CONTEG-DATABUS-MIB
AI MIB Summary
The CONTEG-DATABUS-MIB enables SNMP-based monitoring and management of Conteg network-enabled databus devices, specifically tracking interface status, data transmission counters, and bus communication health metrics.
This MIB describes the SNMP functions of network enabled databus devices.
Main OID:
contegDatabusMIB.1.3.6.1.4.1.28402.12.1
230
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
230 total| Object Name |
|---|
contegDatabusMIBThis MIB describes the SNMP functions of network enabled databus devices. MODULE-IDENTITY .1.3.6.1.4.1.28402.12.1 |
sdbMIBNotifications OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.0 |
sdbDevSsDeviceStatusCodeChangedDevice status code changed. OBJECTS { sdbDevSsDeviceStatusCode } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.1 |
sdbDevSsTemperatureAlertDetectedTemperature alert detected. Internal temperature alert: OBJECTS { sdbDevSsTemperatureAlert, sdbDevMsIntTemperature, sdbDevMsIntTemperaturePeak } External analog temperature alert: OBJECTS { sdbDevSsTemperatureAlert, sdbDevMsExtTemperature, sdbDevMsExtTemperaturePeak } External digital temperature alert: OBJECTS { sdbDevSsTemperatureAlert, sdbDevSnsValue } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.2 |
sdbDevSsInputCurrentAlertDetectedInput current alert detected. OBJECTS { sdbDevSsInputCurrentAlert, sdbDevInActualCurrent } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.3 |
sdbDevSsOutletCurrentAlertDetectedOutlet current alert detected. OBJECTS { sdbDevSsOutletCurrentAlert, sdbDevOutMtActualCurrent } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.4 |
sdbDevSsInputVoltageAlertDetectedInput voltage alert detected. OBJECTS { sdbDevSsInputVoltageAlert, sdbDevInActualVoltage } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.5 |
sdbDevSsOutletCurrentDropAlertDetectedOutlet current drop alert detected. OBJECTS { sdbDevSsOutletCurrentDropAlert, sdbDevOutMtActualCurrent } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.6 |
sdbDevSsInputCurrentDropAlertDetectedInput current drop alert detected. OBJECTS { sdbDevSsInputCurrentDropAlert, sdbDevInActualCurrent } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.7 |
sdbDevSsSensorChangeAlertDetectedSensor channel change alert detected. OBJECTS { sdbDevSsSensorChangeAlert } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.8 |
sdbMgmtStsRingStateChangedRing state changed. Ring state changded to open: OBJECTS { sdbMgmtStsRingState, sdbMgmtStsRingBreachIndex } Ring state changded to closed: OBJECTS { sdbMgmtStsRingState } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.9 |
sdbDevSsOutletVoltageDropAlertDetectedOutlet voltage drop alert detected. OBJECTS { sdbDevSsOutletVoltageDropAlert, sdbDevOutMtActualVoltage } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.10 |
sdbDevSsBranchCurrentAlertDetectedBranch current alert detected. OBJECTS { sdbDevSsBranchCurrentAlert, sdbDevBranchActualCurrent } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.11 |
sdbDevSsBranchVoltageAlertDetectedBranch current alert detected. OBJECTS { sdbDevSsBranchVoltageAlert, sdbDevBranchActualVoltage } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.12 |
sdbDevSsNeutralCurrentAlertDetectedInput current alert detected. OBJECTS { sdbDevSsNeutralCurrentAlert, sdbDevTotalsNeutralCurrent } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.13 |
sdbDevSsResidualCurrentAlertDetectedResidual current alert detected. OBJECTS { sdbDevSsResidualCurrentAlert, sdbDevMsResidualCurrent, sdbDevMsResidualPeak } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.14 |
sdbDevSsHardwareAlertDetectedHardware alert detected. OBJECTS { sdbDevSsHardwareAlert } NOTIFICATION-TYPE .1.3.6.1.4.1.28402.12.1.0.15 |
sdbMIBObjects OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1 |
sdbMgmt OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.1 |
sdbMgmtStatus OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.1.1 |
sdbMgmtStsDevicesThe number of devices on the databus.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.1.1.1 |
sdbMgmtStsAddressableDevicesThe number of devices on the databus addressable by snmp.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.1.1.2 |
