Home/Catalog/CPQRPM-MIB

CPQRPM-MIB

Detailed view of the defined objects, syntax rules, and hierarchical paths.

133
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

133 total
Object Name
cpqRPM
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.154
RFC1213-MIB
Unknown
.1.3.6.1.4.1.232.154
cpqRPMTrapInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.154.1
cpqRPMTrapDescriptionText description of the event that caused the trap.ro
DisplayString
.1.3.6.1.4.1.232.154.1.1
cpqRPMTrapDeviceIdA unique numeric identifier for the device that caused the trap.ro
INTEGER
.1.3.6.1.4.1.232.154.1.2
cpqRPMTrapDeviceNameThe text name for the device.ro
DisplayString
.1.3.6.1.4.1.232.154.1.3
cpqRPMTrapDeviceAddressThe hostname or ip address for the device.ro
DisplayString
.1.3.6.1.4.1.232.154.1.4
cpqRPMTrapTypeIndicates the type of the event that caused the trap.ro
Enumeration
.1.3.6.1.4.1.232.154.1.5
cpqRPMTrapSeverityIndicates the severity of the event that caused the trap.ro
Enumeration
.1.3.6.1.4.1.232.154.1.6
cpqRPMTrapCodeA unique identifier for the alarm.ro
INTEGER
.1.3.6.1.4.1.232.154.1.7
cpqRPMTrapURLThe URL for the management software.ro
DisplayString
.1.3.6.1.4.1.232.154.1.8
cpqRPMTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.154.2
cpqRPMTrapDeviceConnectedA UPS device is reporting a Connection Lost due to one of the following. 1. The serial cable connected to the UPS has been unplugged. 2. The Network cable connected to the UPS has been unplugged. Recommendations: 1. Insure all cables are seated properly. 2. check you network to insure it is functioning properly. 3. If the UPS is serially connected insure that the Serial Relay Agent is installed and running.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.1
cpqRPMTrapConnectionLostA UPS device is reporting a Connection Lost due to one of the following. 1. The serial cable connected to the UPS has been unplugged. 2. The Network cable connected to the UPS has been unplugged. Recommendations: 1. Insure all cables are seated properly. 2. check you network to insure it is functioning properly. 3. If the UPS is serially connected insure that the Serial Relay Agent is installed and running.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.2
cpqRPMTrapLookupFailedCRPM failed to find an IP address for the device hostname.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.3
cpqRPMTrapConnectionFailedCRPM failed to connect to a device.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.4
cpqRPMTrapDeviceSettingsChangedDevice settings have been changed by a user.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.5
cpqRPMTrapCMCTemp1BelowMinA CMC device is reporting temperature 1 below minimum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10001
cpqRPMTrapCMCTemp1AboveWarnA CMC device is reporting temperature 1 above warning threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10002
cpqRPMTrapCMCTemp1AboveMaxA CMC device is reporting temperature 1 above maximum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10003
cpqRPMTrapCMCTemp1NormalA CMC device is reporting temperature 1 has returned to a normal temperature.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10004
cpqRPMTrapCMCTemp2BelowMinA CMC device is reporting temperature 2 below minimum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10005
cpqRPMTrapCMCTemp2AboveWarnA CMC device is reporting temperature 2 above warning threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10006
cpqRPMTrapCMCTemp2AboveMaxA CMC device is reporting temperature 2 above maximum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10007
cpqRPMTrapCMCTemp2NormalA CMC device is reporting temperature 2 has returned to a normal temperature.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10008
cpqRPMTrapCMCVoltUnderA CMC device is reporting voltage below minimum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10011
cpqRPMTrapCMCVoltOverA CMC device is reporting voltage above maximum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10012
cpqRPMTrapCMCVoltNormalA CMC device is reporting voltage has returned to normal.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10013
cpqRPMTrapCMCHmdtUnderA CMC device is reporting humidity below minimum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10021
cpqRPMTrapCMCHmdtOverA CMC device is reporting humidity above maximum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10022
cpqRPMTrapCMCHmdtNormalA CMC device is reporting humidity has returned to normal.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10023
cpqRPMTrapCMCSmokeDetectedA CMC device is reporting smoke detected.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10031
cpqRPMTrapCMCSmokeClearedA CMC device is reporting smoke cleared.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10032
