CPQCMC-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for CPQCMC-MIB.
242
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
242 total| Object Name |
|---|
cpqCmc OBJECT IDENTIFIER .1.3.6.1.4.1.232.153 |
cpqCmcalarmTemp1The temperature at rack sensor 1 is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153001 |
cpqCmcalarmTemp2The temperature at rack sensor 2 is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153002 |
cpqCmcalarmFan1The status of Fan 1 has changed. Action: Refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153003 |
cpqCmcalarmFan2The status of Fan 2 has changed. Action: Refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153004 |
cpqCmcalarmVoltageThe AC voltage of the rack is outside the specified threshold. Action: Check the incoming power source and ensure all cables are inserted correctly. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153005 |
cpqCmcalarmHumidityThe humidity of the rack is outside the specified threshold. Action: Check the
air handling system for the rack and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153006 |
cpqCmcalarmInput1The door or sidepanel of the rack has been opened (access point #1). Action: Check for unauthorized intrusion and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153007 |
cpqCmcalarmInput2The door or sidepanel of the rack has been opened (access point #2). Action: Check for unauthorized intrusion and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153008 |
cpqCmcalarmInput3The door or sidepanel of the rack has been opened (access point #3). Action: Check for unauthorized intrusion and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153009 |
cpqCmcalarmInput4The door or sidepanel of the rack has been opened (access point #4). Action: Check for unauthorized intrusion and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153010 |
cpqCmcalarmLock1Rack door lock #1 alarm. Action: Ensure the door is completely closed and check for unauthorized intrusion and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153011 |
cpqCmcalarmLock2Rack door lock #2 alarm. Action: Ensure the door is completely closed and check for unauthorized intrusion and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153012 |
cpqCmcalarmSmokeThe rack smoke detector has detected smoke. Action: Investigate rack for an over temperature condition and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153013 |
cpqCmcalarmShockThe rack shock detector has detected a vibration to the rack. Action: Investigate rack. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153014 |
cpqCmcalarmAux1The rack auxiliary alarm input #1 has been triggered. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153015 |
cpqCmcalarmAux2The rack auxiliary alarm input #2 has been triggered. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153016 |
cpqCmcalarm1Alarm 1, set from Network management TRAP-TYPE .1.3.6.1.4.1.232.153.0.153017 |
cpqCmcalarm2Alarm 2, set from Network management TRAP-TYPE .1.3.6.1.4.1.232.153.0.153018 |
cpqCmcalarmLock1DevThe rack door locking device #1 has failed. Action: Check the device lock cable or failed battery and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153019 |
cpqCmcalarmLock2DevThe rack door locking device #2 has failed. Action: Check the device lock cable or failed battery and refer to Trap Details for more information. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153020 |
cpqCmcSetupChangedSetup of CMC has changed. TRAP-TYPE .1.3.6.1.4.1.232.153.0.153100 |
cpqCmcMibRev OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.1 |
cpqCmcMibRevMajorThe Major Revision level.
A change in the major revision level represents a major change
in the architecture of the MIB. A change in the major revision
level may indicate a significant change in the information,
correct interpretation of data may require a MIB document
with the same major revision level.ro INTEGER .1.3.6.1.4.1.232.153.1.1 |
cpqCmcMibRevMinorThe Minor Revision level.
A change in the minor revision level may represent some minor
additional support, no changes to any pre-existing information
has occurred.ro INTEGER .1.3.6.1.4.1.232.153.1.2 |
cpqCmcMibConditionThe overall condition (status) of the system (rack(s)) represented by
this MIB.
(2) OK
(3) a minor problem, warning condition (yellow LED on CMC)
(4) a major problem (red LED on CMC)ro Enumeration .1.3.6.1.4.1.232.153.1.3 |
cpqCmcComponent OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2 |
cpqCmcInterface OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.1 |
cpqCmcOsCommon OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.1.1 |
cpqCmcOsCommonPollFreqThe Insight Agent's polling frequency.
The frequency, in seconds, at which the Insight Agent requests
information from the device driver. A frequency of zero (0)
indicates that the Insight Agent retrieves the information upon
request of a management station, it does not poll the device
driver at a specific interval.rw INTEGER .1.3.6.1.4.1.232.153.2.1.1.1 |
cpqCmcDevice OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2 |
cpqCmcDeviceConditionCondition of CMC device,
(3) an overload of the 24V DC supply to the connected accessories occurred
(4) the overload-protection (fuse) has releasedro Enumeration .1.3.6.1.4.1.232.153.2.2.1 |
cpqCmcSetup OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2 |
cpqCmcSetupConfig OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1 |
cpqCmcSetupGeneral OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.1 |
cpqCmcsetLanguageLanguage of LCDrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.1.1 |
cpqCmcsetTempUnitUnit of all temperature values and thresholds, Celsius or Fahrenheitrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.1.2 |
cpqCmcsetAudibleAlarmAudible alarm in CMC unit:
(2): silencing with button on CMC is enabled
(3): silencing with button on CMC is disabled
(4): audible alarm is off (general).
