERE: Component communication lost. The first argument is the serial number. The second argument is the device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.131
ePDUOutletLowLoadWARNING: A Rack PDU has violated the outlet low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.132
ePDUOutletLowLoadClearedINFORMATIONAL: The outlet low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.133
ePDUOutletNearOverloadWARNING: A Rack PDU is near an outlet overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.134
ePDUOutletNearOverloadClearedINFORMATIONAL: The outlet near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.135
ePDUOutletOverloadSEVERE: A Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.136
ePDUOutletOverloadClearedINFORMATIONAL: The outlet overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.137
envHighTemperatureViolationWARNING: The environment high temperature threshold has been violated.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.200
envHighTemperatureBackINFORMATION: The environment temperature returned from high value.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.201
envLowTemperatureViolationWARNING: The environment low temperature threshold has been violated.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.202
envLowTempBackINFORMATION: The environment temperature returned from low value.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.203
envHighHumidityViolationWARNING: The environment high humidity threshold has been violated.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.204
envHighHumidityBackINFORMATION: The environment humidity return from high value.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.205
envLowHumidityViolationWARNING: The environment low humidity threshold has been violated.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.206
envLowHumdBackINFORMATION: The environment humidity return from low value.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.207
envDryContactAbnormalINFORMATION: The Contact is abnormal.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.208
envDryContactNormalINFORMATION: The Contact has returned from abnormal.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.209
envConntectedINFORMATION: The Environment Sensor has been connected.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.210
envDisconntectedINFORMATION: The Environment Sensor has been disconnected.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.211
envRateOfTemperatureChangeAbnormalINFORMATION: The rate of temperature change is abnormal.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.212
envRateOfHumdChangeAbnormalINFORMATION: The rate of humidity change is abnormal.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.213
atsSwitchSourceINFORMATIONAL: ATS has switched source. The first argument is the device name. The second argument is the serial number. The third argument is the selected source.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.301
atsSourceFaultWARNING: Source fault occurs. The first argument is the device name. The second argument is the serial number. The third argument is the source name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.302
atsSourceFaultClearedINFORMATIONAL: Source fault has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.303
atsRedundancyFailWARNING: Redundancy fails. The first argument is the device name. The second argument is the serial number. The third argument is the source name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.304
atsRedundancyRestoredINFORMATIONAL: Redundancy has been restored. The first argument is the device name. The second argument is the serial number. The third argument is the source name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.305
atsInputHighVoltageWARNING: The upper voltage limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the phase voltage.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.306
atsInputHighVoltageClearedINFORMATIONAL: The upper voltage condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the phase voltage.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.307
atsInputLowVoltageWARNING: The lower voltage limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the phase voltage.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.308
atsInputLowVoltageClearedINFORMATIONAL: The lower voltage condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the phase voltage.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.309
atsInputHighFrequencyWARNING: The upper frequency limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the input frequency.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.310
atsInputHighFrequencyClearedINFORMATIONAL: The upper frequency condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the input frequency.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.311
atsInputLowFrequencyWARNING: The lower frequency limit has been crossed. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the input frequency.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.312
atsInputLowFrequencyClearedINFORMATIONAL: The lower frequency condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the source name. The fourth argument is the input frequency.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.313
atsCommunicationLostMAJOR: ATS communication lost. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.314
atsCommunicationEstablishedINFORMATIONAL: ATS communication has been established. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.315
atsLCDCommunicationLostWARNING: LCD communication lost. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.316
atsLCDCommunicationLostClearedINFORMATIONAL: LCD communication lost has been cleared. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.317
atsDB9CommunicationLostWARNING: DB9 communication lost. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.318
atsDB9CommunicationLostClearedINFORMATIONAL: DB9 communication lost has been cleared. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.319
atsPowerSupplyFaultCRITICAL: Power supply failure. The first argument is the device name. The second argument is the serial number. The third argument is the input source of the power supply.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.320
atsPowerSupplyFaultClearedCRITICAL: Power supply failure. The first argument is the device name. The second argument is the serial number. The third argument is the input source of the power supply.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.321
atsDevHardwareFaultCRITICAL: Device hardware failure. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.322
atsDevHardwareFaultClearedINFORMATIONAL: Device hardware failure has been cleared. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.323
atsSourceConfigChangedINFORMATIONAL: A source configuration change has been made. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.324
atsDeviceConfigChangedINFORMATIONAL: A device configuration change has been made. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.325
atsOutletConfigChangedINFORMATIONAL: A outlet configuration change has been made. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.326
atsEventCountsClearedINFORMATIONAL: Event counts has been cleared. The first argument is the device name. The second argument is the serial number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.327
atsOverloadWARNING: The load has exceeded overload threshold. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.328
atsOverloadClearedINFORMATIONAL: The overload condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.329
atsNearOverloadWARNING: The load has exceeded near overload threshold. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.330
atsNearOverloadClearedINFORMATIONAL: The near overload condition has beed cleared. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.331
atsLowLoadWARNING: The load has been lower than low load threshold. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.332
atsLowLoadClearedINFORMATIONAL: The low load condition has been cleared. The first argument is the device name. The second argument is the serial number. The third argument is the bank number. The third argument is the load.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.333
atsOutletOnCommandINFORMATIONAL: An outlet on ATS has been assigned to turn on. The first argument is the device name. The second argument is the serial number. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.334
atsOutletOffCommandINFORMATIONAL: An outlet on ATS has been assigned to turn off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.335
atsOutletRebootCommandINFORMATIONAL: An outlet on ATS has been assigned to reboot. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.336
atsCancelPendingCommandINFORMATIONAL: A cancel pending command has been made on ATS. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number (0 indicates all outlets). The fourth argument is the outlet name (or device name if all outlets).
TRAP-TYPE
.1.3.6.1.4.1.3808.0.337
atsOutletOnINFORMATIONAL: An outlet on ATS has turned on. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.338
atsOutletOffINFORMATIONAL: An outlet on ATS has turned off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.339
pduDeviceEventINFORMATIONAL: A PDU device event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the device table index.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.400
pduDeviceAlarmAlarm: A PDU device alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the device table index.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.401
pduDeviceAlarmClearINFORMATIONAL: A PDU device alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the device table index.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.402
pduPhaseEventINFORMATIONAL: A PDU phase event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the phase table index. The foutrh argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.403
pduPhaseAlarmAlarm: A PDU phase alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the phase table index. The foutrh argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.404
pduPhaseAlarmClearINFORMATIONAL: A PDU phase alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase table index. The foutrh argument is the phase number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.405
pduBankEventINFORMATIONAL: A PDU bank event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the bank table index. The foutrh argument is the bank number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.406
pduBankAlarmAlarm: A PDU bank alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the bank table index. The foutrh argument is the bank number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.407
pduBankAlarmClearINFORMATIONAL: A PDU bank alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the bank table index. The foutrh argument is the bank number.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.408
pduOutletSwitchedEventINFORMATIONAL: A PDU switched outlet event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.409
pduOutletSwitchedAlarmAlarm: A PDU switched outlet alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.410
pduOutletSwitchedAlarmClearINFORMATIONAL: A PDU switched outlet alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.411
pduOutletMeteredEventINFORMATIONAL: A PDU metered outlet event has been happened. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.412
pduOutletMeteredAlarmAlarm: A PDU metered outlet alarm has been detected. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.413
pduOutletMeteredAlarmClearINFORMATIONAL: A PDU metered outlet alarm has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet table index. The foutrh argument is the outlet number. The fifth argument is the outlet name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.414
pduDaisyChainEventINFORMATIONAL: A PDU daisy-chain event has been happened. The first argument is the host serial number. The second argument is the host device name. The third argument is the event device table index. The foutrh argument is the event device serial number. The fifth argument is the event device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.415
pduDaisyChainAlarmAlarm: A PDU daisy-chain alarm has been detected. The first argument is the host serial number. The second argument is the host device name. The third argument is the alarm device table index. The foutrh argument is the alarm device serial number. The fifth argument is the alarm device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.416
pduDaisyChainAlarmClearINFORMATIONAL: A PDU daisy-chain alarm has been cleared. The first argument is the host serial number. The second argument is the host device name. The third argument is the alarm device table index. The foutrh argument is the alarm deice serial number. The fifth argument is the alarm device name.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.417
bmSystemAlarmALARM: System alarm occurance. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the alarm event specific identifier. The fifth argument is the trap information string.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.600
bmSystemWarningWARNING: System warning occurance. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the alarm event specific identifier. The fifth argument is the trap information string.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.601
bmSystemInfoINFO: System information. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the alarm event specific identifier. The fifth argument is the trap information string.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.602
bmProbesAlarmALARM: Probe alarm event. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the string index the probe located. The fifth argument is the battery index the probe located. The sixth argument is the alarm event specific identifier. The seventh argument is the trap information string.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.603
bmSProbesWarningWARNING: Probe warning event. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the string index the probe located. The fifth argument is the battery index the probe located. The sixth argument is the alarm event specific identifier. The seventh argument is the trap information string.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.604
bmProbesInfoINFO: Probe information. The first argument is the bm device serial number. The second argument is the bm system identification name. The third argument is the bm system location. The fourth argument is the string index the probe located. The fifth argument is the battery index the probe located. The sixth argument is the alarm event specific identifier. The seventh argument is the trap information string.
TRAP-TYPE
.1.3.6.1.4.1.3808.0.605
products
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1
hardware
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1
ups
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1
upsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.1
upsBaseIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.1.1
upsBaseIdentModelThe UPS model name.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.1.1.1
upsBaseIdentNameThe UPS identified name could be set by the administrator.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.1.1.2
upsAdvanceIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.1.2
upsAdvanceIdentFirmwareRevisionThe UPS firmware revision.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.1.2.1
upsAdvanceIdentDateOfManufactureThe UPS manufacture date in mm/dd/yy format.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.1.2.2
upsAdvanceIdentSerialNumberThe UPS serial number in the internal microprocessor.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.1.2.3
upsAdvanceIdentAgentFirmwareRevisionThe SNMP agent firmware revision.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.1.2.4
upsAdvanceIdentLCDFirmwareVersionThe revision number of the UPS LCD firmware.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.1.2.5
upsAdvanceIdentPowerRatingThe Volt-Amp rating of the UPS.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.1.2.6
upsAdvanceIdentLoadPowerThe power rating(Watts) of the UPS.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.1.2.7
upsAdvanceIdentCurrentRatingThe output current rating of the UPS. Measured in tenths of Amps.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.1.2.8
upsBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.2
upsBaseBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.2.1
upsBaseBatteryStatusThe UPS battery status. A batteryLow(3) value means the battery will be exhausted soon under the current load. The amount of low battery run time can be configured by the upsAdvanceConfigLowBatteryRunTime.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.1.2.1.1
upsBaseBatteryTimeOnBatteryThe UPS wasted battery time since the UPS has transfered to backup mode.ro
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.3808.1.1.1.2.1.2
upsBaseBatteryLastReplaceDateThe UPS batteries last replaced date in mm/dd/yy format. This value is originally set when manufactured. If batteries replaced, administrator should reset this value.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.2.1.3
upsAdvanceBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.2.2
upsAdvanceBatteryCapacityThe battery capacity expressed in percentage.ro
Gauge
.1.3.6.1.4.1.3808.1.1.1.2.2.1
upsAdvanceBatteryVoltageThe battery voltage expressed in 1/10 VDC.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.2.2.2
upsAdvanceBatteryTemperatureThe UPS battery temperature expressed in Celsius.ro
Gauge
.1.3.6.1.4.1.3808.1.1.1.2.2.3
upsAdvanceBatteryRunTimeRemainingThe UPS battery remaining run time.ro
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.3808.1.1.1.2.2.4
upsAdvanceBatteryReplaceIndicatorThis value indicates if UPS batteries need to be replaced.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.1.2.2.5
upsAdvanceBatteryFullChargeVoltageThe battery charged voltage expressed in 1/10 VDC.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.2.2.6
upsAdvanceBatteryCurrentThe battery current expressed in percentage.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.2.2.7
upsAdvanceBatteryVoltageRatingThe DC voltage rating of the battery set.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.2.2.8
upsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.3
upsBaseInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.3.1
upsBaseInputPhaseThe AC input phase.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.3.1.1
upsAdvanceInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.3.2
upsAdvanceInputLineVoltageThe input line voltage in 1/10 VAC.ro
Gauge
.1.3.6.1.4.1.3808.1.1.1.3.2.1
upsAdvanceInputMaxLineVoltageThe maximum input line voltage in 1/10 VAC over the previous 1 minute period.ro
Gauge
.1.3.6.1.4.1.3808.1.1.1.3.2.2
upsAdvanceInputMinLineVoltageThe minimum input line voltage in 1/10 VAC over the previous 1 minute period.ro
Gauge
.1.3.6.1.4.1.3808.1.1.1.3.2.3
upsAdvanceInputFrequencyThe input line frequency in 1/10 Hz.ro
Gauge
.1.3.6.1.4.1.3808.1.1.1.3.2.4
upsAdvanceInputLineFailCauseThe reason of UPS power failure. This value is set to: - noTransfer(1), if UPS is in utility mode. - highLineVoltage(2), if UPS switch to battery mode by reason of input voltage over the high transfer vloltage. - brownout(3), if UPS switch to battery mode by reason of input voltage under the low transfer vloltage. - selfTest(4), if the UPS was commanded to do a self test.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.1.3.2.5
upsAdvanceInputStatusDisplay the present status of the utility power supplied to the UPS.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.1.3.2.6
upsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.4
upsBaseOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.4.1
upsBaseOutputStatusThe UPS output status.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.1.4.1.1
upsBaseOutputPhaseThe output phase.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.4.1.2
upsBaseOutputWorkingFrequencyThe frequency of the UPS output power.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.4.1.3
upsAdvanceOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.4.2
upsAdvanceOutputVoltageThe UPS output voltage in 1/10 VAC.ro
Gauge
.1.3.6.1.4.1.3808.1.1.1.4.2.1
upsAdvanceOutputFrequencyThe UPS output frequency in 1/10 Hz.ro
Gauge
.1.3.6.1.4.1.3808.1.1.1.4.2.2
upsAdvanceOutputLoadThe UPS output load expressed in percentagero
Gauge
.1.3.6.1.4.1.3808.1.1.1.4.2.3
upsAdvanceOutputCurrentThe UPS output current in Amps.ro
Gauge
.1.3.6.1.4.1.3808.1.1.1.4.2.4
upsAdvanceOutputPowerThe total output active power of the UPS system in W.ro
Gauge
.1.3.6.1.4.1.3808.1.1.1.4.2.5
upsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.5
upsBaseConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.5.1
upsBaseConfigNumDevicesThe number of equipment plugged into the UPS.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.5.1.1
upsBaseConfigDeviceTableA list of equipment plugged into the UPS. The numbers of entries are given by the value of upsBaseConfigNumDevices.