sdbMgmtStsNewDevicesThe number of new devices on the databus.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.1.1.3 |
sdbMgmtStsDuplicateDevicesThe number of duplicate devices on the databus.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.1.1.4 |
sdbMgmtStsRingStateIf the device is in a bridge-like mode, this will indicate the actual state of the databus.ro Enumeration .1.3.6.1.4.1.28402.12.1.1.1.1.5 |
sdbMgmtStsRingBreachIndexIndicates the breach index if the current state of the data bus is open. If the data bus is closed this has no meaning.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.1.1.6 |
sdbMgmtControl OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.1.2 |
sdbMgmtCtrlScanPerform a bus scan. To verify if scanning is completed the value of this object can be read. During the bus scan the value remains 1. When the bus scan completed the value will be 0.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.1.2.1 |
sdbMgmtCtrlRenumberAllFromNRenumber all devices on the databus. If set to 0 all units will be set to 0. If set to another value, all units will be numbered in sequence starting from the value set.rw Integer32 .1.3.6.1.4.1.28402.12.1.1.1.2.2 |
sdbMgmtCtrlRenumberZerosRenumber all devices on the databus having address 0. Renumbering will be done in sequence. The sequence starts with the highest address found on the databus.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.1.2.3 |
sdbMgmtCtrlDevicesTableA table containing information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsDevices. SEQUENCE OF SdbMgmtCtrlDevicesEntry .1.3.6.1.4.1.28402.12.1.1.1.2.4 |
sdbMgmtCtrlDevicesEntryInformation entry containing objects of a particular databus device. SdbMgmtCtrlDevicesEntry .1.3.6.1.4.1.28402.12.1.1.1.2.4.1 |
sdbMgmtCtrlDevIndexA unique value for each device. Its value ranges between 1 and the value of sdbMgmtStsDevices with a maximum of 255. The value for each device will remain constant until the next scan is performed. Integer32 .1.3.6.1.4.1.28402.12.1.1.1.2.4.1.1 |
sdbMgmtCtrlDevUnitAddressUser defined address. This will be used for addressing the device on the databus.rw Integer32 .1.3.6.1.4.1.28402.12.1.1.1.2.4.1.2 |
sdbMgmtCtrlDevHardwareAddressHardware serial number. This cannot be changed. It can be used as backup unit address. format as 3 unsigned ints separated by dashes: int - int - intro DisplayString .1.3.6.1.4.1.28402.12.1.1.1.2.4.1.3 |
sdbMgmtCtrlDevIsNewIndication if the device is new on the databus.ro Enumeration .1.3.6.1.4.1.28402.12.1.1.1.2.4.1.4 |
sdbMgmtCtrlDevIsDuplicateIndication if the device is conflicting with another device on the databus.ro Enumeration .1.3.6.1.4.1.28402.12.1.1.1.2.4.1.5 |
sdbDevice OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2 |
sdbDevIdentification OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.1 |
sdbDevIdTableA table containing identification information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. SEQUENCE OF SdbDevIdEntry .1.3.6.1.4.1.28402.12.1.1.2.1.1 |
sdbDevIdEntryInformation entry containing information objects of a particular databus device. SdbDevIdEntry .1.3.6.1.4.1.28402.12.1.1.2.1.1.1 |
sdbDevIdSPDMVersionData model version.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.1 |
sdbDevIdFirmwareVersionThe firmware revision number.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.2 |
sdbDevIdBuildNumberDate and time the firmware was built.ro DisplayString .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.3 |
sdbDevIdSalesOrderNumberSP sales order number.ro DisplayString .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.4 |
sdbDevIdProductIdSP product id.ro DisplayString .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.5 |
sdbDevIdSerialNumberSP serial number.ro DisplayString .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.6 |
sdbDevIdHardwareAddressHardware serial number. This can not be changed. It can be used as backup unit address. Format as 3 unsigned ints separated by dashes (-) e.g. 12345-54321-00000ro DisplayString .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.7 |
sdbDevIdMacAddressThe MAC address. This can not be changed. It represents an 802 MAC address as if it were transmitted least significant bit first. Format as six groups of 2 hexadecimal digits separated by colons (:) e.g. D0:22:12:B0:00:00ro DisplayString .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.8 |