cpqRPMTrapCMCShockDetectedA CMC device is reporting shock detected.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10041
cpqRPMTrapCMCShockClearedA CMC device is reporting shock cleared.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10042
cpqRPMTrapCMCAux1AlarmA CMC device has entered an alarm condition for auxiliary input 1.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10051
cpqRPMTrapCMCAux1ClearedA CMC device is reporting auxiliary input 1 alarm cleared.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10052
cpqRPMTrapCMCAux2AlarmA CMC device has entered an alarm condition for auxiliary input 2.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10053
cpqRPMTrapCMCAux2ClearedA CMC device is reporting auxiliary input 2 alarm cleared.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10054
cpqRPMTrapCMCInput1OpenedA CMC device is reporting input 1 has been opened.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10101
cpqRPMTrapCMCInput1ClosedA CMC device is reporting input 1 has been closed.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10102
cpqRPMTrapCMCInput2OpenedA CMC device is reporting input 2 has been opened.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10103
cpqRPMTrapCMCInput2ClosedA CMC device is reporting input 2 has been closed.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10104
cpqRPMTrapCMCInput3OpenedA CMC device is reporting input 3 has been opened.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10105
cpqRPMTrapCMCInput3ClosedA CMC device is reporting input 3 has been closed.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10106
cpqRPMTrapCMCInput4OpenedA CMC device is reporting input 4 has been opened.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10107
cpqRPMTrapCMCInput4ClosedA CMC device is reporting input 4 has been closed.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10108
cpqRPMTrapCMCLockset1UnlockedA CMC device is reporting lockset 1 has been unlocked.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10111
cpqRPMTrapCMCLockset1FailedToLockA CMC device is reporting lockset 1 has failed to lock.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10112
cpqRPMTrapCMCLockset1ErrorA CMC device is reporting an error with lockset 1.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10113
cpqRPMTrapCMCLockset1LockedA CMC device is reporting lockset 1 has been locked.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10114
cpqRPMTrapCMCLockset2UnlockedA CMC device is reporting lockset 2 has been unlocked.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10116
cpqRPMTrapCMCLockset2FailedToLockA CMC device is reporting lockset 2 has failed to lock.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10117
cpqRPMTrapCMCLockset2ErrorA CMC device is reporting an error with lockset 2.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10118
cpqRPMTrapCMCLockset2LockedA CMC device is reporting lockset 2 has been locked.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10119
cpqRPMTrapCMCLockset1NormalA CMC device is reporting lockset 2 is normal.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10134
cpqRPMTrapCMCLockset2NormalA CMC device is reporting lockset 2 is normal.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.10135
cpqRPMTrapUPSInputVoltageBelowMinA UPS device is reporting input voltage below minimum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20001
cpqRPMTrapUPSInputVoltageAboveMaxA UPS device is reporting input voltage above maximum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20002
cpqRPMTrapUPSInputVoltageNormalA UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20003
cpqRPMTrapUPSOutputVoltageBelowMinA UPS device is reporting output voltage below minimum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20011
cpqRPMTrapUPSOutputVoltageAboveMaxA UPS device is reporting output voltage above maximum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20012
cpqRPMTrapUPSOutputOverloadA UPS device is reporting an overload condition. Recommendations: 1. Reduce the load on the UPS by moving some of the load to another UPS. 2. Consider moving to a larger UPS to support the current load.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20014
cpqRPMTrapUPSOutputOverloadClearedA UPS device is reporting an overload condition. Recommendations: 1. Reduce the load on the UPS by moving some of the load to another UPS. 2. Consider moving to a larger UPS to support the current load.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20015
cpqRPMTrapUPSBatteryDepletedA UPS device is a depleted battery.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20022
cpqRPMTrapUPSBatteryLevelNormalA UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility power is restored, charge the battery to it's full capacity. If the battery level continues to decrease, the UPS will not be able to sustain the output load!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20023
