Home/Catalog/CPQPOWER-MIB

CPQPOWER-MIB

Detailed view of the defined objects, syntax rules, and hierarchical paths.

277
Objects
Active
Status
5
Dependencies

Imported Objects

Objects

277 total
Object Name
cpqPower
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165
RFC1213-MIB
Unknown
.1.3.6.1.4.1.232.165
trapCriticalA critical alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE
.1.3.6.1.4.1.232.165.0.1
trapWarningA warning alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE
.1.3.6.1.4.1.232.165.0.2
trapInformationAn informational alarm has occurred. Action: Check the Trap Details for more information.
TRAP-TYPE
.1.3.6.1.4.1.232.165.0.3
trapClearedAn alarm has cleared. Action: Check the Trap Details for more information.
TRAP-TYPE
.1.3.6.1.4.1.232.165.0.4
trapTestTest trap sent to a trap receiver to check proper reception of traps
TRAP-TYPE
.1.3.6.1.4.1.232.165.0.5
deviceTrapInitializationThis trap is sent each time a power device is initialized.
TRAP-TYPE
.1.3.6.1.4.1.232.165.0.6
powerDevice
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.1
trapInfo
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.1.1
trapCodeA number identifying the event for the trap that was sent. Mapped unique trap code per unique event to be used by ISEE's decoder ring.ro
INTEGER
.1.3.6.1.4.1.232.165.1.1.1
trapDescriptionA string identifying the event for that last trap that was sent.ro
DisplayString
.1.3.6.1.4.1.232.165.1.1.2
trapDeviceMgmtUrlA string contains the URL for the management software.ro
DisplayString
.1.3.6.1.4.1.232.165.1.1.3
trapDeviceDetailsA string details information about the UPS such as SN (serial number), PN (part number), and MN (Model Name).ro
DisplayString
.1.3.6.1.4.1.232.165.1.1.4
trapDeviceNameA string contains the name of the HP Management Module.ro
DisplayString
.1.3.6.1.4.1.232.165.1.1.5
managementModuleIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.1.2
deviceManufacturerThe device manufacturer.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.1.2.1
deviceModelThe device model.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.1.2.2
deviceFirmwareVersionThe device firmware version(s).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.1.2.3
deviceHardwareVersionThe device hardware version.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.1.2.4
deviceIdentNameA string identifying the device.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.1.2.5
devicePartNumberThe device part number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.1.2.6
deviceSerialNumberThe device serial number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.1.2.7
deviceMACAddressThe device MAC address.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.1.2.8
pdu
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.2
pduIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.2.1
numOfPduThe number of PDUs.ro
INTEGER
.1.3.6.1.4.1.232.165.2.1.1
pduIdentTableThe Aggregate Object with number of entries equal to NumOfPdu and including the PduIdent group.
SEQUENCE OF PduIdentEntry
.1.3.6.1.4.1.232.165.2.1.2
pduIdentEntryThe ident table entry containing the name, model, manufacturer, firmware version, part number, etc.
PduIdentEntry
.1.3.6.1.4.1.232.165.2.1.2.1
pduIdentIndexIndex for the PduIdentEntry table.ro
INTEGER
.1.3.6.1.4.1.232.165.2.1.2.1.1
pduNameThe string identify the device.rw
DisplayString
.1.3.6.1.4.1.232.165.2.1.2.1.2
pduModelThe Device Model.ro
DisplayString
.1.3.6.1.4.1.232.165.2.1.2.1.3
pduManufacturerThe Device Manufacturer Name (e.g. Hewlett-Packard).ro
DisplayString
.1.3.6.1.4.1.232.165.2.1.2.1.4
pduFirmwareVersionThe firmware revision level of the device.ro
DisplayString
.1.3.6.1.4.1.232.165.2.1.2.1.5
pduPartNumberThe device part number.ro
DisplayString
.1.3.6.1.4.1.232.165.2.1.2.1.6
pduSerialNumberThe deice serial number.ro
DisplayString
.1.3.6.1.4.1.232.165.2.1.2.1.7
pduStatusThe overall status of the device. A value of OK(2) indicates the device is operating normally. A value of degraded(3) indicates the device is operating with warning indicators. A value of failed(4) indicates the device is operating with critical indicators.ro
Enumeration
.1.3.6.1.4.1.232.165.2.1.2.1.8
pduControllableThis object indicates whether or not the device is controllable.ro
Enumeration
.1.3.6.1.4.1.232.165.2.1.2.1.9
pduInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.2.2
pduInputTableThe Aggregate Object with number of entries equal to NumOfPdu and including the PduInput group.
SEQUENCE OF PduInputEntry
.1.3.6.1.4.1.232.165.2.2.1
pduInputEntryThe input table entry containing the voltage and current for the PDU
PduInputEntry
.1.3.6.1.4.1.232.165.2.2.1.1
pduInputIndexIndex for the PduInputEntry table.ro
INTEGER
.1.3.6.1.4.1.232.165.2.2.1.1.1
inputVoltageThe measured input voltage from the PDU meters in volts.ro
INTEGER
.1.3.6.1.4.1.232.165.2.2.1.1.2
inputCurrentThe measured input current from the PDU meters in amps.ro
INTEGER
.1.3.6.1.4.1.232.165.2.2.1.1.3
pduOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.2.3
pduOutputTableThe Aggregate Object with number of entries equal to NumOfPdu and including the PduInput group.
SEQUENCE OF PduOutputEntry
.1.3.6.1.4.1.232.165.2.3.1
pduOutputEntryThe input table entry containing the name, heat load, current load, power load, firmware, etc.
