Home/Catalog/CPQWCRM-MIB

CPQWCRM-MIB

Detailed view of the defined objects, syntax rules, and hierarchical paths.

134
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

134 total
Object Name
cpqWcrm
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167
CPQHOST-MIB
Unknown
.1.3.6.1.4.1.232.167
alarmSensorInternalInternal Sensor Alarm
TRAP-TYPE
.1.3.6.1.4.1.232.167.0.1
alarmSensorWaterCoolUnitWater Cool Unit Sensor Alarm
TRAP-TYPE
.1.3.6.1.4.1.232.167.0.2
alarmInternalInternal Unit Alarm
TRAP-TYPE
.1.3.6.1.4.1.232.167.0.5
alarmWaterCoolUnitWater Cool Unit System Alarm
TRAP-TYPE
.1.3.6.1.4.1.232.167.0.6
testTrapTest trap sent to a trap receiver to check proper reception of traps
TRAP-TYPE
.1.3.6.1.4.1.232.167.0.10
cpqWcrmMibRev
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.1
cpqWcrmMibMajRevThe Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information, correct interpretation of data may require a MIB document with the same major revision level.ro
INTEGER
.1.3.6.1.4.1.232.167.1.1
cpqWcrmMibMinRevThe Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred.ro
INTEGER
.1.3.6.1.4.1.232.167.1.2
cpqWcrmMibConditionThe overall condition (status) of the system represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on Environmental Controller) (4) a major problem (red LED on Environmental Controller) (5) configuration of sensor units changed or unit detected (red/yellow/green LED on Environmental Controller)ro
Enumeration
.1.3.6.1.4.1.232.167.1.3
cpqWcrmStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.2
cpqWcrmStatusDeviceEnvironmentalControllerGeneral Status of Environmental Controller unit itself (1) failed (2) OKro
Enumeration
.1.3.6.1.4.1.232.167.2.1
cpqWcrmUnitsConnectedNumber of sensor units connected to the Environmental Controller, Port 1 to 2ro
INTEGER
.1.3.6.1.4.1.232.167.2.2
cpqWcrmStatusSensorInternal
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.2.3
cpqWcrmInternalTypeOfDeviceType of sensor unit connected to port 1ro
Enumeration
.1.3.6.1.4.1.232.167.2.3.1
cpqWcrmInternalTextDescriptional text for sensor unit connected to port 1rw
DisplayString
.1.3.6.1.4.1.232.167.2.3.2
cpqWcrmInternalSerialSerialnumber of sensor unit connected to port 1ro
INTEGER
.1.3.6.1.4.1.232.167.2.3.3
cpqWcrmInternalStatusGeneral Status sensor unit connected to port 1 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) reset from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too lowro
Enumeration
.1.3.6.1.4.1.232.167.2.3.4
cpqWcrmStatusInternalSensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.2.3.5
cpqWcrmInternalNumberOfSensorsNumber of sensors connected to sensor unit 1ro
INTEGER
.1.3.6.1.4.1.232.167.2.3.5.1
cpqWcrmInternalSensorTableHeadline of sensor table
SEQUENCE OF CpqWcrmInternalSensorEntry
.1.3.6.1.4.1.232.167.2.3.5.2
cpqWcrmInternalSensorEntryEntries of sensor table
CpqWcrmInternalSensorEntry
.1.3.6.1.4.1.232.167.2.3.5.2.1
internalSensorIndexIndex for the list of value entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfSensors.ro
INTEGER
.1.3.6.1.4.1.232.167.2.3.5.2.1.1
internalSensorTypeType of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage (OK, NOK) 18: voltage value 19: fan status, from Environmental Controller-FAS-Unit 20: leakage sensorro
Enumeration
.1.3.6.1.4.1.232.167.2.3.5.2.1.2
internalSensorTextDescriptional text for each sensor (entry in the table)rw
DisplayString
.1.3.6.1.4.1.232.167.2.3.5.2.1.3