sdbDevIdUnitAddressUser defined address. This will be used for addressing the device on the databus.rw Integer32 .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.9 |
sdbDevIdNameUser configurable device name or identifier.rw DisplayString .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.10 |
sdbDevIdLocationUser configurable device location identifier.rw DisplayString .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.11 |
sdbDevIdVanityTagCharacters to be displayed as vanity text in display.rw DisplayString .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.12 |
sdbDevIdIndexA unique value for each device. Its value represents the unit address of the device and is used to address individual devices in the tree. The value for each device will remain constant until the next scan is performed. Integer32 .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.13 |
sdbDevIdDeviceTypeA unique value for each device group. Its value represents the device type of the device. Refer to manual for more information.ro Enumeration .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.14 |
sdbDevIdLocateUnitThe LCD-backlight flashes in a heartbeat rhythm to locate the unit.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.15 |
sdbDevIdConfigTypeWiring configuration type used.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.1.1.1.16 |
sdbDevConfiguration OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.2 |
sdbDevCfTableA table containing configuration information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. SEQUENCE OF SdbDevCfEntry .1.3.6.1.4.1.28402.12.1.1.2.2.1 |
sdbDevCfEntryConfiguration entry containing configuration objects of a particular databus device. SdbDevCfEntry .1.3.6.1.4.1.28402.12.1.1.2.2.1.1 |
sdbDevCfPhasesNumber of phases for input metering.ro Integer32 (0 | 1 | 3) .1.3.6.1.4.1.28402.12.1.1.2.2.1.1.1 |
sdbDevCfOutletsTotalTotal number of outlets including hardwired without switch/metered modules.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.2.1.1.2 |
sdbDevCfOutletsSwitchedNumber of switched outlets. If outlet numbering is non-contiguous its the highest outlet number.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.2.1.1.3 |
sdbDevCfOutletsMeteredNumber of metered outlets. If outlet numbering is non-contiguous its the highest outlet number.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.2.1.1.4 |
sdbDevCfSensorsThe number sensors.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.2.1.1.5 |
sdbDevCfMaximumLoadMaximum rated load of device per phasero Integer32 (16 | 32) UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.2.1.1.6 |
sdbDevCfBranchesNumber of branches for input metering.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.2.1.1.7 |
sdbDevCfNeutralNuetral current measurement.ro Integer32 (0 | 1) .1.3.6.1.4.1.28402.12.1.1.2.2.1.1.8 |
sdbDevCfTempSensorsNumber of temperature sensors present in the system.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.2.1.1.9 |
sdbDevCfTotalsThe number of totals rows for the configuration.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.2.1.1.10 |
sdbDevSystemStatus OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.3 |
sdbDevSsTableA table containing system status information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. SEQUENCE OF SdbDevSsEntry .1.3.6.1.4.1.28402.12.1.1.2.3.1 |
sdbDevSsEntrySystem status entry containing system status objects of a particular databus device. SdbDevSsEntry .1.3.6.1.4.1.28402.12.1.1.2.3.1.1 |
sdbDevSsDeviceStatusCodeReturns an internal status or error code. A value of 0 means OK. If not 0 it can be any of the following codes. Multiple status codes can be active at the same time. The value will be the sum of the active status codes. 1 = alert flagged 2 = settings(s) initialized 4 = power-on reset 8 = external reset 16 = watchdog timer caused reset 32 = brownout detected 64 = controller error 128 = slave module was resetro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.1 |
sdbDevSsTemperatureAlertAn alert has been raised due to temperature exceeding treshhold. 0 = no alert 1 = internal temperature sensor 2 = external temperature sensorro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.2 |
