CPQRPM-MIB
Detailed view of the defined objects, syntax rules, and hierarchical paths.
133
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
133 total| Object Name |
|---|
cpqRPM OBJECT IDENTIFIER .1.3.6.1.4.1.232.154 |
RFC1213-MIB Unknown .1.3.6.1.4.1.232.154 |
cpqRPMTrapInfo OBJECT IDENTIFIER .1.3.6.1.4.1.232.154.1 |
cpqRPMTrapDescriptionText description of the event that caused the trap.ro DisplayString .1.3.6.1.4.1.232.154.1.1 |
cpqRPMTrapDeviceIdA unique numeric identifier for the device that caused the trap.ro INTEGER .1.3.6.1.4.1.232.154.1.2 |
cpqRPMTrapDeviceNameThe text name for the device.ro DisplayString .1.3.6.1.4.1.232.154.1.3 |
cpqRPMTrapDeviceAddressThe hostname or ip address for the device.ro DisplayString .1.3.6.1.4.1.232.154.1.4 |
cpqRPMTrapTypeIndicates the type of the event that caused the trap.ro Enumeration .1.3.6.1.4.1.232.154.1.5 |
cpqRPMTrapSeverityIndicates the severity of the event that caused the trap.ro Enumeration .1.3.6.1.4.1.232.154.1.6 |
cpqRPMTrapCodeA unique identifier for the alarm.ro INTEGER .1.3.6.1.4.1.232.154.1.7 |
cpqRPMTrapURLThe URL for the management software.ro DisplayString .1.3.6.1.4.1.232.154.1.8 |
cpqRPMTraps OBJECT IDENTIFIER .1.3.6.1.4.1.232.154.2 |
cpqRPMTrapDeviceConnectedA UPS device is reporting a Connection Lost due to one of the following.
1. The serial cable connected to the UPS has been unplugged.
2. The Network cable connected to the UPS has been unplugged.
Recommendations:
1. Insure all cables are seated properly.
2. check you network to insure it is functioning properly.
3. If the UPS is serially connected insure that the Serial
Relay Agent is installed and running. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.1 |
cpqRPMTrapConnectionLostA UPS device is reporting a Connection Lost due to one of the following.
1. The serial cable connected to the UPS has been unplugged.
2. The Network cable connected to the UPS has been unplugged.
Recommendations:
1. Insure all cables are seated properly.
2. check you network to insure it is functioning properly.
3. If the UPS is serially connected insure that the Serial
Relay Agent is installed and running. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.2 |
cpqRPMTrapLookupFailedCRPM failed to find an IP address for the device hostname. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.3 |
cpqRPMTrapConnectionFailedCRPM failed to connect to a device. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.4 |
cpqRPMTrapDeviceSettingsChangedDevice settings have been changed by a user. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.5 |
cpqRPMTrapCMCTemp1BelowMinA CMC device is reporting temperature 1 below minimum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10001 |
cpqRPMTrapCMCTemp1AboveWarnA CMC device is reporting temperature 1 above warning threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10002 |
cpqRPMTrapCMCTemp1AboveMaxA CMC device is reporting temperature 1 above maximum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10003 |
cpqRPMTrapCMCTemp1NormalA CMC device is reporting temperature 1 has returned to a normal
temperature. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10004 |
cpqRPMTrapCMCTemp2BelowMinA CMC device is reporting temperature 2 below minimum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10005 |
cpqRPMTrapCMCTemp2AboveWarnA CMC device is reporting temperature 2 above warning threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10006 |
cpqRPMTrapCMCTemp2AboveMaxA CMC device is reporting temperature 2 above maximum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10007 |
cpqRPMTrapCMCTemp2NormalA CMC device is reporting temperature 2 has returned to a normal
temperature. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10008 |
cpqRPMTrapCMCVoltUnderA CMC device is reporting voltage below minimum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10011 |
cpqRPMTrapCMCVoltOverA CMC device is reporting voltage above maximum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10012 |
cpqRPMTrapCMCVoltNormalA CMC device is reporting voltage has returned to normal. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10013 |
cpqRPMTrapCMCHmdtUnderA CMC device is reporting humidity below minimum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10021 |
cpqRPMTrapCMCHmdtOverA CMC device is reporting humidity above maximum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10022 |
cpqRPMTrapCMCHmdtNormalA CMC device is reporting humidity has returned to normal. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10023 |
cpqRPMTrapCMCSmokeDetectedA CMC device is reporting smoke detected. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10031 |
cpqRPMTrapCMCSmokeClearedA CMC device is reporting smoke cleared. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10032 |
cpqRPMTrapCMCShockDetectedA CMC device is reporting shock detected. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10041 |
cpqRPMTrapCMCShockClearedA CMC device is reporting shock cleared. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10042 |
cpqRPMTrapCMCAux1AlarmA CMC device has entered an alarm condition for auxiliary input 1. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10051 |