PduOutputEntry
.1.3.6.1.4.1.232.165.2.3.1.1
pduOutputIndexIndex for the PduOutputEntry table.ro
INTEGER
.1.3.6.1.4.1.232.165.2.3.1.1.1
pduOutputLoadThe device output load in percent of rated capacity. A value of -1 will be returned if the heat load is unable to be measured.ro
INTEGER
.1.3.6.1.4.1.232.165.2.3.1.1.2
pduOutputHeatThe total heat load measured on the PDU in BTUs. A value of -1 will be returned if the heat load is unable to be measured.ro
INTEGER -- Units BTU
.1.3.6.1.4.1.232.165.2.3.1.1.3
pduOutputPowerThe total power load measured on the PDU in watts. A value of -1 will be returned if the power load is unable to be measured.ro
INTEGER -- Units Watts
.1.3.6.1.4.1.232.165.2.3.1.1.4
pduOutputNumBreakersThe number of breakers for the device. This variable indicates the number of rows in the breakers table.ro
INTEGER
.1.3.6.1.4.1.232.165.2.3.1.1.5
pduOutputBreakerTableList of breaker table entries. The number of entries is given by pduOutputNumBreakers .
SEQUENCE OF PduOutputBreakerEntry
.1.3.6.1.4.1.232.165.2.3.2
pduOutputBreakerEntryAn entry containing information applicable to an breaker.
PduOutputBreakerEntry
.1.3.6.1.4.1.232.165.2.3.2.1
breakerIndexThe breaker identifier.ro
INTEGER
.1.3.6.1.4.1.232.165.2.3.2.1.1
breakerVoltageThe breaker voltage in volts.ro
INTEGER -- UNITS Volts
.1.3.6.1.4.1.232.165.2.3.2.1.2
breakerCurrentThe breaker current draw in Amps.ro
INTEGER -- UNITS Amps
.1.3.6.1.4.1.232.165.2.3.2.1.3
breakerPercentLoadThe breaker load in percent.ro
INTEGER -- UNITS Percent
.1.3.6.1.4.1.232.165.2.3.2.1.4
breakerStatusThis object indicates the status of the breaker. A value of normal(1) indicates the breaker is operating normally. A value of overloadWarning(2) indicates the breaker has an overload warning. A value of overloadCritical(3) indicates the breaker is overloaded. A value of voltageRangeWarning(4) indicates the breaker voltage is out of tolerance by 10-20%. A value of voltageRangeCritical(5) indicates the breaker voltage is out of tolerance by more than 20%. Note: Overload status has priority over voltage tolerance status.ro
Enumeration
.1.3.6.1.4.1.232.165.2.3.2.1.5
ups
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3
upsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.1
upsIdentManufacturerThe UPS Manufacturer Name (e.g. Hewlett-Packard).ro
DisplayString
.1.3.6.1.4.1.232.165.3.1.1
upsIdentModelThe UPS Model;Part number;Serial number (e.g. HP R5500 XR;204451-B21;B00123456W).ro
DisplayString
.1.3.6.1.4.1.232.165.3.1.2
upsIdentSoftwareVersionsThe firmware revision level(s) of the UPS microcontroller(s).ro
DisplayString
.1.3.6.1.4.1.232.165.3.1.3
upsIdentOemCodeA binary code indicating vendor. This should be a ?0x0c? for HPro
INTEGER
.1.3.6.1.4.1.232.165.3.1.4
upsBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.2
upsBatTimeRemainingBattery run time in seconds before UPS turns off due to low battery.ro
INTEGER
.1.3.6.1.4.1.232.165.3.2.1
upsBatVoltageBattery voltage as reported by the UPS meters.ro
INTEGER
.1.3.6.1.4.1.232.165.3.2.2
upsBatCurrentBattery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery.ro
INTEGER (-2147483648..2147483647) -- UNITS Amp DC
.1.3.6.1.4.1.232.165.3.2.3
upsBatCapacityBattery percent charge.ro
INTEGER
.1.3.6.1.4.1.232.165.3.2.4
upsBatteryAbmStatusGives the status of the Advanced Battery Management; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage; batteryResting(4) is the state when the battery is fully charged and none of the other actions (charging/discharging/floating) is being done.ro
Enumeration
.1.3.6.1.4.1.232.165.3.2.5
upsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.3
upsInputFrequencyThe utility line frequency in tenths of Hz.ro
INTEGER
.1.3.6.1.4.1.232.165.3.3.1
upsInputLineBadsThe number of times the Input was out of tolerance in voltage or frequency.ro
Counter
.1.3.6.1.4.1.232.165.3.3.2
upsInputNumPhasesro
INTEGER
.1.3.6.1.4.1.232.165.3.3.3
upsInputTableThe Aggregate Object with number of entries equal to NumPhases and including the UpsInput group.
SEQUENCE OF UpsInputEntry
.1.3.6.1.4.1.232.165.3.3.4
upsInputEntryThe input table entry containing the current, voltage, etc.