sdbDevSsInputCurrentAlertAn alert has been raised due to current exceeding treshhold. The value indicates the exceeding phase. 0 = no alert.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.3 |
sdbDevSsOutletCurrentAlertAn alert has been raised due to current exceeding treshhold. The value indicates the exceeding outlet. 0 = no alert.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.4 |
sdbDevSsInputVoltageAlertAn alert has been raised due to a voltage dip. The value indicates the dipped phase. 0 = no alert.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.5 |
sdbDevSsOutletCurrentDropAlertAn alert has been raised due to the current of a metered outlet suddenly dropping to near zero, possibly indicating a blown fuse. The value indicates the dropped outlet. 0 = no alert.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.6 |
sdbDevSsInputCurrentDropAlertAn alert has been raised due to the current of a metered input suddenly dropping to near zero, possibly indicating a blown fuse. The value indicates the dropped phase. 0 = no alert.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.7 |
sdbDevSsSensorChangeAlertAn alert has been raised due to a change in the number of sensors. The value indicates the previous amount of sensors.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.8 |
sdbDevSsOutletVoltageDropAlertAn alert has been raised due to voltage drop on this outlet. The value indicates the first failed outlet.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.9 |
sdbDevSsBranchCurrentAlertAn alert has been raised due to current exceeding treshhold. The value indicates the exceeding branch. 0 = no alert.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.10 |
sdbDevSsBranchVoltageAlertAn alert has been raised due to a voltage dip. The value indicates the dipped branch. 0 = no alert.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.11 |
sdbDevSsNeutralCurrentAlertAn alert has been raised due to current exceeding treshhold. 0 = no alert 1 = current alertro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.12 |
sdbDevSsResidualCurrentAlertA residual current alert has been raised. 0 = no alert 1 = current exceeding treshhold alert 2 = sensor errorro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.13 |
sdbDevSsHardwareAlert0 = no alarm >0 = or slave number for alertro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.3.1.1.14 |
sdbDevReset OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.4 |
sdbDevRsTableA table providing reset capabilities to devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. SEQUENCE OF SdbDevRsEntry .1.3.6.1.4.1.28402.12.1.1.2.4.1 |
sdbDevRsEntryReset entry providing reset objects of a particular databus device. SdbDevRsEntry .1.3.6.1.4.1.28402.12.1.1.2.4.1.1 |
sdbDevRsRebootWarm reboot/reset of device controller. NOTE: this will have NO effect on outlet status!rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.4.1.1.1 |
sdbDevRsResetAlertsReset all alert signals and device status code.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.4.1.1.2 |
sdbDevRsZeroInputKWhSubtotalReset of all input kWh subtotal counters to zero.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.4.1.1.3 |
sdbDevRsZeroOutletKWhSubtotalReset of all outlet kWh subtotal counter to zero.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.4.1.1.4 |
sdbDevRsResetPeaksAndDipsReset all peak and dip values to zero.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.4.1.1.5 |
sdbDevSettings OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.5 |
sdbDevStTableA table containing setting information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. SEQUENCE OF SdbDevStEntry .1.3.6.1.4.1.28402.12.1.1.2.5.1 |
sdbDevStEntrySetting entry containing settings objects of a particular databus device. SdbDevStEntry .1.3.6.1.4.1.28402.12.1.1.2.5.1.1 |
sdbDevStAutoResetAlertsAuto reset alerts configuration. If set to 0 the auto reset alerts feature is disabled. If set to a value greater then 0, the auto reset alerts feature is enabled and alerts will get cleared after the configured amount of seconds since the last alert condition have passed.rw Integer32 .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.2 |