internalSensorStatusActual status of the sensorro
Enumeration
.1.3.6.1.4.1.232.167.2.3.5.2.1.4
internalSensorValueValue of sensorro
INTEGER
.1.3.6.1.4.1.232.167.2.3.5.2.1.5
internalSensorSetHighValue for high setpoint of sensorrw
INTEGER
.1.3.6.1.4.1.232.167.2.3.5.2.1.6
internalSensorSetLowValue for low setpoint of sensor, also used as alarm delayrw
INTEGER
.1.3.6.1.4.1.232.167.2.3.5.2.1.7
internalSensorSetWarnValue for warning setpoint of sensor, also used as fan thresholdrw
INTEGER
.1.3.6.1.4.1.232.167.2.3.5.2.1.8
cpqWcrmStatusInternalOutputs
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.2.3.6
cpqWcrmInternalNumberOfOutputsNumber of outputs available on internal sensorro
INTEGER
.1.3.6.1.4.1.232.167.2.3.6.1
cpqWcrmInternalOutputTableHeadline of output table
SEQUENCE OF CpqWcrmInternalOutputEntry
.1.3.6.1.4.1.232.167.2.3.6.2
cpqWcrmInternalOutputEntryEntries of output table
CpqWcrmInternalOutputEntry
.1.3.6.1.4.1.232.167.2.3.6.2.1
internalOutputIndexIndex for the list of output entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfOutputs.ro
INTEGER
.1.3.6.1.4.1.232.167.2.3.6.2.1.1
internalOutputTypeType of output which is connected to internal sensor to output[internalOutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 6, universal relay output 5: output type 8, power outputro
Enumeration
.1.3.6.1.4.1.232.167.2.3.6.2.1.2
internalOutputTextDescriptional text for each output (entry in the table)rw
DisplayString
.1.3.6.1.4.1.232.167.2.3.6.2.1.3
internalOutputStatusActual status of the outputrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.6.2.1.4
internalOutputValueValue for outputrw
INTEGER
.1.3.6.1.4.1.232.167.2.3.6.2.1.5
internalOutputSetCommand for outputrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.6.2.1.6
internalOutputConfigConfiguration for output 1: disable remote control (e.g. keypad) 2: enable remote controlrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.6.2.1.7
internalOutputDelayUnsigned Value for delay, after this time the output will fall into the previous staterw
INTEGER
.1.3.6.1.4.1.232.167.2.3.6.2.1.8
internalOutputTimeoutActionState for output if timeout (RS422) occursrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.6.2.1.9
cpqWcrmStatusInternalMsg
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.2.3.7
cpqWcrmInternalNumberOfMsgsNumber of messages that can be created with internal sensorro
INTEGER
.1.3.6.1.4.1.232.167.2.3.7.1
cpqWcrmInternalMsgTableHeadline of message table
SEQUENCE OF CpqWcrmInternalMsgEntry
.1.3.6.1.4.1.232.167.2.3.7.2
cpqWcrmInternalMsgEntryEntries of message table
CpqWcrmInternalMsgEntry
.1.3.6.1.4.1.232.167.2.3.7.2.1
internalMsgIndexIndex for the list of message entries. Its value ranges between 1 and the value of cpqWcrmInternalNumberOfMsgs.ro
INTEGER
.1.3.6.1.4.1.232.167.2.3.7.2.1.1
internalMsgTextDescriptional text for each message (entry in the table)rw
DisplayString
.1.3.6.1.4.1.232.167.2.3.7.2.1.2
internalMsgStatusActual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to ON 10: output is set to OFFro
Enumeration
.1.3.6.1.4.1.232.167.2.3.7.2.1.3
internalMsgRelaySetup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relayrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.7.2.1.4
internalMsgBeeperSetup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarmrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.7.2.1.5