SEQUENCE OF UpsBaseConfigDeviceEntry
.1.3.6.1.4.1.3808.1.1.1.5.1.2
upsBaseConfigDeviceEntryThe equipment plugged in to the UPS.
UpsBaseConfigDeviceEntry
.1.3.6.1.4.1.3808.1.1.1.5.1.2.1
deviceIndexThe index of the equipment plugged into the UPS.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.5.1.2.1.1
deviceNameThe name of the equipment plugged into the UPS.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.5.1.2.1.2
vaRatingThe VA rating of the equipment plugged into the UPS.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.1.5.1.2.1.3
acceptThisDeviceAn equipment is plugged if yes, unplugged if no.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.5.1.2.1.4
upsAdvanceConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.5.2
upsAdvanceConfigRatedOutputVoltageThe standard UPS output voltage in VAC. The possible values are 100, 110, 120, 127, 208, 220, 230, and 240. If a value other than a possible value is set, it will not be accepted.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.1.5.2.1
upsAdvanceConfigHighTransferVoltAdjust the high transfer vloltage in VAC. The high transfer vloltage will become the UPS default value subtracts this value. The allowed values depend on the output: 100-127 volt system allow settings of 0-15. 208-240 volt system allow settings of 0-30. If the adjustable value is over the allowed values, it will not be accepted.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.1.5.2.2
upsAdvanceConfigLowTransferVoltAdjust the low transfer vloltage in VAC. The low transfer vloltage will become the UPS default value adds this value. The allowed values depend on the output: 100-127 volt system allow settings of 0-15. 208-240 volt system allow settings of 0-30. If the adjustable value is over the allowed values, it will not be accepted.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.1.5.2.3
upsAdvanceConfigAlarmThis value is set to handle audible alarms when power failure.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.5.2.4
upsAdvanceConfigAlarmTimerThe time after power failure at which the UPS begins giving audible alarms. This timer is effective only if the value of upsAdvanceConfigAlarm is timed(1). Accepted values are between 0 to 60 seconds. If a value other than a supported value is set, the value will not be accepted.rw
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.3808.1.1.1.5.2.5
upsAdvanceConfigMinReturnCapacityThe minimum battery capacity that UPS will return from a low battery shutdown condition. The possible values are between 0 to 40. If a value other than a supported value is set, the value will not be accepted.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.1.5.2.6
upsAdvanceConfigSensitivityThe sensitivity of the UPS to power failure detection.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.5.2.7
upsAdvanceConfigLowBatteryRunTimeThe desired run time, in seconds, UPS will enter in a low battery sequence. The possible values are 120, 300, 420, 600. If a value other than a supported value is set, the value will not be accepted.rw
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.3808.1.1.1.5.2.8
upsAdvanceConfigReturnDelayThe delay time the UPS will turn on after power recovery. The value is also used in a 'reboot' or 'wake up' sequence. The possible values are 0 to 600 seconds. If a value other than a supported value is set, the value will not be accepted.rw
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.3808.1.1.1.5.2.9
upsAdvanceConfigShutoffDelayThe delay time the UPS will remain on after receiving a turn off command. The possible values are between 1 to 99 minutes. If a value other than a supported value is set, the value will not be accepted.rw
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.3808.1.1.1.5.2.10
upsAdvanceConfigSleepDelayThe delay time the UPS will enter sleep mode after receiving a sleep command. WThe possible values are between 1 to 99 minutes. If a value other than a supported value is set, the value will not be accepted.rw
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.3808.1.1.1.5.2.11
upsAdvanceConfigSetEEPROMDefaultsReset the UPS EEPROM parameters to default values.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.5.2.12
upsAdvanceConfigAutoRestoreWhen this option is enabled, the UPS will restore output immediately when the utility power restores.When this option is disabled, the UPS will not restore output at that moment and users have to turn it on manually at a later time.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.5.2.13
upsAdvanceConfigRechargedCapacityWhen the utility power restores, the UPS will start to recharge until the specified battery capacity in percentage is met before restoring output power. The possible values are 0, 15, 30, 45, 60, 75, and 90. If a value other than a possible value is set, it will not be accepted.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.1.5.2.14
upsAdvanceConfigColdStartSet the ability of the UPS can start in the absence of input power.When this option is enabled the UPS can be turned on without having input power.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.5.2.15
upsAdvanceConfigDeepDischargeProtectionWhen the UPS is on Battery Mode with 0% load and the status remains for the time configured,the RMCARD will enforce the UPS to Sleep Mode and the output will be turned off. The possible values are 0, 20, 40, and 60 minutes. If a value other than a possible value is set, it will not be accepted.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.1.5.2.16
upsAdvanceConfigSleepAfterAllClientShutIf this option is enabled, UPS will enter sleep mode after utility power failed and remaining MSDT+2 minutes.More information about MSDT please reference to help page of UPS - > PowerPanel List.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.5.2.17
upsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.6
upsBaseControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.6.1
upsBaseControlConserveBatteryUPS on battery will enter sleeping when the variable is set to turnOffUpsToConserveBattery(2). When utility power recovers the UPS will turn back on. Trying to turn off a UPS that is not on battery mode will cause badValue error. It is no effective to set this value to noTurnOffUps(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.6.1.1
upsAdvanceControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.6.2
upsAdvanceControlUpsOffUPS will shutdown when the variable is set to turnUpsOff(2). UPS will shutdown after a delay period specified by upsAdvanceConfigShutoffDelay when the variable is Set to turnUpsOffGracefully(3). Without regard to the utility state the UPS will not provide output power in this state. It is no effective to set this value to noTurnUpsOff(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.6.2.1
upsAdvanceControlRebootUpsUPS will shutdown and turn back on when the variable is set to rebootUps(2). It is no effective to set this value to noRebootUps(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.6.2.2
upsAdvanceControlUpsSleepUPS will enter sleep mode when the variable is set to putUpsToSleep(2). UPS will enter sleep mode after a delay period specified by upsAdvanceConfigSleepDelay when the variable is Set to putUpsToSleepGracefully(3). Without regard to the utility state the UPS will not provide output power in sleep mode. Output power will recover when specified time has elapsed. It is no effective to set this value to noPutUpsToSleep(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.6.2.3
upsAdvanceControlSimulatePowerFailUPS will transfer to backup mode when the variable is set to simulatePowerFailure(2). It is no effective to set this value to noFlashAndBeep(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.6.2.4
upsAdvanceControlFlashAndBeepUPS will beep and simultaneously turn on the panel lights when the variable is set to flashAndBeep(2). It is no effective to set this value to noSimulatePowerFailure(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.6.2.5
upsAdvanceControlTurnOnUPSUPS will turned on immediately when the variable is set to turnOnUPS(2). It is no effective to set this value to noTurnOnUPS(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.6.2.6
upsTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.7
upsBaseTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.7.1
upsAdvanceTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.7.2
upsAdvanceTestDiagnosticScheduleThe schedule of the UPS automatic selftest.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.7.2.1
upsAdvanceTestDiagnosticsUPS will do a diagnostic selftest when the variable is set to testDiagnostics(2). It is no effective to set this value to noTestDiagnostics(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.7.2.2
upsAdvanceTestDiagnosticsResultsThe last UPS selftest result.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.1.7.2.3
upsAdvanceTestLastDiagnosticsDateThe last UPS selftest date in mm/dd/yy format.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.7.2.4
upsAdvanceTestIndicatorsUPS will perform a panel indicator test when the variable is set to testIndicators(2). It is no effective to set this value to noTestIndicators(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.7.2.5
upsAdvanceTestRuntimeCalibrationUPS will discharge to calibrate the UPS runtime when the variable is set to performCalibration(2). This test runs until the UPS is in a low battery condition. UPS will cancel the discharge after setting performCalibration(2) when the variable is set to cancelCurrentCalibration(3). It is no effective to set this value to noPerformCalibration(1). The result of the runtime test will be stored in upsAdvanceTestCalibrationResults.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.7.2.6
upsAdvanceTestCalibrationResultsThe last runtime calibration result. This value means : - ok(1), if a successful runtime calibration. - invalidCalibration(2), if runtime calibration failure. - calibrationInProgress(3), if calibration is processing now.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.1.7.2.7
upsAdvanceTestCalibrationDateThe last UPS runtime calibration datero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.1.7.2.8
upsOutlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.8
upsBankOutletControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.8.1
upsBankOutletControlTableAllows for control of the outlet banks.
SEQUENCE OF UpsBankOutletControlEntry
.1.3.6.1.4.1.3808.1.1.1.8.1.1
upsBankOutletControlEntryThe outlet to control.
UpsBankOutletControlEntry
.1.3.6.1.4.1.3808.1.1.1.8.1.1.1
upsBankControlIndexThe index to the outlet entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.8.1.1.1.1
upsBankControlOutletCommandGetting this variable will return the outlet bank state. If the outlet bank is on, the immediateOn (1) value will be returned. If the outlet bank is off, the immediateOff (2) value will be returned. If the outlet bank is critical (uncontrollable), the criticalBank (4) value will be returned. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.1.8.1.1.1.2
upsPhase
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.9
upsPhaseInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.9.1
upsPhaseInputTableSizeGetting this OID will return the phase number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.1.1
upsPhaseInputTableAllows for getting the Phase Input in the UPS
SEQUENCE OF PhaseInputEntry
.1.3.6.1.4.1.3808.1.1.1.9.1.2
upsPhaseInputEntryThe UPS Phase Input Access.
PhaseInputEntry
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1
upsPhaseInputTableIndexThe index to the UPS Phase Input entry.ro
INTEGER(3)
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1.1
upsPhaseInputVoltageGetting this OID will return the input voltage that each phase of the UPS can provide. It is represented in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1.2
upsPhaseInputCurrentGetting this OID will return the input current that each phase of the UPS can provide. It is represented in 1/10 Amps.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1.3
upsPhaseInputFrequencyGetting this OID will return the input frequency that each phase of the UPS can provide. It is represented in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1.4
upsPhaseInputPowerFactorGetting this OID will return the input power factor that each phase of the UPS can provide. It is represented in 1/100.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.1.2.1.5
upsPhaseOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.9.2
upsPhaseOutputTableSizeGetting this OID will return the Phase number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.2.1
upsPhaseOutputTableAllows for getting the Phase Output in the UPS
SEQUENCE OF PhaseOutputEntry
.1.3.6.1.4.1.3808.1.1.1.9.2.2
upsPhaseOutputEntryThe UPS Phase Output Access.
PhaseOutputEntry
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1
upsPhaseOutputTableIndexThe index to the UPS Phase Output entry.ro
INTEGER(3)
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.1
upsPhaseOutputVoltageGetting this OID will return the output voltage that each phase of the UPS can provide. It is represented in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.2
upsPhaseOutputCurrentGetting this OID will return the output current that each phase of the UPS can provide. It is represented in 1/10 Amps.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.3
upsPhaseOutputFrequencyGetting this OID will return the output frequency that each phase of the UPS can provide. It is represented in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.4
upsPhaseOutputPowerFactorGetting this OID will return the output power factor that each phase of the UPS can provide. It is represented in 1/100.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.5
upsPhaseOutputPowerGetting this OID will return the output power that each phase of the UPS can provide. It is represented in Watt.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.2.2.1.6
upsPhaseBypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.1.9.3
upsPhaseBypassTableSizeGetting this OID will return the Phase number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.3.1
upsPhaseBypassTableAllows for getting the Phase Bypass in the UPS
SEQUENCE OF PhaseBypassEntry
.1.3.6.1.4.1.3808.1.1.1.9.3.2
upsPhaseBypassEntryThe UPS Phase Bypass Access.
PhaseBypassEntry
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1
upsPhaseBypassTableIndexThe index to the UPS Phase Bypass entry.ro
INTEGER(3)
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1.1
upsPhaseBypassVoltageGetting this OID will return the bypass voltage that each phase of the UPS can provide. It is represented in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1.2
upsPhaseBypassCurrentGetting this OID will return the bypass current that each phase of the UPS can provide. It is represented in 1/10 Amps.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1.3
upsPhaseBypassFrequencyGetting this OID will return the bypass frequency that each phase of the UPS can provide. It is represented in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1.4
upsPhaseBypassPowerFactorGetting this OID will return the bypass power factor that each phase of the UPS can provide. It is represented in 1/100.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.1.9.3.2.1.5
eswitch
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.2
eSwitchIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.2.1
eSwitchIdentHardwareRevThe hardware revision set at the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.2.1.1
eSwitchIdentFirmwareRevThe firmware revision set at the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.2.1.2
eSwitchIdentDateOfManufactureThe manufacture date in mm/dd/yy format.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.2.1.3
eSwitchIdentModelNameThe model name set at the factory. This value need to consist with safty report.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.2.1.4
eSwitchBase
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.2.2
eSwitchNumberThe numbers of switch have been attached to the system.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.2.2.1
eSwitchBaseTableA list of switch information. The number of entries is given by the value of eSwitchNumber.