On/off of audible alarm for each event is possible in cpqCmcsetupEvents-grouprw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.1.3 |
cpqCmcPasswordPassword to get access to terminal or LCDrw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.1.4 |
cpqCmcPasswordOptionEnable or disable password entry to get access to terminal or LCDrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.1.5 |
cpqCmcquitRelay1Enable or disable acknowledging currently active alarm relay 1
(with 'ENTER' on CMC).rw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.1.6 |
cpqCmcquitRelay2Enable or disable acknowledging currently active alarm relay 2
(with 'ENTER' on CMC).rw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.1.7 |
cpqCmclogicRelay1Logic of Relay 1: (2) Relay will pick up in case of an alarm
(3) Relay will release in case of an alarm
(4) not usedrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.1.8 |
cpqCmclogicRelay2Logic of Relay 2: (2) Relay will pick up in case of an alarm
(3) Relay will release in case of an alarm
(4) not usedrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.1.9 |
cpqCmcSetupEvents OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2 |
cpqCmcSetupTemp1 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.1 |
cpqCmcSetupTemp1AvailTemperature sensor:
(2) sensor available
(3) sensor not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.1.1 |
cpqCmcSetupTemp1RelaysWarnAlert handling of Alarm Relays in case of warning condition
of temperature sensor 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.1.2 |
cpqCmcSetupTemp1RelaysMaxAlert handling of Alarm Relays in case of max. alarm condition
of temperature sensor 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.1.3 |
cpqCmcSetupTemp1RelaysMinAlert handling of Alarm Relays in case of min. alarm condition
of temperature sensor 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.1.4 |
cpqCmcSetupTemp1AudibleAlarmWarnAlert handling of Audible Alarm of in case of warning condition
of temperature sensor 1:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.1.5 |
cpqCmcSetupTemp1AudibleAlarmMaxAlert handling of Audible Alarm of in case of max. alarm condition
of temperature sensor 1:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.1.6 |
cpqCmcSetupTemp1AudibleAlarmMinAlert handling of Audible Alarm of in case of min. alarm condition
of temperature sensor 1:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.1.7 |
cpqCmcSetupTemp2 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.2 |
cpqCmcSetupTemp2AvailTemperature sensor:
(2) sensor available
(3) sensor not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.2.1 |
cpqCmcSetupTemp2RelaysWarnAlert handling of Alarm Relays in case of warning condition
of temperature sensor 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.2.2 |
cpqCmcSetupTemp2RelaysMaxAlert handling of Alarm Relays in case of max. alarm condition
of temperature sensor 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.2.3 |
cpqCmcSetupTemp2RelaysMinAlert handling of Alarm Relays in case of min. alarm condition
of temperature sensor 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.2.4 |
cpqCmcSetupTemp2AudibleAlarmWarnAlert handling of Audible Alarm of in case of warning condition
of temperature sensor 2:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.2.5 |
cpqCmcSetupTemp2AudibleAlarmMaxAlert handling of Audible Alarm of in case of max. alarm condition
of temperature sensor 2:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.2.6 |
cpqCmcSetupTemp2AudibleAlarmMinAlert handling of Audible Alarm of in case of min. alarm condition
of temperature sensor 2:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.2.7 |
cpqCmcSetupFan1 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.3 |
cpqCmcSetupFan1AvailFan 1:
(2) Fan 1 available
(3) Fan 1 not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.3.1 |
cpqCmcSetupFan1RelaysAlert handling of Alarm Relays in case of alarm condition
of Fan 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.3.2 |
cpqCmcSetupFan1AudibleAlarmAlert handling of Audible Alarm of in case of alarm condition
of Fan 1:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.3.3 |
cpqCmcSetupFan2 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.4 |
cpqCmcSetupFan2AvailFan 2:
(2) Fan 2 available
(3) Fan 2 not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.4.1 |
cpqCmcSetupFan2RelaysAlert handling of Alarm Relays in case of alarm condition
of Fan 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.4.2 |
cpqCmcSetupFan2AudibleAlarmAlert handling of Audible Alarm of in case of alarm condition
of Fan 2:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.4.3 |
cpqCmcSetupVoltage OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.5 |
cpqCmcSetupVoltageAvailVoltage monitoring:
(2) available
(3) not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.5.1 |
cpqCmcSetupVoltageRelaysMaxAlert handling of Alarm Relays in case of max. alarm condition
of voltage monitoring:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.5.2 |
cpqCmcSetupVoltageRelaysMinAlert handling of Alarm Relays in case of min. alarm condition
of voltage monitoring:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.5.3 |
cpqCmcSetupVoltageAudibleAlarmMaxAlert handling of Audible Alarm of in case of max. alarm condition
of voltage monitoring:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.5.4 |
cpqCmcSetupVoltageAudibleAlarmMinAlert handling of Audible Alarm of in case of min. alarm condition
of voltage monitoring:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.5.5 |
cpqCmcSetupHumidity OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.6 |
cpqCmcSetupHumidityAvailHumidity sensor:
(2) available
(3) not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.6.1 |
