Home/Catalog/CPQUPS-MIB

CPQUPS-MIB

AI MIB Summary

Standard SNMP MIB module defining data structures for CPQUPS-MIB.

46
Objects
Active
Status
5
Dependencies

Imported Objects

Objects

46 total
Object Name
cpqUpsLineFailedAC Line power failure. The UPS reports that the AC line power has failed.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12001
cpqUpsLineOkAC line power ok. The UPS reports that the AC line power has returned.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12002
cpqUpsShutdownUPS initiating graceful server shutdown. The UPS software is initiating a graceful server shutdown. Every attempt to preserve the state of the file system will be made. The server shutdown will be initiated due to a power anomaly.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12003
cpqUpsConfirmationServer now operational after power down. This server has previously been shutdown due to a power anomaly and has just become operational again.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12004
cpqUpsBatteryLowUPS Battery Low. The server will soon lose power.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12005
cpqUps2LineFailedAC Line power failure. The UPS reports that the AC line power has failed.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12006
cpqUps2LineOkAC line power ok. The UPS reports that the AC line power has returned.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12007
cpqUps2ShutdownUPS initiating graceful server shutdown. The UPS software is initiating a graceful server shutdown. Every attempt to preserve the state of the file system will be made. The server shutdown will be initiated due to a power anomaly.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12008
cpqUps2ConfirmationServer now operational after power down. This server has previously been shutdown due to a power anomaly and has just become operational again.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12009
cpqUps2BatteryLowUPS Battery Low. The server will soon lose power.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12010
cpqUpsOverloadThe UPS has entered an overload condition. A failure may occur unless the overload is corrected.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12011
cpqUpsPendingBatteryFailureThe UPS battery is about to fail. Replace as soon as possible.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12012
cpqUpsGenericCriticalGeneric UPS critical alarm.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12013
cpqUpsGenericInfoGeneric UPS informational alarm.
TRAP-TYPE
.1.3.6.1.4.1.232.0.12014
cpqUps
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.12
RFC1213-MIB
Unknown
.1.3.6.1.4.1.232.12
cpqUpsMibRev
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.12.1
cpqUpsMibRevMajorThe Major Revision level of the MIB. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information supported and/or the meaning of the supported information, correct interpretation of data may require a MIB document with the same major revision level.ro
INTEGER
.1.3.6.1.4.1.232.12.1.1
cpqUpsMibRevMinorThe Minor Revision level of the MIB. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred.ro
INTEGER
.1.3.6.1.4.1.232.12.1.2
cpqUpsMibConditionThe overall condition. This object represents the overall status of the UPS system represented by this MIB.ro
Enumeration
.1.3.6.1.4.1.232.12.1.3
cpqUpsComponent
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.12.2
cpqUpsInterface
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.12.2.1
cpqUpsOsCommon
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.12.2.1.4
cpqUpsOsCommonPollFreqThe Insight Agent's polling frequency. The frequency, in seconds, at which the Insight Agent requests information from the device driver. A frequency of zero (0) indicates that the Insight Agent retrieves the information upon request of a management station, it does not poll the device driver at a specific interval. If the poll frequency is zero (0) all attempts to write to this object will fail. If the poll frequency is non-zero, setting this value will change the polling frequency of the Insight Agent. Setting the poll frequency to zero (0) will always fail, an agent may also choose to fail any request to change the poll frequency to a value that would severely impact system performance.rw