SEQUENCE OF ESwitchBaseEntry
.1.3.6.1.4.1.3808.1.1.2.2.2
eSwitchBaseEntryAn entry information of the individual switch.
ESwitchBaseEntry
.1.3.6.1.4.1.3808.1.1.2.2.2.1
eSwitchIDThe power switch ID number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.2.2.2.1.1
eSwitchOutletNumThe number of outlets provided in the switch.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.2.2.2.1.2
eSwitchOutletStateGetting this OID will reply the status of all outlets in the switch. '0' for outlet off, '1' for outlet on. The index from left to right is outlet#8, #7, #6, #5, #4, #3, #2, #1. For Example: If the string is '01011010', it means the outlets status are the following: outlet #8 is off, outlet #7 is on, outlet #6 is off, outlet #5 is on, outlet #4 is on, outlet #3 is off, outlet #2 is on, outlet #1 is off.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.2.2.2.1.3
eSwitchBaseCtrTableA list of switch control parameters. The number of entries is given by the value of eSwitchNumber.
SEQUENCE OF ESwitchBaseCtrEntry
.1.3.6.1.4.1.3808.1.1.2.2.3
eSwitchBaseCtrEntryAn entry control information of individual switches.
ESwitchBaseCtrEntry
.1.3.6.1.4.1.3808.1.1.2.2.3.1
eSwitchCtrIDSelect the switch ID to be controlled.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.2.2.3.1.1
eSwitchActOutletThe action outlets to be controlled.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.2.2.3.1.2
eSwitchActTypeThe on/off type of the action outlets. 1 for duration off, 2 for duration on, 3 for immediately off, 4 for immediately on, and 5 for reboot.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.2.2.3.1.3
ePDU
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3
ePDUIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.1
ePDUIdentNameThe name of the Rack PDU. The maximum string size is device dependent.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.1.1
ePDUIdentHardwareRevThe hardware revision of the Rack PDU. This value is set at the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.1.2
ePDUIdentFirmwareRevAn 8-byte ID string identifying the Rack PDU firmware revision. This value is set at the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.1.3
ePDUIdentDateOfManufactureThe date when the Rack PDU was manufactured in mm/dd/yyyy format. This value is set at the factory. The year 2000 will be represented by 00.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.1.4
ePDUIdentModelNumberA 10-character string identifying the model number of the Rack PDU. This value is set at the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.1.5
ePDUIdentSerialNumberA 12-character string identifying the serial number of the Rack PDU. This value is set at the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.1.6
ePDUIdentDeviceRatingGetting this OID will return the electrical rating of the device.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.1.7
ePDUIdentDeviceNumOutletsGetting this OID will return the number of outlets contained in the device.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.1.8
ePDUIdentDeviceNumPhasesGetting this OID will return the number of phases supported by the device.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.1.9
ePDUIdentDeviceNumBreakersGetting this OID will return the number of circuit breakers supported by the device. This is the same as the number of banks of outlets. 0 will be returned if the unit has no phase breakers.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.1.10
ePDUIdentDeviceBreakerRatingGetting this OID will return rating of the circuit breakers on the device if it has any.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.1.11
ePDUIdentDeviceOrientationGetting this OID will return the intended physical orientation of the device. OrientHorizonatal(1) indicates Horizontal. OrientVertical(2) indicates Vertical.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.1.12
ePDUIdentDeviceOutletLayoutGetting this OID will return outlet layout for the device. SeqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... SeqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... SeqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... SeqPhToPhGrouped(4) indicates outlet layout as follows: Otlts1-8::(3-1),Otlts9-16::(2-3),Otlts17-24::(1-2).ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.1.13
ePDUIdentDeviceDisplayOrientationGetting this OID will return the intended physical orientation of the Seven-Segment Display. displayNormal(1) indicates Normal. displayReverse(2)indicates Upside-Down. displayRotate90(3) indicates rotate 90 degree. displayRotate270(4) indicates rotate 270 degree. displayAuto(5) indicates auto-detect and rotate.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.3.1.14
ePDUIdentDeviceLinetoLineVoltageGetting/Setting this OID will return/set the Line to Line Volatage. The valid range is between 0V to 440Vrw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.1.15
ePDUIdentIndicatorPDU will perform a panel indicator test when the variable is set to testIndicators(2). It is no effective to set this value to noTestIndicators(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.3.1.16
ePDULoad
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.2
ePDULoadDevice
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.2.1
ePDULoadDevMaxPhaseLoadGetting this OID will return the maximum rated power that each phase of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the unit is banked.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.1
ePDULoadDevNumPhasesThe number of phases available with this Rack PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.2
ePDULoadDevMaxBankLoadGetting this OID will return the maximum rated power that a bank of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the device does not have any banks.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.3
ePDULoadDevNumBanksThe number of banks of outlets available with this Rack PDU. A bank of outlets has a unique circuit breaker for a subset of the total number of outlets on the ePDU. 0 will be returned if the unit no banks.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.4
ePDULoadDevBankTableSizeThe size of the Bank Table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.5
ePDULoadDevBankTableAllows for getting the Bank Max Load in the Rack PDU.
SEQUENCE OF LoadDevBankEntry
.1.3.6.1.4.1.3808.1.1.3.2.1.6
ePDULoadDevBankEntryThe Rack PDU Banks Access.
LoadDevBankEntry
.1.3.6.1.4.1.3808.1.1.3.2.1.6.1
ePDULoadDevBankIndexThe index to the Rack PDU bank entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.6.1.1
ePDULoadDevBankNumberGetting this OID will return the bank number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.6.1.2
ePDULoadDevBankMaxLoadGetting this OID will return the maximum rated power that each bank of the Rack PDU can provide. It is represented in Amps.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.6.1.3
ePDULoadDevMaxOutletTableSizeThe size of the Outlet Table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.7
ePDULoadDevMaxOutletTableAllows for getting the Max Outlet Load in an Outlet Monitored Rack PDU.
SEQUENCE OF LoadDevMaxOutletEntry
.1.3.6.1.4.1.3808.1.1.3.2.1.8
ePDULoadDevMaxOutletEntryThis gives access to Max Outlet Load of an Outlet Monitored Rack PDU
LoadDevMaxOutletEntry
.1.3.6.1.4.1.3808.1.1.3.2.1.8.1
ePDULoadDevOutletIndexThe index to the Outlet Monitored Rack PDU Max Outlet Load entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.8.1.1
ePDULoadDevOutletNumberGetting this OID will return the Outlet number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.8.1.2
ePDULoadDevMaxOutletLoadGetting this OID will return the maximum rated power that each Outlet of an Outlet Monitored Rack PDU can provide. It is represented in Amps.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.1.8.1.3
ePDULoadPhaseConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.2.2
ePDULoadPhaseConfigTableAllows for configuration of each Rack PDU phase. The number of entries is contained in the ePDULoadDevNumPhases OID.
SEQUENCE OF LoadPhaseConfigEntry
.1.3.6.1.4.1.3808.1.1.3.2.2.1
ePDULoadPhaseConfigEntryThe Rack PDU phase to configure.
LoadPhaseConfigEntry
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1
ePDULoadPhaseConfigIndexThe index to the Rack PDU phase entry.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1.1
ePDULoadPhaseConfigLowLoadThresholdA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning. Maximum value must be less than the value returned by the ePDULoadPhaseConfigNearOverloadThreshold OID.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1.2
ePDULoadPhaseConfigNearOverloadThresholdA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the ePDULoadPhaseConfigLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDULoadPhaseConfigOverloadThreshold OID.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1.3
ePDULoadPhaseConfigOverloadThresholdA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the ePDULoadPhaseConfigNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDULoadDevMaxPhaseLoad OID.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1.4
ePDULoadPhaseConfigAlarmGetting this OID will return the current Phase Alarm.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.2.2.1.1.5
ePDULoadStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.2.3
ePDULoadStatusTableAllows for getting of status of each Rack PDU phase/bank. The number of entries is calculated by adding the number of phases (ePDULoadDevNumPhases OID) and the number of banks of outlets (ePDULoadDevNumBanks) Number of entries = #phases + #banks. NOTE: If a device has phase and bank information, all phase information shall precede the bank information.
SEQUENCE OF LoadStatusEntry
.1.3.6.1.4.1.3808.1.1.3.2.3.1
ePDULoadStatusEntryThe Rack PDU phase/bank to gather status from.
LoadStatusEntry
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1
ePDULoadStatusIndexThe index to the Rack PDU phase/bank entry. All phase information will precede any bank informationro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.1
ePDULoadStatusLoadGetting this OID will return the phase/bank load measured in tenths of Amps.ro
Gauge
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.2
ePDULoadStatusLoadStateGetting this OID will return the phase/bank load state. loadNormal(1) indicates that the phase/bank is operating properly within the ePDULoadConfigLowLoadThreshold and ePDULoadConfigNearOverloadThreshold OID values. loadLow(2) indicates that the phase/bank load has dropped below the ePDULoadConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. loadNearOverload(3) indicates that the phase/bank load is greater than or equal to the ePDULoadConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. loadOverload(4) indicates that the phase/bank load is greater than or equal to the ePDULoadConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.3
ePDULoadStatusPhaseNumberThe phase number to which this record refers.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.4
ePDULoadStatusBankNumberThe bank number to which this record refers. A value of 0 will be returned if any bank is not present or if it is phase related.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.5
ePDULoadStatusVoltageGetting this OID will return the phase/bank voltage measured in 0.1 volts.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.6
ePDULoadStatusActivePowerGetting this OID will return the phase/bank active power measured in watts.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.7
ePDULoadStatusApparentPowerGetting this OID will return the phase/bank apparent power measured in VA.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.8
ePDULoadStatusPowerFactorGetting this OID will return power factor of the output measured in hundredths. A value of 100 representing a unity power factor (1.00).ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.9
ePDULoadStatusEnergyGetting this OID will return the phase/bank apparent power measured in 0.1 kilowatt-hours.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.10
ePDULoadStatusEnergyStartTimeGetting this OID will return the date and time of the last energy meter resetro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.2.3.1.1.11
ePDULoadBankConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.2.4
ePDULoadBankConfigTableAllows for configuration of each Rack PDU bank. The number of entries is contained in the ePDULoadDevNumBanks OID.
SEQUENCE OF LoadBankConfigEntry
.1.3.6.1.4.1.3808.1.1.3.2.4.1
ePDULoadBankConfigEntryThe Rack PDU bank to configure.
LoadBankConfigEntry
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1
ePDULoadBankConfigIndexThe index to the Rack PDU bank entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1.1
ePDULoadBankConfigLowLoadThresholdA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning. Maximum value must be less than the value returned by the ePDULoadBankConfigNearOverloadThreshold OID.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1.2
ePDULoadBankConfigNearOverloadThresholdA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the ePDULoadBankConfigLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDULoadBankConfigOverloadThreshold OID.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1.3
ePDULoadBankConfigOverloadThresholdA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the ePDULoadBankConfigNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDULoadDevMaxBankLoad OID.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1.4
ePDULoadBankConfigAlarmGetting this OID will return the current Bank Alarm.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.2.4.1.1.5
ePDUOutlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.3
ePDUOutletDevice
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.3.1
ePDUOutletDevCommandSetting this OID to immediateAllOn (2) will turn all outlets on immediately. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will reboot all outlets immediately. Setting this OID to delayedAllOn (5) will turn all outlets on as defined by each outlet's ePDUOutletConfigPowerOnTime OID value. Setting this OID to delayedAllOff (6) will turn all outlets off as defined by each outlet's ePDUOutletConfigPowerOffTime OID value. Setting this OID to delayedAllReboot (7) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest ePDUOutletConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be canceled. Getting this OID will return the noCommandAll (1) value.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.1.1
ePDUOutletDevColdstartDelayThe amount of delay, in seconds, between when power is provided to the Switched Rack PDU and when the Switched Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes).rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.1.2
ePDUOutletDevNumCntrlOutletsThe number of controlled outlets on this Switched Rack PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.1.3
ePDUOutletDevNumTotalOutletsThe total number of outlets on this Rack PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.1.4
ePDUOutletDevMonitoredOutletsThe total number of monitored outlets on this Rack PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.1.5
ePDUOutletDevColdstartStateThe ePDU outlet state after coldstart. Allowed values are: 1 - all outlets on after coldstart. 2 - outlet status same as previous state.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.1.6
ePDUOutletPhase
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.3.2
ePDUOutletPhaseTableAllows for management of outlets on a per phase basis.
SEQUENCE OF OutletPhaseEntry
.1.3.6.1.4.1.3808.1.1.3.3.2.1
ePDUOutletPhaseEntryThe phase to manage.
OutletPhaseEntry
.1.3.6.1.4.1.3808.1.1.3.3.2.1.1
ePDUOutletPhaseIndexThe index to the Switched Rack PDU phase entry.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.2.1.1.1
ePDUOutletPhaseOverloadRestrictionThis OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigOverloadThreshold OID is exceeded.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.2.1.1.2
ePDUOutletControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.3.3
ePDUOutletControlTableAllows for control of the individual outlets. The number of entries is contained in the ePDUOutletDevNumCntrlOutlets OID.
SEQUENCE OF EPDUOutletControlEntry
.1.3.6.1.4.1.3808.1.1.3.3.3.1
ePDUOutletControlEntryThe outlet to control.
EPDUOutletControlEntry
.1.3.6.1.4.1.3808.1.1.3.3.3.1.1
ePDUOutletControlIndexThe index to the outlet entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.3.1.1.1
ePDUOutletControlOutletNameThe name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. This OID is provided for informational purposes only.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.3.3.1.1.2
ePDUOutletControlOutletPhaseThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.3.1.1.3
ePDUOutletControlOutletCommandGetting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will immediately reboot the outlet. Setting this variable to delayedOn (4) will turn the outlet on after the ePDUOutletConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (5) will turn the outlet off after the ePDUOutletConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched Rack PDU to perform a delayedOff command, wait the ePDUOutletConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (7) will cause any pending command to this outlet to be canceled. Setting this variable to outletIdentify (8) will cause PDU LED to display the number of the outlet.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.3.1.1.4
ePDUOutletControlOutletBankThe bank associated with this outlet.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.3.1.1.5
ePDUOutletConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.3.4
ePDUOutletConfigTableAllows for configuration of individual outlets. The number of entries is contained in the ePDUOutletDevNumCntrlOutlets OID.