cpqCmcSetupHumidityRelaysMaxAlert handling of Alarm Relays in case of max. alarm condition
of humidity monitoring:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.6.2 |
cpqCmcSetupHumidityRelaysMinAlert handling of Alarm Relays in case of min. alarm condition
of humidity monitoring:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.6.3 |
cpqCmcSetupHumidityAudibleAlarmMaxAlert handling of Audible Alarm of in case of max. alarm condition
of humidity monitoring:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.6.4 |
cpqCmcSetupHumidityAudibleAlarmMinAlert handling of Audible Alarm of in case of min. alarm condition
of humidity monitoring:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.6.5 |
cpqCmcSetupInput1 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.7 |
cpqCmcSetupInput1AvailInput 1 sensor:
(2) available
(3) not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.7.1 |
cpqCmcSetupInput1RelaysAlert handling of Alarm Relays in case of a warning condition
of Input 1 (Door/Sidewall open):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.7.2 |
cpqCmcSetupInput1AudibleAlarmAlert handling of Audible Alarm of in case of a warning condition
of Input 1 (Door/Sidewall open):
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.7.3 |
cpqCmcSetupInput1FansOffFan switching off if Door/Sidewall 1 is opened:
(2) both fans would be switched off
(3) only fan1 will be switched off
(4) only fan2 will be switched off
(5) no fan will be switched offrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.7.4 |
cpqCmcSetupInput1ShockSensorShock sensor function if Door/Sidewall 1 is opened:
(2) Shock Sensor is off (disabled)
(3) Shock Sensor is on (enabled)rw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.7.5 |
cpqCmcSetupInput1DescriptionDescriptional text of Input1rw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.2.7.6 |
cpqCmcSetupInput1LockDoor/Sidewall 1 is locked by:
(2) no locking device
(3) locking device 1
(4) locking device 2
(5) both locking devicesrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.7.7 |
cpqCmcSetupInput2 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.8 |
cpqCmcSetupInput2AvailInput 2 sensor:
(2) available
(3) not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.8.1 |
cpqCmcSetupInput2RelaysAlert handling of Alarm Relays in case of a warning condition
of Input 2 (Door/Sidewall open):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.8.2 |
cpqCmcSetupInput2AudibleAlarmAlert handling of Audible Alarm of in case of a warning condition
of Input 2 (Door/Sidewall open):
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.8.3 |
cpqCmcSetupInput2FansOffFan switching off if Door/Sidewall 2 is opened:
(2) both fans would be switched off
(3) only fan1 will be switched off
(4) only fan2 will be switched off
(5) no fan will be switched offrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.8.4 |
cpqCmcSetupInput2ShockSensorShock sensor function if Door/Sidewall 2 is opened:
(2) Shock Sensor is off (disabled)
(3) Shock Sensor is on (enabled)rw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.8.5 |
cpqCmcSetupInput2DescriptionDescriptional text of Input2rw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.2.8.6 |
cpqCmcSetupInput2LockDoor/Sidewall 2 is locked by:
(2) no locking device
(3) locking device 1
(4) locking device 2
(5) both locking devicesrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.8.7 |
cpqCmcSetupInput3 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.9 |
cpqCmcSetupInput3AvailInput 3 sensor:
(2) available
(3) not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.9.1 |
cpqCmcSetupInput3RelaysAlert handling of Alarm Relays in case of a warning condition
of Input 3 (Door/Sidewall open):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.9.2 |
cpqCmcSetupInput3AudibleAlarmAlert handling of Audible Alarm of in case of a warning condition
of Input 3 (Door/Sidewall open):
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.9.3 |
cpqCmcSetupInput3FansOffFan switching off if Door/Sidewall 3 is opened:
(2) both fans would be switched off
(3) only fan1 will be switched off
(4) only fan2 will be switched off
(5) no fan will be switched offrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.9.4 |
cpqCmcSetupInput3ShockSensorShock sensor function if Door/Sidewall 3 is opened:
(2) Shock Sensor is off (disabled)
(3) Shock Sensor is on (enabled)rw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.9.5 |
cpqCmcSetupInput3DescriptionDescriptional text of Input3rw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.2.9.6 |
cpqCmcSetupInput3LockDoor/Sidewall 3 is locked by:
(2) no locking device
(3) locking device 1
(4) locking device 2
(5) both locking devicesrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.9.7 |
cpqCmcSetupInput4 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.10 |
cpqCmcSetupInput4AvailInput 4 sensor:
(2) available
(3) not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.10.1 |
cpqCmcSetupInput4RelaysAlert handling of Alarm Relays in case of a warning condition
of Input 4 (Door/Sidewall open):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.10.2 |
cpqCmcSetupInput4AudibleAlarmAlert handling of Audible Alarm of in case of a warning condition
of Input 4 (Door/Sidewall open):
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.10.3 |
cpqCmcSetupInput4FansOffFan switching off if Door/Sidewall 4 is opened:
(2) both fans would be switched off
(3) only fan1 will be switched off
(4) only fan2 will be switched off
(5) no fan will be switched offrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.10.4 |
cpqCmcSetupInput4ShockSensorShock sensor function if Door/Sidewall 4 is opened:
(2) Shock Sensor is off (disabled)
(3) Shock Sensor is on (enabled)rw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.10.5 |
