CPI-UNITY-MIB
AI MIB Summary
The CPI-UNITY-MIB module enables SNMP-based monitoring and management of Chatsworth Products eConnect UPS and power distribution units by exposing vendor-specific OIDs for operational status, configuration parameters, and environmental telemetry across all supported models.
The MIB module is used to register Chatsworth eConnect related SNMP OIDs for all models.
Copyright 2014-2019 Chatsworth Products, Inc. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Chatsworth Products, Inc makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Main OID:
products.1.3.6.1.4.1.30932.1
1066
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
1066 total| Object Name |
|---|
cpi OBJECT IDENTIFIER .1.3.6.1.4.1.30932 |
productsThe MIB module is used to register Chatsworth eConnect related
SNMP OIDs for all models.
Copyright 2014-2019 Chatsworth Products, Inc. All rights reserved.
Reproduction of this document is authorized on the condition
that the forgoing copyright notice is included.
This Specification is supplied 'AS IS' and Chatsworth Products, Inc
makes no warranty, either express or implied, as to the use,
operation, condition, or performance of the Specification. MODULE-IDENTITY .1.3.6.1.4.1.30932.1 |
cpiPDU OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1 |
systemInfo OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.1 |
versionSoftware Version.ro DisplayString .1.3.6.1.4.1.30932.1.1.1.1 |
modelCodeModel code for the PDU.ro DisplayString .1.3.6.1.4.1.30932.1.1.1.2 |
hwAddressPDU hardware MAC address.ro DisplayString .1.3.6.1.4.1.30932.1.1.1.3 |
metrics OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3 |
mcurrent OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.1 |
currentxy1XY1 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.1.1 |
currentyz1YZ1 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.1.2 |
currentzx1ZX1 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.1.3 |
currentxy2XY2 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.1.4 |
currentyz2YZ2 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.1.5 |
currentzx2ZX2 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.1.6 |
mvoltage OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.2 |
voltagexy1XY1 voltage in 1/10 volts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.2.1 |
voltageyz1YZ1 voltage in 1/10 volts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.2.2 |
voltagezx1ZX1 voltage in 1/10 volts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.2.3 |
voltagexy2XY2 voltage in 1/10 volts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.2.4 |
voltageyz2YZ2 voltage in 1/10 volts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.2.5 |
voltagezx2ZX2 voltage in 1/10 volts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.2.6 |
mpower OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.3 |
powerxy1XY1 power consumption in Watts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.3.1 |
poweryz1YZ1 power consumption in Watts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.3.2 |
powerzx1ZX1 power consumption in Watts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.3.3 |
powerxy2XY2 power consumption in Watts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.3.4 |
poweryz2YZ2 power consumption in Watts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.3.5 |
powerzx2ZX2 power consumption in Watts.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.3.6 |
mpowerFactor OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.4 |
powerFactxy1XY1 power factor x 100.ro Integer32 (-100..100) .1.3.6.1.4.1.30932.1.1.3.4.1 |
powerFactyz1YZ1 power factor x 100.ro Integer32 (-100..100) .1.3.6.1.4.1.30932.1.1.3.4.2 |
powerFactzx1ZX1 power factor x 100.ro Integer32 (-100..100) .1.3.6.1.4.1.30932.1.1.3.4.3 |
powerFactxy2XY2 power factor x 100.ro Integer32 (-100..100) .1.3.6.1.4.1.30932.1.1.3.4.4 |
powerFactyz2YZ2 power factor x 100.ro Integer32 (-100..100) .1.3.6.1.4.1.30932.1.1.3.4.5 |
powerFactzx2ZX2 power factor x 100.ro Integer32 (-100..100) .1.3.6.1.4.1.30932.1.1.3.4.6 |
receptacleCurrent OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.5 |
outlet1CurrentOutlet1 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.1 |
outlet2CurrentOutlet2 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.2 |
outlet3CurrentOutlet3 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.3 |
outlet4CurrentOutlet4 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.4 |
outlet5CurrentOutlet5 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.5 |
outlet6CurrentOutlet6 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.6 |
outlet7CurrentOutlet7 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.7 |
outlet8CurrentOutlet8 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.8 |
outlet9CurrentOutlet9 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.9 |
outlet10CurrentOutlet10 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.10 |
outlet11CurrentOutlet11 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.11 |
outlet12CurrentOutlet12 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.12 |
outlet13CurrentOutlet13 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.13 |
outlet14CurrentOutlet14 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.14 |
outlet15CurrentOutlet15 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.15 |
outlet16CurrentOutlet16 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.16 |
outlet17CurrentOutlet17 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.17 |
outlet18CurrentOutlet18 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.18 |
outlet19CurrentOutlet19 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.19 |
outlet20CurrentOutlet20 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.20 |
outlet21CurrentOutlet21 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.21 |
outlet22CurrentOutlet22 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.22 |
outlet23CurrentOutlet23 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.23 |
outlet24CurrentOutlet24 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.5.24 |
receptacleCurrentMapMap of receptacle currents in ascending order and delimited by space.ro DisplayString .1.3.6.1.4.1.30932.1.1.3.6 |
receptacleStatus OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.7 |
outlet1StateOutlet1 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.1 |
outlet2StateOutlet2 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.2 |
outlet3StateOutlet3 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.3 |
outlet4StateOutlet4 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.4 |
outlet5StateOutlet5 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.5 |
outlet6StateOutlet6 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.6 |
outlet7StateOutlet7 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.7 |
outlet8StateOutlet8 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.8 |
outlet9StateOutlet9 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.9 |
outlet10StateOutlet10 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.10 |
outlet11StateOutlet11 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.11 |
outlet12StateOutlet12 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.12 |
outlet13StateOutlet13 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.13 |
outlet14StateOutlet14 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.14 |
outlet15StateOutlet15 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.15 |
outlet16StateOutlet16 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.16 |
outlet17StateOutlet17 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.17 |
outlet18StateOutlet18 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.18 |
outlet19StateOutlet19 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.19 |
outlet20StateOutlet20 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.20 |
outlet21StateOutlet21 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.21 |
outlet22StateOutlet22 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.22 |
outlet23StateOutlet23 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.23 |
outlet24StateOutlet24 power state, 0=OFF, 1=ON.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.7.24 |
temperature OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.8 |
temperatureProbe1Probe 1 temperature in 1/100 degree Fahrenheit.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.8.1 |
temperatureProbe2Probe 2 temperature in 1/100 degree Fahrenheit.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.8.2 |
humidity OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.9 |
humidityProbe1Probe 1 humidity in 1/100 %.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.9.1 |
humidityProbe2Probe 2 humidity in 1/100 %.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.9.2 |
alarms OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.10 |
alarmsMaxMapMax threshold alarmed state bitmap: bit0=currA, bit1=currB, bit2=currC ...
bit6=voltA, bit7=voltB, bit8=voltC ...
bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2ro Integer32 .1.3.6.1.4.1.30932.1.1.3.10.1 |
alarmsMinMapMin threshold alarmed state bitmap: bit0=currA, bit1=currB, bit2=currC ...
bit6=voltA, bit7=voltB, bit8=voltC ...
bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2ro Integer32 .1.3.6.1.4.1.30932.1.1.3.10.2 |
alarmsWarnHiMapHigh threshold warning state bitmap: bit0=currA, bit1=currB, bit2=currC ...
bit6=voltA, bit7=voltB, bit8=voltC ...
bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2ro Integer32 .1.3.6.1.4.1.30932.1.1.3.10.3 |
alarmsWarnLoMapLow threshold warning state bitmap: bit0=currA, bit1=currB, bit2=currC ...
bit6=voltA, bit7=voltB, bit8=voltC ...
bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2ro Integer32 .1.3.6.1.4.1.30932.1.1.3.10.4 |
recep1To32AlarmsMaxMapMax threshold alarmed receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32ro Integer32 .1.3.6.1.4.1.30932.1.1.3.10.5 |
recep1To32AlarmsMinMapMin threshold alarmed receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32ro Integer32 .1.3.6.1.4.1.30932.1.1.3.10.7 |
recep1To32WarnHiMapHigh threshold warning receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32ro Integer32 .1.3.6.1.4.1.30932.1.1.3.10.9 |
recep1To32WarnLoMapLow threshold warning receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32ro Integer32 .1.3.6.1.4.1.30932.1.1.3.10.11 |
menergy OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.11 |
energyxy1sXY1 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.11.1 |
energyyz1sYZ1 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.11.2 |
energyzx1sZX1 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.11.3 |
energyxy2sXY2 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.11.4 |
energyyz2sYZ2 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.11.5 |
energyzx2sZX2 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.11.6 |
receptacleEnergy OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.12 |
receptacleEnergyoutlet1sOutlet1 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.1 |
receptacleEnergyoutlet2sOutlet2 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.2 |
receptacleEnergyoutlet3sOutlet3 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.3 |
receptacleEnergyoutlet4sOutlet4 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.4 |
receptacleEnergyoutlet5sOutlet5 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.5 |
receptacleEnergyoutlet6sOutlet6 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.6 |
receptacleEnergyoutlet7sOutlet7 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.7 |
receptacleEnergyoutlet8sOutlet8 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.8 |
receptacleEnergyoutlet9sOutlet9 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.9 |
receptacleEnergyoutlet10sOutlet10 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.10 |
receptacleEnergyoutlet11sOutlet11 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.11 |
receptacleEnergyoutlet12sOutlet12 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.12 |
receptacleEnergyoutlet13sOutlet13 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.13 |
receptacleEnergyoutlet14sOutlet14 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.14 |
receptacleEnergyoutlet15sOutlet15 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.15 |
receptacleEnergyoutlet16sOutlet16 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.16 |
receptacleEnergyoutlet17sOutlet17 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.17 |
receptacleEnergyoutlet18sOutlet18 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.18 |
receptacleEnergyoutlet19sOutlet19 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.19 |
receptacleEnergyoutlet20sOutlet20 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.20 |
receptacleEnergyoutlet21sOutlet21 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.21 |
receptacleEnergyoutlet22sOutlet22 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.22 |
receptacleEnergyoutlet23sOutlet23 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.23 |
receptacleEnergyoutlet24sOutlet24 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.1.3.12.24 |
mline OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.3.13 |
line1currLine 1 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.13.1 |
line2currLine 2 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.13.2 |
line3currLine 3 current draw in 1/100 Amps.ro Integer32 .1.3.6.1.4.1.30932.1.1.3.13.3 |
control OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.4 |
creceptacleControl OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.4.1 |
outlet1ONOFFTurn ON or OFF power to Outlet1, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.1 |
outlet2ONOFFTurn ON or OFF power to Outlet2, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.2 |
outlet3ONOFFTurn ON or OFF power to Outlet3, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.3 |
outlet4ONOFFTurn ON or OFF power to Outlet4, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.4 |
outlet5ONOFFTurn ON or OFF power to Outlet5, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.5 |
outlet6ONOFFTurn ON or OFF power to Outlet6, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.6 |
outlet7ONOFFTurn ON or OFF power to Outlet7, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.7 |
outlet8ONOFFTurn ON or OFF power to Outlet8, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.8 |
outlet9ONOFFTurn ON or OFF power to Outlet9, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.9 |
outlet10ONOFFTurn ON or OFF power to Outlet10, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.10 |
outlet11ONOFFTurn ON or OFF power to Outlet11, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.11 |
outlet12ONOFFTurn ON or OFF power to Outlet12, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.12 |
outlet13ONOFFTurn ON or OFF power to Outlet13, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.13 |
outlet14ONOFFTurn ON or OFF power to Outlet14, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.14 |
outlet15ONOFFTurn ON or OFF power to Outlet15, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.15 |
outlet16ONOFFTurn ON or OFF power to Outlet16, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.16 |
outlet17ONOFFTurn ON or OFF power to Outlet17, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.17 |
outlet18ONOFFTurn ON or OFF power to Outlet18, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.18 |
outlet19ONOFFTurn ON or OFF power to Outlet19, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.19 |
outlet20ONOFFTurn ON or OFF power to Outlet20, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.20 |