sdbDevStExtendedNamesUse original or longer names for inputs, outlets and sensors.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.3 |
sdbDevStPeakDurationAmount of ms a current peak should last before an alert is raised.rw MilliSecond .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.4 |
sdbDevStFixedOutletDelayMinimal delay between two successive relay switches in milliseconds. Minimal delay is 100 ms. Will always be respected!rw MilliSecond .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.5 |
sdbDevStPowerSaverModeSet backlight on time in seconds. 0 keeps display always on. Note that keeping the backlight on may decrease luminosity over time.rw Second (0 | 10 | 60 | 120 | 240) UNITS "s" .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.6 |
sdbDevStOutletPowerUpModeBehaviour of outlets on power-up.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.7 |
sdbDevStMaximumTemperatureMaximum temperature threshold An alert will be generated whenever the temperature is above this value. Zero means disabled.rw Integer32 .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.8 |
sdbDevStDisplayOrientationDisplay orientation.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.9 |
sdbDevStLocalAlertResetAllow alerts to be reset locally on device by pushing one of the buttons.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.10 |
sdbDevStCurrentDropDetectionEnables the current drop detection function.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.11 |
sdbDevStUsbModeAllow the USB port to be used for specific tasksrw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.13 |
sdbDevStSensorChangeAlertModeEnable sensoe change alertsrw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.14 |
sdbDevStOutletUnlockOverrideOverrides the timeout. If this is set to 1 then the timeout will be ignored, otherwise the timeout will be taken into account.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.5.1.1.15 |
sdbDevInput OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.6 |
sdbDevInTableA table containing information of inputs of devices connected to the databus. SEQUENCE OF SdbDevInEntry .1.3.6.1.4.1.28402.12.1.1.2.6.1 |
sdbDevInEntryInputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevInIndex to identify a particular input of the device identified by sdbDevIdIndex. SdbDevInEntry .1.3.6.1.4.1.28402.12.1.1.2.6.1.1 |
sdbDevInIndexA unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases. Integer32 .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.1 |
sdbDevInKWhTotalTotal kWh value of an input. This value can not be reset.ro KiloWattHour UNITS "kWh" .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.2 |
sdbDevInKWhSubtotalSubtotal kWh value of an input. This value can be reset.ro KiloWattHour UNITS "kWh" .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.3 |
sdbDevInPowerFactorPower factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This value is expressed as a percentage between 0% and 100%.ro CentiPercent UNITS "%" .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.4 |
sdbDevInActualCurrentActual apparent, RMS current.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.5 |
sdbDevInPeakCurrentPeak apparent, RMS current. Highest value since last reset of the alerts.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.6 |
sdbDevInActualVoltageThe actual voltage.ro CentiVolt UNITS "V" .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.7 |
sdbDevInMinVoltageRMS voltage dip. Lowest value since reset of alerts.ro CentiVolt UNITS "V" .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.8 |
sdbDevInPowerVoltAmpereCalculated apparent power.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.9 |
sdbDevInPowerWattCalculated real power.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.10 |
sdbDevInMaxAmpsMaximum current per input phase. Should last at least sdbDevStPeakDuration ms before triggering an alert.rw CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.11 |
sdbDevInCTRatioThe multiplier to use for the input CTs.rw Integer32 .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.12 |
sdbDevInNameUser configurable naming of inputs or phases.rw DisplayString .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.13 |