cpqRPMTrapCMCAux1ClearedA CMC device is reporting auxiliary input 1 alarm cleared. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10052 |
cpqRPMTrapCMCAux2AlarmA CMC device has entered an alarm condition for auxiliary input 2. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10053 |
cpqRPMTrapCMCAux2ClearedA CMC device is reporting auxiliary input 2 alarm cleared. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10054 |
cpqRPMTrapCMCInput1OpenedA CMC device is reporting input 1 has been opened. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10101 |
cpqRPMTrapCMCInput1ClosedA CMC device is reporting input 1 has been closed. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10102 |
cpqRPMTrapCMCInput2OpenedA CMC device is reporting input 2 has been opened. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10103 |
cpqRPMTrapCMCInput2ClosedA CMC device is reporting input 2 has been closed. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10104 |
cpqRPMTrapCMCInput3OpenedA CMC device is reporting input 3 has been opened. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10105 |
cpqRPMTrapCMCInput3ClosedA CMC device is reporting input 3 has been closed. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10106 |
cpqRPMTrapCMCInput4OpenedA CMC device is reporting input 4 has been opened. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10107 |
cpqRPMTrapCMCInput4ClosedA CMC device is reporting input 4 has been closed. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10108 |
cpqRPMTrapCMCLockset1UnlockedA CMC device is reporting lockset 1 has been unlocked. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10111 |
cpqRPMTrapCMCLockset1FailedToLockA CMC device is reporting lockset 1 has failed to lock. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10112 |
cpqRPMTrapCMCLockset1ErrorA CMC device is reporting an error with lockset 1. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10113 |
cpqRPMTrapCMCLockset1LockedA CMC device is reporting lockset 1 has been locked. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10114 |
cpqRPMTrapCMCLockset2UnlockedA CMC device is reporting lockset 2 has been unlocked. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10116 |
cpqRPMTrapCMCLockset2FailedToLockA CMC device is reporting lockset 2 has failed to lock. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10117 |
cpqRPMTrapCMCLockset2ErrorA CMC device is reporting an error with lockset 2. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10118 |
cpqRPMTrapCMCLockset2LockedA CMC device is reporting lockset 2 has been locked. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10119 |
cpqRPMTrapCMCLockset1NormalA CMC device is reporting lockset 2 is normal. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10134 |
cpqRPMTrapCMCLockset2NormalA CMC device is reporting lockset 2 is normal. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.10135 |
cpqRPMTrapUPSInputVoltageBelowMinA UPS device is reporting input voltage below minimum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20001 |
cpqRPMTrapUPSInputVoltageAboveMaxA UPS device is reporting input voltage above maximum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20002 |
cpqRPMTrapUPSInputVoltageNormalA UPS device is reporting input voltage is out of range.
Recommendations:
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20003 |
cpqRPMTrapUPSOutputVoltageBelowMinA UPS device is reporting output voltage below minimum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20011 |
cpqRPMTrapUPSOutputVoltageAboveMaxA UPS device is reporting output voltage above maximum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20012 |
cpqRPMTrapUPSOutputOverloadA UPS device is reporting an overload condition.
Recommendations:
1. Reduce the load on the UPS by moving some of the load to another UPS.
2. Consider moving to a larger UPS to support the current load. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20014 |
cpqRPMTrapUPSOutputOverloadClearedA UPS device is reporting an overload condition.
Recommendations:
1. Reduce the load on the UPS by moving some of the load to another UPS.
2. Consider moving to a larger UPS to support the current load. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20015 |
cpqRPMTrapUPSBatteryDepletedA UPS device is a depleted battery. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20022 |
cpqRPMTrapUPSBatteryLevelNormalA UPS device is reporting low battery.
Recommendations:
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. When utility power is restored, charge the battery to it's full capacity.
If the battery level continues to decrease, the UPS will not be able to sustain the output load! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20023 |
cpqRPMTrapUPSOnBypassA UPS device is being bypassed. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20032 |
cpqRPMTrapUPSTemperatureLowA UPS device is reporting temperature blow minimum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20101 |
cpqRPMTrapUPSTemperatureHighA UPS device is reporting temperature above maximum threshold. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20102 |
cpqRPMTrapUPSTemperatureNormalA UPS device is reporting temperature is out of range.