outlet21ONOFFTurn ON or OFF power to Outlet21, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.21 |
outlet22ONOFFTurn ON or OFF power to Outlet22, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.22 |
outlet23ONOFFTurn ON or OFF power to Outlet23, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.23 |
outlet24ONOFFTurn ON or OFF power to Outlet24, 1=ON, 0=OFF.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.1.24 |
receptacleReset OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.4.2 |
outlet1ResetReset power to Outlet1, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.1 |
outlet2ResetReset power to Outlet2, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.2 |
outlet3ResetReset power to Outlet3, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.3 |
outlet4ResetReset power to Outlet4, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.4 |
outlet5ResetReset power to Outlet5, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.5 |
outlet6ResetReset power to Outlet6, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.6 |
outlet7ResetReset power to Outlet7, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.7 |
outlet8ResetReset power to Outlet8, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.8 |
outlet9ResetReset power to Outlet9, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.9 |
outlet10ResetReset power to Outlet10, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.10 |
outlet11ResetReset power to Outlet11, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.11 |
outlet12ResetReset power to Outlet12, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.12 |
outlet13ResetReset power to Outlet13, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.13 |
outlet14ResetReset power to Outlet14, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.14 |
outlet15ResetReset power to Outlet15, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.15 |
outlet16ResetReset power to Outlet16, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.16 |
outlet17ResetReset power to Outlet17, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.17 |
outlet18ResetReset power to Outlet18, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.18 |
outlet19ResetReset power to Outlet19, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.19 |
outlet20ResetReset power to Outlet20, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.20 |
outlet21ResetReset power to Outlet21, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.21 |
outlet22ResetReset power to Outlet22, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.22 |
outlet23ResetReset power to Outlet23, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.23 |
outlet24ResetReset power to Outlet24, 1=reset.rw Integer32 .1.3.6.1.4.1.30932.1.1.4.2.24 |
receptacleCtrlMapMap of receptacle status in ascending order, 1=ON, 0=OFF.ro DisplayString .1.3.6.1.4.1.30932.1.1.4.3 |
chained OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.5 |
pduCountCount of number of PDUs in the chain.ro Integer32 .1.3.6.1.4.1.30932.1.1.5.1 |
pduMapTable map of PDU IDs in the chain, each ID consists of 4 bytes.ro OCTET STRING .1.3.6.1.4.1.30932.1.1.5.2 |
pduSelectSelects the PDUs in the chain for access.rw Integer32 .1.3.6.1.4.1.30932.1.1.5.3 |
pduNamelistList of PDU Names in the chain link, delimited by '|' and in matching order with pduMap.ro OCTET STRING .1.3.6.1.4.1.30932.1.1.5.4 |
cpiTraps OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.6 |
cpiSpecific OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.1.6.0 |
maxCurrentxy1Trap is sent when current in XY1 exceeds set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.1 |
maxCurrentyz1Trap is sent when current in YZ1 exceeds set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.2 |
maxCurrentzx1Trap is sent when current in ZX1 exceeds set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.3 |
maxCurrentxy2Trap is sent when current in XY2 exceeds set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.4 |
maxCurrentyz2Trap is sent when current in YZ2 exceeds set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.5 |
maxCurrentzx2Trap is sent when current in ZX2 exceeds set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.6 |
minCurrentxy1Trap is sent when current in XY1 drops below set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.7 |
minCurrentyz1Trap is sent when current in YZ1 drops below set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.8 |
minCurrentzx1Trap is sent when current in ZX1 drops below set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.9 |
minCurrentxy2Trap is sent when current in XY2 drops below set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.10 |
minCurrentyz2Trap is sent when current in YZ2 drops below set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.11 |
minCurrentzx2Trap is sent when current in ZX2 drops below set limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.12 |
maxVoltxy1Trap is sent when voltage in XY1 exceeds high limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.13 |
maxVoltyz1Trap is sent when voltage in YZ1 exceeds high limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.14 |
maxVoltzx1Trap is sent when voltage in ZX1 exceeds high limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.15 |
maxVoltxy2Trap is sent when voltage in XY2 exceeds high limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.16 |
maxVoltyz2Trap is sent when voltage in YZ2 exceeds high limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.17 |
maxVoltzx2Trap is sent when voltage in ZX2 exceeds high limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.18 |
minVoltxy1Trap is sent when voltage in XY1 drops below low limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.19 |
minVoltyz1Trap is sent when voltage in YZ1 drops below low limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.20 |
minVoltzx1Trap is sent when voltage in ZX1 drops below low limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.21 |
minVoltxy2Trap is sent when voltage in XY2 drops below low limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.22 |
minVoltyz2Trap is sent when voltage in YZ2 drops below low limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.23 |
minVoltzx2Trap is sent when voltage in ZX2 drops below low limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.24 |
maxTemperature1Trap is sent when temperature exceeds high limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.25 |
maxTemperature2Trap is sent when temperature exceeds high limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.26 |
minTemperature1Trap is sent when temperature drops below low limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.27 |
minTemperature2Trap is sent when temperature drops below low limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.28 |
maxHumidity1Trap is sent when humidity exceeds high limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.29 |
maxHumidity2Trap is sent when humidity exceeds high limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.30 |
minHumidity1Trap is sent when humidity drops below low limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.31 |
minHumidity2Trap is sent when humidity drops below low limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.32 |
changeLogTrap is sent when changes in current exceed the amount set in LOGDIFFERENCE. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.33 |
dataLogTrap is sent when the data logging interval time is reached NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.34 |
alarmChangeTrap is sent when all alarms have been resolved/cleared NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.1.6.0.35 |
cpiMIBConformance OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.2 |
cpiMIBCompliances OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.2.1 |
cpiMIBGroups OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.2.2 |
unity OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10 |
econnect OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1 |
configuration OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1 |
network OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.1 |
ipv4 OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.1.1 |
ipV4EnableControls whether the IPv4 network interface is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.1.1.1 |
pduIPSet or get the IPv4 address of the PDU.rw IpAddress .1.3.6.1.4.1.30932.1.10.1.1.1.1.2 |
autoIPControls whether the IPv4 address is retrieved from a
DHCP server or is set statically.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.1.1.3 |
autoDNSControls whether the DNS addresses are retrieved from
a DHCP server or are set statically.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.1.1.4 |
subnetMaskThe subnet mask associated with the IPv4 address of this
entry. The value of the mask is an IPv4 address with all the
network bits set to 1 and all the hosts bits set to 0.rw IpAddress .1.3.6.1.4.1.30932.1.10.1.1.1.1.5 |
gatewaySet or get the IPv4 address of the gateway router for the PDU.rw IpAddress .1.3.6.1.4.1.30932.1.10.1.1.1.1.6 |
dns1Set or get the IPv4 address of the first DNS entry for the PDU.rw IpAddress .1.3.6.1.4.1.30932.1.10.1.1.1.1.7 |
dns2Set or get the IPv4 address of the second DNS entry for the PDU.rw IpAddress .1.3.6.1.4.1.30932.1.10.1.1.1.1.8 |
dns3Set or get the IPv4 address of the third DNS entry for the PDU.rw IpAddress .1.3.6.1.4.1.30932.1.10.1.1.1.1.9 |
ipv6 OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.1.2 |
ipV6EnableControls whether the IPv6 network interface is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.1.2.1 |
linkLocalEnableControls whether the IPv6 link-local address is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.1.2.2 |
globalAddrEnableControls whether the IPv6 global address is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.1.2.3 |
pduIPv6Set or get the IPv6 address of the PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.1.2.4 |
autoIPv6Controls whether the IPv6 address is retrieved from a
DHCP server or is set statically.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.1.2.5 |
autoDNSv6Controls whether the DNS IPv6 address is retrieved from a
DHCP server or is set statically.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.1.2.6 |
subnetMaskv6The subnet mask associated with the IPv6 address of this
entry. The value of the mask is an IPv6 address with all the
network bits set to 1 and all the hosts bits set to 0.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.1.2.7 |
gatewayv6Set or get the IPv6 address of the gateway router for the PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.1.2.8 |
dns1v6Set or get the IPv6 address of the first DNS entry for the PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.1.2.9 |
dns2v6Set or get the IPv6 address of the second DNS entry for the PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.1.2.10 |
dns3v6Set or get the IPv6 address of the third DNS entry for the PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.1.2.11 |
time OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.1.3 |
rfcTimeServerSet or get the IP address of the RFC Time Server.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.1.3.1 |
ntpTimeServerSet or get the IP address of the NTP Time Server.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.1.3.2 |
interfaces OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.2 |
snmp OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.2.1 |
snmpEnableControls whether the SNMP network service is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.2.1.1 |
snmpHosts OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.2.1.2 |
snmpHostOnlyControls whether access to the SNMP service responsed to
the listed hosts (snmpHost1, snmpHost2, snmpHost3) or
to any host requesting data.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.2.1.2.1 |
snmpHost1Set or get the IPv4 address of the first host the SNMP service
will reply to.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.2.2 |
snmpHost2Set or get the IPv4 address of the second host the SNMP service
will reply to.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.2.3 |
snmpHost3Set or get the IPv4 address of the third host the SNMP service
will reply to.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.2.4 |
snmpHostIPv61Set or get the IPv6 address of the first host the SNMP service
will reply to.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.2.5 |
snmpHostIPv62Set or get the IPv6 address of the first host the SNMP service
will reply to.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.2.6 |
snmpHostIPV63Set or get the IPv6 address of the first host the SNMP service
will reply to.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.2.7 |
snmpQueryPortSet or get the port for SNMP query access.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.2.1.3 |
snmpTrapPortSet or get the port for SNMP traps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.2.1.4 |
snmpReadCommSet or get the SNMP Read Community.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.5 |
snmpWriteCommSet or get the SNMP Write Community.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.6 |
snmpUSMuserNameSet or get the SNMP USM User Name.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.7 |
snmpSecurityLevelSet or get the security Level for SNMP: 0 = v1, 1 = v2c, 2 = v3 no authentication,
3 = v3 with authentication only, 4 = v3 with authentication and privacyrw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.2.1.8 |
snmpAuthAlgoSet or get the Authentication Algorithm for SNMP.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.2.1.9 |
snmpPrivAlgoGet or get the Privacy Algorithm for SNMP.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.2.1.10 |
snmpAuthPasswdSet or Get the SNMP Authentication Password.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.2.1.11 |
snmpPrivPasswdSet or get the SNMP Privacy Password.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.2.1.12 |
snmpContextNameSet or get the SNMP Context Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.2.1.13 |
snmpEngineIDSet or get the SNMP Engine ID.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.2.1.14 |
snmpLocAuthKeySet or get the SNMP Local Authentication Key.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.2.1.15 |
snmpLocPrivKeySet or get the SNMP Local Privacy Key.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.2.1.16 |
snmpTrapHosts OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.2.1.17 |
snmpTrapHost1Set or get the IPv4 address of the first SNMP Trap Host.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.17.1 |
snmpTrapHost2Set or get the IPv4 address of the second SNMP Trap Host.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.17.2 |
snmpTrapHost3Set or get the IPv4 address of the third SNMP Trap Host.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.17.3 |
snmpTrapHostIPv61Set or get the IPv6 address of the first SNMP Trap Host.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.17.4 |
snmpTrapHostIPv62Set or get the IPv6 address of the second SNMP Trap Host.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.17.5 |
snmpTrapHostIPv63Set or get the IPv6 address of the third SNMP Trap Host.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.1.17.6 |
snmpControl OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.2.1.18 |
enableEASSNMPControlAllows the use of SNMP to open/close the door locks. It is recommended that this only be enabled with SNMP v3 configurations.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.2.1.18.5 |
http OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.2.2 |
enableWebControls whether the web interface is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.2.2.1 |
httpEnableControls whether the HTTP service is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.2.2.2 |
httpsEnableControls whether the HTTPS service is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.2.2.3 |
httpPortSet or get the port for unsecure HTTP access.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.2.2.4 |
httpsPortSet or get the port for secure HTTPS access.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.2.2.5 |
smtp OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.2.3 |
enableSMTPControls whether the mail notification service is enabled..rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.2.3.1 |
smtpSendPortSet or get the port for SMTP send.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.2.3.2 |
smtpReceivePortSet or get the port for SMTP Receive.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.2.3.3 |
smtpServerSet or get the IP address of the e-mail server.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.3.4 |
smtpUserNameSet or get the PDU e-mail user login name.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.3.5 |
smtpUserPasswdSet or get the PDU e-mail user login password.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.3.6 |
smtpEmailAddrSet or get the PDU e-mail address.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.2.3.7 |
smtpEmailDestination1Set or get the e-mail address of the first recipient.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.2.3.8 |
smtpEmailDestination2Set or get the e-mail address of the second recipient.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.2.3.9 |
smtpEmailDestination3Set or get the e-mail address of the third recipient.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.2.3.10 |
smtpServOptionsSet or get the SMTP server options.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.2.3.11 |
logging OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.3 |
logEnableControls whether the data logging feature is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.1 |
logIntervalSet or get the time interval in seconds for logging metrics (disabled if < 10).rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.3.2 |
logDifferenceSet or get the current difference in 1/100 Amps that triggers logging metrics.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.3.3 |
netservdLogControls sending the data logs to log server over network.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.4 |
autonetLogControls whether automatic transfer to log server every 6 hours is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.5 |
stdmeterdLogControls whether logging of branch, receptacle and environmental metrics is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.6 |
groupmeterdLogControls whether logging of grouped receptacle metrics is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.7 |
alarmdLogControls whether logging of alarm events is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.8 |
userlogindLogControl whether logging of user login events is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.9 |
usersetupdLogControl whether logging of user setup change events is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.10 |
fwupdatedLogControl whether the logging of firmware updates is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.11 |
setupchangedLogControl whether the logging of setup change events is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.12 |
recepchangedLogControl whether logging of receptacle state changes is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.13 |
pduopchangedLogControl whether logging of PDU operation and state changes is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.14 |
dLogCycleSet or get the time interval in minutes for internal data logging to occur.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.3.15 |
dLogFullWarnLevelSet or get the warning threshold for percentage of storage full (min=50, max=100).rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.3.16 |
netdLogServerSet or get the network address for the data server.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.3.17 |
netdLogPortSet or get the port used by the data server.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.3.18 |
netdLogUserSet or get the user name to access the data server.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.3.19 |
netdLogPasswdSet or get the user password to access the data server.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.3.20 |
netdLogDestdirGet or get the destination directory in the data server.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.3.21 |
netdLogOptionsGet or set the options string when accessing the data server.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.3.22 |
sysLogIdentityGet or set the identity to use with the syslog. The identity is an arbitrary identification string which syslog will prefix to each message. This is intended to identify the source of the message.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.3.23 |
sysLogFacilityGet or set the facility to use with the syslog. The facility argument is used to specify what type of program is logging the message.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.3.24 |
sysLogCentralServerAddrGet or set the IP address for the central syslog server.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.3.25 |
sysLogCentralServerPortGet or set the port for the central syslog server.rw INTEGER .1.3.6.1.4.1.30932.1.10.1.1.3.26 |
accesscontrol OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.4 |
ldap OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.4.1 |
enableADAuthControls whether the Active Directory authentication is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.4.1.1 |
adServerSet or get the IP address of the Active Directory Server.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.1.2 |
adDomainSet or get the Active Directory Domain.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.1.3 |
adPortSet or get the port for Active Directory authentication.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.4.1.4 |
adResvPortSet or get the alternate or reserved port for Active Directory Authentication.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.4.1.5 |
radius OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.4.2 |
enableRadiusAuthControls whether radius authentication is enabled.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.4.2.1 |
radiusServerSet or get the IP address of the Radius Authentication Server.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.2.2 |
radiusSHSecretSet or get the Radius Shared Secret.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.2.3 |
radiusNASServerSet or get the Radius Network Access Service.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.2.4 |
radiusPortSet or get the port for radius authentication.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.4.2.5 |
nasPortSet or get the port for Radius Network Access Service.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.4.2.6 |
radiusip6Enable/Disable IPv6 for radius authentication.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.4.2.7 |
radiuscardenableEnable/Disable Radius for card authentication.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.4.2.8 |
cardradiusserverSet or get the IP address of the Primary Radius Card Authentication Server.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.2.9 |
cardradiusshsecretSet or get the Radius Card Shared Secret.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.2.10 |
cardradiusPortSet or get the port for Radius Card Authentication.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.4.2.11 |
cardradiusip6Enable/Disable IPv6 for Radius Card Authentication.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.4.2.12 |
radiusServer2Set or get the IP address of the Secondary Radius Authentication Server.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.2.13 |
radiusPort2Set or get the port for Secondary Radius Authentication.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.4.2.14 |
radiusServer3Set or get the IP address of the Tertiary Radius Authentication Server.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.2.15 |
radiusPort3Set or get the port for Tertiary Radius Authentication.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.4.2.16 |
cardradiusServer2Set or get the IP address of the Secondary Radius Card Authentication Server.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.2.17 |
cardradiusPort2Set or get the port for Secondary Radius Card Authentication.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.4.2.18 |
cardradiusServer3Set or get the IP address of the Tertiary Radius Card Authentication Server.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.1.4.2.19 |
cardradiusPort3Set or get the port for Tertiary Radius Card Authentication.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.4.2.20 |
netOptions OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.5 |
telnetEnableEnable Telnet service, 0=disable and 1=enable.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.5.5 |
sshEnableEnable SSH Service, 0=disable and 1=enable.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.5.6 |
pdu OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.6 |
inputTopSet or get the input cord entry orientation.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.6.1 |
celsiusTempSet or get the temperature units.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.6.2 |
shareRoleControls whether to allow sharing of PDU Primary and Alternate Roles.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.6.3 |
missingPDUNotifyControls whether to notify when a PDU is missing from the link.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.6.4 |
roleChangeNotifyControl whether to notify when a PDU changes role in the link.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.6.5 |
dispTimeoutSet or get the inactivity timeout in minutes to blank the local display (minimum is 1 minute).rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.6.6 |
loginTimeoutSet or get the inactivity timeout in minutes to terminate a logged in session (minimum is 1 minute).rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.6.7 |
dispBrightnessSet or get the relative brightness of the local display (0 in min, 9 is max).rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.6.8 |
sumAmpsControl whether the PDU displays the amperage sum of all branchs.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.6.9 |
alerts OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.7 |
alarmIntervalSet or get the time interval in seconds for alarm cycle (disabled if < 10).rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.7.1 |
dnsHosts OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.8 |
routing OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.8 |
eventLogRouting OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.8.1 |
logBranchCritLowVoltageEnable/Disable logging of Critical Low Voltage on the Branch to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.1 |
logBranchWarnLowVoltageEnable/Disable logging of Warning Low Voltage on the Branch to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.2 |
logBranchWarnHighVoltageEnable/Disable logging of Warning High Voltage on the Branch to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.3 |
logBranchCritHighVoltageEnable/Disable logging of Critical High Voltage on the Branch to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.4 |
logBranchCritLowCurrentEnable/Disable logging of Critical Low Current on the Branch to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.5 |
logBranchWarnLowCurrentEnable/Disable logging of Warning Low Current on the Branch to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.6 |
logBranchWarnHighCurrentEnable/Disable logging of Warning High Current on the Branch to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.7 |
logBranchCritHighCurrentEnable/Disable logging of Critical High Current on the Branch to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.8 |
logOutletCritLowCurrentEnable/Disable logging of Critical Low Current on the Outlet to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.9 |
logOutletWarnLowCurrentEnable/Disable logging of Warning Low Current on the Outlet to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.10 |
logOutletWarnHighCurrentEnable/Disable logging of Warning High Current on the Outlet to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.11 |
logOutletCritHighCurrentEnable/Disable logging of Critical High Current to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.12 |
logTempCritLowEnable/Disable logging of Critical Low Temperature to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.13 |
logTempWarnLowEnable/Disable logging of Warning Low Temperature to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.14 |
logTempWarnHighEnable/Disable logging of Warning High Temperature to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.15 |
logTempCritHighEnable/Disable logging of Critical High Temperature to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.16 |
logHumidCritLowEnable/Disable logging of Critical Low Humidity to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.17 |
logHumidWarnLowEnable/Disable logging of Warning Low Humidity to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.18 |
logHumidWarnHighEnable/Disable logging of Warning High Humidity to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.19 |
logHumidCritHighEnable/Disable logging of Critical High Humidity to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.20 |
logScanPassEnable/Disable logging of successful card scan events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.21 |
logScanFailEnable/Disable logging of failed card scan events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.22 |
logDoorStateEnable/Disable logging of Door Open/Close events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.23 |
logLockStateEnable/Disable logging of Lock Open/Close events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.24 |
logExtendedOpenEnable/Disable logging of extended door open events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.25 |
logFirmareUpdateEnable/Disable logging of Firmare Update events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.26 |
logConfigUpdateEnable/Disable logging of configuration change events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.27 |
logRecepChangeEnable/Disable logging of receptacle change events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.28 |
logSystemEnable/Disable logging of system events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.29 |
logPduAccessEnable/Disable logging of access to PDU events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.30 |
logSecureArrayEnable/Disable logging of SecureArray events to the event log.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.1.31 |
emailRouting OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.8.2 |
emailBranchCritLowVoltageEnable/Disable notification of Critical Low Voltage on the Branch in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.1 |
emailBranchWarnLowVoltageEnable/Disable notification of Warning Low Voltage on the Branch in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.2 |