UpsInputEntry
.1.3.6.1.4.1.232.165.3.3.4.1
upsInputPhaseThe number of the phase. Serves as index for input table.ro
INTEGER
.1.3.6.1.4.1.232.165.3.3.4.1.1
upsInputVoltageThe measured input voltage from the UPS meters in volts.ro
INTEGER
.1.3.6.1.4.1.232.165.3.3.4.1.2
upsInputCurrentThe measured input current from the UPS meters in amps.ro
INTEGER
.1.3.6.1.4.1.232.165.3.3.4.1.3
upsInputWattsThe measured input real power in watts.ro
INTEGER
.1.3.6.1.4.1.232.165.3.3.4.1.4
upsInputSourceThe present external source of input power. The enumeration none(2) indicates that there is no external source of power, for example, the UPS is On Battery (an internal source). The bypassFeed(4) can only be used when the Bypass source is known to be a separate utility feed than the primaryUtility(3).ro
Enumeration
.1.3.6.1.4.1.232.165.3.3.5
upsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.4
upsOutputLoadThe UPS output load in percent of rated capacity.ro
INTEGER
.1.3.6.1.4.1.232.165.3.4.1
upsOutputFrequencyThe measured UPS output frequency in tenths of Hz.ro
INTEGER
.1.3.6.1.4.1.232.165.3.4.2
upsOutputNumPhasesThe number of metered output phases, serves as the table index.ro
INTEGER
.1.3.6.1.4.1.232.165.3.4.3
upsOutputTableThe Aggregate Object with number of entries equal to NumPhases and including the UpsOutput group.
SEQUENCE OF UpsOutputEntry
.1.3.6.1.4.1.232.165.3.4.4
upsOutputEntryOutput Table Entry containing voltage, current, etc.
UpsOutputEntry
.1.3.6.1.4.1.232.165.3.4.4.1
upsOutputPhaseThe number {1..3} of the output phase.ro
INTEGER
.1.3.6.1.4.1.232.165.3.4.4.1.1
upsOutputVoltageThe measured output voltage from the UPS metering in volts.ro
INTEGER
.1.3.6.1.4.1.232.165.3.4.4.1.2
upsOutputCurrentThe measured UPS output current in amps.ro
INTEGER
.1.3.6.1.4.1.232.165.3.4.4.1.3
upsOutputWattsThe measured real output power in watts.ro
INTEGER
.1.3.6.1.4.1.232.165.3.4.4.1.4
upsOutputSourceThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.ro
Enumeration
.1.3.6.1.4.1.232.165.3.4.5
upsBypass
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.5
upsBypassFrequencyThe bypass frequency in tenths of Hz.ro
INTEGER
.1.3.6.1.4.1.232.165.3.5.1
upsBypassNumPhasesThe number of lines in the UPS bypass table.ro
INTEGER
.1.3.6.1.4.1.232.165.3.5.2
upsBypassTable
SEQUENCE OF UpsBypassEntry
.1.3.6.1.4.1.232.165.3.5.3
upsBypassEntryEntry in the UpsBypassTable.
UpsBypassEntry
.1.3.6.1.4.1.232.165.3.5.3.1
upsBypassPhaseThe Bypass Phase, index for the table.ro
INTEGER
.1.3.6.1.4.1.232.165.3.5.3.1.1
upsBypassVoltageThe measured UPS bypass voltage in volts.ro
INTEGER
.1.3.6.1.4.1.232.165.3.5.3.1.2
upsEnvironment
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.6
upsEnvAmbientTempThe reading of the ambient temperature in the vicinity of the UPS or SNMP agent.ro
INTEGER (-100..200) -- UNITS Degrees Centigrade
.1.3.6.1.4.1.232.165.3.6.1
upsEnvAmbientLowerLimitThe Lower Limit of the ambient temperature; if UpsEnvAmbientTemp falls below this value, the UpsAmbientTempBad alarm will occur.rw
INTEGER (-100..200) -- UNITS Degrees Centigrade
.1.3.6.1.4.1.232.165.3.6.2
upsEnvAmbientUpperLimitThe Upper Limit of the ambient temperature; if UpsEnvAmbientTemp rises above this value, the UpsAmbientTempBad alarm will occur. This value should be greater than UpsEnvAmbientLowerLimit.rw
INTEGER (-100..200) -- UNITS Degrees Centigrade
.1.3.6.1.4.1.232.165.3.6.3
upsEnvAmbientHumidityThe reading of the ambient humidity in the vicinity of the UPS or SNMP agent.ro
INTEGER
.1.3.6.1.4.1.232.165.3.6.4
upsEnvRemoteTempThe reading of a remote temperature sensor connected to the UPS or SNMP agent.ro
INTEGER (-100..200) -- UNITS Degrees Centigrade
.1.3.6.1.4.1.232.165.3.6.5
upsEnvRemoteHumidityThe reading of a remote humidity sensor connected to the UPS or SNMP agent.ro
INTEGER
.1.3.6.1.4.1.232.165.3.6.6
upsEnvNumContactsThe number of Contacts in the UpsContactsTable. This object indicates the number of rows in the UpsContactsTable.ro
INTEGER
.1.3.6.1.4.1.232.165.3.6.7
upsContactsTableA list of Contact Sensing table entries. The number of entries is given by the value of UpsEnvNumContacts.
SEQUENCE OF UpsContactsTableEntry
.1.3.6.1.4.1.232.165.3.6.8
upsContactsTableEntryAn entry containing information applicable to a particular Contact input.