internalMsgTrap1Trap receiver 1 activatedrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.7.2.1.6
internalMsgTrap2Trap receiver 2 activatedrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.7.2.1.7
internalMsgTrap3Trap receiver 3 activatedrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.7.2.1.8
internalMsgTrap4Trap receiver 4 and Event Logging activatedrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.7.2.1.9
internalMsgResetReset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' keyrw
Enumeration
.1.3.6.1.4.1.232.167.2.3.7.2.1.10
cpqWcrmStatusSensorWaterCoolUnit
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.2.4
cpqWcrmWaterCoolUnitTypeOfDeviceType of sensor unit connected to port 2ro
Enumeration
.1.3.6.1.4.1.232.167.2.4.1
cpqWcrmWaterCoolUnitTextDescriptional text for sensor unit connected to port 2rw
DisplayString
.1.3.6.1.4.1.232.167.2.4.2
cpqWcrmWaterCoolUnitSerialSerialnumber of sensor unit connected to port 2ro
INTEGER
.1.3.6.1.4.1.232.167.2.4.3
cpqWcrmWaterCoolUnitStatusGeneral Status sensor unit connected to port 2 (1) OK (2) error (3) configuration of sensor unit has changed, confirmation required (4) reset from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required (6) sensor unit detected, needs to be confirmed (8) supply voltage is too lowro
Enumeration
.1.3.6.1.4.1.232.167.2.4.4
cpqWcrmStatusWaterCoolUnitSensors
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.2.4.5
cpqWcrmWaterCoolUnitNumberOfSensorsNumber of sensors connected to water cool unitro
INTEGER
.1.3.6.1.4.1.232.167.2.4.5.1
cpqWcrmWaterCoolUnitSensorTableHeadline of sensor table
SEQUENCE OF CpqWcrmWaterCoolUnitSensorEntry
.1.3.6.1.4.1.232.167.2.4.5.2
cpqWcrmWaterCoolUnitSensorEntryEntries of sensor table
CpqWcrmWaterCoolUnitSensorEntry
.1.3.6.1.4.1.232.167.2.4.5.2.1
waterCoolUnitSensorIndexIndex for the list of value entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfSensors.ro
INTEGER
.1.3.6.1.4.1.232.167.2.4.5.2.1.1
waterCoolUnitSensorTypeType of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: average temperature of air inlet to rack, average or max/min from each HEX 5: average temperature of air outlet from rack, average or max/min from each HEX 6: heatflow sensor 7: alarm: Bit 0: Leakage Bit 1: IIC Failure 8: warning: Bit 0..2: Fan Tach 1..3 Bit 3,4: Temp. sensor HEX1 In,Out Bit 5,6: Temp. sensor HEX2 In,Out Bit 7,8: Temp. sensor HEX3 In,Out Bit 9: Air temp. sensor Bit 10..12: IIC failure, HEX1..3 Bit 13: Waterflow low Bit 14,15: Watertemp. In,Out Bit 16: Waterflow sensor fail. Bit 17: Magnetic valve fail. Bit 18: Leakdetector fail. Bit 19: Uneven heat load Bit 20: Condensation Pump Cycles > Max Bit 21: Condensation Pump Running Time > Max 9: rpm speed of Fan1 10: rpm speed of Fan2 11: rpm speed of Fan3 12: fanSpeed setpoint, calculated from average temperatures 13: temperature air inlet to rack, HEX 1 14: temperature air outlet from rack, HEX 1 15: temperature air inlet to rack, HEX 1 16: temperature air outlet from rack, HEX 1 17: temperature air inlet to rack, HEX 1 18: temperature air outlet from rack, HEX 1 19: water temperature In 20: water temperature Out 21: water Flow 22: water valve status: MCS:0: Valve opened, 1: valve closed; MCSS: valve setpoint (%) 23: status: Bit 0..Bit 2: fan module 1..3 available Bit 3: water module available 24: condensation pump number of seconds on counter (last operating time) 25: condensation pump on/off cycle counter 26: rpm speed of Fan4 27: rpm speed of Fan5 28: rpm speed of Fan6 29: status of transfer switch, 1=AC1, 2=AC2, 3=AC1 and AC2 30: water valve actual value (%)ro