sdbDevInZeroKWhSubtotalReset input kWh subtotal counter of a single input to zero.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.6.1.1.14 |
sdbDevOutlet OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.7 |
sdbDevOutTableA table containing information of outlets of devices connected to the databus. SEQUENCE OF SdbDevOutEntry .1.3.6.1.4.1.28402.12.1.1.2.7.1 |
sdbDevOutEntryOutlets entry containing objects of an outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevOutIndex to identify a particular outlet of the device identified by sdbDevIdIndex. SdbDevOutEntry .1.3.6.1.4.1.28402.12.1.1.2.7.1.1 |
sdbDevOutIndexA unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsTotal. Integer32 .1.3.6.1.4.1.28402.12.1.1.2.7.1.1.1 |
sdbDevOutNameUser configurable naming of individual outlets.rw DisplayString .1.3.6.1.4.1.28402.12.1.1.2.7.1.1.2 |
sdbDevOutMtTableA table containing information of metered outlets of devices connected to the databus. SEQUENCE OF SdbDevOutMtEntry .1.3.6.1.4.1.28402.12.1.1.2.7.2 |
sdbDevOutMtEntryMetered outlets entry containing objects of a metered outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevOutMtIndex to identify a particular outlet of the device identified by sdbDevIdIndex. SdbDevOutMtEntry .1.3.6.1.4.1.28402.12.1.1.2.7.2.1 |
sdbDevOutMtIndexA unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsMetered. Integer32 .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.1 |
sdbDevOutMtKWhTotalTotal kWh value of an outlet. This value can not be reset.ro KiloWattHour UNITS "kWh" .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.2 |
sdbDevOutMtKWhSubtotalSubotal kWh value of an outlet. This value can be reset.ro KiloWattHour UNITS "kWh" .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.3 |
sdbDevOutMtPowerFactorPower factor of outlet. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This number is expressed as a percentage between 0% and 100%.ro CentiPercent UNITS "%" .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.4 |
sdbDevOutMtActualCurrentActual apparent, RMS current.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.5 |
sdbDevOutMtPeakCurrentPeak apparent, RMS current. Highest value since last reset of the alerts.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.6 |
sdbDevOutMtActualVoltageActual voltage on outlet.ro CentiVolt UNITS "V" .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.7 |
sdbDevOutMtMaxAmpsMaximum current per outlet. Should last at least sdbDevStPeakDuration ms before triggering an alert.rw CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.8 |
sdbDevOutMtCTRatioThe multiplier to use for the outlet CTs.rw Integer32 .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.9 |
sdbDevOutMtPowerVoltAmpereCalculated apparent power.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.10 |
sdbDevOutMtPowerWattCalculated real power.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.7.2.1.11 |
sdbDevOutSwTableA table containing information of switched outlets of devices connected to the databus. SEQUENCE OF SdbDevOutSwEntry .1.3.6.1.4.1.28402.12.1.1.2.7.3 |
sdbDevOutSwEntrySwitched outlets entry containing objects of a switched outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevOutSwIndex to identify a particular outlet of the device identified by sdbDevIdIndex. SdbDevOutSwEntry .1.3.6.1.4.1.28402.12.1.1.2.7.3.1 |
sdbDevOutSwIndexA unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsSwitched. Integer32 .1.3.6.1.4.1.28402.12.1.1.2.7.3.1.1 |
sdbDevOutSwCurrentStateThe actual state of the outlet relay. Note that Writing is only effective after setting sdbDevOutSwUnlock.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.7.3.1.2 |
sdbDevOutSwScheduledA one indicates pending activity; the switch delay has not yet expired.ro Enumeration .1.3.6.1.4.1.28402.12.1.1.2.7.3.1.3 |
sdbDevOutSwUnlockSwitching and rebooting is unlocked for 10 seconds by writing a 1.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.7.3.1.4 |
sdbDevOutSwIndividualOutletDelayDelay before an individual outlet switches on at power-up.rw Second .1.3.6.1.4.1.28402.12.1.1.2.7.3.1.5 |
sdbDevOutSwRebootReboot outlet relay if current state is on and outlet is unlocked; The outlet will be turned on after 10 seconds.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.7.3.1.6 |