UpsContactsTableEntry
.1.3.6.1.4.1.232.165.3.6.8.1
upsContactIndexThe Contact identifier; identical to the Contact Number.ro
INTEGER
.1.3.6.1.4.1.232.165.3.6.8.1.1
upsContactTypeThe normal state for this contact. The 'other' state is the Active state for generating the UpstdContactActiveNotice trap. If anyChange(3) is selected, then this trap is sent any time the contact changes to either Open or Closed. No traps are sent if the Contact is set to notUsed(4). In many cases, the configuration for Contacts may be done by other means, so this object may be read-only.rw
Enumeration
.1.3.6.1.4.1.232.165.3.6.8.1.2
upsContactStateThe current state of the Contact input; the value is based on the open/closed input state and the setting for UpsContactType. When entering the openWithNotice(3) and closedWithNotice(4) states, no entries added to the UpsAlarmTable, but the UpstdContactActiveNotice trap is sent.ro
Enumeration
.1.3.6.1.4.1.232.165.3.6.8.1.3
upsContactDescrA label identifying the Contact. This object should be set by the administrator.rw
DisplayString
.1.3.6.1.4.1.232.165.3.6.8.1.4
upsEnvRemoteTempLowerLimitThe Lower Limit of the remote temperature; if UpsEnvRemoteTemp falls below this value, the UpsRemoteTempBad alarm will occur.rw
INTEGER (-100..200) -- UNITS Degrees Centigrade
.1.3.6.1.4.1.232.165.3.6.9
upsEnvRemoteTempUpperLimitThe Upper Limit of the remote temperature; if UpsEnvRemoteTemp rises above this value, the UpsRemoteTempBad alarm will occur. This value should be greater than UpsEnvRemoteTempLowerLimit.rw
INTEGER (-100..200) -- UNITS Degrees Centigrade
.1.3.6.1.4.1.232.165.3.6.10
upsEnvRemoteHumidityLowerLimitThe Lower Limit of the remote humidity reading; if UpsEnvRemoteHumidity falls below this value, the UpsRemoteHumidityBad alarm will occur.rw
INTEGER
.1.3.6.1.4.1.232.165.3.6.11
upsEnvRemoteHumidityUpperLimitThe Upper Limit of the remote humidity reading; if UpsEnvRemoteHumidity rises above this value, the UpsRemoteHumidityBad alarm will occur. This value should be greater than UpsEnvRemoteHumidityLowerLimit.rw
INTEGER
.1.3.6.1.4.1.232.165.3.6.12
upsTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.7
upsTestBatterySetting this variable to startTest initiates the battery test. All other set values are invalid.rw
Enumeration
.1.3.6.1.4.1.232.165.3.7.1
upsTestBatteryStatusReading this enumerated value gives an indication of the UPS Battery test status.ro
Enumeration
.1.3.6.1.4.1.232.165.3.7.2
upsTestTrapSetting this variable to startTestTrap initiates a TrapTest is sent out from HPMM. All other set values are invalid.rw
Enumeration
.1.3.6.1.4.1.232.165.3.7.3
upsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.8
upsControlOutputOffDelaySetting this value to other than zero will cause the UPS output to turn off after the number of seconds. Setting it to 0 will cause an attempt to abort a pending shutdown.rw
INTEGER
.1.3.6.1.4.1.232.165.3.8.1
upsControlOutputOnDelaySetting this value to other than zero will cause the UPS output to turn on after the number of seconds. Setting it to 0 will cause an attempt to abort a pending startup.rw
INTEGER
.1.3.6.1.4.1.232.165.3.8.2
upsControlOutputOffTrapDelayWhen UpsControlOutputOffDelay reaches this value, a trap will be sent.rw
INTEGER
.1.3.6.1.4.1.232.165.3.8.3
upsControlOutputOnTrapDelayWhen UpsControlOutputOnDelay reaches this value, a UpsOutputOff trap will be sent.rwdeprecated
INTEGER
.1.3.6.1.4.1.232.165.3.8.4
upsControlToBypassDelaySetting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the UPS to not supply power to the load. Setting it to 0 will cause an attempt to abort a pending shutdown.rw
INTEGER
.1.3.6.1.4.1.232.165.3.8.5
upsLoadShedSecsWithRestartSetting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike UpsControlOutputOffDelay, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted. This is the preferred Control object to use when performing an On Battery OS Shutdown.rw
INTEGER
.1.3.6.1.4.1.232.165.3.8.6
upsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.9
upsConfigOutputVoltageThe nominal UPS Output voltage per phase in volts.ro
INTEGER
.1.3.6.1.4.1.232.165.3.9.1
upsConfigInputVoltageThe nominal UPS Input voltage per phase in volts.ro
INTEGER
.1.3.6.1.4.1.232.165.3.9.2
upsConfigOutputWattsThe nominal UPS available real power output in watts.ro
INTEGER
.1.3.6.1.4.1.232.165.3.9.3
upsConfigOutputFreqThe nominal output frequency in tenths of Hz.ro
INTEGER
.1.3.6.1.4.1.232.165.3.9.4
upsConfigDateAndTimeDate and time information for the UPS. Setting this variable will initiate a set UPS date and time to this value. Reading this variable will return the UPS time and date. This value is not referenced to sysUpTime. It is simply the clock value from the UPS real time clock. Format is as follows: MM/DD/YYYY:HH:MM:SS.rw
DisplayString
.1.3.6.1.4.1.232.165.3.9.5
upsConfigLowOutputVoltageLimitThe Lower limit for acceptable Output Voltage, per the UPS specifications.ro
INTEGER
.1.3.6.1.4.1.232.165.3.9.6
upsConfigHighOutputVoltageLimitThe Upper limit for acceptable Output Voltage, per the UPS specifications.ro
INTEGER
.1.3.6.1.4.1.232.165.3.9.7
upsRecep
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.10
upsNumReceptaclesThe number of independently controllable Receptacles, as described in the UpsRecepTable.ro
INTEGER
.1.3.6.1.4.1.232.165.3.10.1
upsRecepTableThe Aggregate Object with number of entries equal to NumReceptacles and including the UpsRecep group.
SEQUENCE OF UpsRecepEntry
.1.3.6.1.4.1.232.165.3.10.2
upsRecepEntryThe Recep table entry, etc.