cpqCmcSetupInput4DescriptionDescriptional text of Input4rw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.2.10.6 |
cpqCmcSetupInput4LockDoor/Sidewall 4 is locked by:
(2) no locking device
(3) locking device 1
(4) locking device 2
(5) both locking devicesrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.10.7 |
cpqCmcSetupLock1 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.11 |
cpqCmcSetupLock1AvailDoor locking device 1:
(2) device available
(3) device not available, no alarm, if door is not lockedrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.11.1 |
cpqCmcSetupLock1RelaysAlert handling of Alarm Relays in case of an alarm condition
of Lock 1 (door not locked..):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.11.2 |
cpqCmcSetupLock1RelaysDeviceAlert handling of Alarm Relays in case of an alarm condition
of Locking device 1 (power fail, low battery...):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.11.3 |
cpqCmcSetupLock1AudibleAlarmAlert handling of Audible Alarm of in case of an alarm condition
of Lock 1:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.11.4 |
cpqCmcSetupLock1AudibleAlarmDeviceAlert handling of Audible Alarm of in case of an alarm condition
of Locking device 1 (power fail, low battery..):
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.11.5 |
cpqCmcSetupLock1TimeTime in seconds while the lock 1 is unlocked
after getting an unlock-commandrw INTEGER .1.3.6.1.4.1.232.153.2.2.2.1.2.11.6 |
cpqCmcSetupLock1PwrFailUnlockUnlock door in case of power fail of locking device:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signalrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.11.7 |
cpqCmcSetupLock1BattLowUnlockUnlock door in case of low battery of locking device:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signalrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.11.8 |
cpqCmcSetupLock1NetFailUnlockUnlock door in case of network failure:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signalrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.11.9 |
cpqCmcSetupLock1LifeFailUnlockUnlock door in case of lifecheck failure (connection CMC<->locking device):
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signalrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.11.10 |
cpqCmcSetupLock2 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.12 |
cpqCmcSetupLock2AvailDoor locking device 2:
(2) device available
(3) device not available, no alarm, if door is not lockedrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.12.1 |
cpqCmcSetupLock2RelaysAlert handling of Alarm Relays in case of an alarm condition
of Lock 2 (door not locked..):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.12.2 |
cpqCmcSetupLock2RelaysDeviceAlert handling of Alarm Relays in case of an alarm condition
of Locking device 2 (power fail, low battery...):
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.12.3 |
cpqCmcSetupLock2AudibleAlarmAlert handling of Audible Alarm of in case of an alarm condition
of Lock 2:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.12.4 |
cpqCmcSetupLock2AudibleAlarmDeviceAlert handling of Audible Alarm of in case of an alarm condition
of Locking device 2 (power fail, low battery..):
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.12.5 |
cpqCmcSetupLock2TimeTime in seconds while the lock 2 is unlocked
after getting an unlock-commandrw INTEGER .1.3.6.1.4.1.232.153.2.2.2.1.2.12.6 |
cpqCmcSetupLock2PwrFailUnlockUnlock door in case of power fail of locking device:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signalrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.12.7 |
cpqCmcSetupLock2BattLowUnlockUnlock door in case of low battery of locking device:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signalrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.12.8 |
cpqCmcSetupLock2NetFailUnlockUnlock door in case of network failure:
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signalrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.12.9 |
cpqCmcSetupLock2LifeFailUnlockUnlock door in case of lifecheck failure (connection CMC<->locking device):
(2) disabled
(3) auto unlock the door
(4) unlock door with remote signalrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.12.10 |
cpqCmcSetupSmoke OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.13 |
cpqCmcSetupSmokeAvailSmoke sensor:
(2) available
(3) not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.13.1 |
cpqCmcSetupSmokeRelaysAlert handling of Alarm Relays in case of an alarm condition
of Smoke Sensor:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.13.2 |
cpqCmcSetupSmokeAudibleAlarmAlert handling of Audible Alarm of in case of an alarm condition
of Smoke Sensor:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.13.3 |
cpqCmcSetupSmokeFansOffFan switching off if in case of smoke-alarm:
(2) both fans would be switched off
(3) only fan1 will be switched off
(4) only fan2 will be switched off
(5) no fan will be switched offrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.13.4 |
cpqCmcSetupSmokeUnlockLock is unlocked in case of smoke-alarm:
(2) both locks will be unlocked
(3) only lock1 will be unlocked
(4) only lock2 will be unlocked
(5) no lock will be unlockedrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.13.5 |
cpqCmcSetupShock OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.14 |
cpqCmcSetupShockAvailShock sensor:
(2) available
(3) not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.14.1 |
cpqCmcSetupShockRelaysAlert handling of Alarm Relays in case of an alarm condition
of Shock Sensor:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.14.2 |
cpqCmcSetupShockAudibleAlarmAlert handling of Audible Alarm of in case of an alarm condition
of Shock Sensor:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.14.3 |
cpqCmcSetupShockSensitivitySensitivity of shock-sensor.