INTEGER
.1.3.6.1.4.1.232.12.2.1.4.1
cpqUpsOsCommonModuleTableA table of software modules/ that provide an interface to the device this MIB describes.
SEQUENCE OF CpqUpsOsCommonModuleEntry
.1.3.6.1.4.1.232.12.2.1.4.2
cpqUpsOsCommonModuleEntryA description of a software module that provides an interface to the device this MIB describes.
CpqUpsOsCommonModuleEntry
.1.3.6.1.4.1.232.12.2.1.4.2.1
cpqUpsOsCommonModuleIndexA unique index for this module description.ro
INTEGER
.1.3.6.1.4.1.232.12.2.1.4.2.1.1
cpqUpsOsCommonModuleNameThe module name.ro
DisplayString
.1.3.6.1.4.1.232.12.2.1.4.2.1.2
cpqUpsOsCommonModuleVersionThe module version in XX.YY format. Where XX is the major version number and YY is the minor version number. This field will be a null (size 0) string if the agent cannot provide the module version.ro
DisplayString
.1.3.6.1.4.1.232.12.2.1.4.2.1.3
cpqUpsOsCommonModuleDateThe module date. field octets contents range ===== ====== ======= ===== 1 1-2 year 0..65536 2 3 month 1..12 3 4 day 1..31 4 5 hour 0..23 5 6 minute 0..59 6 7 second 0..60 (use 60 for leap-second) This field will be set to year = 0 if the agent cannot provide the module date. The hour, minute, and second field will be set to zero (0) if they are not relevant. The year field is set with the most significant octet first.ro
OCTET STRING
.1.3.6.1.4.1.232.12.2.1.4.2.1.4
cpqUpsOsCommonModulePurposeThe purpose of the module described in this entry.ro
DisplayString
.1.3.6.1.4.1.232.12.2.1.4.2.1.5
cpqUpsBasic
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.12.2.2
cpqUpsLineStatusThe status of the AC line input to the UPS.ro
Enumeration
.1.3.6.1.4.1.232.12.2.2.1
cpqUpsNameThe UPS name (type).ro
DisplayString
.1.3.6.1.4.1.232.12.2.2.2
cpqUpsEstimatedBatteryLifeThe estimated time, in minutes, of battery power available. The value will be negative one (-1) if the agent is unable to determine this information. A UPS may not provide this information when AC power is available.ro
INTEGER
.1.3.6.1.4.1.232.12.2.2.3
cpqUpsAutoShutdownDelayThe number of minutes of battery power remaining before the UPS driver will begin a graceful shutdown of the OS. A value of -1 indicates that no automatic shutdown will occur.rw
INTEGER
.1.3.6.1.4.1.232.12.2.2.4
cpqUpsLaunchCommandApplication to launch for UPS support.ro
OCTET STRING
.1.3.6.1.4.1.232.12.2.2.5
cpqUpsAlarmThis variable contains the UPS alarm text.ro
DisplayString
.1.3.6.1.4.1.232.12.2.2.6
cpqUpsFamily
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.12.2.3
cpqUpsMemberTableA table of entries that describes the family of rack-mounted servers that a single UPS supports.
SEQUENCE OF CpqUpsMemberEntry
.1.3.6.1.4.1.232.12.2.3.1
cpqUpsMemberEntryA table of entries that describes the family of rack-mounted servers that a single UPS supports.
CpqUpsMemberEntry
.1.3.6.1.4.1.232.12.2.3.1.1
cpqUpsMemberIndexA unique index for this module description.rw
INTEGER
.1.3.6.1.4.1.232.12.2.3.1.1.1
cpqUpsMemberNameThe name or address of one of the individual servers that is served by the rack-mounted UPS. Set cpqUpsMemberName to 0 to delete this row.rw
DisplayString
.1.3.6.1.4.1.232.12.2.3.1.1.2
cpqUpsMemberCommunityStrThe Community string for this individual server.rw
DisplayString
.1.3.6.1.4.1.232.12.2.3.1.1.3
cpqUpsAddMemberNameTo add a row to the cpqUpsMemberTable, this variable must be set, followed immediately by the set of the cpqUpsAddMemberCommunityStr. Sets must occur in this order, or else a new row will not be added to the table.rw
DisplayString
.1.3.6.1.4.1.232.12.2.3.2
cpqUpsAddMemberCommunityStrTo add a row to the cpqUpsMemberTable, the cpqUpsAddMemberName must be set, followed immediately by a set of this variable. Sets must occur in this order, or else a new row will not be added to the cpqUpsMemberTable.rw
DisplayString
.1.3.6.1.4.1.232.12.2.3.3
CPQUPS-MIB - SNMP MIB Reference | MIBs Explorer