UpsRecepEntry
.1.3.6.1.4.1.232.165.3.10.2.1
upsRecepIndexThe number of the Receptacle. Serves as index for Receptacle table.ro
INTEGER
.1.3.6.1.4.1.232.165.3.10.2.1.1
upsRecepStatusThe Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off, 4=Off w/Pending ON, 5=Unknown.ro
Enumeration
.1.3.6.1.4.1.232.165.3.10.2.1.2
upsRecepOffDelaySecsThe Delay until the Receptacle is turned Off. Setting this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending shutdown. When this object is set while the UPS is On Battery, it is not necessary to set UpsRecepOnDelaySecs, since the outlet will turn back on automatically when power is available again.rw
INTEGER (-1..2147483647) -- UNITS seconds
.1.3.6.1.4.1.232.165.3.10.2.1.3
upsRecepOnDelaySecsThe Delay until the Receptacle is turned On. Setting this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending restart.rw
INTEGER (-1..2147483647) -- UNITS seconds
.1.3.6.1.4.1.232.165.3.10.2.1.4
upsRecepAutoOffDelayThe delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 to 30 are valid, but probably innappropriate. The AutoOffDelay can be used to prioritize loads in the event of a prolonged power outage; less critical loads will turn off earlier to extend battery time for the more critical loads. If the utility power is restored before the AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off.rw
INTEGER (-1..32767) -- UNITS seconds
.1.3.6.1.4.1.232.165.3.10.2.1.5
upsRecepAutoOnDelaySeconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON. A value of -1 means that this Output should never be turned On automatically, but only when specifically commanded to do so. A value of 0 means that the Receptacle should come On immediately at power-up or for an On command.rw
INTEGER (-1..32767) -- UNITS seconds
.1.3.6.1.4.1.232.165.3.10.2.1.6
upsRecepShedSecsWithRestartSetting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike UpsRecepOffDelaySecs, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted.rw
INTEGER
.1.3.6.1.4.1.232.165.3.10.2.1.7
upsTopology
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.3.11
upsTopologyTypeValue which denotes the type of UPS by its power topology. Values are the same as those described in the XCP Topology block's Overall Topology field.ro
INTEGER
.1.3.6.1.4.1.232.165.3.11.1
upsTopoMachineCodeID Value which denotes the Compaq/HP model of the UPS for software. Values are the same as those described in the XCP Configuration block's Machine Code field.ro
INTEGER
.1.3.6.1.4.1.232.165.3.11.2
upsTopoUnitNumberIdentifies which unit and what type of data is being reported. A value of 0 means that this MIB information comes from the top-level system view (eg, manifold module or system bypass cabinet reporting total system output). Standalone units also use a value of 0, since they are the 'full system' view. A value of 1 or higher indicates the number of the module in the system which is reporting only its own data in the HP MIB objects.ro
INTEGER
.1.3.6.1.4.1.232.165.3.11.3
upsTopoPowerStrategyValue which denotes which Power Strategy is currently set for the UPS. The values are: highAlert(1) - The UPS shall optimize its operating state to maximize its power-protection levels. This mode will be held for at most 24 hours. standard(2) - Balanced, normal power protection strategy. UPS will not enter HE operating mode from this setting. enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to optimize its operating state to maximize its efficiency, when conditions change to permit it (as determined by the UPS). forceHighEfficiency(4) - If this value is permitted to be Set for this UPS, and if conditions permit, requires the UPS to enter High Efficiency mode now, without delay (for as long as utility conditions permit). After successfully set to forceHighEfficiency(4), UpsTopoPowerStrategy changes to value enableHighEfficiency(3). UpsOutputSource will indicate if the UPS status is actually operating in High Efficiency mode.rw
Enumeration
.1.3.6.1.4.1.232.165.3.11.4
pdr
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.4
pdrIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.4.1
pdrNameThe string identify the device.rw
DisplayString
.1.3.6.1.4.1.232.165.4.1.1
pdrModelThe Device Model.ro
DisplayString
.1.3.6.1.4.1.232.165.4.1.2
pdrManufacturerThe Device Manufacturer Name (e.g. Hewlett-Packard).ro
DisplayString
.1.3.6.1.4.1.232.165.4.1.3
pdrFirmwareVersionThe firmware revision level of the device.ro
DisplayString
.1.3.6.1.4.1.232.165.4.1.4
pdrPartNumberThe device part number.ro
DisplayString
.1.3.6.1.4.1.232.165.4.1.5
pdrSerialNumberThe PDR's serial number.ro
DisplayString
.1.3.6.1.4.1.232.165.4.1.6
pdrVARatingThe VA Rating of this PDR (all phases)ro
INTEGER
.1.3.6.1.4.1.232.165.4.1.7
pdrNominalOutputVoltageThe nominal Output Voltage may differ from the nominal Input Voltage if the PDR has an input transformerro
INTEGER
.1.3.6.1.4.1.232.165.4.1.8
pdrNumPhasesThe number of phases for this PDRro
INTEGER
.1.3.6.1.4.1.232.165.4.1.9
pdrNumPanelsThe number of panels or subfeeds in this PDRro
INTEGER
.1.3.6.1.4.1.232.165.4.1.10
pdrNumBreakersThe number of breakers in this PDRro
INTEGER
.1.3.6.1.4.1.232.165.4.1.11
pdrPanel
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.4.2
pdrPanelTableAggregate Object with number of entries equal to pdrNumPanels
SEQUENCE OF PdrPanelEntry
.1.3.6.1.4.1.232.165.4.2.1
pdrPanelEntryThe panel table entry containing all power parameters for each panel.