Recommendations:
1. Check to make sure the UPS is in a well ventilated area.
2. Lower the ambient temperature in the area where the UPS is located. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20103 |
cpqRPMTrapUPSInternalFailureA UPS device is reporting a general UPS failure.
Recommendations:
1. Initiate a UPS self test.
2. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20111 |
cpqRPMTrapUPSInternalFailureClearedA UPS device is reporting a general UPS failure.
Recommendations:
1. Initiate a UPS self test.
2. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20112 |
cpqRPMTrapUPSBatteryFailureA UPS device is reporting a battery failure.
Recommendations:
1. Initiate a UPS self test.
2. If this error persists contact technical support.
3. Your battery may need to be replaced.
The UPS may not be capable of supporting it's load if utility power fails! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20121 |
cpqRPMTrapUPSBatteryFailureClearedA UPS device is reporting a battery failure.
Recommendations:
1. Initiate a UPS self test.
2. If this error persists contact technical support.
3. Your battery may need to be replaced.
The UPS may not be capable of supporting it's load if utility power fails! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20122 |
cpqRPMTrapUPSDiagnosticTestFailedA UPS device is reporting a diagnostic test failed.
Recommendations:
1. Your battery may need to be replaced.
2. If this error persists contact technical support.
3. The UPS may not be capable of supporting it's load if utility power fails! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20131 |
cpqRPMTrapUPSDiagnosticTestSucceededA UPS device is reporting a diagnostic test failed.
Recommendations:
1. Your battery may need to be replaced.
2. If this error persists contact technical support.
3. The UPS may not be capable of supporting it's load if utility power fails! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20132 |
cpqRPMTrapUPSInputUnderOverFreqInput (Utility) fault: measured input frequency is outside of either the upper or lower frequency limit specification for normal operation. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20141 |
cpqRPMTrapUPSInputUnderOverFreqClearedMeasured input frequency is normal TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20142 |
cppqRPMtrapUPSStartedOnBatteryA UPS device has been started while on battery power. AC input power is not present.
Recommendations:
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
If the UPS remains on battery for an extended time it will not be able to sustain the output load. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20151 |
cppqRPMtrapUPSStartedOnBatteryClearedA UPS device has been started while on battery power. AC input power is not present.
Recommendations:
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
If the UPS remains on battery for an extended time it will not be able to sustain the output load! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20152 |
cpqRPMTrapUPSBypassNotAvailableA UPS device is reporting bypass not avaliable.
Recommendations:
1. Initiate a UPS self test.
2. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20161 |
cpqRPMTrapUPSBypassNotAvailableClearedA UPS device is reporting bypass not avaliable.
Recommendations:
1. Initiate a UPS self test.
2. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20162 |
cpqRPMTrapUPSUtilityFailIndicates that the utility input power is not within predetermined limits.
This could be, but is not limited to, over voltage, under voltage, over frequency,
under frequency or over current. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20171 |
cpqRPMTrapUPSUtilityFailClearedIndicates that the utility input power is within predetermined limits. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20172 |
cpqRPMTrapUPSUtilityNotPresentIndicates that the utility input is not present. This differs from
alarm #57 in that the detected voltage is zero in this case. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20181 |
cpqRPMTrapUPSUtilityNotPresentClearedIndicates that the utility input is present. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20182 |
cpqRPMTrapUPSBypassManualTurnedOnThe bypass has been given a manual turn on command. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20191 |
cpqRPMTrapUPSBypassManualTurnedOffThe bypass has been given a manual turn off command. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20192 |
cpqRPMTrapUPSSiteWiringFaultA UPS device is reporting a fault in the input wiring, other than
Phase Rotation: e.g., Ground/Neutral reversed.
Recommendations:
1. Contact an electrician. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20201 |
cpqRPMTrapUPSSiteWiringNormalA UPS device is reporting a fault in the input wiring, other than
Phase Rotation: e.g., Ground/Neutral reversed.
Recommendations:
1. Contact an electrician. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.20202 |
cpqRPMtrapUPSTemperatureOutOfRangeA UPS device is reporting temperature is out of range.
Recommendations:
1. Check to make sure the UPS is in a well ventilated area.
2. Lower the ambient temperature in the area where the UPS is located. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21007 |
cpqRPMtrapUPSTemperatureOutOfRangeClearedA UPS device is reporting temperature is out of range.