emailBranchWarnHighVoltageEnable/Disable notification of Warning High Voltage on the Branch in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.3 |
emailBranchCritHighVoltageEnable/Disable notification of Critical High Voltage on the Branch in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.4 |
emailBranchCritLowCurrentEnable/Disable notification of Critical Low Current on the Branch in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.5 |
emailBranchWarnLowCurrentEnable/Disable notification of Warning Low Current on the Branch in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.6 |
emailBranchWarnHighCurrentEnable/Disable notification of Warning High Current on the Branch in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.7 |
emailBranchCritHighCurrentEnable/Disable notification of Critical High Current on the Branch in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.8 |
emailOutletCritLowCurrentEnable/Disable notification of Critical Low Current on the Outlet in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.9 |
emailOutletWarnLowCurrentEnable/Disable notification of Warning Low Current on the Outlet in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.10 |
emailOutletWarnHighCurrentEnable/Disable notification of Warning High Current on the Outlet in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.11 |
emailOutletCritHighCurrentEnable/Disable notification of Critical High Current in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.12 |
emailTempCritLowEnable/Disable notification of Critical Low Temperature in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.13 |
emailTempWarnLowEnable/Disable notification of Warning Low Temperature in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.14 |
emailTempWarnHighEnable/Disable notification of Warning High Temperature in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.15 |
emailTempCritHighEnable/Disable notification of Critical High Temperature in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.16 |
emailHumidCritLowEnable/Disable notification of Critical Low Humidity in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.17 |
emailHumidWarnLowEnable/Disable notification of Warning Low Humidity in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.18 |
emailHumidWarnHighEnable/Disable notification of Warning High Humidity in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.19 |
emailHumidCritHighEnable/Disable notification of Critical High Humidity in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.20 |
emailScanPassEnable/Disable notification of successful card scan events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.21 |
emailScanFailEnable/Disable notification of failed card scan events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.22 |
emailDoorStateEnable/Disable notification of Door Open/Close events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.23 |
emailLockStateEnable/Disable notification of Lock Open/Close events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.24 |
emailExtendedOpenEnable/Disable notification of extended door open events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.25 |
emailFirmareUpdateEnable/Disable notification of Firmare Update events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.26 |
emailConfigUpdateEnable/Disable notification of configuration change events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.27 |
emailRecepChangeEnable/Disable notification of receptacle change events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.28 |
emailSystemEnable/Disable notification of system events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.29 |
emailPduAccessEnable/Disable notification of access to PDU events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.30 |
emailSecureArrayEnable/Disable notification of SecureArray events in an email.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.2.31 |
trapRouting OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.8.3 |
trapBranchCritLowVoltageEnable/Disable notification of Critical Low Voltage on the Branch in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.1 |
trapBranchWarnLowVoltageEnable/Disable notification of Warning Low Voltage on the Branch in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.2 |
trapBranchWarnHighVoltageEnable/Disable notification of Warning High Voltage on the Branch in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.3 |
trapBranchCritHighVoltageEnable/Disable notification of Critical High Voltage on the Branch in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.4 |
trapBranchCritLowCurrentEnable/Disable notification of Critical Low Current on the Branch in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.5 |
trapBranchWarnLowCurrentEnable/Disable notification of Warning Low Current on the Branch in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.6 |
trapBranchWarnHighCurrentEnable/Disable notification of Warning High Current on the Branch in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.7 |
trapBranchCritHighCurrentEnable/Disable notification of Critical High Current on the Branch in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.8 |
trapOutletCritLowCurrentEnable/Disable notification of Critical Low Current on the Outlet in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.9 |
trapOutletWarnLowCurrentEnable/Disable notification of Warning Low Current on the Outlet in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.10 |
trapOutletWarnHighCurrentEnable/Disable notification of Warning High Current on the Outlet in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.11 |
trapOutletCritHighCurrentEnable/Disable notification of Critical High Current in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.12 |
trapTempCritLowEnable/Disable notification of Critical Low Temperature in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.13 |
trapTempWarnLowEnable/Disable notification of Warning Low Temperature in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.14 |
trapTempWarnHighEnable/Disable notification of Warning High Temperature in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.15 |
trapTempCritHighEnable/Disable notification of Critical High Temperature in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.16 |
trapHumidCritLowEnable/Disable notification of Critical Low Humidity in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.17 |
trapHumidWarnLowEnable/Disable notification of Warning Low Humidity in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.18 |
trapHumidWarnHighEnable/Disable notification of Warning High Humidity in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.19 |
trapHumidCritHighEnable/Disable notification of Critical High Humidity in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.20 |
trapScanPassEnable/Disable notification of successful card ID scans in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.21 |
trapScanFailEnable/Disable notification of failed card ID scans in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.22 |
trapDoorStateEnable/Disable notification of Door Open/Closed events in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.23 |
trapLockStateEnable/Disable notification of Lock Open/Closed events in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.24 |
trapExtendedOpenEnable/Disable notification of extended door open events in an trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.25 |
trapFirmareUpdateEnable/Disable notification of Firmare Update events in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.26 |
trapConfigUpdateEnable/Disable notification of configuration change events in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.27 |
trapRecepChangeEnable/Disable notification of receptacle change events in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.28 |
trapSystemEnable/Disable notification of system events in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.29 |
trapPduAccessEnable/Disable notification of access to PDU events in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.30 |
trapSecureArrayEnable/Disable notification of SecureArray events in a trap.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.1.8.3.31 |
netOptionsIPv6 OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.11 |
autoDNSIPv6Select IPV6 dynamic (Auto) or static DNS, 0=static and 1=dynamic.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.11.2 |
ipv6EnableEnable IPV6 Network, 0=disable and 1=enable.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.11.3 |
subnetMaskIPv6PDU IPV6 Subnet Mask.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.12 |
gatewayIPv6PDU IPV6 Gateway Address.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.13 |
dnsHostIPv6 OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.14 |
dns1IPv6PDU DNS 2 for IPV6.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.14.1 |
dns2IPv6PDU DNS 3 for IPV6.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.14.2 |
dns3IPv6PDU DNS 4 for IPV6.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.14.3 |
snmpHostsIPv6 OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.15 |
snmpHost1IPv6SNMP Host 1 IPV6.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.15.1 |
snmpHost2IPv6SNMP Host 2 IPV6.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.15.2 |
snmpHost3IPv6SNMP Host 3 IPV6.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.15.3 |
receptacleControl OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.16 |
outlet1CtrlOutlet1 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.1 |
outlet2CtrlOutlet2 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.2 |
outlet3CtrlOutlet3 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.3 |
outlet4CtrlOutlet4 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.4 |
outlet5CtrlOutlet5 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.5 |
outlet6CtrlOutlet6 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.6 |
outlet7CtrlOutlet7 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.7 |
outlet8CtrlOutlet8 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.8 |
outlet9CtrlOutlet9 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.9 |
outlet10CtrlOutlet10 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.10 |
outlet11CtrlOutlet11 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.11 |
outlet12CtrlOutlet12 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.12 |
outlet13CtrlOutlet13 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.13 |
outlet14CtrlOutlet14 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.14 |
outlet15CtrlOutlet15 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.15 |
outlet16CtrlOutlet16 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.16 |
outlet17CtrlOutlet17 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.17 |
outlet18CtrlOutlet18 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.18 |
outlet19CtrlOutlet19 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.19 |
outlet20CtrlOutlet20 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.20 |
outlet21CtrlOutlet21 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.21 |
outlet22CtrlOutlet22 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.22 |
outlet23CtrlOutlet23 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.23 |
outlet24CtrlOutlet24 power state, 0=OFF, 1=ON.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.16.24 |
receptacleONdelay OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.17 |
outlet1ONdlyOutlet1 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.1 |
outlet2ONdlyOutlet2 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.2 |
outlet3ONdlyOutlet3 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.3 |
outlet4ONdlyOutlet4 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.4 |
outlet5ONdlyOutlet5 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.5 |
outlet6ONdlyOutlet6 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.6 |
outlet7ONdlyOutlet7 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.7 |
outlet8ONdlyOutlet8 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.8 |
outlet9ONdlyOutlet9 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.9 |
outlet10ONdlyOutlet10 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.10 |
outlet11ONdlyOutlet11 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.11 |
outlet12ONdlyOutlet12 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.12 |
outlet13ONdlyOutlet13 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.13 |
outlet14ONdlyOutlet14 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.14 |
outlet15ONdlyOutlet15 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.15 |
outlet16ONdlyOutlet16 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.16 |
outlet17ONdlyOutlet17 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.17 |
outlet18ONdlyOutlet18 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.18 |
outlet19ONdlyOutlet19 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.19 |
outlet20ONdlyOutlet20 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.20 |
outlet21ONdlyOutlet21 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.21 |
outlet22ONdlyOutlet22 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.22 |
outlet23ONdlyOutlet23 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.23 |
outlet24ONdlyOutlet24 power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.17.24 |
receptacleResetDelay OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.18 |
outlet1RESdlyOutlet1 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.1 |
outlet2RESdlyOutlet2 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.2 |
outlet3RESdlyOutlet3 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.3 |
outlet4RESdlyOutlet4 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.4 |
outlet5RESdlyOutlet5 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.5 |
outlet6RESdlyOutlet6 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.6 |
outlet7RESdlyOutlet7 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.7 |
outlet8RESdlyOutlet8 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.8 |
outlet9RESdlyOutlet9 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.9 |
outlet10RESdlyOutlet10 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.10 |
outlet11RESdlyOutlet11 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.11 |
outlet12RESdlyOutlet12 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.12 |
outlet13RESdlyOutlet13 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.13 |
outlet14RESdlyOutlet14 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.14 |
outlet15RESdlyOutlet15 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.15 |
outlet16RESdlyOutlet16 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.16 |
outlet17RESdlyOutlet17 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.17 |
outlet18RESdlyOutlet18 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.18 |
outlet19RESdlyOutlet19 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.19 |
outlet20RESdlyOutlet20 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.20 |
outlet21RESdlyOutlet21 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.21 |
outlet22RESdlyOutlet22 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.22 |
outlet23RESdlyOutlet23 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.23 |
outlet24RESdlyOutlet24 reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.18.24 |
maxCurrentLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.19 |
xy1MaxCurrMaximum current that XY1 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.19.1 |
yz1MaxCurrMaximum current that YZ1 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.19.2 |