PdrPanelEntry
.1.3.6.1.4.1.232.165.4.2.1.1
pdrPanelIndexIndex for the pdrPanelEntry table.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.1
pdrPanelFrequencyThe present frequency reading for the panel voltage.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.2
pdrPanelPowerThe present power of the panel.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.3
pdrPanelRatedCurrentThe present rated current of the panel.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.4
pdrPanelMonthlyKWHThe accumulated KWH for this panel since the beginning of this calendar month or since the last reset.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.5
pdrPanelYearlyKWHThe accumulated KWH for this panel since the beginning of this calendar year or since the last reset.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.6
pdrPanelTotalKWHThe accumulated KWH for this panel since it was put into service or since the last reset.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.7
pdrPanelVoltageAThe measured panel output voltage.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.8
pdrPanelVoltageBThe measured panel output voltage.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.9
pdrPanelVoltageCThe measured panel output voltage.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.10
pdrPanelCurrentAThe measured panel output current.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.11
pdrPanelCurrentBThe measured panel output current.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.12
pdrPanelCurrentCThe measured panel output current.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.13
pdrPanelLoadAThe percentage of load is the ratio of each output current to the rated output current to the panel.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.14
pdrPanelLoadBThe percentage of load is the ratio of each output current to the rated output current to the panel.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.15
pdrPanelLoadCThe percentage of load is the ratio of each output current to the rated output current to the panel.ro
INTEGER
.1.3.6.1.4.1.232.165.4.2.1.1.16
pdrBreaker
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.4.3
pdrBreakerTableList of breaker table entries. The number of entries is given by pdrNumBreakers for this panel.
SEQUENCE OF PdrBreakerEntry
.1.3.6.1.4.1.232.165.4.3.1
pdrBreakerEntryAn entry containing information applicable to a particular output breaker of a particular panel.
PdrBreakerEntry
.1.3.6.1.4.1.232.165.4.3.1.1
pdrBreakerIndexThe index of breakers. 42 breakers in each panel, arranged in odd and even columnsro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.1
pdrBreakerPanelThe index of panel that these breakers are installed on.ro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.2
pdrBreakerNumPositionThe position of this breaker in the panel, 1-phase breaker or n-m breaker for 2-phase or n-m-k breaker for 3-phase.ro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.3
pdrBreakerNumPhasesThe number of phase for this particular breaker.ro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.4
pdrBreakerNumSequenceThe sequence of this breaker. i.e. 1 for single phase 1,2 for 2-phase or 1,2,3 for 3-phase.ro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.5
pdrBreakerRatedCurrentThe rated current in Amps for this particular breaker.ro
INTEGER -- UNITS 0.1 A
.1.3.6.1.4.1.232.165.4.3.1.1.6
pdrBreakerMonthlyKWHThe accumulated KWH for this breaker since the beginning of this calendar month or since the last reset.ro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.7
pdrBreakerYearlyKWHThe accumulated KWH for this breaker since the beginning of this calendar year or since the last reset.ro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.8
pdrBreakerTotalKWHThe accumulated KWH for this breaker since it was put into service or since the last reset.ro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.9
pdrBreakerCurrentThe measured output current for this breaker Current.ro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.10
pdrBreakerCurrentPercentThe ratio of output current over rated current for each breaker.ro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.11
pdrBreakerPowerThe power for this breaker in Watts.ro
INTEGER -- UNITS Watts
.1.3.6.1.4.1.232.165.4.3.1.1.12
pdrBreakerPercentWarningThe percentage of Warning set for this breaker.ro
INTEGER
.1.3.6.1.4.1.232.165.4.3.1.1.13
pdrBreakerPercentOverloadThe percentage of Overload set for this breaker.ro
INTEGER -- UNITS 0.1 Percent
.1.3.6.1.4.1.232.165.4.3.1.1.14
mpdu
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.5
mpduIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.5.1
mpduNumMPDUThe number of Modular PDUs (Core) detected.ro
INTEGER
.1.3.6.1.4.1.232.165.5.1.1
mpduIdentTableIndexed by mpduNumMPDU. So aggregate objects for each entry equal to mpduNumMPDU before go to the next entry. i.e if 4 MPDU detected, display 4 indexes, 4 Manufacturers, 4 Models..., start with 1.
SEQUENCE OF MpduIdentEntry
.1.3.6.1.4.1.232.165.5.1.2
mpduIdentEntryThe table entry containing the identifications of each MPDU as well as names of PDR panel, location of MPDU in a Data Center.