Enumeration
.1.3.6.1.4.1.232.167.2.4.5.2.1.2
waterCoolUnitSensorTextDescriptional text for each sensor (entry in the table)rw
DisplayString
.1.3.6.1.4.1.232.167.2.4.5.2.1.3
waterCoolUnitSensorStatusActual status of the sensorro
Enumeration
.1.3.6.1.4.1.232.167.2.4.5.2.1.4
waterCoolUnitSensorValueValue of sensor added to traps, msg index also added (waterCoolUnitMsgIndex) If msg index = 1, 5 or 6 This value represents the actual Server Intake Temperature. If msg index = 2: This value represents the bit coded warning condition Bit 0: Top Fan Module Failed Bit 1: Middle Fan Module Failed Bit 2: Bottom Fan Module Failed Bit 3: Top HEX Intake Air Temperature Sensor to Server Failed Bit 4: Top HEX Exhaust Air Temperature Sensor from Server Failed Bit 5: Middle HEX Intake Air Temperature Sensor to Server Failed Bit 6: Middle HEX Exhaust Air Temperature Sensor from Server Failed Bit 7: Bottom HEX Intake Air Temperature Sensor to Server Failed Bit 8: Bottom HEX Exhaust Air Temperature Sensor from Server Failed Bit 9: Air Temperature Sensor Failed Bit 10: Top Fan not installed Bit 11: Middle Fan not installed Bit 12: Bottom Fan not installed Bit 13: Waterflow low Bit 14: Water Unit Temperature Input Out of Range Bit 15: Water Unit Temperature Output Out of Range Bit 16: Waterflow Sensor Value Out of Range Bit 17: Water Valve Failed Bit 18: Leakdetector Failed Bit 19: Heat Load Warning Bit 20: The Condensation Pump has exceeded the max. number of cycles Bit 21: The Condensation Pump has exceeded the max. Running Time If msg index = 3: This value represents the bit coded alarm condition Bit 0: Leakage Detected Bit 1: Comm. Failure IICro
INTEGER
.1.3.6.1.4.1.232.167.2.4.5.2.1.5
waterCoolUnitSensorSetHighValue for high setpoint of sensorrw
INTEGER
.1.3.6.1.4.1.232.167.2.4.5.2.1.6
waterCoolUnitSensorSetLowValue for low setpoint of sensor, also used as alarm delayrw
INTEGER
.1.3.6.1.4.1.232.167.2.4.5.2.1.7
waterCoolUnitSensorSetWarnValue for warning setpoint of sensor, also used as fan thresholdrw
INTEGER
.1.3.6.1.4.1.232.167.2.4.5.2.1.8
cpqWcrmStatusWaterCoolUnitOutputs
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.2.4.6
cpqWcrmWaterCoolUnitNumberOfOutputsNumber of outputs available on sensor water cool unitro
INTEGER
.1.3.6.1.4.1.232.167.2.4.6.1
cpqWcrmWaterCoolUnitOutputTableHeadline of output table
SEQUENCE OF CpqWcrmWaterCoolUnitOutputEntry
.1.3.6.1.4.1.232.167.2.4.6.2
cpqWcrmWaterCoolUnitOutputEntryEntries of output table
CpqWcrmWaterCoolUnitOutputEntry
.1.3.6.1.4.1.232.167.2.4.6.2.1
waterCoolUnitOutputIndexIndex for the list of output entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfOutputs.ro
INTEGER
.1.3.6.1.4.1.232.167.2.4.6.2.1.1
waterCoolUnitOutputTypeType of output which is connected to water cool unit to output[waterCoolUnitOutputIndex] 1: no output connected 2: output failure 3: value overflow 4: water valve setpoint 5: water valve hysteresis 6: command for manual control 7: Flow Meter Model, 0=SIKA, 1=Chemline 8: minimum fan speed 9: min delta T, used for fan control 10: max delta T, used for fan control 11: specific heat capacity 12: setpoint heatload warning 13: setpoint Water Flow Loss Emergency Door Opening 14: setpoint High Temperature Emergency Door Opening 15: setpoint Condensation Pump Cycles (Warning) 16: setpoint Condensation Pump Running Time (Warning) 17: command for door opening, 0=lock door, 1=unlock door 18: KP parameter for PID controller 19: KI parameter for PID controller 20: KD parameter for PID controller 21: sampling time PID controllerro