SEQUENCE OF EPDUOutletConfigEntry
.1.3.6.1.4.1.3808.1.1.3.3.4.1
ePDUOutletConfigEntryThe outlet to configure.
EPDUOutletConfigEntry
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1
ePDUOutletConfigIndexThe index to the outlet entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.1
ePDUOutletConfigOutletNameThe name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.2
ePDUOutletConfigOutletPhaseThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.3
ePDUOutletConfigPowerOnTimeThe amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 - never power on. 0 - power on immediately. 1 to 7200 - power on up to 7200 seconds after being commanded.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.4
ePDUOutletConfigPowerOffTimeThe amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never power off. 0 - power off immediately. 1 to 7200 - power off up to 7200 seconds after being commanded.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.5
ePDUOutletConfigRebootDurationDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed range is any value between 5 and 60 seconds (1 minute).rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.6
ePDUOutletConfigOutletBankThe bank associated with this outlet.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.7
ePDUOutletConfigMonitoredTableSizeThe size of the Outlet Config Monitored Tablero
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.2
ePDUOutletConfigMonitoredTableAllows for getting/setting of outlet thresholds of an Outlet Monitored Rack PDU.
SEQUENCE OF OutletConfigMonitoredEntry
.1.3.6.1.4.1.3808.1.1.3.3.4.3
ePDUOutletConfigMonitoredEntryThis gives access to Monitored Outlet entries
OutletConfigMonitoredEntry
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1
ePDUOutletConfigMonitoredIndexThe index to the RACK PDU Phase entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.1
ePDUOutletConfigMonitoredNameThe name of the Monitored Outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.2
ePDUOutletConfigMonitoredNumberThe outlet number of an Outlet Monitored RACK PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.3
ePDUOutletConfigMonitoredLowLoadThresholdA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in watts. A warning will be issued when the load is less than the threshold value. A threshold value of 0 effectively disables this warning. Maximum value must be less than the value returned by the ePDUOutletConfigMonitoredNearOverloadThreshold OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4
ePDUOutletConfigMonitoredNearOverloadThresholdA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in watts. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the ePDUOutletConfigMonitoredLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDUOutletConfigMonitoredOverloadThreshold OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.5
ePDUOutletConfigMonitoredOverloadThresholdA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in watts. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the ePDUOutletConfigMonitoredNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the ePDULoadDevMaxOutletLoad OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.6
ePDUOutletConfigMonitoredPeakLoadResetSetting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this oid will do nothing and return noAction (1) if the PDU support this feature, return notSupport (3) if the PDU do not support this feature.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.7
ePDUOutletConfigMonitoredEnergyResetSetting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this oid will do nothing and return noAction (1) if the PDU support this feature, return notSupport (3) if the PDU do not support this feature.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.8
ePDUOutletStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.3.5
ePDUOutletStatusTableAllows for getting of status of individual outlets. The number of entries is contained in the ePDUOutletDevNumCntrlOutlets OID.
SEQUENCE OF EPDUOutletStatusEntry
.1.3.6.1.4.1.3808.1.1.3.3.5.1
ePDUOutletStatusEntryThe outlet to gather status from.
EPDUOutletStatusEntry
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1
ePDUOutletStatusIndexThe index to the outlet entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.1
ePDUOutletStatusOutletNameThe name of the outlet. The maximum string size is device dependent. This OID is provided for informational purposes only.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.2
ePDUOutletStatusOutletPhaseThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.3
ePDUOutletStatusOutletStateGetting this variable will return the outlet state. If the outlet is on, the outletStatusOn (1) value will be returned. If the outlet is off, the outletStatusOff (2) value will be returned.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.4
ePDUOutletStatusCommandPendingGetting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusNoCommandPending (2) will be returned.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.5
ePDUOutletStatusOutletBankThe bank associated with this outlet.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.6
ePDUOutletStatusLoadGetting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in tenths of Amps.ro
Gauge
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.7
ePDUOutletStatusActivePowerGetting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in wattsro
Gauge
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.8
ePDUOutletStatusAlarmGetting this OID will return the current outlet alarmro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.9
ePDUOutletStatusPeakPowerThe peak power consumption of the Rack PDU load in watts. This value can be reset by setting the oid ePDUOutletConfigMonitoredPeakLoadReset to reset (2)ro
Gauge
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.10
ePDUOutletStatusPeakPowerTimeGet this oid shows the date and time that peak power consumption occurredro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.11
ePDUOutletStatusPeakPowerStartGet this oid shows the date and time that peak power consumption startedro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.12
ePDUOutletStatusEnergyEnergy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. This value can be reset by setting the oid ePDUOutletConfigMonitoredEnergyReset to reset (2)ro
Gauge
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.13
ePDUOutletStatusEnergyStartTimeIndicates the date and time of the last device energy meter resetro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.14
ePDUOutletBank
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.3.6
ePDUOutletBankTableAllows for management of outlets on a per bank basis.
SEQUENCE OF OutletBankEntry
.1.3.6.1.4.1.3808.1.1.3.3.6.1
ePDUOutletBankEntryThe bank to manage.
OutletBankEntry
.1.3.6.1.4.1.3808.1.1.3.3.6.1.1
ePDUOutletBankIndexThe index to the Switched Rack PDU bank entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.3.6.1.1.1
ePDUOutletBankOverloadRestrictionThis OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding bank to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding bank to turn on if the ePDULoadBankConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding bank to turn on if the ePDULoadBankConfigOverloadThreshold OID is exceeded.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.3.3.6.1.1.2
ePDUPowerSupply
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.4
ePDUPowerSupplyDevice
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.4.1
ePDUPowerSupply1StatusGetting this OID will return powerSupply1Ok(1) if power supply 1 is functioning normally. If not functioning normally, this OID will return powerSupply1Failed(2).ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.4.1.1
ePDUPowerSupply2StatusGetting this OID will return powerSupply2Ok(1) if power supply 2 is functioning normally. If not functioning normally, this OID will return powerSupply2Failed(2). Metered Rack PDUs do not have a redundant powersupply.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.4.1.2
ePDUPowerSupplyAlarmGetting this OID will return powerSupply Alarmro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.4.1.3
ePDUStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.3.5
ePDUStatusBankTableSizeThe size of the Status Bank Tablero
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.1
ePDUStatusBankTableAllows for getting of status of each Rack PDU Bank
SEQUENCE OF BankEntry
.1.3.6.1.4.1.3808.1.1.3.5.2
ePDUStatusBankEntryThis gives access to Bank entries
BankEntry
.1.3.6.1.4.1.3808.1.1.3.5.2.1
ePDUStatusBankIndexThe index to the RACK PDU Bank entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.2.1.1
ePDUStatusBankNumberGetting this OID will return the bank number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.2.1.2
ePDUStatusBankStateGetting this OID will return the bank load state. bankLoadNormal(1) indicates that the bank is operating properly within the ePDULoadBankConfigLowLoadThreshold and ePDULoadBankConfigNearOverloadThreshold OID values. bankLoadLow(2) indicates that the bank load has dropped below the ePDULoadBankConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. bankLoadNearOverload(3) indicates that the bank load is greater than or equal to the ePDULoadBankConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. bankLoadOverload(4) indicates that the bank load is greater than or equal to the ePDULoadBankConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.5.2.1.3
ePDUStatusPhaseTableSizeThe size of the Status Phase Tablero
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.3
ePDUStatusPhaseTableAllows for getting of status of each Rack PDU Phase
SEQUENCE OF PhaseEntry
.1.3.6.1.4.1.3808.1.1.3.5.4
ePDUStatusPhaseEntryThis gives access to Phase entries
PhaseEntry
.1.3.6.1.4.1.3808.1.1.3.5.4.1
ePDUStatusPhaseIndexThe index to the RACK PDU Phase entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.4.1.1
ePDUStatusPhaseNumberGetting this OID will return the phase number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.4.1.2
ePDUStatusPhaseStateGetting this OID will return the Phase load state. phaseLoadNormal(1) indicates that the Phase is operating properly within the ePDULoadPhaseConfigLowLoadThreshold and ePDULoadPhaseConfigNearOverloadThreshold OID values. phaseLoadLow(2) indicates that the Phase load has dropped below the ePDULoadPhaseConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadNearOverload(3) indicates that the Phase load is greater than or equal to the ePDULoadPhaseConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadOverload(4) indicates that the Phase load is greater than or equal to the ePDULoadPhaseConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.5.4.1.3
ePDUStatusOutletTableSizeThe size of the Status Outlet Tablero
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.5
ePDUStatusOutletTableAllows for getting of status of each Outlet of an Outlet Monitored Rack PDU.
SEQUENCE OF OutletEntry
.1.3.6.1.4.1.3808.1.1.3.5.6
ePDUStatusOutletEntryThis gives access to Outlet entries
OutletEntry
.1.3.6.1.4.1.3808.1.1.3.5.6.1
ePDUStatusOutletIndexThe index to the RACK PDU Outlet entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.6.1.1
ePDUStatusOutletNumberGetting this OID will return the Outlet number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.6.1.2
ePDUStatusOutletStateGetting this OID will return the Outlet load state. outletLoadNormal(1) indicates that the Outlet is operating properly within the ePDUOutletConfigMonitoredLowLoadThreshold and ePDUOutletConfigMonitoredNearOverloadThreshold OID values. outletLoadLow(2) indicates that the Outlet load has dropped below the ePDUOutletConfigMonitoredLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. outletLoadNearOverload(3) indicates that the Outlet load is greater than or equal to the ePDUOutletConfigMonitoredNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. outletLoadOverload(4) indicates that the Outlet load is greater than or equal to the ePDUOutletConfigMonitoredOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.3.5.6.1.3
ePDUStatusInputVoltageThe input voltage in 0.1 Volt.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.7
ePDUStatusInputFrequencyThe input frequency in 0.1 Hertz.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.3.5.8
environmentSensor
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.4
envirIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.4.1
envirIdentNameThe name of the environment sensor. The maximum string size is device dependent.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.4.1.1
envirIdentLocationThe location of the environment sensor. The maximum string size is device dependent.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.4.1.2
envirTemp
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.4.2
envirTemperatureThe environment temperature expressed in 1/10 Fahrenheitro
INTEGER
.1.3.6.1.4.1.3808.1.1.4.2.1
envirTempHighThresholdThe high temperature threshold of the environment sensor. The value expressed in Fahrenheit.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.4.2.2
envirTempLowThresholdThe low temperature threshold of the environment sensor. The value expressed in Fahrenheit.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.4.2.3
envirTempRateOfChangeThe rate of change of the temperature. The value expressed in Fahrenheit per 5 minute.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.4.2.4
envirTempHysteresisThe number of degrees beyond the temperature thresholds at which an active temperature alarm will be cleared. This configuration setting applies to all temperature thresholds. Units are displayed in Fahrenheit.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.4.2.5
envirHumid
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.4.3
envirHumidityThe environment relative humidity expressed in persentage.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.4.3.1
envirHumidHighThresholdThe high relative humidity threshold of the environment sensor. The value expressed in persentage.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.4.3.2
envirHumidLowThresholdThe low relative humidity threshold of the environment sensor. The value expressed in persentage.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.4.3.3
envirHumidRateOfChangeThe rate of change of the relative humidity. The value expressed in persentage per 5 minute.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.4.3.4
envirHumidHysteresisThe number of degrees beyond the relative humidity thresholds at which an active relative humidity alarm will be cleared. This configuration setting applies to all relative humidity thresholds. Units are displayed in persentage.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.4.3.5
envirContact
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.4.4
envirContactTableSizeThe number of the contact in the environment sensor.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.4.4.1
envirContactTableAllows for getting of information of each contact of the environment sensor.
SEQUENCE OF ContactEntry
.1.3.6.1.4.1.3808.1.1.4.4.2
envirContactEntryThis gives access to contact entries
ContactEntry
.1.3.6.1.4.1.3808.1.1.4.4.2.1
envirContactIndexThe index to the contact of the environment sensor.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.4.4.2.1.1
envirContactNameGetting or setting the name of the contact of the environment sensor.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.4.4.2.1.2
envirContactStatusGetting this OID will return the Contact Status.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.4.4.2.1.3
envirContactNormalStateSet the contact normal state.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.4.4.2.1.4
ats
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5
atsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.1
atsIdentNameThe name of the ATS. The maximum string size is device dependent.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.1
atsIdentModelNameA string identifying the model name of the Automatic Transfer Switch. This value is set at the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.2
atsIdentHardwareRevThe hardware revision of the Automatic Transfer Switch. This value is set at the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.3
atsIdentFirmwareRevA string identifying the Automatic Transfer Switch firmware revision.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.4
atsIdentSerialNumberA string identifying the serial number of the Automatic Transfer Switch. This value is set at the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.5
atsIdentDateOfManufactureThe date when the Automatic Transfer Switch was manufactured in mm/dd/yyyy format. This value is set at the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.6
atsIdentDeviceRatingVoltageA string identifing the Automatic Transfer Switch rating voltage.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.7
atsIdentDeviceRatingCurrentThis gives the device rating current in Ampsro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.1.8
atsIdentDeviceOutletNumThis gives the outlet number of the devicero
INTEGER
.1.3.6.1.4.1.3808.1.1.5.1.9
atsIdentAgentModelNameA string identifying the model name of the Agent.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.10
atsIdentAgentHardwareRevisionThe hardware revision of the Agent.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.11
atsIdentAgentFirmwareRevisionA string identifying the Agent firmware revision.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.12
atsIdentAgentSerialNumberA string identifying the serial number of the Agent.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.1.13
atsStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.2
atsStatusDevice
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.2.1
atsStatusCommStatusThis variable returns the current communication status between the Automatic Transfer Switch and the Agent.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.1
atsStatusSelectedSourceThis variable returns the current source of power.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.2
atsStatusRedundancyStateThis variable returns the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power source if the current source fails. atsFullyRedundant(2) indicates that the ATS will switch over to the alternate power source if the current source fails.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.3
atsStatusPhaseSyncStatusThis variable returns the status of the phase sync.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.4
atsStatusDevSourceRelayStatusThis variable returns the status of the source relay.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.5
atsStatusDevInRelayStatusThis variable returns the status of the input relay.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.6
atsStatusDevOutRelayStatusThis variable returns the status of the Output relay.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.7
atsStatusDevLCDCommStatusThis variable returns the communication status of the LCD.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.8
atsStatusDevDB9CommStatusThis variable returns the communication status of the DB9.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.9
atsStatusPowerSupplyTableA list of power supply table entries.