MpduIdentEntry
.1.3.6.1.4.1.232.165.5.1.2.1
mpduIdentIndexIndex for the MpduIdentEntry table. Start with 1ro
INTEGER
.1.3.6.1.4.1.232.165.5.1.2.1.1
mpduManufacturerThe Core PDU manufacturer.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.2
mpduModelThe Core PDU model, marketing name.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.3
mpduNameThe Core PDU name, descriptive name or hostnamero
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.4
mpduFirmwareVersionThe Core PDU firmware version(s).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.5
mpduHardwareVersionThe Core PDU hardware version.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.6
mpduPartNumberThe Core PDU part number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.7
mpduSerialNumberThe PDU external serial number.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.8
mpduUUIDThe PDU's UUID equals PN add SN.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.9
mpduIPThe PDU's assigned IP.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.10
mpduMACAddressThe Core PDU MAC address.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.11
mpduControlStatusThe Core PDU Control Status: master or slave units.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.12
mpduRegionThe PDU's Region: NA, Intl, Japan...ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.13
mpduTypeThe PDU's Type: Delta, Wye, single, Wye+lowline.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.14
mpduPowerRatingThe PDU's Power Rating in KVA (Name Plate). Value is presented in 1/100 of the KVA. i.e. read 1750 means 17.50 KVAro
DisplayString --UNITS 0.01 KVA
.1.3.6.1.4.1.232.165.5.1.2.1.15
mpduInputRatingThe PDU's Input Current Rating in A (Name Plate)ro
DisplayString --UNITS A
.1.3.6.1.4.1.232.165.5.1.2.1.16
mpduInputPlugThe PDU's Input Plug: IEC60309 516P6,NEMA L15-30P...ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.17
mpduNumBreakersThe number of breakers used in each MPDU (6 by default).ro
INTEGER
.1.3.6.1.4.1.232.165.5.1.2.1.18
mpduNumOutletThe number of outlets of each MPDU (6 by default).ro
INTEGER
.1.3.6.1.4.1.232.165.5.1.2.1.19
mpduUHeightThe MPDU U Height (1U by default).ro
INTEGER
.1.3.6.1.4.1.232.165.5.1.2.1.20
mpduRedundantStatusStatus of Core PDU in paired or not: Stand-alone or Redundant.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.1.2.1.21
mpduOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.5.2
mpduOutputTableIndexed by mpduNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU multiplies mpduNumOutlet) before go to the next entry. i.e if 4 MPDU detected, display 6x4 indexes, 6x4 OutputStatus, 6x4 OutputBreakerRating...start with 1.
SEQUENCE OF MpduOutputEntry
.1.3.6.1.4.1.232.165.5.2.1
mpduOutputEntryThe output table entry containing the voltage, current, PF, percent load, VA, Watts for the Modular PDU.
MpduOutputEntry
.1.3.6.1.4.1.232.165.5.2.1.1
mpduOutputIndexIndex for the MpduOutputEntry table.ro
INTEGER
.1.3.6.1.4.1.232.165.5.2.1.1.1
mpduOutputStatusThe overall status of the device: off, on, problem.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.2.1.1.2
mpduOutputBreakerRatingThe rating of each MPDU Output in Ampere.ro
INTEGER --UNITS A
.1.3.6.1.4.1.232.165.5.2.1.1.3
mpduOutputSmartDeviceA smart cord device detected: False, True.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.2.1.1.4
mpduOutputPercentLoadThe MPDU's each output load in percent of rated capacity. Value is presented in 1/10 of the percentage i.e. 125 is 12.5%. A value of -1 will be returned if the current is unable to be measured.ro
INTEGER
.1.3.6.1.4.1.232.165.5.2.1.1.5
mpduOutputVoltageThe measured output voltage from the PDU meters in volts. Value is presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value of -1 will be returned if the voltage is unable to be measured.ro
INTEGER
.1.3.6.1.4.1.232.165.5.2.1.1.6
mpduOutputCurrentThe measured output current from the PDU meters in amps. Value is presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value of -1 will be returned if the current is unable to be measured.ro
INTEGER
.1.3.6.1.4.1.232.165.5.2.1.1.7
mpduOutputPowerVAThe total VA load (VI) measured on the PDU in VA. A value of -1 will be returned if the power is unable to be calculated.ro
INTEGER -- Units VA
.1.3.6.1.4.1.232.165.5.2.1.1.8
mpduOutputPowerWattThe total power load measured on the PDU in Watts. A value of -1 will be returned if the power is unable to be calculated.ro
INTEGER -- Units Watts
.1.3.6.1.4.1.232.165.5.2.1.1.9
mpduOutputPowerFactorThe power factor is presented in 1/100 of the unit i.e. 98 is 0.98. A value of -1 will be returned if the power factor is unable to be measured.ro
INTEGER
.1.3.6.1.4.1.232.165.5.2.1.1.10
mpduOutputWarningThresholdReport the User-set threshhold limit for Warning in percentagero
INTEGER
.1.3.6.1.4.1.232.165.5.2.1.1.11
mpduOutputCriticalThresholdReport the User-set threshhold limit for Critical in percentagero
INTEGER
.1.3.6.1.4.1.232.165.5.2.1.1.12
mpduDeviceIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.5.3
mpduDeviceIdentTableIndexed by mpduNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU multiplies mpduNumOutlet) before go to the next entry. i.e if 4 MPDU detected, display 6x4 indexes, 6x4 mpduDeviceStatus, 6x4 DeviceUIDStatus...start with 1.
SEQUENCE OF MpduDeviceIdentEntry
.1.3.6.1.4.1.232.165.5.3.1
mpduDeviceIdentEntryThe ident table entry containing the name, model, manufacturer, firmware version, part number... for each smart device, null value for unknown device.