cpqRPMTrapUPSOnBypassA UPS device is being bypassed.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20032
cpqRPMTrapUPSTemperatureLowA UPS device is reporting temperature blow minimum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20101
cpqRPMTrapUPSTemperatureHighA UPS device is reporting temperature above maximum threshold.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20102
cpqRPMTrapUPSTemperatureNormalA UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temperature in the area where the UPS is located.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20103
cpqRPMTrapUPSInternalFailureA UPS device is reporting a general UPS failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20111
cpqRPMTrapUPSInternalFailureClearedA UPS device is reporting a general UPS failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20112
cpqRPMTrapUPSBatteryFailureA UPS device is reporting a battery failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support. 3. Your battery may need to be replaced. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20121
cpqRPMTrapUPSBatteryFailureClearedA UPS device is reporting a battery failure. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support. 3. Your battery may need to be replaced. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20122
cpqRPMTrapUPSDiagnosticTestFailedA UPS device is reporting a diagnostic test failed. Recommendations: 1. Your battery may need to be replaced. 2. If this error persists contact technical support. 3. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20131
cpqRPMTrapUPSDiagnosticTestSucceededA UPS device is reporting a diagnostic test failed. Recommendations: 1. Your battery may need to be replaced. 2. If this error persists contact technical support. 3. The UPS may not be capable of supporting it's load if utility power fails!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20132
cpqRPMTrapUPSInputUnderOverFreqInput (Utility) fault: measured input frequency is outside of either the upper or lower frequency limit specification for normal operation.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20141
cpqRPMTrapUPSInputUnderOverFreqClearedMeasured input frequency is normal
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20142
cppqRPMtrapUPSStartedOnBatteryA UPS device has been started while on battery power. AC input power is not present. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20151
cppqRPMtrapUPSStartedOnBatteryClearedA UPS device has been started while on battery power. AC input power is not present. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20152
cpqRPMTrapUPSBypassNotAvailableA UPS device is reporting bypass not avaliable. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20161
cpqRPMTrapUPSBypassNotAvailableClearedA UPS device is reporting bypass not avaliable. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20162
cpqRPMTrapUPSUtilityFailIndicates that the utility input power is not within predetermined limits. This could be, but is not limited to, over voltage, under voltage, over frequency, under frequency or over current.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20171
cpqRPMTrapUPSUtilityFailClearedIndicates that the utility input power is within predetermined limits.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20172
cpqRPMTrapUPSUtilityNotPresentIndicates that the utility input is not present. This differs from alarm #57 in that the detected voltage is zero in this case.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20181
cpqRPMTrapUPSUtilityNotPresentClearedIndicates that the utility input is present.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20182
cpqRPMTrapUPSBypassManualTurnedOnThe bypass has been given a manual turn on command.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20191
cpqRPMTrapUPSBypassManualTurnedOffThe bypass has been given a manual turn off command.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20192
cpqRPMTrapUPSSiteWiringFaultA UPS device is reporting a fault in the input wiring, other than Phase Rotation: e.g., Ground/Neutral reversed. Recommendations: 1. Contact an electrician.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20201
cpqRPMTrapUPSSiteWiringNormalA UPS device is reporting a fault in the input wiring, other than Phase Rotation: e.g., Ground/Neutral reversed. Recommendations: 1. Contact an electrician.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.20202
cpqRPMtrapUPSTemperatureOutOfRangeA UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temperature in the area where the UPS is located.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21007