1 = low sensitivity, 10 = high sensitivityrw INTEGER .1.3.6.1.4.1.232.153.2.2.2.1.2.14.4 |
cpqCmcSetupAux1 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.15 |
cpqCmcSetupAux1AvailAux 1 sensor:
(2) available
(3) not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.15.1 |
cpqCmcSetupAux1RelaysAlert handling of Alarm Relays in case of an alarm condition
of Aux 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.15.2 |
cpqCmcSetupAux1AudibleAlarmAlert handling of Audible Alarm of in case of an alarm condition
of Aux 1:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.15.3 |
cpqCmcSetupAux1InputTypeType of other digital input (used for any digital signal):
(2) contact is normally open, no alarm if contact is open,
alarm if contact is closed
(3) contact is normally closed, no alarm if contact is closed,
alarm if contact is openrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.15.4 |
cpqCmcSetupAux1DescriptionDescriptional text of the digital input (Aux1)rw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.2.15.5 |
cpqCmcSetupAux1UnlockLock will be unlocked with Aux-Input 1:
(2) no lock will be unlocked
(3) only lock1 will be unlocked
(4) only lock2 will be unlocked
(5) both locks will be unlockedrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.15.6 |
cpqCmcSetupAux2 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.16 |
cpqCmcSetupAux2AvailAux 2 sensor:
(2) available
(3) not availablerw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.16.1 |
cpqCmcSetupAux2RelaysAlert handling of Alarm Relays in case of an alarm condition
of Aux 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.16.2 |
cpqCmcSetupAux2AudibleAlarmAlert handling of Audible Alarm of in case of an alarm condition
of Aux 2:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.16.3 |
cpqCmcSetupAux2InputTypeType of other digital input (used for any digital signal):
(2) contact is normally open, no alarm if contact is open,
alarm if contact is closed
(3) contact is normally closed, no alarm if contact is closed,
alarm if contact is openrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.16.4 |
cpqCmcSetupAux2DescriptionDescriptional text of the digital input (Aux2)rw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.2.16.5 |
cpqCmcSetupAux2UnlockLock will be unlocked with Aux-Input 2:
(2) no lock will be unlocked
(3) only lock1 will be unlocked
(4) only lock2 will be unlocked
(5) both locks will be unlockedrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.16.6 |
cpqCmcSetupAlarm1 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.17 |
cpqCmcSetupAlarm1RelaysAlert handling of Alarm Relays in case of an alarm condition
of Alarm 1:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.17.1 |
cpqCmcSetupAlarm1AudibleAlarmAlert handling of Audible Alarm of in case of an alarm condition
of Alarm 1:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.17.2 |
cpqCmcSetupAlarm1DescriptionDescriptional text of alarm 1rw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.2.17.3 |
cpqCmcSetupAlarm2 OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.2.18 |
cpqCmcSetupAlarm2RelaysAlert handling of Alarm Relays in case of an alarm condition
of Alarm 2:
(2) no switching of Relays
(3) Relay 1 will switch
(4) Relay 2 will switch
(5) both Relays will switchrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.18.1 |
cpqCmcSetupAlarm2AudibleAlarmAlert handling of Audible Alarm of in case of an alarm condition
of Alarm 2:
(2) Start Audible Alarm
(3) No Audible Alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.1.2.18.2 |
cpqCmcSetupAlarm2DescriptionDescriptional text of alarm 2rw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.2.18.3 |
cpqCmcSetupClock OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.1.3 |
cpqCmcSetupDateactual Date in format DD.MM.YYYYrw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.3.1 |
cpqCmcSetupTimeactual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)rw DisplayString .1.3.6.1.4.1.232.153.2.2.2.1.3.2 |
cpqCmcSetupThreshold OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.2 |
cpqCmcThresholdMaxTemp1Threshold value maximum temperature 1rw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.1 |
cpqCmcThresholdWarningTemp1Threshold value warning temperature 1rw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.2 |
cpqCmcThresholdMinTemp1Threshold value minimum temperature 1rw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.3 |
cpqCmcThresholdMaxTemp2Threshold value maximum temperature 2rw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.4 |
cpqCmcThresholdWarningTemp2Threshold value warning temperature 2rw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.5 |
cpqCmcThresholdMinTemp2Threshold value minimum temperature 2rw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.6 |
cpqCmcThresholdFan1Threshold Fan 1 in deg F or deg C, Fan 1 will start