Enumeration
.1.3.6.1.4.1.232.167.2.4.6.2.1.2
waterCoolUnitOutputTextDescriptional text for each output (entry in the table)rw
DisplayString
.1.3.6.1.4.1.232.167.2.4.6.2.1.3
waterCoolUnitOutputStatusActual status of the outputrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.6.2.1.4
waterCoolUnitOutputValueSigned value for outputrw
INTEGER
.1.3.6.1.4.1.232.167.2.4.6.2.1.5
waterCoolUnitOutputSetCommand for outputrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.6.2.1.6
waterCoolUnitOutputConfigConfiguration for output 1: disable remote control (e.g. keypad) 2: enable remote controlrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.6.2.1.7
waterCoolUnitOutputDelayUnsigned Value for delay, after this time the output will fall into the previous staterw
INTEGER
.1.3.6.1.4.1.232.167.2.4.6.2.1.8
waterCoolUnitOutputTimeoutActionState for output if timeout (RS422) occursrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.6.2.1.9
cpqWcrmStatusWaterCoolUnitMsg
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.2.4.7
cpqWcrmWaterCoolUnitNumberOfMsgsNumber of alarms that can be created with water cool unitro
INTEGER
.1.3.6.1.4.1.232.167.2.4.7.1
cpqWcrmWaterCoolUnitMsgTableHeadline of message table
SEQUENCE OF CpqWcrmWaterCoolUnitMsgEntry
.1.3.6.1.4.1.232.167.2.4.7.2
cpqWcrmWaterCoolUnitMsgEntryEntries of message table
CpqWcrmWaterCoolUnitMsgEntry
.1.3.6.1.4.1.232.167.2.4.7.2.1
waterCoolUnitMsgIndexIndex for the list of alarm entries. Its value ranges between 1 and the value of cpqWcrmWaterCoolUnitNumberOfMsgs.ro
INTEGER
.1.3.6.1.4.1.232.167.2.4.7.2.1.1
waterCoolUnitMsgTextDescriptional text for each message (entry in the table)rw
DisplayString
.1.3.6.1.4.1.232.167.2.4.7.2.1.2
waterCoolUnitMsgStatusActual message status 4: OK 5: alarm 6: warning 7: analog value too low, value reached low threshold 8: analog value too high, value reached high thresholdro
Enumeration
.1.3.6.1.4.1.232.167.2.4.7.2.1.3
waterCoolUnitMsgRelaySetup of Alarm relay for this alarm 2: no switching of alarm relay 1: switching of alarm relayrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.7.2.1.4
waterCoolUnitMsgBeeperSetup of Alarm beeper for this alarm 2: no audible alarm 1: audible alarmrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.7.2.1.5
waterCoolUnitMsgTrap1Trap receiver 1 activatedrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.7.2.1.6
waterCoolUnitMsgTrap2Trap receiver 2 activatedrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.7.2.1.7
waterCoolUnitMsgTrap3Trap receiver 3 activatedrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.7.2.1.8
waterCoolUnitMsgTrap4Trap receiver 4 and Event Logging activatedrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.7.2.1.9
waterCoolUnitMsgResetReset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' keyrw
Enumeration
.1.3.6.1.4.1.232.167.2.4.7.2.1.10
cpqWcrmURLURL of the management interface in the format http[s]://ipaddr[:port#][/page]ro
DisplayString
.1.3.6.1.4.1.232.167.2.7
cpqWcrmSetup
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.3
cpqWcrmSetupGeneral