Recommendations:
1. Check to make sure the UPS is in a well ventilated area.
2. Lower the ambient temperature in the area where the UPS is located. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21008 |
cpqRPMTrapUPSShutdownPendingA UPS device is reporting shutdown pending condition.
Recommendations:
1. Immediately restore power to the UPS.
The UPS will not continue to supply power to devices following the shutdown! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21011 |
cpqRPMTrapUPSShutdownPendingClearedA UPS device is reporting shutdown pending condition.
Recommendations:
1. Immediately restore power to the UPS.
The UPS will not continue to supply power to devices following the shutdown! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21012 |
cpqRPMTrapUPSShutdownImminentA UPS device is reporting a shutdown imminent condition.
Recommendations:
1. Immediately restore power to the UPS.
The UPS will not continue to supply power to devices following the shutdown! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21013 |
cpqRPMTrapUPSShutdownImminentClearedA UPS device is reporting a shutdown imminent condition.
Recommendations:
1. Immediately restore power to the UPS.
The UPS will not continue to supply power to devices following the shutdown! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21014 |
cpqRPMtrapUPSOutputoutofRangeA UPS device is reporting output voltage is out of Range.
Recommendations:
1. Initiate a UPS self test.
2. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21019 |
cpqRPMTrapUPSOutputVoltageNormalA UPS device is reporting output voltage is out of Range.
Recommendations:
1. Initiate a UPS self test.
2. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21020 |
cpqRPMtrapUPSInputOutofRangeA UPS device is reporting input voltage is out of range.
Recommendations:
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21021 |
cpqRPMtrapUPSInputOutofRangeClearedA UPS device is reporting input voltage is out of range.
Recommendations:
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21022 |
cpqRPMTrapUPSLossOfRedundancyA UPS device is reporting a loss of redundancy due to one of the following.
1. One or more of the Electronics Modules has failed
2. One or more of the electronics modules has been manually removed.
3. The amount of load on the UPS has increased to the point that the UPS
is no longer able to support an N+1 configuration.
Recommendations:
1. Check the UPS to see if one of the modules has failed.
2. Make sure that all modules are securely plugged in.
3. Reduce the load to return the N+1 configuration.
4. If the amount of load is now going to exceed and N+1 configuration
permanently, change the configuration on the front panel of the UPS
to Capacity instead of Parallel N+1. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21023 |
cpqRPMTrapUPSLossOfRedundancyClearedA UPS device is reporting a loss of redundancy due to one of the following.
1. One or more of the Electronics Modules has failed
2. One or more of the electronics modules has been manually removed.
3. The amount of load on the UPS has increased to the point that the UPS is no longer
able to support an N+1 configuration.
Recommendations:
1. Check the UPS to see if one of the modules has failed.
2. Make sure that all modules are securely plugged in.
3. Reduce the load to return the N+1 configuration.
4. If the amount of load is now going to exceed and N+1 configuration permanently,
change the configuration on the front panel of the UPS to Capacity instead of Parallel N+1. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21024 |
cpqRPMTrapUPSOnBuckA UPS device is reporting an On Buck condition due to the following.
1. Utility power has increased above recommended utility input levels.
Recommendation:
1. Contact an electrician. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21029 |
cpqRPMTrapUPSOnBoostA UPS device is reporting an On Boost condition due to the following.
1. Utility power has dropped below recommended utility input levels.
Recommendation:
1. Contact an electrician. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21031 |
cpqRPMTrapUPSManualLoadDumpedThe UPS has been powered off with user interaction. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21033 |
cpqRPMTrapUPSManualLoadDumpedClearedThe UPS has been powered off with user interaction. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21034 |
cpqRPMTrapUPSFanFailureA UPS device is reporting a fan failure has occurred.
Recommendations:
1. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21035 |
cpqRPMTrapUPSFanFailureClearedA UPS device is reporting a fan failure has occurred.
Recommendations:
1. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21036 |
cpqRPMTrapUPSEPOInitiatedA UPS device is reporting an Emergency Power Off (EPO) command has been
received to shutdown the UPS immediately with out delay. This command
may come from a local control panel or from a remote source.
Recommendations:
1. Turn the UPS on to reapply power to attached equipment. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21037 |
cpqRPMTrapUPSCheckBreakerA UPS device is reporting an output Breaker or Relay has failed or may be
stuck open or closed with this alarm.
Recommendations:
1. Check all breakers on the UPS.
2. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21041 |
cpqRPMTrapUPSCheckBreakerClearedA UPS device is reporting an output Breaker or Relay has failed or may be
stuck open or closed with this alarm.