if temperature 1 exceeds this valuerw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.7 |
cpqCmcThresholdFan1HysteresisHystersis of Fan 1, Fan 1 will stop if temperature 1 falls below
value of cpqCmcThresholdFan1 minus cpqCmcThresholdFan1Hysteresisrw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.8 |
cpqCmcThresholdFan2Threshold Fan 2 in deg F or deg C, Fan 2 will start
if temperature 2 exceeds this valuerw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.9 |
cpqCmcThresholdFan2HysteresisHystersis of Fan 2, Fan 2 will stop if temperature 2 falls below
value of cpqCmcThresholdFan2 minus cpqCmcThresholdFan2Hysteresisrw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.10 |
cpqCmcThresholdMaxVoltageThreshold high value Voltage alarmrw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.11 |
cpqCmcThresholdMinVoltageThreshold low value Voltage alarmrw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.12 |
cpqCmcThresholdMaxHumidityThreshold high value Humidity alarmrw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.13 |
cpqCmcThresholdMinHumidityThreshold low value Humidity alarmrw INTEGER .1.3.6.1.4.1.232.153.2.2.2.2.14 |
cpqCmcTraps OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.2.3 |
cpqCmcTrapTableNumberNumber of trapTable entries. The number of trap-receiversro INTEGER .1.3.6.1.4.1.232.153.2.2.2.3.1 |
cpqCmcTrapTableA list of trap-receiver entries SEQUENCE OF CpqCmcTrapEntry .1.3.6.1.4.1.232.153.2.2.2.3.2 |
cpqCmcTrapEntryEntries of trapTable CpqCmcTrapEntry .1.3.6.1.4.1.232.153.2.2.2.3.2.1 |
cpqCmcTrapIndexIndex for the trap-receiver-table. Its value ranges between
1 and the value of cpqCmcTrapTableNumberro INTEGER .1.3.6.1.4.1.232.153.2.2.2.3.2.1.1 |
cpqCmcTrapStatusEnable or disable trap receiverrw Enumeration .1.3.6.1.4.1.232.153.2.2.2.3.2.1.2 |
cpqCmcTrapIPaddressIP-address of trap-receiverrw DisplayString .1.3.6.1.4.1.232.153.2.2.2.3.2.1.3 |
cpqCmcValues OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.3 |
cpqCmcValueTemp1Actual temperature value of temperature sensor 1 in deg C or deg Fro INTEGER .1.3.6.1.4.1.232.153.2.2.3.1 |
cpqCmcValueTemp2Actual temperature value of temperature sensor 2 in deg C or deg Fro INTEGER .1.3.6.1.4.1.232.153.2.2.3.2 |
cpqCmcValueVoltageActual value of power supply (voltage monitoring and fans) in Vro INTEGER .1.3.6.1.4.1.232.153.2.2.3.3 |
cpqCmcValueHumidityActual value of humidity
0..100%ro INTEGER .1.3.6.1.4.1.232.153.2.2.3.4 |
cpqCmcValueOperatingTimeOperating time CMC-unitro DisplayString .1.3.6.1.4.1.232.153.2.2.3.5 |
cpqCmcStatus OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.4 |
cpqCmcStatusTemp1The status of temperature 1,
see thresholds of temperature 1:
(2) temperature normal
(3) temperature exceeds warning threshold
(4) temperature exceeds max. threshold
(5) temperature drops under min. threshold
(6) no sensor connected, not available
(7) error, sensor disconnectedro Enumeration .1.3.6.1.4.1.232.153.2.2.4.1 |
cpqCmcStatusTemp2The status of temperature 2,
see thresholds of temperature 2:
(2) temperature normal
(3) temperature exceeds warning threshold
(4) temperature exceeds max. threshold
(5) temperature drops under min. threshold
(6) no sensor connected, not available
(7) error, sensor disconnectedro Enumeration .1.3.6.1.4.1.232.153.2.2.4.2 |
cpqCmcStatusFan1The status of fan 1:
(2) fan is switched off by temperature sensor 1
(3) fan is switched on by temperature sensor 1
(4) fan is switched off by Manual Control (cpqCmcSetFan1)
(5) fan is switched on by Manual Control (cpqCmcSetFan1)
(6) fan is switched off because of smoke alarm
(7) fan is switched off because door is open
(8) no fan
(9) fan error, current monitoringro Enumeration .1.3.6.1.4.1.232.153.2.2.4.3 |
cpqCmcStatusFan2The status of fan 2:
(2) fan is switched off by temperature sensor 2
(3) fan is switched on by temperature sensor 2
(4) fan is switched off by Manual Control (cpqCmcSetFan2)
(5) fan is switched on by Manual Control (cpqCmcSetFan2)
(6) fan is switched off because of smoke alarm
(7) fan is switched off because door is open
(8) no fan
(9) fan error, current monitoringro Enumeration .1.3.6.1.4.1.232.153.2.2.4.4 |
cpqCmcStatusVoltageThe voltage-status,
see thresholds of power supply:
(2) voltage normal
(3) voltage exceeds max. threshold
(4) voltage drops under min. threshold
(5) no power connectedro Enumeration .1.3.6.1.4.1.232.153.2.2.4.5 |
cpqCmcStatusHumidityThe humidity-status,
see thresholds of humidity:
(2) humidity normal
(3) humidity exceeds max. threshold
(4) humidity drops under min. threshold
(5) no sensor connected, not available
(6) error, sensor disconnectedro Enumeration .1.3.6.1.4.1.232.153.2.2.4.6 |
cpqCmcStatusInput1The status of door/sidepanel 1, closed (2), open (3)
or no sensor connected (4)ro Enumeration .1.3.6.1.4.1.232.153.2.2.4.7 |
cpqCmcStatusInput2The status of door/sidepanel 2, closed (2), open (3)
or no sensor connected (4)ro Enumeration .1.3.6.1.4.1.232.153.2.2.4.8 |