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.3.1
cpqWcrmSetTempUnitUnit of all temperature values and setpoints, Celsius or Fahrenheitrw
Enumeration
.1.3.6.1.4.1.232.167.3.1.1
cpqWcrmSetBeeperAudible alarm in Environmental Controller unit: (2): beeper is on (1): beeper is off (general)rw
Enumeration
.1.3.6.1.4.1.232.167.3.1.2
cpqWcrmResetRelayEnable or disable acknowledging currently active alarm relay (with 'C' on Environmental Controller).rw
Enumeration
.1.3.6.1.4.1.232.167.3.1.3
cpqWcrmLogicRelayLogic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay off (general)rw
Enumeration
.1.3.6.1.4.1.232.167.3.1.4
cpqWcrmWebAccessWeb access via HTTP: (1) view only (2) full Access, read and set (3) Web disabled (general)rw
Enumeration
.1.3.6.1.4.1.232.167.3.1.5
cpqWcrmSetupDateactual Date in format DD.MM.YYYYrw
DisplayString
.1.3.6.1.4.1.232.167.3.1.6
cpqWcrmSetupTimeactual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)rw
DisplayString
.1.3.6.1.4.1.232.167.3.1.7
cpqWcrmTimerTable1
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.3.1.8
cpqWcrmTimerNumberNumber of value-table entries=number of outlets available on this unitro
INTEGER
.1.3.6.1.4.1.232.167.3.1.8.1
cpqWcrmTimerTableHeadline of status-table
SEQUENCE OF CpqWcrmTimerEntry
.1.3.6.1.4.1.232.167.3.1.8.2
cpqWcrmTimerEntryEntries of timer-table
CpqWcrmTimerEntry
.1.3.6.1.4.1.232.167.3.1.8.2.1
cpqWcrmTimerIndexIndex for the list of timer entries. Its value ranges between 1 and the value of cpqWcrmTimerNumber.ro
INTEGER
.1.3.6.1.4.1.232.167.3.1.8.2.1.1
cpqWcrmTimerStatusActual status of the timerro
Enumeration
.1.3.6.1.4.1.232.167.3.1.8.2.1.2
cpqWcrmTimerDayOfWeekSelection of day of week for timer to switchrw
Enumeration
.1.3.6.1.4.1.232.167.3.1.8.2.1.3
cpqWcrmTimeOnTime to switch on current function, Format: HH:MMrw
DisplayString
.1.3.6.1.4.1.232.167.3.1.8.2.1.4
cpqWcrmTimeOffTime to switch off current function, Format: HH:MMrw
DisplayString
.1.3.6.1.4.1.232.167.3.1.8.2.1.5
cpqWcrmTimeControlControl via RTCrw
Enumeration
.1.3.6.1.4.1.232.167.3.1.8.2.1.6
cpqWcrmTimerFunctionFunction which is controlled via timer 1-4: sending Traps to this Trap receiver will be disabled 5 - 8: scheduled alarm offrw
Enumeration
.1.3.6.1.4.1.232.167.3.1.8.2.1.7
cpqWcrmSetFlowUnitUnit of Water Flow, Liter/min or Gallon/minrw
Enumeration
.1.3.6.1.4.1.232.167.3.1.9
cpqWcrmTrapControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.4
cpqWcrmTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.4.7
cpqWcrmTraptableNumberNumber of trapTable entries. The number of trap-receiverro
INTEGER
.1.3.6.1.4.1.232.167.4.7.1
cpqWcrmTrapTableTableA list of trap-receiver entries
SEQUENCE OF CpqWcrmTrapTableEntry
.1.3.6.1.4.1.232.167.4.7.2
cpqWcrmTrapTableEntryEntries of trapTable
CpqWcrmTrapTableEntry
.1.3.6.1.4.1.232.167.4.7.2.1
trapIndexIndex for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumberro
INTEGER
.1.3.6.1.4.1.232.167.4.7.2.1.1
trapStatusEnable or disable trap receiverrw
Enumeration
.1.3.6.1.4.1.232.167.4.7.2.1.2
trapIPaddressIP-address of trap-receiverrw
DisplayString
.1.3.6.1.4.1.232.167.4.7.2.1.3
cpqWcrmControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.167.5
cpqWcrmResetUnitCommand to reset (acknowledge) alarms of Environmental Controller unit. Setting to 'reset' (2) will have same result as pressing 'C' on Units. Variable is automatically set back to 'noReset' (1).rw
Enumeration
.1.3.6.1.4.1.232.167.5.1