zx1MaxCurrMaximum current that ZX1 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.19.3 |
xy2MaxCurrMaximum current that XY2 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.19.4 |
yz2MaxCurrMaximum current that YZ2 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.19.5 |
zx2MaxCurrMaximum current that ZX2 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.19.6 |
minCurrentLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.20 |
xy1MinCurrMinimum current that XY1 should draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.20.1 |
yz1MinCurrMinimum current that YZ1 should draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.20.2 |
zx1MinCurrMinimum current that ZX1 should draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.20.3 |
xy2MinCurrMinimum current that XY2 should draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.20.4 |
yz2MinCurrMinimum current that YZ2 should draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.20.5 |
zx2MinCurrMinimum current that ZX2 should draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.20.6 |
warnHiCurrentLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.21 |
xy1WarnHiCurrWarning upper current limit that XY1 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.21.1 |
yz1WarnHiCurrWarning upper current limit that YZ1 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.21.2 |
zx1WarnHiCurrWarning upper current limit that ZX1 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.21.3 |
xy2WarnHiCurrWarning upper current limit that XY2 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.21.4 |
yz2WarnHiCurrWarning upper current limit that YZ2 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.21.5 |
zx2WarnHiCurrWarning upper current limit that ZX2 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.21.6 |
warnLoCurrentLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.22 |
xy1WarnLoCurrWarning lower current limit that XY1 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.22.1 |
yz1WarnLoCurrWarning lower current limit that YZ1 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.22.2 |
zx1WarnLoCurrWarning lower current limit that ZX1 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.22.3 |
xy2WarnLoCurrWarning lower current limit that XY2 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.22.4 |
yz2WarnLoCurrWarning lower current limit that YZ2 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.22.5 |
zx2WarnLoCurrWarning lower current limit that ZX2 can draw in 1/100 Amps, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.22.6 |
maxVoltageLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.24 |
xy1MaxVoltMaximum voltage that XY1 can reach up to in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.24.1 |
yz1MaxVoltMaximum voltage that YZ1 can reach up to in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.24.2 |
zx1MaxVoltMaximum voltage that ZX1 can reach up to in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.24.3 |
xy2MaxVoltMaximum voltage that XY2 can reach up to in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.24.4 |
yz2MaxVoltMaximum voltage that YZ2 can reach up to in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.24.5 |
zx2MaxVoltMaximum voltage that ZX2 can reach up to in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.24.6 |
minVoltageLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.25 |
xy1MinVoltMinimum voltage that XY1 can sag in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.25.1 |
yz1MinVoltMinimum voltage that YZ1 can sag in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.25.2 |
zx1MinVoltMinimum voltage that ZX1 can sag in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.25.3 |
xy2MinVoltMinimum voltage that XY2 can sag in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.25.4 |
yz2MinVoltMinimum voltage that YZ2 can sag in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.25.5 |
zx2MinVoltMinimum voltage that ZX2 can sag in volts, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.25.6 |
warnHiVoltageLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.26 |
xy1WarnHiVoltWarning High voltage in volts that XY1 can reach before triggering warning notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.26.1 |
yz1WarnHiVoltWarning High voltage in volts that YZ1 can reach before triggering warning notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.26.2 |
zx1WarnHiVoltWarning High voltage in volts that ZX1 can reach before triggering warning notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.26.3 |
xy2WarnHiVoltWarning High voltage in volts that XY2 can reach before triggering warning notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.26.4 |
yz2WarnHiVoltWarning High voltage in volts that YZ2 can reach before triggering warning notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.26.5 |
zx2WarnHiVoltWarning High voltage in volts that ZX2 can reach before triggering warning notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.26.6 |
warnLoVoltageLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.27 |
xy1WarnLoVoltWarning Low voltage in volts that XY1 can sag before triggering notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.27.1 |
yz1WarnLoVoltWarning Low voltage in volts that YZ1 can sag before triggering notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.27.2 |
zx1WarnLoVoltWarning Low voltage in volts that ZX1 can sag before triggering notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.27.3 |
xy2WarnLoVoltWarning Low voltage in volts that XY2 can sag before triggering notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.27.4 |
yz2WarnLoVoltWarning Low voltage in volts that YZ2 can sag before triggering notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.27.5 |
zx2WarnLoVoltWarning Low voltage in volts that ZX2 can sag before triggering notifications, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.27.6 |
receptacleMaxCurrent OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.28 |
outlet1MaxCurrOutlet1 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.1 |
outlet2MaxCurrOutlet2 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.2 |
outlet3MaxCurrOutlet3 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.3 |
outlet4MaxCurrOutlet4 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.4 |
outlet5MaxCurrOutlet5 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.5 |
outlet6MaxCurrOutlet6 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.6 |
outlet7MaxCurrOutlet7 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.7 |
outlet8MaxCurrOutlet8 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.8 |
outlet9MaxCurrOutlet9 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.9 |
outlet10MaxCurrOutlet10 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.10 |
outlet11MaxCurrOutlet11 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.11 |
outlet12MaxCurrOutlet12 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.12 |
outlet13MaxCurrOutlet13 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.13 |
outlet14MaxCurrOutlet14 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.14 |
outlet15MaxCurrOutlet15 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.15 |
outlet16MaxCurrOutlet16 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.16 |
outlet17MaxCurrOutlet17 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.17 |
outlet18MaxCurrOutlet18 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.18 |
outlet19MaxCurrOutlet19 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.19 |
outlet20MaxCurrOutlet20 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.20 |
outlet21MaxCurrOutlet21 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.21 |
outlet22MaxCurrOutlet22 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.22 |
outlet23MaxCurrOutlet23 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.23 |
outlet24MaxCurrOutlet24 maximum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.28.24 |
receptacleMinCurrent OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.29 |
outlet1MinCurrOutlet1 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.1 |
outlet2MinCurrOutlet2 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.2 |
outlet3MinCurrOutlet3 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.3 |
outlet4MinCurrOutlet4 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.4 |
outlet5MinCurrOutlet5 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.5 |
outlet6MinCurrOutlet6 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.6 |
outlet7MinCurrOutlet7 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.7 |
outlet8MinCurrOutlet8 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.8 |
outlet9MinCurrOutlet9 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.9 |
outlet10MinCurrOutlet10 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.10 |
outlet11MinCurrOutlet11 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.11 |
outlet12MinCurrOutlet12 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.12 |
outlet13MinCurrOutlet13 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.13 |
outlet14MinCurrOutlet14 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.14 |
outlet15MinCurrOutlet15 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.15 |
outlet16MinCurrOutlet16 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.16 |
outlet17MinCurrOutlet17 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.17 |
outlet18MinCurrOutlet18 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.18 |
outlet19MinCurrOutlet19 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.19 |
outlet20MinCurrOutlet20 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.20 |
outlet21MinCurrOutlet21 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.21 |
outlet22MinCurrOutlet22 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.22 |
outlet23MinCurrOutlet23 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.23 |
outlet24MinCurrOutlet24 minimum current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.29.24 |
receptacleWarnHiCurrent OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.30 |
outlet1WarnHiCurrOutlet1 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.1 |
outlet2WarnHiCurrOutlet2 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.2 |
outlet3WarnHiCurrOutlet3 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.3 |
outlet4WarnHiCurrOutlet4 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.4 |
outlet5WarnHiCurrOutlet5 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.5 |
outlet6WarnHiCurrOutlet6 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.6 |
outlet7WarnHiCurrOutlet7 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.7 |
outlet8WarnHiCurrOutlet8 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.8 |
outlet9WarnHiCurrOutlet9 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.9 |
outlet10WarnHiCurrOutlet10 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.10 |
outlet11WarnHiCurrOutlet11 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.11 |
outlet12WarnHiCurrOutlet12 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.12 |
outlet13WarnHiCurrOutlet13 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.13 |
outlet14WarnHiCurrOutlet14 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.14 |
outlet15WarnHiCurrOutlet15 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.15 |
outlet16WarnHiCurrOutlet16 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.16 |
outlet17WarnHiCurrOutlet17 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.17 |
outlet18WarnHiCurrOutlet18 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.18 |
outlet19WarnHiCurrOutlet19 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.19 |
outlet20WarnHiCurrOutlet20 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.20 |
outlet21WarnHiCurrOutlet21 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.21 |
outlet22WarnHiCurrOutlet22 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.22 |
outlet23WarnHiCurrOutlet23 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.23 |
outlet24WarnHiCurrOutlet24 warning high current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.30.24 |
receptacleWarnLoCurrent OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.31 |
outlet1WarnLoCurrOutlet1 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.1 |
outlet2WarnLoCurrOutlet2 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.2 |
outlet3WarnLoCurrOutlet3 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.3 |
outlet4WarnLoCurrOutlet4 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.4 |
outlet5WarnLoCurrOutlet5 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.5 |
outlet6WarnLoCurrOutlet6 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.6 |
outlet7WarnLoCurrOutlet7 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.7 |
outlet8WarnLoCurrOutlet8 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.8 |
outlet9WarnLoCurrOutlet9 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.9 |
outlet10WarnLoCurrOutlet10 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.10 |
outlet11WarnLoCurrOutlet11 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.11 |
outlet12WarnLoCurrOutlet12 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.12 |
outlet13WarnLoCurrOutlet13 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.13 |
outlet14WarnLoCurrOutlet14 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.14 |
outlet15WarnLoCurrOutlet15 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.15 |
outlet16WarnLoCurrOutlet16 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.16 |
outlet17WarnLoCurrOutlet17 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.17 |
outlet18WarnLoCurrOutlet18 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.18 |
outlet19WarnLoCurrOutlet19 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.19 |
outlet20WarnLoCurrOutlet20 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.20 |
outlet21WarnLoCurrOutlet21 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.21 |
outlet22WarnLoCurrOutlet22 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.22 |
outlet23WarnLoCurrOutlet23 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.23 |
outlet24WarnLoCurrOutlet24 warning low current in 1/100 Amps.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.31.24 |
maxTempLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.32 |
maxTempProbe1Maximum temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.32.1 |
maxTempProbe2Maximum temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.32.2 |
minTempLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.33 |
minTempProbe1Minimum temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.33.1 |
minTempProbe2Minimum temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.33.2 |
warnHiTempLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.34 |
warnHiTempProbe1Warning High temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.34.1 |
warnHiTempProbe2Warning High temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.34.2 |
warnLoTempLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.35 |
warnLoTempProbe1Warning Low temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.35.1 |
warnLoTempProbe2Warning Low temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.35.2 |
maxHumidityLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.36 |
maxHumidProbe1Maximum humidity for Probe 1 in 1/100 of %, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.36.1 |
maxHumidProbe2Maximum humidity for Probe 2 in 1/100 of %, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.36.2 |
minHumidityLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.37 |
minHumidProbe1Minimum humidity for Probe 1 in 1/100 of %, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.37.1 |
minHumidProbe2Minimum humidity for Probe 2 in 1/100 of %, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.37.2 |
warnHiHumidityLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.38 |
warnHiHumidProbe1Warning High humidity for Probe 1 in 1/100 of %, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.38.1 |
warnHiHumidProbe2Warning High humidity for Probe 2 in 1/100 of %, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.38.2 |
warnLoHumidityLimits OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.39 |
warnLoHumidProbe1Warning Low humidity for Probe 1 in 1/100 of %, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.39.1 |
warnLoHumidProbe2Warning Low humidity for Probe 2 in 1/100 of %, 0=ignore.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.39.2 |
pduNamePDU Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.40 |
pduDescripPDU Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.41 |
receptacleNames OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.42 |
outlet1NameOutlet1 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.1 |
outlet2NameOutlet2 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.2 |
outlet3NameOutlet3 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.3 |
outlet4NameOutlet4 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.4 |
outlet5NameOutlet5 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.5 |
outlet6NameOutlet6 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.6 |
outlet7NameOutlet7 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.7 |
outlet8NameOutlet8 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.8 |
outlet9NameOutlet9 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.9 |
outlet10NameOutlet10 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.10 |
outlet11NameOutlet11 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.11 |
outlet12NameOutlet12 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.12 |
outlet13NameOutlet13 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.13 |
outlet14NameOutlet14 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.14 |
outlet15NameOutlet15 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.15 |
outlet16NameOutlet16 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.16 |
outlet17NameOutlet17 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.17 |
outlet18NameOutlet18 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.18 |
outlet19NameOutlet19 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.19 |
outlet20NameOutlet20 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.20 |
outlet21NameOutlet21 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.21 |
outlet22NameOutlet22 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.22 |
outlet23NameOutlet23 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.23 |
outlet24NameOutlet24 Name.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.42.24 |
receptacleDescrips OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.43 |
outlet1DescripOutlet1 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.1 |
outlet2DescripOutlet2 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.2 |
outlet3DescripOutlet3 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.3 |
outlet4DescripOutlet4 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.4 |
outlet5DescripOutlet5 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.5 |
outlet6DescripOutlet6 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.6 |
outlet7DescripOutlet7 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.7 |
outlet8DescripOutlet8 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.8 |
outlet9DescripOutlet9 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.9 |
outlet10DescripOutlet10 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.10 |
outlet11DescripOutlet11 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.11 |
outlet12DescripOutlet12 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.12 |
outlet13DescripOutlet13 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.13 |
outlet14DescripOutlet14 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.14 |
outlet15DescripOutlet15 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.15 |
outlet16DescripOutlet16 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.16 |
outlet17DescripOutlet17 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.17 |
outlet18DescripOutlet18 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.18 |
outlet19DescripOutlet19 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.19 |
outlet20DescripOutlet20 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.20 |
outlet21DescripOutlet21 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.21 |
outlet22DescripOutlet22 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.22 |
outlet23DescripOutlet23 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.23 |
outlet24DescripOutlet24 Description.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.43.24 |
groupNames OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.50 |
group1NameName for GROUP 1 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.1 |
group2NameName for GROUP 2 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.2 |
group3NameName for GROUP 3 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.3 |
group4NameName for GROUP 4 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.4 |
group5NameName for GROUP 5 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.5 |
group6NameName for GROUP 6 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.6 |
group7NameName for GROUP 7 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.7 |
group8NameName for GROUP 8 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.8 |
group9NameName for GROUP 9 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.9 |
group10NameName for GROUP 10 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.10 |
group11NameName for GROUP 11 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.11 |
group12NameName for GROUP 12 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.12 |
group13NameName for GROUP 13 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.13 |
group14NameName for GROUP 14 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.14 |
group15NameName for GROUP 15 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.15 |
group16NameName for GROUP 16 of receptacles.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.50.16 |
groupMaps OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.51 |
group1MapMap for Group 1 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.1 |
group2MapMap for Group 2 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.2 |
group3MapMap for Group 3 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.3 |
group4MapMap for Group 4 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.4 |
group5MapMap for Group 5 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.5 |
group6MapMap for Group 6 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.6 |
group7MapMap for Group 7 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.7 |
group8MapMap for Group 8 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.8 |
group9MapMap for Group 9 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.9 |
group10MapMap for Group 10 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.10 |
group11MapMap for Group 11 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.11 |
group12MapMap for Group 12 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.12 |
group13MapMap for Group 13 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.13 |
group14MapMap for Group 14 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.14 |
group15MapMap for Group 15 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.15 |
group16MapMap for Group 16 of receptacels.rw OCTET STRING .1.3.6.1.4.1.30932.1.10.1.1.51.16 |
pduOptions OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.58 |
pduRolePDU Role, 1 = primary, 0 = secondary.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.58.2 |
disLocalAuthDisable local authentication, 1 = disable, 0 = enable.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.58.6 |
enaRadiusAuthEnable Radius authentication, 1 = disable, 0 = enable.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.58.7 |
enaADAuthEnable Active Directory authentication, 1 = disable, 0 = enable.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.58.8 |
enaSMTPEnable Mail Notification, 1 = disable, 0 = enable.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.58.9 |
pduAltRolePDU Alternate Role, 1 = alternate, 0 = secondary.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.58.10 |
outOfServiceRemove a PDU from normal operation, 1 = out of service, 0 = normal operation.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.58.12 |
sumAmpDisplay the sum of the current across branches, 1 = enable, 0 = disable.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.58.15 |
httpPorts OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.59 |
sshPorts OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.60 |
sshPortPort for secure SSH access.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.60.1 |
telnetPortPort for non secure Telnet access.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.60.2 |
snmpPorts OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.61 |
smtpPorts OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.62 |
snmpSecurityLevelAlgorithm OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.69 |
smtpEmailDestinations OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.79 |
radiusNASPorts OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.84 |
adAllPorts OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.87 |
envProbeNames OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.88 |
probe1NameName for Environmental Probe 1.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.88.1 |
probe2NameName for Environmental Probe 2.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.88.2 |
dLogOptions OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.89 |
dLogEnableEnable data logging feature, 0=disable and 1=enable.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.89.1 |
snmpTrapHostsIPv6 OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.1.99 |
snmpTrapHost1IPv6SNMP Trap Host 1 IPV6.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.99.1 |
snmpTrapHost2IPv6SNMP Trap Host 2 IPV6.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.99.2 |
snmpTrapHost3IPv6SNMP Trap Host 3 IPV6.rw DisplayString .1.3.6.1.4.1.30932.1.10.1.1.99.3 |
lnkAttachCountCount of secondary PDUs that are attached to the link.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.1.100 |
systeminfo OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.2 |
cpiPduTableCountGet the number of PDUs being monitored by this PDU. This is the
number of entries in the cpiPduTable.ro Unsigned32 UNITS "Count" .1.3.6.1.4.1.30932.1.10.1.2.1 |
cpiPduTableThis table contains a list of PDU entries that are being monitored
by the PDU.
The table contains one, or many rows, depending upon the
number of PDUs being monitored. Each row in the table represents a PDU
in the daisy chain.
This table always contains at least one entry and a maximum of 32 entries.
The MAC address is used as an index on the table to allow data collectors
to ensure that information can be retrieved for a specific PDU. SEQUENCE OF CpiPduEntry .1.3.6.1.4.1.30932.1.10.1.2.10 |
cpiPduEntryThis entry defines the columns to be populated in the
'cpiPduTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU MAC that is globally unique. CpiPduEntry .1.3.6.1.4.1.30932.1.10.1.2.10.1 |
cpiPduMacGet the MAC address of the PDU.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.2.10.1.1 |
cpiPduModelGet the model number of the PDU.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.2.10.1.2 |
cpiPduNameSet or get the user assigned name of the PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.2.10.1.3 |
cpiPduDescriptionSet or get the user assigned description of the PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.2.10.1.4 |
cpiPduHasBranchMonitorAn indicator if the PDU supports monitoring voltage, and current on branches in the PDU.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.2.10.1.5 |
cpiPduHasOutletMonitorAn indicator if the PDU supports monitoring current on the individual outlets in the PDU.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.2.10.1.6 |
cpiPduHasOutletControlAn indicator if the PDU supports control (turn on/off) individual outlets in the PDU.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.2.10.1.7 |
cpiPduNumberBranchesGet the number of branches (breakers) in the PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.2.10.1.8 |
cpiPduNumberOutletsGet the number of outlets in the PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.2.10.1.9 |
cpiPduOutOfServiceSet or get whether the PDU is in-service.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.2.10.1.10 |
cpiPduVersionGet the firmware version number of the PDU.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.2.10.1.11 |
cpiPduUpgradeAn indicator if the PDU firmware is being upgraded.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.2.10.1.12 |
cpiPduChainRoleGet the role of the PDU in a daisy chain.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.2.10.1.13 |
cpiPduIpGet IP address of the PDU.ro IpAddress .1.3.6.1.4.1.30932.1.10.1.2.10.1.14 |
cpiPduIpv6Get the IPv6 address of the PDU.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.2.10.1.15 |
cpiPduTotalPowerGet the power in volt-amps for the entire PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.2.10.1.16 |
cpiPduCabinetIdGet/set the name of the cabinet the PDU is in.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.2.10.1.17 |
cpiPduSerialNumGet the serial number of the PDU.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.2.10.1.18 |
branch OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.3 |
cpiLineTableCountGet the number of PDU input lines being monitored by this PDU.
This is the number of entries in the cpiLineTable and accounts
for all input lines in a daisy chain.ro Unsigned32 UNITS "Count" .1.3.6.1.4.1.30932.1.10.1.3.1 |
cpiPduLineTableThis table contains a list of PDU line entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of input lines. Each row
in the table represents a PDU line in the daisy chain.
The table is indexed based on the corresponding Line Input ID and
the source PDU MAC. SEQUENCE OF CpiPduLineEntry .1.3.6.1.4.1.30932.1.10.1.3.10 |
cpiPduLineEntryThis entry defines the columns to be populated in the
'cpiPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU. CpiPduLineEntry .1.3.6.1.4.1.30932.1.10.1.3.10.1 |
cpiPduLineMacGet the MAC address of the PDU that owns the input line.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.3.10.1.1 |
cpiPduLineIdGet the ID of the input line on the PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.3.10.1.2 |
cpiPduLineCurrentGet current draw in 1/100 amp of the line on the PDU. Convert the value by dividing by 100.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.3.10.1.3 |
cpiBranchTableCountGet the number of PDU branches being monitored by this PDU. This is the
number of entries in the cpiPduBranchTable.ro Unsigned32 UNITS "Count" .1.3.6.1.4.1.30932.1.10.1.3.100 |
cpiPduBranchTableThis table contains a list of PDU branch entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row
in the table represents a PDU branch in the daisy chain.