SEQUENCE OF AtsStatusPowerSupplyEntry
.1.3.6.1.4.1.3808.1.1.5.2.1.10
atsStatusPowerSupplyEntryAn entry containing power supply information applicable to a particular input.
AtsStatusPowerSupplyEntry
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1
atsStatusPowerSupplyTableIndexThe input identifier.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1.1
atsStatusPowerSupplyInputSourceThe input source to the power supply.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1.2
atsStatusPowerSupply12VStatusThis variable returns the status of the power supply A 12V in system.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1.3
atsStatusPowerSupply5VStatusThis variable returns the status of the power supply A 5V in system.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1.4
atsStatusPowerSupply3p3VStatusThis variable returns the status of the power supply A 3.3V in system.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.1.10.1.5
atsStatusInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.2.2
atsStatusInputNumThe number of input feeds to this device. This variable indicates the number of rows in the status input table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.2.1
atsStatusInputTableA list of input table entries. The number of entries is given by the value of atsNumInputs.
SEQUENCE OF AtsStatusInputEntry
.1.3.6.1.4.1.3808.1.1.5.2.2.2
atsStatusInputEntryAn entry containing information applicable to a particular input.
AtsStatusInputEntry
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1
atsStatusInputTableIndexThe input identifier.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.1
atsStatusInputNameA name given to a particular input.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.2
atsStatusNumInputPhaseThe number of input phases utilized in this device. The sum of all the atsStatusNumInputPhase variable indicates the number of rows in the status input phase table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.3
atsStatusInputVoltageOrientationThe input voltage orientation: 1: unknown for this Source 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase 2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.4
atsStatusInputVoltageThe input voltage in 0.1 Volt.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.5
atsStatusInputFrequencyThe input frequency in 0.1 Hertz.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.6
atsStatusInputVolStateThe input voltage status.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.7
atsStatusInputFreqStateThe input frequency status.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.2.2.2.1.8
atsStatusInputPhaseTableA list of input table entries. The number of entries is given by the sum of the atsNumInputPhases.
SEQUENCE OF AtsStatusInputPhaseEntry
.1.3.6.1.4.1.3808.1.1.5.2.2.3
atsStatusInputPhaseEntryAn entry containing information applicable to a particular input phase.
AtsStatusInputPhaseEntry
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1
atsStatusInputPhaseTableIndexThe input identifier.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1.1
atsStatusInputPhaseIndexThe input phase identifier.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1.2
atsStatusInputPhaseVoltageThe input voltage in VAC, or -1 if it's unsupported by this Source.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1.3
atsStatusInputPhaseCurrentThe input current in amperes, or -1 if it's unsupported by this Source.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1.4
atsStatusInputPhasePowerThe input power in Watts, or -1 if it's unsupported by this Source.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.2.2.3.1.5
atsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.3
atsConfigPreferredSourceThis variable returns the preferred source of power when both sources are OK.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.3.1
atsConfigNominalVoltageThis variable returns the nominal voltage of the input.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.3.2
atsConfigVoltageSensitivityThis variable defines the sensitivity to changes in voltage: high(1) for best protection, low(3) for frequent small line voltage changes.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.3.3
atsConfigTransferVoltageRangeThis variable defines the range of acceptable voltage from a power source. If the voltage measured from the selected input source is not within this range, the Automatic Transfer Switch will switch over (transfer) to the alternate power source.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.3.4
atsConfigNarrowRangeValueTo configure the Narrow Range value of acceptable voltage from a power source.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.3.5
atsConfigMediumRangeValueTo configure the Medium Range value of acceptable voltage from a power source.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.3.6
atsConfigWideRangeValueTo configure the Wide Range value of acceptable voltage from a power source.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.3.7
atsConfigFrequencyDeviationTo configure the frequency deviation.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.3.8
atsConfigDevLCDOffTimeThe amount of time (in seconds) which LCD turn off automatically after it remains idle for.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.3.9
atsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.4
atsCtrlResetATSSetting this variable will cause the Automatic Transfer Switch to reboot or reset relative setting to default value.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.4.1
atsCtrlClearEventCountsSetting this variable will clear all event counts in Automatic Transfer Switch. Returns (-1) if unsupported.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.4.2
atsLoad
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.5
atsLoadDevice
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.5.1
atsLoadDevPhaseTableSizeThe size of the Phase Table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.1.1
atsLoadDevPhaseTableAllows for getting the Phase Max Load in the ATS.
SEQUENCE OF LoadDevPhaseEntry
.1.3.6.1.4.1.3808.1.1.5.5.1.2
atsLoadDevPhaseEntryThe ATS Phases Access.
LoadDevPhaseEntry
.1.3.6.1.4.1.3808.1.1.5.5.1.2.1
atsLoadDevPhaseTableIndexThe index to ATS phase entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.1.2.1.1
atsLoadDevPhaseFor single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), phase3 (3), phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.1.2.1.2
atsLoadDevPhaseMaxLoadGetting this OID will return the maximum rated power that each phase of the ATS can provide. It is represented in Amps.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.1.2.1.3
atsLoadDevBankTableSizeThe size of the Bank Table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.1.3
atsLoadDevBankTableAllows for getting the Bank Max Load in the ATS.
SEQUENCE OF AtsLoadDevBankEntry
.1.3.6.1.4.1.3808.1.1.5.5.1.4
atsLoadDevBankEntryThe ATS Banks Access.
AtsLoadDevBankEntry
.1.3.6.1.4.1.3808.1.1.5.5.1.4.1
atsLoadDevBankTableIndexThe index to the ATS bank entry.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.1.4.1.1
atsLoadDevBankMaxLoadGetting this OID will return the maximum rated power that each bank of the ATS can provide. It is represented in Amps.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.1.4.1.2
atsLoadStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.5.2
atsLoadStatusPhaseTableSizeThe size of the Phase Table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.2.1
atsLoadStatusPhaseTableAllows for getting the Phase Load status in the ATS.
SEQUENCE OF LoadStatusPhaseEntry
.1.3.6.1.4.1.3808.1.1.5.5.2.2
atsLoadStatusPhaseEntryThe ATS Phases Access.
LoadStatusPhaseEntry
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1
atsLoadStatusPhaseTableIndexThe index to ATS phase entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1.1
atsLoadStatusPhaseFor single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), phase3 (3), phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1.2
atsLoadStatusPhaseLoadThe output current in 0.1 amperes drawn by the load on the ATSro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1.3
atsLoadStatusPhaseLoadStateGetting this OID will return the phase load state.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1.4
atsLoadStatusPhasePowerThe output power in Watts.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.2.2.1.5
atsLoadStatusBankTableSizeThe size of the Bank Table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.2.3
atsLoadStatusBankTableAllows for getting the Bank Load status in the ATS.
SEQUENCE OF LoadStatusBankEntry
.1.3.6.1.4.1.3808.1.1.5.5.2.4
atsLoadStatusBankEntryThe ATS Bank Access.
LoadStatusBankEntry
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1
atsLoadStatusBankTableIndexThe index to ATS bank entry.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.1
atsLoadStatusBankPhaseGetting this OID will return the phase number.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.2
atsLoadStatusBankLoadThe output current in 0.1 amperes drawn by the load on the ATSro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.3
atsLoadStatusBankLoadStateGetting this OID will return the bank load state.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.4
atsLoadStatusBankPowerThe output power in Watts.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.5
atsLoadStatusBankEnergyGetting this OID will return the phase/bank apparent power measured in 0.1 kilowatt-hours.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.6
atsLoadStatusBankStartTimeGetting this OID will return the date and time of the last energy meter resetro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.2.4.1.7
atsLoadConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.5.3
atsLoadCfgPhaseTableSizeThe size of the Phase Table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.3.1
atsLoadCfgPhaseTableAllows for configuration of each ATS phase.
SEQUENCE OF LoadCfgPhaseEntry
.1.3.6.1.4.1.3808.1.1.5.5.3.2
atsLoadCfgPhaseEntryThe ATS phase to configure.
LoadCfgPhaseEntry
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1
atsLoadCfgPhaseTableIndexThe index to the ATS phase entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.1
atsLoadCfgPhaseFor single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), phase3 (3), phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.2
atsLoadCfgPhaseLowLoadA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.3
atsLoadCfgPhaseNearOverLoadA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.4
atsLoadCfgPhaseOverLoadA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.5
atsLoadCfgPhaseOutletRestrictionThis OID controls the behavior of a ATS phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigOverloadThreshold OID is exceeded.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.3.2.1.6
atsLoadCfgBankTableSizeThe size of the Bank Table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.3.3
atsLoadCfgBankTableAllows for configuration of each ATS bank.
SEQUENCE OF LoadCfgBankEntry
.1.3.6.1.4.1.3808.1.1.5.5.3.4
atsLoadCfgBankEntryThe ATS phase to configure.
LoadCfgBankEntry
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1
atsLoadCfgBankTableIndexThe index to the ATS bank entry.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.1
atsLoadCfgBankLowLoadA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.2
atsLoadCfgBankNearOverLoadA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.3
atsLoadCfgBankOverLoadA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.4
atsLoadCfgBankOutletRestrictionThis OID controls the behavior of a ATS phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the ePDULoadConfigOverloadThreshold OID is exceeded.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.5
atsOutlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.6
atsOutletDevice
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.5.6.1
atsOutletDevTotalOutletNumThe total number of outlets on the ATS.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.1.1
atsOutletDevCtrlOutletNumThe number of controlled outlets on the ATS.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.1.2
atsOutletDevColdStartDelayThe amount of delay, in seconds, between when power is provided to the ATS and when the ATS provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes).rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.1.3
atsOutletDevColdStartStateThe ATS outlet state after coldstart. Allowed values are: 1 - all outlets on after coldstart. 2 - outlet status same as previous state.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.6.1.4
atsOutletDevLocalCtrlTo configure enable or disable outlet local control function.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.6.1.5
atsOutletDevCommandSetting this OID to immediateAllOn (2) will turn all outlets on immediately. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will reboot all outlets immediately. Setting this OID to delayedAllOn (5) will turn all outlets on as defined by each outlet's atsOutletCfgPowerOnTime OID value. Setting this OID to delayedAllOff (6) will turn all outlets off as defined by each outlet's atsOutletCfgPowerOffTime OID value. Setting this OID to delayedAllReboot (7) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack ATS will then delay the largest atsOutletCfgRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack ATS to be canceled. Getting this OID will return the noCommandAll (1) value.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.6.1.6
atsOutletStatusTableSizeThe size of the outlet status table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.2
atsOutletStatusTableAllows for getting of status of individual outlets.
SEQUENCE OF OutletStatusEntry
.1.3.6.1.4.1.3808.1.1.5.6.3
atsOutletStatusEntryThe outlet to gather status from.
OutletStatusEntry
.1.3.6.1.4.1.3808.1.1.5.6.3.1
atsOutletStatusTableIndexThe index to the outlet entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.3.1.1
atsOutletStatusOutletNameThe name of the outlet. The maximum string size is device dependent. This OID is provided for informational purposes only.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.6.3.1.2
atsOutletStatusOutletStateGetting this variable will return the outlet state. If the outlet is on, the outletStatusOn (1) value will be returned. If the outlet is off, the outletStatusOff (2) value will be returned.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.6.3.1.3
atsOutletStatusOutletCmdPendingGetting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusNoCommandPending (2) will be returned.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.6.3.1.4
atsOutletStatusOutletPhaseThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.5.6.3.1.5
atsOutletStatusOutletBankThe bank associated with this outlet.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.3.1.6
atsOutletCtrlTableSizeThe size of the outlet control table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.4
atsOutletCtrlTableAllows for control of the individual outlets.
SEQUENCE OF OutletCtrlEntry
.1.3.6.1.4.1.3808.1.1.5.6.5
atsOutletCtrlEntryThe outlet to control.
OutletCtrlEntry
.1.3.6.1.4.1.3808.1.1.5.6.5.1
atsOutletCtrlTableIndexThe index to the outlet entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.5.1.1
atsOutletCtrlOutletNameThe name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. This OID is provided for informational purposes only.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.6.5.1.2
atsOutletCtrlCommandGetting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. Setting this variable to immediateOn (2) will immediately turn the outlet on. Setting this variable to immediateOff (3) will immediately turn the outlet off. Setting this variable to immediateReboot (4) will immediately reboot the outlet. Setting this variable to delayedOn (5) will turn the outlet on after the ePDUOutletConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (6) will turn the outlet off after the ePDUOutletConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (7) will cause the ATS to perform a delayedOff command, wait the atsOutletCfgRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (8) will cause any pending command to this outlet to be canceled.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.5.6.5.1.3
atsOutletCfgTableSizeThe size of the outlet config table.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.6
atsOutletCfgTableAllows for configuration of individual outlets.
SEQUENCE OF AtsOutletConfigEntry
.1.3.6.1.4.1.3808.1.1.5.6.7
atsOutletCfgEntryThe outlet to configure.