cpqCmcStatusInput3The status of door/sidepanel 3, closed (2), open (3)
or no sensor connected (4)ro Enumeration .1.3.6.1.4.1.232.153.2.2.4.9 |
cpqCmcStatusInput4The status of door/sidepanel 4, closed (2), open (3)
or no sensor connected (4)ro Enumeration .1.3.6.1.4.1.232.153.2.2.4.10 |
cpqCmcStatusLock1LockThe status of door locking 1
(2) Door locking-device is activated, door is locked
(3) Door locking-device is not activated, door is unlocked by Network Management
(4) Door locking-device is not activated for x sec, time see
cpqCmcSetupLock1Time, door is unlocked by Network Management
(5) Door locking-device is not activated, door is unlocked because of Smoke alarm
(6) Door is unlocked from remote-signal
(7) Door locking-device is not activated, door is unlocked
because of Power Fail of locking device
(8) Door locking-device is not activated, door is unlocked
because of low Battery of locking device
(9) Door locking-device is not activated, door is unlocked
because of Network Fail
(10)Door locking-device is not activated, door is unlocked
because of connection fail, no connection locking device <-> CMC
(11)Door locking-device is ready to lock, lock will be activated after doors are closed
(12)Door locking-device is activated but door is not locked, alarm
(13)Configuration error, association door to locking-device missing
(14)Lock not installedro Enumeration .1.3.6.1.4.1.232.153.2.2.4.11 |
cpqCmcStatusLock2LockThe status of door locking 2
(2) Door locking-device is activated, door is locked
(3) Door locking-device is not activated, door is unlocked by Network Management
(4) Door locking-device is not activated for x sec, time see
cpqCmcSetupLock1Time, door is unlocked by Network Management
(5) Door locking-device is not activated, door is unlocked because of Smoke alarm
(6) Door is unlocked from remote-signal
(7) Door locking-device is not activated, door is unlocked
because of Power Fail of locking device
(8) Door locking-device is not activated, door is unlocked
because of low Battery of locking device
(9) Door locking-device is not activated, door is unlocked
because of Network Fail
(10)Door locking-device is not activated, door is unlocked
because of connection fail, no connection locking device <-> CMC
(11)Door locking-device is ready to lock, lock will be activated after doors are closed
(12)Door locking-device is activated but door is not locked, alarm
(13)Configuration error, association door to locking-device missing
(14)Lock not installedro Enumeration .1.3.6.1.4.1.232.153.2.2.4.12 |
cpqCmcStatusSmokeStatus smoke-sensor, OK (2), smoke detected (3)
or no sensor connected (4)ro Enumeration .1.3.6.1.4.1.232.153.2.2.4.13 |
cpqCmcStatusShockStatus Shock sensor, OK (2), shock detected (3)
or no sensor connected (4)ro Enumeration .1.3.6.1.4.1.232.153.2.2.4.14 |
cpqCmcStatusAux1Status aux. digital inputro Enumeration .1.3.6.1.4.1.232.153.2.2.4.15 |
cpqCmcStatusAux2Status aux. digital inputro Enumeration .1.3.6.1.4.1.232.153.2.2.4.16 |
cpqCmcStatusAlarm1Status of alarm 1, see cmpCmcsetAlarm1. This alarm can be set from
the Network management system. A descriptional text for this alarm
can be set in cpqCmcSetupAlarm1Description.ro Enumeration .1.3.6.1.4.1.232.153.2.2.4.17 |
cpqCmcStatusAlarm2Status of alarm 2, see cmpCmcsetAlarm2. This alarm can be set from
the Network management system. A descriptional text for this alarm
can be set in cpqCmcSetupAlarm2Description.ro Enumeration .1.3.6.1.4.1.232.153.2.2.4.18 |
cpqCmcStatusLock1DevThe status of door-locking device 1
(2) OK
(3) Power fail of door locking-device
(4) Low Battery of door locking-device
(5) Battery of door locking device needs to be replaced
(6) Battery missing, insert all batteries
(7) Connection CMC->door locking device lost
(8) Lock not installedro Enumeration .1.3.6.1.4.1.232.153.2.2.4.19 |
cpqCmcStatusLock2DevThe status of door-locking device 2
(2) OK
(3) Power fail of door locking-device
(4) Low Battery of door locking-device
(5) Battery of door locking device needs to be replaced
(6) Battery missing, insert all batteries
(6) Connection CMC->door locking device lost
(7) Lock not installedro Enumeration .1.3.6.1.4.1.232.153.2.2.4.20 |
cpqCmcControl OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.5 |
cpqCmcStatusAccessStatus access, for future userw DisplayString .1.3.6.1.4.1.232.153.2.2.5.1 |
cpqCmcSetLock1LockSet door locking device 1, see table
With this command the management-station can set the conditions for
the door locking device
(2) Door will be locked
(3) Door will be unlocked for a defined time,
time can be changed, see cpqCmcSetupLock1Time
(4) Door is generally unlocked
Locking and unlocking with this command can not be
enabled or disabled with cpqCmcSetLock1Key-commandrw Enumeration .1.3.6.1.4.1.232.153.2.2.5.2 |
cpqCmcSetLock1KeyEnable or disable unlocking of the rack-door with external components
like keypad or remote input.