The table is indexed based on the corresponding Branch ID and
the source PDU MAC. SEQUENCE OF CpiPduBranchEntry .1.3.6.1.4.1.30932.1.10.1.3.110 |
cpiPduBranchEntryThis entry defines the columns to be populated in the
'cpiPduBranchTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU. CpiPduBranchEntry .1.3.6.1.4.1.30932.1.10.1.3.110.1 |
cpiPduBranchMacGet the MAC address of the PDU that owns the branch.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.3.110.1.1 |
cpiPduBranchIdGet the ID of the branch on the owning PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.3.110.1.2 |
cpiPduBranchCurrentGet the current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.3.110.1.3 |
cpiPduBranchMaxCurrentGet the maximum current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.3.110.1.4 |
cpiPduBranchVoltageGet the voltage in 1/10 volts of the branch on the PDU. Convert the value by dividing by 10.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.3.110.1.5 |
cpiPduBranchPowerGet the power in volt-amps for the branch.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.3.110.1.6 |
cpiPduBranchPowerFactorGet the power factor for the branch.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.3.110.1.7 |
cpiPduBranchStatusGet the alarm status of the branch.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.3.110.1.8 |
cpiPduBranchEnergyGet the branch energy accumulated in decaVA-secs, divide by 360 to obtain VA-hr.ro Counter64 .1.3.6.1.4.1.30932.1.10.1.3.110.1.9 |
cpiPduBranchAlertTableThis table contains a list of PDU branch alert entries that are
being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row
in the table represents a PDU branch in the daisy chain.
The table is indexed based on the corresponding Branch ID and the
source PDU MAC. SEQUENCE OF CpiPduBranchAlertEntry .1.3.6.1.4.1.30932.1.10.1.3.210 |
cpiPduBranchAlertEntryThis entry defines the columns to be populated in the
'cpiPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU. CpiPduBranchAlertEntry .1.3.6.1.4.1.30932.1.10.1.3.210.1 |
cpiPduBranchAlertMacGet the MAC address of the PDU.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.3.210.1.1 |
cpiPduBranchAlertBranchIdGet the branch ID on the PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.2 |
cpiPduBranchAlertWarnLoCurrentSet or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.3 |
cpiPduBranchAlertWarnHiCurrentSet or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.4 |
cpiPduBranchAlertLoCurrentSet or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the
value by dividing by 100.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.5 |
cpiPduBranchAlertHiCurrentSet or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the
value by dividing by 100.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.6 |
cpiPduBranchAlertCriticalCurrentSet or get the critical current draw in 1/100 amp of the
branch on the PDU. Convert the value by dividing by 100.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.7 |
cpiPduBranchAlertWarnLoVoltSet or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.8 |
cpiPduBranchAlertWarnHiVoltSet or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.9 |
cpiPduBranchAlertLoVoltSet or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.10 |
cpiPduBranchAlertHiVoltSet or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by
dividing by 10.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.11 |
cpiPduBranchAlertIndexIndex for branch alert.ro Unsigned32 .1.3.6.1.4.1.30932.1.10.1.3.210.1.13 |
outlet OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.4 |
cpiOutletTableCountGet the number of PDU outlets being monitored by this PDU. This
is the number of entries in the cpiPduOutletTable.ro Unsigned32 UNITS "Count" .1.3.6.1.4.1.30932.1.10.1.4.1 |
cpiPduOutletTableThis table contains a list of PDU outlet entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets on each PDU.
Each row in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and
the source PDU MAC. SEQUENCE OF CpiPduOutletEntry .1.3.6.1.4.1.30932.1.10.1.4.10 |
cpiPduOutletEntryThis entry defines the columns to be populated in the
'cpiPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU. CpiPduOutletEntry .1.3.6.1.4.1.30932.1.10.1.4.10.1 |
cpiPduOutletMacGet the MAC address of the source PDU.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.4.10.1.1 |
cpiPduOutletIdGet the ID of the outlet on the PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.4.10.1.2 |
cpiPduOutletBranchIdGet the ID of the branch the outlet is associated with on the PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.4.10.1.3 |
cpiPduOutletNameSet or get the user supplied name of the outlet on the PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.4.10.1.4 |
cpiPduOutletDescriptionSet or get the user supplied description of the outlet on the PDU.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.4.10.1.5 |
cpiPduOutletCurrentGet the current draw in 1/100 amp of the outlet on the PDU. Convert
the value by dividing by 100.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.4.10.1.6 |
cpiPduOutletVoltageGet the voltage in 1/10 volts of the outlet on the PDU. Convert the
value by dividing by 10.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.4.10.1.7 |
cpiPduOutletPowerThe power in Volt-Amps of the outlet on the PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.4.10.1.8 |
cpiPduOutletStatusGet the alarm status of the outlet.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.4.10.1.9 |
cpiPduOutletEnergyGet the outlet energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.ro Counter64 .1.3.6.1.4.1.30932.1.10.1.4.10.1.10 |
cpiPduOutletControlSet or get power control to the outlet.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.4.10.1.11 |
cpiPduOutletResetSet or get reset power to the outlet.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.4.10.1.12 |
cpiPduOutletConfigTableThis table contains a list of PDU outlet configuration entries
that are being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets per PDU. Each row
in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and
the source PDU MAC. SEQUENCE OF CpiPduOutletConfigEntry .1.3.6.1.4.1.30932.1.10.1.4.210 |
cpiPduOutletConfigEntryThis entry defines the columns to be populated in the
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
unique within the PDU. CpiPduOutletConfigEntry .1.3.6.1.4.1.30932.1.10.1.4.210.1 |
cpiPduOutletConfigMacGet the MAC address of the PDU.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.4.210.1.1 |
cpiPduOutletConfigOutletIdGet the ID of the outlet on the PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.4.210.1.2 |
cpiPduOutletConfigOnDelaySet or get the outlet power-on delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.4.210.1.3 |
cpiPduOutletConfigResetDelaySet or get the outlet reset delay in seconds.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.4.210.1.4 |
cpiPduOutletAlertTableThis table contains a list of PDU outlet alert entries that are
being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets per PDU. Each row
in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and the
source PDU MAC. SEQUENCE OF CpiPduOutletAlertEntry .1.3.6.1.4.1.30932.1.10.1.4.310 |
cpiPduOutletAlertEntryThis entry defines the columns to be populated in the
'cpiPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU. CpiPduOutletAlertEntry .1.3.6.1.4.1.30932.1.10.1.4.310.1 |
cpiPduOutletAlertMacGet the MAC address of the PDU.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.4.310.1.1 |
cpiPduOutletAlertOutletIdGet the outlet ID on the PDU.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.4.310.1.2 |
cpiPduOutletAlertWarnLoCurrentSet or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.4.310.1.3 |
cpiPduOutletAlertWarnHiCurrentSet or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the
value by dividing by 100.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.4.310.1.4 |
cpiPduOutletAlertLoCurrentSet or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the
value by dividing by 100.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.4.310.1.5 |
cpiPduOutletAlertHiCurrentSet or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the
value by dividing by 100.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.4.310.1.6 |
cpiPduOutletAlertCriticalCurrentSet or get the critical current draw in 1/100 amp of the
outlet on the PDU. Convert the value by dividing by 100.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.4.310.1.7 |
sensors OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.5 |
cpiPduSensorCountGet the number of PDU sensors being monitored by this PDU. This is the
number of entries in the cpiPduSensorTable.ro Unsigned32 UNITS "Count" .1.3.6.1.4.1.30932.1.10.1.5.1 |
cpiPduProbeTableThis table contains a list of PDU probes that are being monitored
by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of probes attached to the PDUs in
the daisy chain. Each row in the table represents a probe in the daisy chain.
The table is index based on the corresponding Probe ID and the source
PDU MAC. SEQUENCE OF CpiPduProbeEntry .1.3.6.1.4.1.30932.1.10.1.5.5 |
cpiPduProbeEntryThis entry defines the columns to be populated in the
'cpiPduProbeTable'. Each column represents an attribute of a PDU probe.
This table is indexed by the PDU identifier that is unique
within the PDU and the probe ID. CpiPduProbeEntry .1.3.6.1.4.1.30932.1.10.1.5.5.1 |
cpiPduProbeMacGet the MAC address of the PDU.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.5.5.1.1 |
cpiPduProbeIdGet the probe ID on the PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.5.5.1.2 |
cpiPduProbeNameSet or get the user defined name of the probe.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.5.5.1.3 |
cpiPduSensorTableThis table contains a list of PDU sensor entries that are being monitored
by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
The table is index based on the corresponding Sensor ID and the source
PDU MAC. SEQUENCE OF CpiPduSensorEntry .1.3.6.1.4.1.30932.1.10.1.5.10 |
cpiPduSensorEntryThis entry defines the columns to be populated in the 'cpiPduSensorTable'.
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor ID. CpiPduSensorEntry .1.3.6.1.4.1.30932.1.10.1.5.10.1 |
cpiPduSensorMacGet the MAC address of the PDU.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.5.10.1.1 |
cpiPduSensorIdGet the sensor ID on the PDU.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.5.10.1.2 |
cpiPduSensorNameSet or get the user defined name of the sensor.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.5.10.1.3 |
cpiPduSensorTypeGet the type of sensor for the entry.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.5.10.1.4 |
cpiPduSensorValueGet the value of the sensor. For temperature the value is in degrees
Fahrenheit and for humidity the value is percent humidity.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.5.10.1.5 |
cpiPduSensorAlertTableThis table contains a list of PDU sensor alert entries that are
being monitored by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
The table is index based on the corresponding Sonsor ID and the source
PDU MAC. SEQUENCE OF CpiPduSensorAlertEntry .1.3.6.1.4.1.30932.1.10.1.5.110 |
cpiPduSensorAlertEntryThis entry defines the columns to be populated in the 'cpiPduSensorAlertTable'.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU. CpiPduSensorAlertEntry .1.3.6.1.4.1.30932.1.10.1.5.110.1 |
cpiPduSensorAlertMacGet the MAC address of the PDU.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.5.110.1.1 |
cpiPduSensorAlertSensorIdGet the id of the sensor.ro Integer32 .1.3.6.1.4.1.30932.1.10.1.5.110.1.2 |
cpiPduSensorAlertWarnMinSet or get the minimum warning value of the sensor.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.5.110.1.3 |
cpiPduSensorAlertWarnMaxSet or get the maximum warning value of the sensor.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.5.110.1.4 |
cpiPduSensorAlertMinSet or get the minimum alarm value of the sensor.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.5.110.1.5 |
cpiPduSensorAlertMaxSet or get the maximum alarm value of the sensor.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.5.110.1.6 |
group OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.6 |
cpiPduGroupCountGet the number of supported groups by the PDU. Value from 0 to 16.ro Unsigned32 UNITS "Count" .1.3.6.1.4.1.30932.1.10.1.6.1 |
cpiPduGroupOutletCountGet the number of outlets in the Group Outlet Table.ro Unsigned32 UNITS "Count" .1.3.6.1.4.1.30932.1.10.1.6.2 |
cpiGroupTableThis table contains a list of PDU group entries that are being monitored
by the PDU.