AtsOutletConfigEntry
.1.3.6.1.4.1.3808.1.1.5.6.7.1
atsOutletCfgTableIndexThe index to the outlet entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.7.1.1
atsOutletCfgOutletNameThe name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.5.6.7.1.2
atsOutletCfgPowerOnTimeThe amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 - never power on. 0 - power on immediately. 1 to 7200 - power on up to 7200 seconds after being commanded.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.7.1.3
atsOutletCfgPowerOffTimeThe amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never power off. 0 - power off immediately. 1 to 7200 - power off up to 7200 seconds after being commanded.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.7.1.4
atsOutletCfgRebootDurationDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed range is any value between 5 and 60 seconds (1 minute).rw
INTEGER
.1.3.6.1.4.1.3808.1.1.5.6.7.1.5
ePDU2
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.6
ePDU2RoleGet this oid shows the role the PDU played on Daisy Chain Group. The PDU as a Host can access whole ePDU2 content, and the PDU be standalong or a Slave can access itself instead.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.1
ePDU2Ident
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.6.2
ePDU2IdentTableSizePDU as a Host response total PDU ident number on daisy chain. PDU as a Slave can only response 1.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.2.1
ePDU2IdentTableA table of Rack PDU identification information.
SEQUENCE OF EPDU2IdentEntryStruct
.1.3.6.1.4.1.3808.1.1.6.2.2
ePDU2IdentEntryIdentification data from Rack PDU being queried.
EPDU2IdentEntryStruct
.1.3.6.1.4.1.3808.1.1.6.2.2.1
ePDU2IdentIndexThe index to the Rack PDU identification table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.2.2.1.1
ePDU2IdentModuleIndexThe Rack PDU identification table entry numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.2.2.1.2
ePDU2IdentNameA user-defined string identifying the name of the Rack PDU.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.2.2.1.3
ePDU2IdentLocationA user-defined string identifying the location of the Rack PDU.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.2.2.1.4
ePDU2IdentContactA user-defined string identifying the person to contact of the Rack PDU.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.2.2.1.5
ePDU2IdentHardwareRevThe Rack PDU hardware version.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.2.2.1.6
ePDU2IdentFirmwareRevThe Rack PDU firmware version.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.2.2.1.7
ePDU2IdentDateOfManufactureThe date the Rack PDU was manufactured in mm/dd/yyyy format.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.2.2.1.8
ePDU2IdentModelNameThe Rack PDU model number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.2.2.1.9
ePDU2IdentSerialNumberThe Rack PDU serial number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.2.2.1.10
ePDU2IdentIndicatorPDU will perform a panel indicator test when the variable is set to testIndicators(2). It is no effective to set this value to noTestIndicators(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.2.2.1.11
ePDU2Device
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.6.3
ePDU2DeviceTableSizeA Host Rack PDU response total number of Rack PDUs on daisy chain. Rack PDU as a Slave can only response 1.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.1
ePDU2DeviceConfigTableA table of Rack PDU configuration data.
SEQUENCE OF EPDU2DeviceConfigEntryStruct
.1.3.6.1.4.1.3808.1.1.6.3.2
ePDU2DeviceConfigEntryConfiguration data from Rack PDU being queried.
EPDU2DeviceConfigEntryStruct
.1.3.6.1.4.1.3808.1.1.6.3.2.1
ePDU2DeviceConfigIndexThe index to the Rack PDU table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.2.1.1
ePDU2DeviceConfigModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.2.1.2
ePDU2DeviceConfigNameA user-defined string identifying the name of Rack PDU.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.3.2.1.3
ePDU2DeviceConfigLocationA user-defined string identifying the location of the Rack PDU.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.3.2.1.4
ePDU2DeviceConfigContactA user-defined string identifying the person to contact of the Rack PDU.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.3.2.1.5
ePDU2DeviceConfigDisplayOrientationGetting this OID will return the intended physical orientation of the Seven-Segment Display. displayNormal(1) indicates Normal. displayReverse(2)indicates Upside-Down. displayRotate90(3) indicates rotate 90 degree. displayRotate270(4) indicates rotate 270 degree. displayAuto(5) indicates auto-detect and rotate.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.2.1.6
ePDU2DeviceConfigColdstartDelayThe amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes).rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.2.1.7
ePDU2DeviceConfigLowLoadThresholdUser-defined low current draw alarm threshold, measured in Amps.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.2.1.8
ePDU2DeviceConfigNearOverloadThresholdUser-defined near overload current threshold, measured in Amps.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.2.1.9
ePDU2DeviceConfigOverloadThresholdUser-defined current overload threshold, measured in Amps.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.2.1.10
ePDU2DeviceConfigPeakLoadResetSetting this OID to resetAll (2) will cause the existing peak current value of Rack PDU and its outlets to be replaced by the current load current value. Setting this OID to resetDevice (3) to reset the Rack PDU only. Setting this OID to resetOutlets (4) to reset the PDU outlets only. Getting this OID will do nothing and return the noOperation(1) value.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.2.1.11
ePDU2DeviceConfigEnergyResetSetting this OID to resetAll (2) will cause the device energy meter value to be reset to zero. Setting this OID to resetDevice (3) to reset the Rack PDU only. Setting this OID to resetOutlets (4) to reset the PDU outlets only. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.2.1.12
ePDU2DeviceInfoTableA table of Rack PDU information.
SEQUENCE OF EPDU2DeviceInfoEntryStruct
.1.3.6.1.4.1.3808.1.1.6.3.3
ePDU2DeviceInfoEntryInformation of the Rack PDU being queried.
EPDU2DeviceInfoEntryStruct
.1.3.6.1.4.1.3808.1.1.6.3.3.1
ePDU2DeviceInfoIndexThe index to the Rack PDU Information table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.3.1.1
ePDU2DeviceInfoModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.3.1.2
ePDU2DeviceInfoNameA user-defined string identifying the name of the Rack PDU.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.3.3.1.3
ePDU2DeviceInfoRatingThe electrical rating of the Rack PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.3.1.4
ePDU2DeviceInfoNumOutletsThe number of outlets on the Rack PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.3.1.5
ePDU2DeviceInfoSwitchedOutletsThe number of switched outlets on the Rack PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.3.1.6
ePDU2DeviceInfoMeteredOutletsThe number of metered outlets on the Rack PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.3.1.7
ePDU2DeviceInfoNumPhasesThe number of phases present in the Rack PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.3.1.8
ePDU2DeviceInfoNumBreakersThe number of metered banks present in the Rack PDU.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.3.1.9
ePDU2DeviceInfoBreakerRatingThe maximum current rating, measured in Amps, for the Rack PDU. Getting this OID will return rating of the circuit breakers on the device if it has any.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.3.1.10
ePDU2DeviceInfoOrientationRack PDU orientation.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.3.1.11
ePDU2DeviceInfoOutletLayoutGetting this OID will return outlet layout for the device. SeqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... SeqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... SeqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... SeqPhToPhGrouped(4) indicates outlet layout as follows: Otlts1-8::(3-1),Otlts9-16::(2-3),Otlts17-24::(1-2).ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.3.1.12
ePDU2DeviceStatusTableA table of Rack PDU current status.
SEQUENCE OF EPDU2DeviceStatusEntryStruct
.1.3.6.1.4.1.3808.1.1.6.3.4
ePDU2DeviceStatusEntryStatus data from the Rack PDU being queried.
EPDU2DeviceStatusEntryStruct
.1.3.6.1.4.1.3808.1.1.6.3.4.1
ePDU2DeviceStatusIndexThe index to the Rack PDU status table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.4.1.1
ePDU2DeviceStatusModuleIndexThe Rack PDU numeric IDro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.4.1.2
ePDU2DeviceStatusNameA user-defined string identifying the name of the Rack PDU.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.3.4.1.3
ePDU2DeviceStatusLoadStateIndicates the present load status of the Rack PDU.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.4.1.4
ePDU2DeviceStatusLoadThe power consumption of the Rack PDU load in tenths of amps.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.3.4.1.5
ePDU2DeviceStatusPeakLoadThe peak power consumption of the Rack PDU load in tenths of amps.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.3.4.1.6
ePDU2DeviceStatusPeakLoadTimestampIndicates the date and time that peak load current occurred.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.3.4.1.7
ePDU2DeviceStatusPeakLoadStartTimeIndicates the date and time of the last device peak load reset.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.3.4.1.8
ePDU2DeviceStatusEnergyA user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.3.4.1.9
ePDU2DeviceStatusEnergyStartTimeIndicates the date and time of the last device energy meter reset.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.3.4.1.10
ePDU2DeviceStatusCommandPendingIndicates whether or not the device is processing a pending command.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.4.1.11
ePDU2DeviceStatusPowerSupplyAlarmIndicates a power supply alarm is active when value equals alarm (2).ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.4.1.12
ePDU2DeviceStatusPowerSupply1StatusIndicates whether or not an alarm is active in Power Supply 1.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.4.1.13
ePDU2DeviceStatusPowerSupply2StatusIndicates whether or not an alarm is active in Power Supply 2.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.4.1.14
ePDU2DeviceStatusApparentPowerThe apparent power consumption of the Rack PDU load in VoltAmps (VA).ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.3.4.1.15
ePDU2DeviceStatusPowerFactorThe power factor of the Rack PDU load in hundredths.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.3.4.1.16
ePDU2DeviceStatusRoleTypeGet this oid shows the role the PDU played on Daisy Chain Group. The PDU as a Host can access whole ePDU2 content, and the PDU be standalong or a Slave can access itself instead.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.4.1.17
ePDU2DeviceControlTableA table of Rack PDU control data.
SEQUENCE OF EPDU2DeviceControlEntryStruct
.1.3.6.1.4.1.3808.1.1.6.3.5
ePDU2DeviceControlEntryControl data from Rack PDU being queried.
EPDU2DeviceControlEntryStruct
.1.3.6.1.4.1.3808.1.1.6.3.5.1
ePDU2DeviceControlIndexThe index to the Rack PDU control table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.5.1.1
ePDU2DeviceControlModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.3.5.1.2
ePDU2DeviceControlNameA user-defined string identifying the name of the Rack PDU.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.3.5.1.3
ePDU2DeviceControlCommandSetting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to immediateAllOff (2) will turn all outlets off immediately. Setting this OID to immediateAllReboot (3) will cause an immediateAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the ePDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateAllOn command. Setting this OID to delayedAllOn (4) will turn all outlets on as defined by each outlet's ePDU2OutletSwitchedConfigPowerOnTime OID value. Setting this OID to delayedAllOff (5) will turn all outlets off as defined by each outlet's ePDU2OutletSwitchedConfigPowerOffTime OID value. Setting this OID to delayedAllReboot (6) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest ePDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to cancelAllPendingCommand (7) will cause all pending commands on the Switched Rack PDU to be cancelled. Setting this OID to noCommand (8) will have no effect. Getting this OID will return the noCommand (8) value.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.3.5.1.4
ePDU2Phase
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.6.4
ePDU2PhaseTableSizeA Host Rack PDU response total phase number of Rack PDUs on daisy chain. Rack PDU as a Slave can only response itself number of phase.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.1
ePDU2PhaseConfigTableA table of Rack PDU phase configuration data.
SEQUENCE OF EPDU2PhaseConfigEntryStruct
.1.3.6.1.4.1.3808.1.1.6.4.2
ePDU2PhaseConfigEntryConfiguration data from currently queried Rack PDU phase.
EPDU2PhaseConfigEntryStruct
.1.3.6.1.4.1.3808.1.1.6.4.2.1
ePDU2PhaseConfigIndexThe index to the Rack PDU phase configuration table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.2.1.1
ePDU2PhaseConfigModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.2.1.2
ePDU2PhaseConfigNumberThe numeric phase ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.2.1.3
ePDU2PhaseConfigOverloadRestrictionThis OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the ePDU2PhaseConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the ePDU2PhaseConfigOverloadThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (-1). Attempts to set this OID in these models will fail.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.4.2.1.4
ePDU2PhaseConfigLowLoadThresholdUser-defined low load phase current threshold in Amps.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.2.1.5
ePDU2PhaseConfigNearOverloadThresholdUser-defined near phase overload current warning threshold in Amps.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.2.1.6
ePDU2PhaseConfigOverloadThresholdUser-defined phase overload current threshold in Ampsrw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.2.1.7
ePDU2PhaseConfigPhasePeakLoadResetSetting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.4.2.1.8
ePDU2PhaseInfoTableA table of Rack PDU phase information.
SEQUENCE OF EPDU2PhaseInfoEntryStruct
.1.3.6.1.4.1.3808.1.1.6.4.3
ePDU2PhaseInfoEntryInformation data from currently queried Rack PDU phase.