With this command the management station can set the conditions for
unlocking the door:
(2) unlocking is disabled, no unlocking with keypad or remote input
(3) unlocking with keypad or remote signal (both) is enabled
(4) unlocking with keypad (only) is enabled
(5) unlocking with remote input (only) is enabled
Unlocking door with the cpqCmcSetLock1Lock-command does not depend
on this variablerw Enumeration .1.3.6.1.4.1.232.153.2.2.5.3 |
cpqCmcSetLock2LockSet door locking device 2, see table
With this command the management-station can set the conditions for
the door locking device
(2) Door will be locked
(3) Door will be unlocked for a defined time,
time can be changed, see cpqCmcSetupLock2Time
(4) Door is generally unlocked
Locking and unlocking with this command can not be
enabled or disabled with cpqCmcSetLock2Key-commandrw Enumeration .1.3.6.1.4.1.232.153.2.2.5.4 |
cpqCmcSetLock2KeyEnable or disable unlocking of the rack-door with external components
like keypad or remote input.
With this command the management-station can set the conditions for
unlocking the door:
(2) unlocking is disabled, no unlocking with keypad or remote input
(3) unlocking with keypad or remote signal (both) is enabled
(4) unlocking with keypad (only) is enabled
(5) unlocking with remote input (only) is enabled
Unlocking door with the cpqCmcSetDoor2-command does not depend
on this variablerw Enumeration .1.3.6.1.4.1.232.153.2.2.5.5 |
cpqCmcSetMessageSet message to CMC, for future userw DisplayString .1.3.6.1.4.1.232.153.2.2.5.6 |
cpqCmcSetAlarm1Is used to set an alarm in the CMC from the management-station.
With this command the management-station can i.e. switch on an
alarm-relay or the AudibleAlarm of the CMC.
Can be used for alert-handlingrw Enumeration .1.3.6.1.4.1.232.153.2.2.5.7 |
cpqCmcSetAlarm2Is used to set an alarm in the CMC from the management-station.
With this command the management-station can i.e. switch on an
alarm-relay or the AudibleAlarm of the CMC.
Can be used for alert-handlingrw Enumeration .1.3.6.1.4.1.232.153.2.2.5.8 |
cpqCmcSetFan1Is used for run and stop control of fan1.
(2) fan will run and stop according to temperature of sensor 1
and threshold of fan1
(3) fan will run independent of temperature and threshold
(4) fan will stop independent of temperature and threshold
(3) and (4) can be used for alert handling.rw Enumeration .1.3.6.1.4.1.232.153.2.2.5.9 |
cpqCmcSetFan2Is used for run and stop control of fan2.
(2) fan will run and stop according to temperature of sensor 2
and threshold of fan2
(3) fan will run independent of temperature and threshold
(4) fan will stop independent of temperature and threshold
(3) and (4) can be used for alert handlingrw Enumeration .1.3.6.1.4.1.232.153.2.2.5.10 |
cpqCmcSetQuitRelay1Status and quit of alarm relay 1.
(2) relay is switched because of an alarm
(3) relay is not switched, no alarm
(4) (set) will quit relay 1 in case of alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.5.11 |
cpqCmcSetQuitRelay2Status and quit of alarm relay 2.
(2) relay is switched because of an alarm
(3) relay is not switched, no alarm
(4) (set) will quit relay 2 in case of alarmrw Enumeration .1.3.6.1.4.1.232.153.2.2.5.12 |
cpqCmcLog OBJECT IDENTIFIER .1.3.6.1.4.1.232.153.2.2.6 |
cpqCmcLogsNumberNumber of Log-entriesro INTEGER .1.3.6.1.4.1.232.153.2.2.6.1 |
cpqCmcLogTableLog-table SEQUENCE OF CpqCmcLogEntry .1.3.6.1.4.1.232.153.2.2.6.2 |
cpqCmcLogEntryLog-table entries CpqCmcLogEntry .1.3.6.1.4.1.232.153.2.2.6.2.1 |
cpqCmcLogIndexIndex for the Log-table. Its value ranges between
1 and the value of cpqCmcLogsNumberro INTEGER .1.3.6.1.4.1.232.153.2.2.6.2.1.1 |
cpqCmcLogDateDate of log information.ro DisplayString .1.3.6.1.4.1.232.153.2.2.6.2.1.2 |
cpqCmcLogTimeTime of log information.ro DisplayString .1.3.6.1.4.1.232.153.2.2.6.2.1.3 |
cpqCmcLogTextLog information.ro DisplayString .1.3.6.1.4.1.232.153.2.2.6.2.1.4 |
cpqCmcLogClassStatus of log information.ro DisplayString .1.3.6.1.4.1.232.153.2.2.6.2.1.5 |