MpduDeviceIdentEntry
.1.3.6.1.4.1.232.165.5.3.1.1
mpduDeviceIdentIndexIndex is based on the total number of Smart Extension Bars plus smart devices (with smart cord i.e. blades) detected.ro
INTEGER
.1.3.6.1.4.1.232.165.5.3.1.1.1
mpduDeviceStatusThe overall status of the device: off, on, problem.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.3.1.1.2
mpduDeviceUIDStatusThe overall status of the device UID: off, on, blink.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.3.1.1.3
mpduDeviceNumOutletThe number of outlets of detected the device. This variable indicates the number of rows in the breakers table. Default is 5ro
INTEGER
.1.3.6.1.4.1.232.165.5.3.1.1.4
mpduDeviceUHeightThe U height of ext bar or device.ro
INTEGER
.1.3.6.1.4.1.232.165.5.3.1.1.5
mpduDevicePowerRatingThe device's Power Rating in VA. Enter null if not detected.ro
DisplayString
.1.3.6.1.4.1.232.165.5.3.1.1.6
mpduDeviceManufacturerThe Device Manufacturer Name (e.g. Hewlett-Packard). Enter null if not detected.ro
DisplayString
.1.3.6.1.4.1.232.165.5.3.1.1.7
mpduDeviceTypeThe Device's Type: Ext Bar, server, or network device...ro
DisplayString
.1.3.6.1.4.1.232.165.5.3.1.1.8
mpduDeviceModelThe Device Model is Managed or Non-managed Ext Bar. Enter null if not detected.ro
DisplayString
.1.3.6.1.4.1.232.165.5.3.1.1.9
mpduDeviceNameThe string identify the Device. i.e. 'BAR#1' (descriptive name) Enter null if not detected.ro
DisplayString
.1.3.6.1.4.1.232.165.5.3.1.1.10
mpduDeviceFirmwareVersionThe firmware revision level of Sm Ext Bar. Enter null if not detected.ro
DisplayString
.1.3.6.1.4.1.232.165.5.3.1.1.11
mpduDeviceHardwareVersionThe hardware version of Sm Ext Bar. Enter null if not detected.ro
DisplayString
.1.3.6.1.4.1.232.165.5.3.1.1.12
mpduDevicePartNumberThe device's part number. Enter null if not detected.ro
DisplayString
.1.3.6.1.4.1.232.165.5.3.1.1.13
mpduDeviceSerialNumberThe device's serial number. Enter null if not detectedro
DisplayString
.1.3.6.1.4.1.232.165.5.3.1.1.14
mpduDeviceUUIDThe device's UUID. Enter null if not detectedro
DisplayString
.1.3.6.1.4.1.232.165.5.3.1.1.15
mpduSmExtBarOutlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.232.165.5.4
mpduSmExtBarOutletTableIndexed by mpduDeviceNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU multiplies mpduNumOutlet multiplies mpduDeviceNumOutlet) before go to the next entry. i.e if 4 MPDU detected, display 5x6x4 indexes, 5x6x4 mpduSmExtBarOutletStatus, 5x6x4 mpduSmExtBarOutletUIDStatus...start with 1.
SEQUENCE OF MpduSmExtBarOutletEntry
.1.3.6.1.4.1.232.165.5.4.1
mpduSmExtBarOutletEntryEntries contain status, measurements for each outlet (no PowerVA) Display null if it can't be measured or no device detected.
MpduSmExtBarOutletEntry
.1.3.6.1.4.1.232.165.5.4.1.1
mpduSmExtBarOutletIndexThe Index of Smart Extension Bar.ro
INTEGER
.1.3.6.1.4.1.232.165.5.4.1.1.1
mpduSmExtBarOutletStatusThe overall status of the Smart Extension Bar's outlet: off, on, problem...ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.4.1.1.2
mpduSmExtBarOutletUIDStatusThe overall status of the Smart Extension Bar's UID: off, on, blink...ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.232.165.5.4.1.1.3
mpduSmExtBarOutletRatingSm Ext Bar Outlet's Rating in Amp. A value of -1 will be returned if the stick is unable to detect.ro
INTEGER -- UNITS A
.1.3.6.1.4.1.232.165.5.4.1.1.4
mpduSmExtBarOutletVoltageThe SM Ext Bar voltage in volts. Value is presented 1/10 of the Volt i.e. 2098 is 209.8 V. A value of -1 will be returned if the voltage is unable to be measured.ro
INTEGER -- UNITS 0.1 Volts
.1.3.6.1.4.1.232.165.5.4.1.1.5
mpduSmExtBarOutletCurrentThe SM Ext Bar current draw in Amps. Value is presented in 1/100 of the Ampere i.e. 127 is 1.27 A. A value of -1 will be returned if the current is unable to be measured.ro
INTEGER -- UNITS 0.01 Amps
.1.3.6.1.4.1.232.165.5.4.1.1.6
mpduSmExtBarOutletPowerWattThe Sm Ext Bar's Power measured in Watts. A value of -1 will be returned if the power is unable to be measured.ro
INTEGER -- UNITS Watts
.1.3.6.1.4.1.232.165.5.4.1.1.7
mpduSmExtBarOutletPowerFactorThe outlet's power factor in 0.01 unit. It is presented in 1/100 of the unit. i.e. 98 is 0.98. A value of -1 will be returned if the power factor is unable to be measured.ro
INTEGER
.1.3.6.1.4.1.232.165.5.4.1.1.8
mpduSmExtBarOutletDeviceNameThe Device (Blade/Server/Storage) Name that connects to this Sm Ext Bar. Enter null if not detectedro
DisplayString
.1.3.6.1.4.1.232.165.5.4.1.1.9
mpduSmExtBarOutletDeviceUUIDThe Device (Blade/Server/Storage) UUID that connects to this Sm Ext Bar. Enter null if not detectedro
DisplayString
.1.3.6.1.4.1.232.165.5.4.1.1.10
mpduSmExtBarOutletDeviceProductThe Device (Blade/Server/Storage) Model that connects to this Sm Ext Bar. Enter null if not detectedro
DisplayString
.1.3.6.1.4.1.232.165.5.4.1.1.11
mpduSmExtBarOutletDeviceIPThe Device (Blade/Server/Storage) IP of iLO that connects to this Sm Ext Bar. Enter null if not detectedro
DisplayString
.1.3.6.1.4.1.232.165.5.4.1.1.12
mpduSmExtBarOutletAutoDiscoveredBoolean values of 0 or 1. 1 means this Sm Ext Bar Outlet is able to get information from a blade with smart power supply (auto discovery is enabled)...ro
INTEGER
.1.3.6.1.4.1.232.165.5.4.1.1.13