EPDU2PhaseInfoEntryStruct
.1.3.6.1.4.1.3808.1.1.6.4.3.1
ePDU2PhaseInfoIndexThe index to the Rack PDU phase properties table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.3.1.1
ePDU2PhaseInfoModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.3.1.2
ePDU2PhaseInfoNumberThe numeric phase ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.3.1.3
ePDU2PhaseStatusTableA table of Rack PDU phase status data
SEQUENCE OF EPDU2PhaseStatusEntryStruct
.1.3.6.1.4.1.3808.1.1.6.4.4
ePDU2PhaseStatusEntryStatus data from currently queried Rack PDU phase
EPDU2PhaseStatusEntryStruct
.1.3.6.1.4.1.3808.1.1.6.4.4.1
ePDU2PhaseStatusIndexThe index to the Rack PDU phase status table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.4.1.1
ePDU2PhaseStatusModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.4.1.2
ePDU2PhaseStatusNumberThe numeric phase ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.4.4.1.3
ePDU2PhaseStatusLoadStateIndicates the present load status of the Rack PDU phase being queried.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.4.4.1.4
ePDU2PhaseStatusLoadIndicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.4.4.1.5
ePDU2PhaseStatusVoltageIndicates the Voltage, in Volts, of the Rack PDU phase being queriedro
Gauge
.1.3.6.1.4.1.3808.1.1.6.4.4.1.6
ePDU2PhaseStatusPowerIndicates the load power, in watts (kW), consumed on the Rack PDU phase being queriedro
Gauge
.1.3.6.1.4.1.3808.1.1.6.4.4.1.7
ePDU2PhaseStatusApparentPowerIndicates the load apparent power, in hundredths of kiloVoltAmps (kVA), consumed on the Rack PDU phase being queriedro
Gauge
.1.3.6.1.4.1.3808.1.1.6.4.4.1.8
ePDU2PhaseStatusPowerFactorIndicates the load power factor, in hundredths, of the Rack PDU phase being queriedro
Gauge
.1.3.6.1.4.1.3808.1.1.6.4.4.1.9
ePDU2PhaseStatusPeakLoadThe peak current of the Rack PDU phase load in tenths of Ampsro
Gauge
.1.3.6.1.4.1.3808.1.1.6.4.4.1.10
ePDU2PhaseStatusPeakLoadTimestampIndicates the date and time the phase peak current occurred.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.4.4.1.11
ePDU2PhaseStatusPeakLoadStartTimeIndicates the date and time of the last phase peak current reset.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.4.4.1.12
ePDU2Bank
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.6.5
ePDU2BankTableSizeA Host Rack PDU response total bank number of Rack PDUs on daisy chain. Rack PDU as a Slave can only response itself number of bank.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.1
ePDU2BankConfigTableA table of Rack PDU bank configuration data.
SEQUENCE OF EPDU2BankConfigEntryStruct
.1.3.6.1.4.1.3808.1.1.6.5.2
ePDU2BankConfigEntryConfiguration data from currently queried Rack PDU bank.
EPDU2BankConfigEntryStruct
.1.3.6.1.4.1.3808.1.1.6.5.2.1
ePDU2BankConfigIndexThe index to the Rack PDU bank configuration table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.2.1.1
ePDU2BankConfigModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.2.1.2
ePDU2BankConfigNumberThe numeric bank ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.2.1.3
ePDU2BankConfigOverloadRestrictionThis OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding bank to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding bank to turn on if the ePDU2BankConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding bank to turn on if the ePDU2BankConfigOverloadThreshold OID is exceeded.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.5.2.1.4
ePDU2BankConfigLowLoadThresholdUser-defined low load bank current threshold in Amps.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.2.1.5
ePDU2BankConfigNearOverloadThresholdUser-defined near bank overload current warning threshold in Amps.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.2.1.6
ePDU2BankConfigOverloadThresholdUser-defined bank overload current threshold in Ampsrw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.2.1.7
ePDU2BankConfigPeakLoadResetSetting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.5.2.1.8
ePDU2BankInfoTableA table of Rack PDU bank information.
SEQUENCE OF EPDU2BankInfoEntryStruct
.1.3.6.1.4.1.3808.1.1.6.5.3
ePDU2BankInfoEntryInformation data from currently queried Rack PDU bank.
EPDU2BankInfoEntryStruct
.1.3.6.1.4.1.3808.1.1.6.5.3.1
ePDU2BankInfoIndexThe index to the Rack PDU bank properties table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.3.1.1
ePDU2BankInfoModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.3.1.2
ePDU2BankInfoNumberThe numeric bank ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.3.1.3
ePDU2BankStatusTableA table of Rack PDU bank status data
SEQUENCE OF EPDU2BankStatusEntryStruct
.1.3.6.1.4.1.3808.1.1.6.5.4
ePDU2BankStatusEntryStatus data from currently queried Rack PDU bank
EPDU2BankStatusEntryStruct
.1.3.6.1.4.1.3808.1.1.6.5.4.1
ePDU2BankStatusIndexThe index to the Rack PDU bank status table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.4.1.1
ePDU2BankStatusModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.4.1.2
ePDU2BankStatusNumberThe numeric bank ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.5.4.1.3
ePDU2BankStatusLoadStateIndicates the present load status of the Rack PDU bank being queried.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.5.4.1.4
ePDU2BankStatusLoadIndicates the current draw, in tenths of Amps, of the load on the Rack PDU bank being queried.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.5.4.1.5
ePDU2BankStatusPeakLoadThe peak current of the Rack PDU bank load in tenths of Amps.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.5.4.1.6
ePDU2BankStatusPeakLoadTimestampIndicates the date and time the bank peak current occurred.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.5.4.1.7
ePDU2BankStatusPeakLoadStartTimeIndicates the date and time of the last bank peak current reset.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.5.4.1.8
ePDU2Outlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.6.6
ePDU2OutletSwitched
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.6.6.1
ePDU2OutletSwitchedTableSizeThe number of switched outlets on connected Rack PDUs.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.1
ePDU2OutletSwitchedConfigTableA table of Rack PDU switched outlet configuration data.
SEQUENCE OF EPDU2OutletSwitchedConfigEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.1.2
ePDU2OutletSwitchedConfigEntryConfiguration data from currently queried Rack PDU switched outlet.
EPDU2OutletSwitchedConfigEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1
ePDU2OutletSwitchedConfigIndexThe index to the Rack PDU switched outlet configuration table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.1
ePDU2OutletSwitchedConfigModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.2
ePDU2OutletSwitchedConfigNumberThe numeric switched outlet ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.3
ePDU2OutletSwitchedConfigNameThe user-defined switched outlet name string.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.4
ePDU2OutletSwitchedConfigPowerOnTimeThe amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 - never power on. 0 - power on immediately. 1 to 7200 - power on up to 7200 seconds after being commanded.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.5
ePDU2OutletSwitchedConfigPowerOffTimeThe amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never power off. 0 - power off immediately. 1 to 7200 - power off up to 7200 seconds after being commanded.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.6
ePDU2OutletSwitchedConfigRebootDurationDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed range is any value between 5 and 60 seconds (1 minute).rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.2.1.7
ePDU2OutletSwitchedInfoTableA table of Rack PDU switched outlet information.
SEQUENCE OF EPDU2OutletSwitchedInfoEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.1.3
ePDU2OutletSwitchedInfoEntryInformation of the currently queried Rack PDU switched outlet.
EPDU2OutletSwitchedInfoEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1
ePDU2OutletSwitchedInfoIndexThe index to the Rack PDU switched outlet information table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.1
ePDU2OutletSwitchedInfoModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.2
ePDU2OutletSwitchedInfoNumberThe numeric switched outlet ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.3
ePDU2OutletSwitchedInfoNameThe numeric switched outlet name.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.4
ePDU2OutletSwitchedInfoPhaseLayoutThis OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that the outlet is wired from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that the outlet is wired from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that the outlet is wired from Phase 1 to Phase 2. seqPhase2ToPhase3(5) indicates that the outlet is wired from Phase 2 to Phase 3. seqPhase3ToPhase1(6) indicates that the outlet is wired from Phase 3 to Phase 1.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.5
ePDU2OutletSwitchedInfoBankThe numeric bank ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.3.1.6
ePDU2OutletSwitchedStatusTableA table of Rack PDU switched outlet status information.
SEQUENCE OF EPDU2OutletSwitchedStatusEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.1.4
ePDU2OutletSwitchedStatusEntryStatus information for currently queried Rack PDU switched outlet.
EPDU2OutletSwitchedStatusEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1
ePDU2OutletSwitchedStatusIndexThe index to the Rack PDU switched outlet status information table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.1
ePDU2OutletSwitchedStatusModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.2
ePDU2OutletSwitchedStatusNumberThe numeric switched outlet ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.3
ePDU2OutletSwitchedStatusNameThe user-defined switched outlet name string.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.4
ePDU2OutletSwitchedStatusStateIndicates the present switch state of the Rack PDU switched outlet being queried.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.5
ePDU2OutletSwitchedStatusCommandPendingGetting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusNoCommandPending (2) will be returned.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.6.1.4.1.6
ePDU2OutletSwitchedControlTableA table of Rack PDU switched outlet control data.
SEQUENCE OF EPDU2OutletSwitchedControlEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.1.5
ePDU2OutletSwitchedControlEntryControl data for currently queried Rack PDU switched outlet.
EPDU2OutletSwitchedControlEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.1.5.1
ePDU2OutletSwitchedControlIndexThe index to the Rack PDU switched outlet control data table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.5.1.1
ePDU2OutletSwitchedControlModuleIndexThe user-defined Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.5.1.2
ePDU2OutletSwitchedControlNumberThe numeric switched outlet ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.1.5.1.3
ePDU2OutletSwitchedControlNameThe user-defined switched outlet name string.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.6.1.5.1.4
ePDU2OutletSwitchedControlCommandGetting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will immediately reboot the outlet. Setting this variable to delayedOn (4) will turn the outlet on after the ePDUOutletConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (5) will turn the outlet off after the ePDUOutletConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched Rack PDU to perform a delayedOff command, wait the ePDUOutletConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (7) will cause any pending command to this outlet to be canceled. Setting this variable to outletIdentify (8) will cause PDU LED to display the number of the outlet.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.6.1.5.1.5
ePDU2OutletMetered
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.6.6.2
ePDU2OutletMeteredTableSizeThe number of metered outlets on connected Rack PDUs.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.1
ePDU2OutletMeteredConfigTableA table of Rack PDU metered outlet configuration data.
SEQUENCE OF EPDU2OutletMeteredConfigEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.2.2
ePDU2OutletMeteredConfigEntryConfiguration data from currently queried Rack PDU metered outlet.
EPDU2OutletMeteredConfigEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1
ePDU2OutletMeteredConfigIndexThe index to the Rack PDU metered outlet configuration table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.1
ePDU2OutletMeteredConfigModuleIndexThe user-defined Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.2
ePDU2OutletMeteredConfigNumberThe numeric metered outlet ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.3
ePDU2OutletMeteredConfigNameThe user-defined metered outlet name string.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.4
ePDU2OutletMeteredConfigLowLoadThresholdUser-defined outlet low load current threshold in Watts.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.5
ePDU2OutletMeteredConfigNearOverloadThresholdUser-defined outlet near overload warning threshold in Watts.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.6
ePDU2OutletMeteredConfigOverloadThresholdUser-defined outlet overload current threshold in Watts.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.2.1.7
ePDU2OutletMeteredInfoTableA table of Rack PDU metered outlet information.
SEQUENCE OF EPDU2OutletMeteredInfoEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.2.3
ePDU2OutletMeteredInfoEntryInformation of currently queried Rack PDU metered outlet.
EPDU2OutletMeteredInfoEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1
ePDU2OutletMeteredInfoIndexThe index to the Rack PDU metered information table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.1
ePDU2OutletMeteredInfoModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.2
ePDU2OutletMeteredInfoNumberThe numeric metered outlet ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.3
ePDU2OutletMeteredInfoNameThe user-defined metered outlet name string.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.4
ePDU2OutletMeteredInfoLayoutThis OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that the outlet is wired from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that the outlet is wired from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that the outlet is wired from Phase 1 to Phase 2. seqPhase2ToPhase3(5) indicates that the outlet is wired from Phase 2 to Phase 3. seqPhase3ToPhase1(6) indicates that the outlet is wired from Phase 3 to Phase 1.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.5
ePDU2OutletMeteredInfoRatingMaximum power rating of Rack PDU metered outlet.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.6
ePDU2OutletMeteredInfoBankThis outlet's numeric bank ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.3.1.7
ePDU2OutletMeteredStatusTableA table of Rack PDU metered outlet status data.
SEQUENCE OF EPDU2OutletMeteredStatusEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.2.4
ePDU2OutletMeteredStatusEntryStatus data from currently queried Rack PDU metered outlet.