cpqRPMtrapUPSTemperatureOutOfRangeClearedA UPS device is reporting temperature is out of range. Recommendations: 1. Check to make sure the UPS is in a well ventilated area. 2. Lower the ambient temperature in the area where the UPS is located.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21008
cpqRPMTrapUPSShutdownPendingA UPS device is reporting shutdown pending condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21011
cpqRPMTrapUPSShutdownPendingClearedA UPS device is reporting shutdown pending condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21012
cpqRPMTrapUPSShutdownImminentA UPS device is reporting a shutdown imminent condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21013
cpqRPMTrapUPSShutdownImminentClearedA UPS device is reporting a shutdown imminent condition. Recommendations: 1. Immediately restore power to the UPS. The UPS will not continue to supply power to devices following the shutdown!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21014
cpqRPMtrapUPSOutputoutofRangeA UPS device is reporting output voltage is out of Range. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21019
cpqRPMTrapUPSOutputVoltageNormalA UPS device is reporting output voltage is out of Range. Recommendations: 1. Initiate a UPS self test. 2. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21020
cpqRPMtrapUPSInputOutofRangeA UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21021
cpqRPMtrapUPSInputOutofRangeClearedA UPS device is reporting input voltage is out of range. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. If the UPS remains on battery for an extended period of time it will not be able to sustain the load.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21022
cpqRPMTrapUPSLossOfRedundancyA UPS device is reporting a loss of redundancy due to one of the following. 1. One or more of the Electronics Modules has failed 2. One or more of the electronics modules has been manually removed. 3. The amount of load on the UPS has increased to the point that the UPS is no longer able to support an N+1 configuration. Recommendations: 1. Check the UPS to see if one of the modules has failed. 2. Make sure that all modules are securely plugged in. 3. Reduce the load to return the N+1 configuration. 4. If the amount of load is now going to exceed and N+1 configuration permanently, change the configuration on the front panel of the UPS to Capacity instead of Parallel N+1.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21023
cpqRPMTrapUPSLossOfRedundancyClearedA UPS device is reporting a loss of redundancy due to one of the following. 1. One or more of the Electronics Modules has failed 2. One or more of the electronics modules has been manually removed. 3. The amount of load on the UPS has increased to the point that the UPS is no longer able to support an N+1 configuration. Recommendations: 1. Check the UPS to see if one of the modules has failed. 2. Make sure that all modules are securely plugged in. 3. Reduce the load to return the N+1 configuration. 4. If the amount of load is now going to exceed and N+1 configuration permanently, change the configuration on the front panel of the UPS to Capacity instead of Parallel N+1.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21024
cpqRPMTrapUPSOnBuckA UPS device is reporting an On Buck condition due to the following. 1. Utility power has increased above recommended utility input levels. Recommendation: 1. Contact an electrician.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21029
cpqRPMTrapUPSOnBoostA UPS device is reporting an On Boost condition due to the following. 1. Utility power has dropped below recommended utility input levels. Recommendation: 1. Contact an electrician.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21031
cpqRPMTrapUPSManualLoadDumpedThe UPS has been powered off with user interaction.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21033
cpqRPMTrapUPSManualLoadDumpedClearedThe UPS has been powered off with user interaction.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21034
cpqRPMTrapUPSFanFailureA UPS device is reporting a fan failure has occurred. Recommendations: 1. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21035
cpqRPMTrapUPSFanFailureClearedA UPS device is reporting a fan failure has occurred. Recommendations: 1. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21036
cpqRPMTrapUPSEPOInitiatedA UPS device is reporting an Emergency Power Off (EPO) command has been received to shutdown the UPS immediately with out delay. This command may come from a local control panel or from a remote source. Recommendations: 1. Turn the UPS on to reapply power to attached equipment.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21037
cpqRPMTrapUPSCheckBreakerA UPS device is reporting an output Breaker or Relay has failed or may be stuck open or closed with this alarm. Recommendations: 1. Check all breakers on the UPS. 2. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21041