Recommendations:
1. Check all breakers on the UPS.
2. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21042 |
cpqRPMTrapUPSCabinetDoorOpenA UPS device is reporting a cover panel has been removed while utility power is present.
Recommendations:
1. Reinstall all panels.
2. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21045 |
cpqRPMTrapUPSCabinetDoorOpenClearedA UPS device is reporting a cover panel has been removed while utility power is present.
Recommendations:
1. Reinstall all panels.
2. If this error persists contact technical support. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21046 |
cpqRPMtrapUPSBypassOnAutoA UPS device is operating in auto bypass mode.
Recommendations:
1. In bypass mode, the UPS cannot support devices if there is a power failure.
2. Once maintenance has been performed return the UPS to normal mode. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21047 |
cpqRPMtrapUPSBypassOnAutoClearedA UPS device is operating in auto bypass mode.
Recommendations:
1. In bypass mode, the UPS cannot support devices if there is a power failure.
2. Once maintenance has been performed return the UPS to normal mode. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21048 |
cpqRPMTrapUPSBatteriesDisconnectedA UPS device is reporting batteries are not connected to the UPS.
Recomendations:
1. Connect the UPS Batteries.
The UPS will not be capable of supporting it's load if the utility power fails! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21053 |
cpqRPMTrapUPSBatteriesDisconnectedClearedA UPS device is reporting batteries are not connected to the UPS.
Recomendations:
1. Connect the UPS Batteries.
The UPS will not be capable of supporting it's load if the utility power fails! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21054 |
cpqRPMTrapUPSBatteryLowA UPS device is reporting low battery.
Recommendations:
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. When utility power is restored, charge the battery to it's full capacity.
If the battery level continues to decrease, the UPS will not be able to sustain the output load! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21055 |
cpqRPMTrapUPSBatteryLowClearedA UPS device is reporting low battery.
Recommendations:
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
2. When utility power is restored, charge the battery to it's full capacity.
If the battery level continues to decrease, the UPS will not be able to sustain the output load! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21056 |
cpqRPMTrapUPSBatteryDischargedA UPS device is reporting batteries are completely discharged.
Recommendations:
1. Connect the UPS to utility power to charge the batteries.
The UPS will not be able to support it's load if the utility power fails! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21057 |
cpqRPMTrapUPSBatteryDischargedClearedA UPS device is reporting batteries are completely discharged.
Recommendations:
1. Connect the UPS to utility power to charge the batteries.
The UPS will not be able to support it's load if the utility power fails! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21058 |
cpqRPMtrapUPSBypassONManualA UPS device is operating in manual bypass mode.
Recommendations:
1. In bypass mode, the UPS cannot support devices if there is a power failure.
2. Once maintenance has been performed return the UPS to normal mode. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21059 |
cpqRPMtrapUPSBypassOffManualA UPS device is operating in manual bypass mode.
Recommendations:
1. In bypass mode, the UPS cannot support devices if there is a power failure.
2. Once maintenance has been performed return the UPS to normal mode. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21060 |
cpqRPMTrapUPSOnBatteryA UPS device is reporting on battery condition.
Recommendations:
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
If the UPS remains on battery for an extended time it will not be able to sustain the output load! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21063 |
cpqRPMTrapUPSOnUtilityPowerA UPS device is reporting on battery condition.
Recommendations:
1. Check to make sure the UPS is plugged into an outlet supplied with utility power.
If the UPS remains on battery for an extended time it will not be able to sustain the output load! TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.21064 |
cpqRPMTrapUPSDCStartOccurredThe UPS has been started on battery when AC input power is not present. This alarm is used to record the date and time of this event. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.29998 |
cpqRPMTrapUPSDCStartOccurredClearedThe UPS has been started on utility while AC input power is present. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.29999 |
cpqRPMTestTrapThis trap is sent to test SNMP setup. TRAP-TYPE .1.3.6.1.4.1.232.154.2.0.50001 |
cpqPMTraps OBJECT IDENTIFIER .1.3.6.1.4.1.232.154.3 |
cpqPMTrapCriticalA critical alarm has occurred. Action: Check the Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.154.3.0.1 |
cpqPMTrapWarningA warning alarm has occurred. Action: Check the Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.154.3.0.2 |
cpqPMTrapInformationAn information alarm has occurred. Action: Check the Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.154.3.0.3 |
cpqPMTrapClearedAn alarm has cleared. Action: Check the Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.154.3.0.4 |