EPDU2OutletMeteredStatusEntryStruct
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1
ePDU2OutletMeteredStatusIndexThe index to the Rack PDU metered status table entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.1
ePDU2OutletMeteredStatusModuleIndexThe Rack PDU numeric ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.2
ePDU2OutletMeteredStatusNumberThe numeric metered outlet ID.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.3
ePDU2OutletMeteredStatusNameThe user-defined metered outlet name string.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.4
ePDU2OutletMeteredStatusAlarmGetting this OID will return the current outlet alarm.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.5
ePDU2OutletMeteredStatusLoadGetting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in tenths of Amps.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.6
ePDU2OutletMeteredStatusActivePowerGetting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in watts.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.7
ePDU2OutletMeteredStatusPeakPowerThe peak power consumption of the Rack PDU load in watts.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.8
ePDU2OutletMeteredStatusPeakPowerTimestampGet this oid shows the date and time that peak power consumption occurred.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.9
ePDU2OutletMeteredStatusPeakPowerStartTimeGet this oid shows the date and time that peak power consumption started.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.10
ePDU2OutletMeteredStatusEnergyEnergy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.11
ePDU2OutletMeteredStatusEnergyStartIndicates the date and time of the last device energy meter reset.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.6.6.2.4.1.12
ePDU2Sensor
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.6.7
ePDU2SensorTableSizeePDU2SensorTableSizero
INTEGER
.1.3.6.1.4.1.3808.1.1.6.7.1
ePDU2Group
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.6.8
ePDU2GroupNumberOfDevicesGetting this OID will return the number of Rack PDU devices contributing to the Daisy Chain group power and energy values. Queries to slave units in an Daisy Chain group will return 0.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.6.8.1
ePDU2GroupTotalPowerGetting this OID will return the total power consumption of the Rack PDU Daisy Chain group devices in watts. Queries to slave units in an Daisy Chain group will return 0.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.8.2
ePDU2GroupTotalEnergyGetting this OID will return the total energy consumption of the Rack PDU Daisy Chain group devices in tenths of kilowatt-hours. To reset the energy meters for each of the Rack PDU devices that contribute to this value, see the ePDU2GroupEnergyReset OID. To view the start time for each of the Rack PDU device energy meters that contribute to this value, see the ePDU2DeviceStatusEnergyStartTime OID. Queries to slave units in an Daisy Chain group will return 0.ro
Gauge
.1.3.6.1.4.1.3808.1.1.6.8.3
ePDU2GroupEnergyResetSetting this OID to reset (2) will cause the device energy meter value on each device in the Rack PDU Daisy Chain group to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.8.4
ePDU2GroupPeakRecordResetSetting this OID to reset (2) will cause the device peak record value on each device in the Rack PDU Daisy Chain group to be reset to current load/power. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.6.8.5
battmgr
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.7
bmIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.7.1
bmIdentModelNameBattery manager model name.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.1.1
bmIdentHardwareRevBattery manager hardware version.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.1.2
bmIdentFirmwareRevBattery manager firmware version.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.1.3
bmIdentLCDHardwareRevBattery manager LCD hardware version.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.1.4
bmIdentLCDFirmwareRevBattery manager LCD firmware version.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.1.5
bmIdentDateOfManufactureBattery manager manufacture date.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.1.6
bmIdentSerialNumberBattery manager serial number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.1.7
bmIdentNameBattery manager system identification name.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.1.8
bmIdentLocationBattery manager system location.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.1.9
bmProperty
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.7.2
bmPropertyStringMaxBattery manager max string count supported.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.2.1
bmPropertyMaxProbeOnStringBattery manager max probes on a string supported.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.2.2
bmPropertyInputVoltageRangeBattery manager line input voltage range.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.2.3
bmConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.7.3
bmConfigBattAHBattery manager battery AH type configuration, unit in 0.1 AH.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.1
bmConfigStringCountBattery manager string count setting.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.2
bmConfigProbesCountOnStringBattery manager probe count on a string setting.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.3
bmConfigLowVoltAlarmThresholdBattery low voltage alarm threshold setting, unit in 0.1 volt.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.4
bmConfigHighVoltAlarmThresholdBattery high voltage alarm threshold setting, unit in 0.1 volt.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.5
bmConfigVoltDiffAlarmThresholdBatteries within a string voltage difference threshold, unit in 0.1 volt.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.6
bmConfigLowTempAlarmThresholdBattery low temperature alarm threshold, unit in 0.1 degree C.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.7
bmConfigHighTempAlarmThresholdBattery high temperature alarm threshold, unit in 0.1 degree C.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.8
bmConfigLowResAlarmThresholdBattery low resistance alarm threshold, unit in 0.01 mOhm.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.9
bmConfigHighResAlarmThresholdBattery high resistance alarm threshold, unit in 0.01 mOhm.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.10
bmConfigLowResWarnThresholdBattery low resistance warning threshold, unit in 0.01 mOhm.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.11
bmConfigHighResWarnThresholdBattery high resistance warning threshold, unit in 0.01 mOhm.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.12
bmConfigResHealthAlarmThresholdBattery resistance health alarm threshold, unit in percentage and should larger than 100.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.13
bmConfigResHealthWarnThresholdBattery resistance health warn threshold, unit in percentage and should larger than 100.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.3.14
bmControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.7.4
bmControlSysytemIdenticatorBattery manager will perform a panel indicator test when the variable is set to testIndicators(2). Get this oid will get noTestIndicators(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.7.4.1
bmControlProbeIndicatorBattery manager will perform a probe indicator test when the variable is set to testIndicators(2). Get this oid will get noTestIndicators(1).rw
Enumeration
.1.3.6.1.4.1.3808.1.1.7.4.2
bmProbes
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.7.5
bmProbesNumCurrent connected probe number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.1
bmProbesTableSizeCurrent configured probe number.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.2
bmProbesTableAllows for getting of status of probes.
SEQUENCE OF BmProbesEntry
.1.3.6.1.4.1.3808.1.1.7.5.3
bmProbesEntryThe status of probes installation to gather status from.
BmProbesEntry
.1.3.6.1.4.1.3808.1.1.7.5.3.1
bmProbesIndexProbes table indexro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.3.1.1
bmProbesPackIndexThe battery pack number the probe installed.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.3.1.2
bmProbesStringIndexThe string number the probe installed.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.3.1.3
bmProbesBattIndexThe battery number the probe installed.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.3.1.4
bmProbesVoltageTableSizeThe size of the battery voltage tablero
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.4
bmProbesVoltageTableAllows for getting of voltage of batteries.
SEQUENCE OF BmProbesVoltageEntry
.1.3.6.1.4.1.3808.1.1.7.5.5
bmProbesVoltageEntryBatteries voltage status.
BmProbesVoltageEntry
.1.3.6.1.4.1.3808.1.1.7.5.5.1
bmProbesVoltageIndexThe index of the voltage status entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.5.1.1
bmProbesVoltagePackIndexThe battery pack index to the voltage record.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.5.1.2
bmProbesVoltageStringIndexThe battery string index to the voltage record.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.5.1.3
bmProbesVoltageBattIndexThe battery index to the voltage record within its string.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.5.1.4
bmProbesVoltageProbeIndexThe probe index to the voltage record.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.5.1.5
bmProbesVoltageAlarmStatusThe battery voltage alarm status.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.7.5.5.1.6
bmProbesVoltageGetting this oid to get battery voltage, unit in 0.01 volt.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.5.1.7
bmProbesVoltageEqualPercentageGetting this oid to get battery voltage equalizing power, unit in percentage.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.5.1.8
bmProbesTempTableSizeThe size of the Temperature tablero
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.6
bmProbesTempTableAllows for getting of temperature of probes.
SEQUENCE OF BmProbesTempEntry
.1.3.6.1.4.1.3808.1.1.7.5.7
bmProbesTempEntryTemperature status entry.
BmProbesTempEntry
.1.3.6.1.4.1.3808.1.1.7.5.7.1
bmProbesTempIndexThe index of the temperature entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.7.1.1
bmProbesTempPackIndexThe battery pack index of the temperature entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.7.1.2
bmProbesTempStringIndexThe index to the string.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.7.1.3
bmProbesTempBattIndexThe index to the battery.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.7.1.4
bmProbesTempProbeIndexThe index to the probe.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.7.1.5
bmProbesTempAlarmStatusThe alarm status of the temperature.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.7.5.7.1.6
bmProbesTemperatureThe temperature record, measure in 0.1 degree C.ro
INTEGER(-40..60)
.1.3.6.1.4.1.3808.1.1.7.5.7.1.7
bmProbesResTableSizeThe size of the Resistance tablero
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.8
bmProbesResTableAllows for getting of resistance of probes.
SEQUENCE OF BmProbesResEntry
.1.3.6.1.4.1.3808.1.1.7.5.9
bmProbesResEntryThe resistance status entry.
BmProbesResEntry
.1.3.6.1.4.1.3808.1.1.7.5.9.1
bmProbesResIndexThe index of the resistance entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.9.1.1
bmProbesResPackIndexThe battery pack index to the resistance entry.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.9.1.2
bmProbesResStringIndexThe index to the string.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.9.1.3
bmProbesResBattIndexThe index to the battery.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.9.1.4
bmProbesResProbeIndexThe index to the probe.ro
INTEGER
.1.3.6.1.4.1.3808.1.1.7.5.9.1.5
bmProbesResAlarmStatusThe alarm status of the battery resistance.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.7.5.9.1.6
bmProbesResistanceThe resistance of the battery, unit in 0.01 mOhm.ro
INTEGER(-40..60)
.1.3.6.1.4.1.3808.1.1.7.5.9.1.7
bmProbesResHealthThe resistance health status, unit in percentage.ro
INTEGER(-40..60)
.1.3.6.1.4.1.3808.1.1.7.5.9.1.8
bmFuncRes
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.7.6
bmFuncResMeasure
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.7.6.1
bmFuncResMeasureIntervalThe time interval for battery manager to exercising resistance measurement, unit in hour(s).rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.6.1.1
bmFuncResMeasureManualCmdThis oid allows user to manual resistance measurement. Set this oid to measureResNow(2) to measure resistance immediately. Get bmFuncResMeasureLastCmdResult oid to check command acceptance.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.7.6.1.2
bmFuncResMeasureManualResultGet this oid to confirm the last manual command result.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.7.6.1.3
bmFuncResMeasureLastUpdateWhen resistance measurement complete either by auto or manual, this oid will update to the last update time.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.6.1.4
bmFuncEqual
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.1.1.7.7
bmFuncEqualEnableBattery voltage equalization configuration.rw
Enumeration
.1.3.6.1.4.1.3808.1.1.7.7.1
bmFuncEqualActiveCondVolatge equalization will active when the voltage difference larger than this value, unit in 10mV.rw
INTEGER
.1.3.6.1.4.1.3808.1.1.7.7.2
bmFuncEqualStatusThis oid shows the current equalization status.ro
Enumeration
.1.3.6.1.4.1.3808.1.1.7.7.3
bmFuncEqualStartTimeThis oid shows the last equalization start time.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.1.1.7.7.4
bmFuncEqualElapseTimeThis oid shows the elapsed time since last equalization started.ro
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.3808.1.1.7.7.5
cpsmgmt
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.2
mconfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.2.1
mconfigNumTrapAcceptersThe number of receivers to send traps to.ro
INTEGER
.1.3.6.1.4.1.3808.2.1.1
mconfigTrapAccepterTableA list of receivers to send traps to. The numbers of entries are given by the value of mconfigNumTrapAccepters.
SEQUENCE OF MconfigTrapAccepterEntry
.1.3.6.1.4.1.3808.2.1.2
mconfigTrapAccepterEntryThe receivers to send traps to.
MconfigTrapAccepterEntry
.1.3.6.1.4.1.3808.2.1.2.1
trapIndexThe trap receiver entry index.
INTEGER
.1.3.6.1.4.1.3808.2.1.2.1.1
accepterAddrThe trap receiver IP address.rw
IpAddress
.1.3.6.1.4.1.3808.2.1.2.1.2
communityStringThe trap receiver community name.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.2.1.2.1.3
severityDegreeThe trap receiver severity level. Traps are marked in severity level as informational(1), warning(2), severe(3). Only send the traps of equal or greater severity than this value to the receiver.ro
Enumeration
.1.3.6.1.4.1.3808.2.1.2.1.4
accepterActiveA receiver will accept traps if yes, and none if no.rw
Enumeration
.1.3.6.1.4.1.3808.2.1.2.1.5
mconfigDHCPEnabledThe system will automatically obtain its IP from a DHCP server if yes, and none if no.rw
Enumeration
.1.3.6.1.4.1.3808.2.1.3
mconfigMyAddrThe system IP address.ro
IpAddress
.1.3.6.1.4.1.3808.2.1.4
mconfigClock
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.2.1.5
mconfigClockDateThe current date in the mm/dd/yyyy format. Example: 01/01/2000.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.2.1.5.1
mconfigClockTimeThe current time in the hh:mm:ss 24H format.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.2.1.5.2
mtrapinfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.2.2
mtrapinfoIntegerAllow CPS traps with an integer argument for providing detail information. Not being defined in the MIB, only reply 0.ro
INTEGER
.1.3.6.1.4.1.3808.2.2.1
mtrapinfoIpAddressAllow CPS traps with an IP address argument for providing detail information. Not being defined in the MIB, only reply 0.0.0.0.ro
IpAddress
.1.3.6.1.4.1.3808.2.2.2
mtrapinfoStringAllow CPS traps with an octet string argument for providing detail information. Not being defined in the MIB, only reply a NULL string.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.3808.2.2.3
mtrapinfoGaugeAllow CPS traps with an Gauge argument for providing detail information. Not being defined in the MIB, only reply 0.ro
Gauge
.1.3.6.1.4.1.3808.2.2.4
mtrapinfoTimeTicksAllow CPS traps with an TimeTicks argument for providing detail information. Not being defined in the MIB, only reply 0.ro
TimeTicks (SNMPv2-SMI)
.1.3.6.1.4.1.3808.2.2.5
mtrapinfoBmEventIdAllow CPS traps with an integer argument for providing detail information about Battery Manager specific event identifier. Not being defined in the MIB, only reply 0. Known Specific Event ID: Battery Manager 0 - not used 1 - Alarm: The battery manager system fault. 2 - Info: Device configuration changed. 3 - Alarm: Probe configuration mismatched. 4 - Info: Probe configuration matched. 5 - Alarm: Communication with battery manager has been lost. 6 - Info: Communication with battery manager has been restored. 7 - Alarm: Communication with LCD has been lost. 8 - Info: Communication with LCD has been restored. 9 - Warning: Enter battery equalization active mode. 10- Warning: Leave battery equalization active mode. 11- Alarm: Battery equalizing has failed. 12- Info: Battery equalizing succeed. Known Specific Event ID: Battery Probes 101 - Alarm: Low battery voltage. 102 - Alarm: High battery voltage. 103 - Info: Battery voltage event has cleared. 104 - Alarm: Low battery temperature. 105 - Alarm: High battery temperature. 106 - Info: Battery temperature event has cleared. 107 - Alarm: Critical low battery resistance. 108 - Alarm: Critical high battery resistance. 109 - Warning: Low battery resistance. 110 - Warning: high battery resistance. 111 - Info: Battery resistance event has cleared. 112 - Alarm: Battery resistance health has crossed alarm threshold. 113 - Warning: Battery resistance health has crossed warning threshold. 114 - Info: Battery resistance health has returned to Normal.ro
INTEGER
.1.3.6.1.4.1.3808.2.2.6
mcontrol
OBJECT IDENTIFIER
.1.3.6.1.4.1.3808.2.3
mcontrolRestartSetting this OID to restartCurrentSystem (2) will restart the current system. Setting this OID to restartCurrentAgent (3) will restart the current agent. Setting this OID to restartCurrentSystemAnd Agent (4) will restart the current the current system and agent.rw
Enumeration
.1.3.6.1.4.1.3808.2.3.1
mcontrolResetSetting this OID to resetCurrentSystem (2) will reset the current system. Setting this OID to resetCurrentAgent (3) will reset the current agent. Setting this OID to resetCurrentSystemAndAgenta (4) will reset the current system and the current agent.rw
Enumeration
.1.3.6.1.4.1.3808.2.3.2
CPS-MIB - SNMP MIB Reference | MIBs Explorer