cpqRPMTrapUPSCheckBreakerClearedA UPS device is reporting an output Breaker or Relay has failed or may be stuck open or closed with this alarm. Recommendations: 1. Check all breakers on the UPS. 2. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21042
cpqRPMTrapUPSCabinetDoorOpenA UPS device is reporting a cover panel has been removed while utility power is present. Recommendations: 1. Reinstall all panels. 2. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21045
cpqRPMTrapUPSCabinetDoorOpenClearedA UPS device is reporting a cover panel has been removed while utility power is present. Recommendations: 1. Reinstall all panels. 2. If this error persists contact technical support.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21046
cpqRPMtrapUPSBypassOnAutoA UPS device is operating in auto bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21047
cpqRPMtrapUPSBypassOnAutoClearedA UPS device is operating in auto bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21048
cpqRPMTrapUPSBatteriesDisconnectedA UPS device is reporting batteries are not connected to the UPS. Recomendations: 1. Connect the UPS Batteries. The UPS will not be capable of supporting it's load if the utility power fails!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21053
cpqRPMTrapUPSBatteriesDisconnectedClearedA UPS device is reporting batteries are not connected to the UPS. Recomendations: 1. Connect the UPS Batteries. The UPS will not be capable of supporting it's load if the utility power fails!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21054
cpqRPMTrapUPSBatteryLowA UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility power is restored, charge the battery to it's full capacity. If the battery level continues to decrease, the UPS will not be able to sustain the output load!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21055
cpqRPMTrapUPSBatteryLowClearedA UPS device is reporting low battery. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. 2. When utility power is restored, charge the battery to it's full capacity. If the battery level continues to decrease, the UPS will not be able to sustain the output load!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21056
cpqRPMTrapUPSBatteryDischargedA UPS device is reporting batteries are completely discharged. Recommendations: 1. Connect the UPS to utility power to charge the batteries. The UPS will not be able to support it's load if the utility power fails!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21057
cpqRPMTrapUPSBatteryDischargedClearedA UPS device is reporting batteries are completely discharged. Recommendations: 1. Connect the UPS to utility power to charge the batteries. The UPS will not be able to support it's load if the utility power fails!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21058
cpqRPMtrapUPSBypassONManualA UPS device is operating in manual bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21059
cpqRPMtrapUPSBypassOffManualA UPS device is operating in manual bypass mode. Recommendations: 1. In bypass mode, the UPS cannot support devices if there is a power failure. 2. Once maintenance has been performed return the UPS to normal mode.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21060
cpqRPMTrapUPSOnBatteryA UPS device is reporting on battery condition. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21063
cpqRPMTrapUPSOnUtilityPowerA UPS device is reporting on battery condition. Recommendations: 1. Check to make sure the UPS is plugged into an outlet supplied with utility power. If the UPS remains on battery for an extended time it will not be able to sustain the output load!
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.21064
cpqRPMTrapUPSDCStartOccurredThe UPS has been started on battery when AC input power is not present. This alarm is used to record the date and time of this event.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.29998
cpqRPMTrapUPSDCStartOccurredClearedThe UPS has been started on utility while AC input power is present.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.29999
cpqRPMTestTrapThis trap is sent to test SNMP setup.
TRAP-TYPE
.1.3.6.1.4.1.232.154.2.0.50001
cpqPMTraps
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.154.3
cpqPMTrapCriticalA critical alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE
.1.3.6.1.4.1.232.154.3.0.1
cpqPMTrapWarningA warning alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE
.1.3.6.1.4.1.232.154.3.0.2
cpqPMTrapInformationAn information alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE
.1.3.6.1.4.1.232.154.3.0.3
cpqPMTrapClearedAn alarm has cleared. Action: Check the Trap Details for more information.
TRAP-TYPE
.1.3.6.1.4.1.232.154.3.0.4
CPQRPM-MIB - SNMP MIB Reference | MIBs Explorer