The table contains one, or many rows, depending upon the number
of groups that have been configured. Each row in the table represents a
group. SEQUENCE OF CpiGroupEntry .1.3.6.1.4.1.30932.1.10.1.6.10 |
cpiGroupEntryThis entry defines the columns to be populated in the
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU. CpiGroupEntry .1.3.6.1.4.1.30932.1.10.1.6.10.1 |
cpiGroupEntryIndexThis is the index that indicates the row of the 'cpiPduTable'.ro Unsigned32 .1.3.6.1.4.1.30932.1.10.1.6.10.1.1 |
cpiGroupNameName for GROUP 1 of receptacles.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.6.10.1.2 |
cpiGroupOutletTableThis table contains a list of PDU group entries.
The table contains zero, one, or many rows, depending upon the number
of groups that have been configured. Each row in the table represents a
group. SEQUENCE OF CpiGroupOutletEntry .1.3.6.1.4.1.30932.1.10.1.6.20 |
cpiGroupOutletEntryThis entry defines the columns to be populated in the
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU. CpiGroupOutletEntry .1.3.6.1.4.1.30932.1.10.1.6.20.1 |
cpiGroupOutletEntryIndexThis is the index that indicates the row of the 'cpiGroupOutletTable'.ro Unsigned32 .1.3.6.1.4.1.30932.1.10.1.6.20.1.1 |
cpiGroupOutletGroupIDName for GROUP 1 of receptacles.ro Unsigned32 .1.3.6.1.4.1.30932.1.10.1.6.20.1.2 |
cpiGroupOutletPDUMacMAC of PDU the outlet is on.rw MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.6.20.1.3 |
cpiGroupOutletOutletIdThe ID of the outlet on the PDU.rw Integer32 .1.3.6.1.4.1.30932.1.10.1.6.20.1.4 |
easData OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.7 |
cpiEasCountGet the number of locks connected to the PDU. This includes the PDUs on the daisy chain.ro Unsigned32 UNITS "Count" .1.3.6.1.4.1.30932.1.10.1.7.1 |
cpiEasConfigTableThis table contains a list of electronic locks that are connected to the PDU
and allows for the configuration of the various settings associated with the
EAS (electronic access system).
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
The table is index based on the corresponding lock ID and the source
PDU MAC. SEQUENCE OF CpiEasConfigEntry .1.3.6.1.4.1.30932.1.10.1.7.90 |
cpiEasConfigEntryThis entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID. CpiEasConfigEntry .1.3.6.1.4.1.30932.1.10.1.7.90.1 |
cpiEasConfigLockMacGet the MAC address of the PDU.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.7.90.1.1 |
cpiEasConfigEnabledIndicates whether the Electronic Access System (EAS) is available on the PDU.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.7.90.1.2 |
cpiEasFrontLockEnabledEnables the front lock on the EAS.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.7.90.1.3 |
cpiEasRearLockEnabledEnables the rear lock on the EAS.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.7.90.1.4 |
cpiEasLockHoldOpenTimeThe length of time in seconds to hold open the lock after a successful card scan.rw INTEGER .1.3.6.1.4.1.30932.1.10.1.7.90.1.5 |
cpiEasDoorOpenAlarmTimeThe length of time in minutes before alerting that the door is open.rw INTEGER .1.3.6.1.4.1.30932.1.10.1.7.90.1.6 |
cpiEasTableThis table contains a list of electronic locks that are connected to the PDU
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
The table is index based on the corresponding lock ID and the source
PDU MAC. SEQUENCE OF CpiEasEntry .1.3.6.1.4.1.30932.1.10.1.7.100 |
cpiEasEntryThis entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID. CpiEasEntry .1.3.6.1.4.1.30932.1.10.1.7.100.1 |
cpiPduLockMacGet the MAC address of the PDU.ro MacAddress (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.7.100.1.1 |
cpiPduLockIdGet the lock ID on the PDU.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.7.100.1.2 |
cpiPduEasStatusIndicates if the Electronic Access Control system is ready, inactive, or in an error state.
If the status is Inactive, then the lock is not enabled on the PDU.
If the status is Error, then the cpiEasError field will have an error code to help diagnose the issue.
If the status is Ready, then the lock at the door is enabled and ready.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.7.100.1.3 |
cpiPduDoorStatusIndicates if the door sensor is closed or open.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.7.100.1.4 |
cpiPduLockStatusIndicates if the lock is closed or open.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.7.100.1.5 |
cpiPduForceStatusIndicates if the cabinet was forced open by a command from the webUI or SNMP interfaces.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.7.100.1.6 |
cpiPduTamperStatusIndicates if the cabinet is currently unlocked/opened without an authorization scan.ro Enumeration .1.3.6.1.4.1.30932.1.10.1.7.100.1.7 |
cpiEasErrorGets the error code associated for the electronic lock system. The possible error codes are:
196608 (0x00030000
) - No error, the lock is working and ready.
167968771 (0x0a030003
) - The lock is not enabled. Enable the lock through the cpiEasConfigTable.
167837698 (0x0a010002
) - The lock is not responding. Ensure that the lock is connected to the PDU,
and is recieving power. Try to disable and re-enable the lock in the
cpiEasConfigTable.ro Unsigned32 .1.3.6.1.4.1.30932.1.10.1.7.100.1.8 |
cpiEasLockVerGets the version of the electronic lock control.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.7.100.1.9 |
cpiEasLockSerialNumberGet the serial number of the electronic lock control.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.7.100.1.10 |
cpiPduLockCtrlTells the system to open the locks on the cabinet.rw Enumeration .1.3.6.1.4.1.30932.1.10.1.7.100.1.11 |
traps OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.500 |
trapInformation OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.500.0 |
trapInfoUserNameThe user Id associated with the action. DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.500.0.1 |
trapInfoCardIdThe card Id associated with the action. DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.500.0.2 |
trapInfoConfigNameThe configuration value that was changed. DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.500.0.3 |
trapInfoInterfaceAn identifier for the affected interface. Enumeration .1.3.6.1.4.1.30932.1.10.1.500.0.4 |
trapInfoVarIdAn identifier for the value that was changed. OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.500.0.5 |
trapInfoBootTypeIndicates that type of boot up occurring. A Cold boot is done from a complete power off. A Warm boot
was not a loss in power, but just a reboot of the control module. Enumeration .1.3.6.1.4.1.30932.1.10.1.500.0.6 |
trapInfoProgressIndicates the percent complete of an operation. Integer32 .1.3.6.1.4.1.30932.1.10.1.500.0.7 |
trapInfoResultIndicates the result of an operation. Enumeration .1.3.6.1.4.1.30932.1.10.1.500.0.8 |
trapInfoErrorCodeIndicates the error code of an operation. See the operation for details.
Firmware Update Operation Error Codes:
151060481 - Error: Insufficient space available on the PDU to complete the operation.
151060482 - Error: Too many packets were lost in the transfer process. Please try the operation again.
151060483 - Error: The firmware file is corrupted and can not be used.
151060484 - Error: There was a failure in writing the firmware data out to internal memory.
151060485 - Error: The firmware file could not be opened and processed correctly.
151060489 - Error: A unknown failure occured while performing a firmware upgrade.
151060490 - Info: A firmware update is in progress. No issue currently.
151191558 - Info: A firmware upgrade has completed and does not need to reboot.
151191559 - Info: A firmware upgrade has compelted and will reboot.
151191560 - Info: A firmware upgrade has compelted and it was not needed. PDU will not reboot. INTEGER .1.3.6.1.4.1.30932.1.10.1.500.0.9 |
trapInfoGroupNameThe user group Id associated with the action. DisplayString (SNMPv2-TC) .1.3.6.1.4.1.30932.1.10.1.500.0.10 |
systemNotifications OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.500.1 |
systemConfigChangeAlertNotification that a configuration value was changed on the PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.1.1 |
systemBootAlertNotification that a PDU is booting up. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.1.2 |
systemFWUpdateStartAlertNotification that a firmware update has been initiated. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.1.3 |
systemFWUpdateStatusAlertNotification that about the progress of the firmware update. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.1.4 |
systemFWUpdateCompleteAlertNotification that about the progress of the firmware update. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.1.5 |
systemSecureArrayFailoverAlertNotification that the SecureArray is being managed by the identified PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.1.6 |
systemSecureArrayDisconnectAlertNotification that the specified PDU disconnected from the SecureArray. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.1.7 |
systemSecureArrayConnectAlertNotification that the specified PDU connected to the SecureArray. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.1.8 |
systemConfigCertAlertNotification that the HTTPS certificate was changed on the PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.1.9 |
userNotifications OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.500.2 |
userLoginAlertNotification that a user logged onto the PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.2.1 |
userLoginFailAlertNotification that a user failed to log onto the PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.2.2 |
userAddAlertNotification that a user was added to the PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.2.3 |
userDeleteAlertNotification that a user was deleted from the PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.2.4 |
userModifiedAlertNotification that a user was modified on the PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.2.5 |
userGroupAddAlertNotification that a user group was added to the PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.2.6 |
userGroupDeleteAlertNotification that a user group was deleted from the PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.2.7 |
userGroupModifyAlertNotification that a user group was modified on the PDU. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.2.8 |
inletNotifications OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.500.3 |
branchNotifications OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.500.4 |
outletNotifications OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.500.5 |
outletStateChangeAlertThe outlet state has changed. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.5.1 |
environNotification OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.500.6 |
environMaxTempAlertThe temperature sensor reached the Maximum limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.6.1 |
environMinTempAlertThe temperature sensor reached the minimum limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.6.2 |
environMaxHumidAlertThe humidity sensor reached the maximum limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.6.3 |
environMinHumidAlertThe humidity sensor reached the maximum limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.6.4 |
environMaxWarnTempAlertThe temperature sensor reached the Maximum limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.6.5 |
environMinWarnTempAlertThe temperature sensor reached the minimum limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.6.6 |
environMaxWarnHumidAlertThe humidity sensor reached the maximum limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.6.7 |
environMinWarnHumidAlertThe humidity sensor reached the maximum limit. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.6.8 |
easNotification OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.500.7 |
easScanPassAlertA card was scanned and the associated user was authenticated and authorized to access the cabinet. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.7.1 |
easScanFailAlertA card was scanned but was not authenticated or authorized to access the cabinet. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.7.2 |
easDoorOpenAlertNotification that a door was opened. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.7.3 |
easDoorCloseAlertNotification that a door was closed. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.7.4 |
easLockOpenAlertNotification that a lock was opened. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.7.5 |
easLockCloseAlertNotification that a lock was closed. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.7.6 |
easDoorExtOpenAlertNotification that a door was open for longer that the time set in cpiEasDoorOpenAlarmTime setting. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.7.7 |
easDoorExtOpenClearAlertNotification that a door was open for longer that the time set in cpiEasDoorOpenAlarmTime setting. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.7.8 |
easForceUnlockAlertNotification that a door was open for longer that the time set in cpiEasDoorOpenAlarmTime setting. NOTIFICATION-TYPE .1.3.6.1.4.1.30932.1.10.1.500.7.9 |
mibconformance OBJECT IDENTIFIER .1.3.6.1.4.1.30932.1.10.1.600 |