sdbDevSensor OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.8 |
sdbDevMeasuresTableA table containing information of temperatures of devices connected to the databus. SEQUENCE OF SdbDevMeasuresEntry .1.3.6.1.4.1.28402.12.1.1.2.8.1 |
sdbDevMeasuresEntryDevice measures entry containing temperature information objects of a particular databus device. SdbDevMeasuresEntry .1.3.6.1.4.1.28402.12.1.1.2.8.1.1 |
sdbDevMsIntTemperatureActual internal device temperature in deg Cro CentiCelsius UNITS "degrees Celsius" .1.3.6.1.4.1.28402.12.1.1.2.8.1.1.1 |
sdbDevMsExtTemperatureActual external device temperature sensor in deg C.ro CentiCelsius UNITS "degrees Celsius" .1.3.6.1.4.1.28402.12.1.1.2.8.1.1.2 |
sdbDevMsIntTemperaturePeakPeak internal device temperature since last reset of alerts.ro CentiCelsius UNITS "degrees Celsius" .1.3.6.1.4.1.28402.12.1.1.2.8.1.1.3 |
sdbDevMsExtTemperaturePeakPeak external device temperature since last reset of alerts.ro CentiCelsius UNITS "degrees Celsius" .1.3.6.1.4.1.28402.12.1.1.2.8.1.1.4 |
sdbDevMsResidualCurrentResidual current.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.8.1.1.5 |
sdbDevMsResidualPeakPeak residual current.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.8.1.1.6 |
sdbDevSnsTableA table containing information of sensors of devices connected to the databus. SEQUENCE OF SdbDevSnsEntry .1.3.6.1.4.1.28402.12.1.1.2.8.2 |
sdbDevSnsEntrySensors entry containing objects of a sensor of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevSnsIndex to identify a particular sensor of the device identified by sdbDevIdIndex. SdbDevSnsEntry .1.3.6.1.4.1.28402.12.1.1.2.8.2.1 |
sdbDevSnsIndexA unique value for each sensor. Its value ranges between 1 and the value of sdbDevCfSensors. Integer32 .1.3.6.1.4.1.28402.12.1.1.2.8.2.1.1 |
sdbDevSnsTypeType of connected sensor. T = Temperature (C) H = Humidity (%) I = dry switch contactro DisplayString .1.3.6.1.4.1.28402.12.1.1.2.8.2.1.2 |
sdbDevSnsValueValue of connected sensorro CentiValue .1.3.6.1.4.1.28402.12.1.1.2.8.2.1.3 |
sdbDevSnsNameUser definable name for sensors.rw DisplayString .1.3.6.1.4.1.28402.12.1.1.2.8.2.1.4 |
sdbDevPerformance OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.9 |
sdbDevPerformanceTableA table containing information of sensors of devices connected to the databus. SEQUENCE OF SdbDevPerformanceEntry .1.3.6.1.4.1.28402.12.1.1.2.9.1 |
sdbDevPerformanceEntryPerformance counters of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevPerformanceIndex to identify a particular counter of the device identified by sdbDevIdIndex. SdbDevPerformanceEntry .1.3.6.1.4.1.28402.12.1.1.2.9.1.1 |
sdbDevPerformanceIndexA unique value for each counter. Its value ranges between 1 and 16. Integer32 .1.3.6.1.4.1.28402.12.1.1.2.9.1.1.1 |
sdbDevPerformanceValueValue of counterro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.9.1.1.2 |
sdbDevPerformanceMaxMax of counterro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.9.1.1.3 |
sdbDevPerformanceLimitLimit of counterro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.9.1.1.4 |
sdbDevPerformanceNameUser definable name for counter.rw DisplayString .1.3.6.1.4.1.28402.12.1.1.2.9.1.1.5 |
sdbDevPerformanceResetTableA table containing the last reset reason of the device SEQUENCE OF SdbDevPerformanceResetEntry .1.3.6.1.4.1.28402.12.1.1.2.9.2 |
sdbDevPerformanceResetEntrySetting entry containing settings objects of a particular databus device. SdbDevPerformanceResetEntry .1.3.6.1.4.1.28402.12.1.1.2.9.2.1 |
sdbDevPerformanceResetReasonLast reset reason.rw DisplayString .1.3.6.1.4.1.28402.12.1.1.2.9.2.1.1 |
sdbDevResetUptimeUptime before last resetro Unsigned32 .1.3.6.1.4.1.28402.12.1.1.2.9.2.1.2 |
sdbDevBranches OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.10 |
sdbDevBranchTableA table containing information of inputs of devices connected to the databus. SEQUENCE OF SdbDevBranchEntry .1.3.6.1.4.1.28402.12.1.1.2.10.1 |
sdbDevBranchEntryInputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevBranchIndex to identify a particular input of the device identified by sdbDevIdIndex. SdbDevBranchEntry .1.3.6.1.4.1.28402.12.1.1.2.10.1.1 |
sdbDevBranchIndexA unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases. Integer32 .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.1 |
sdbDevBranchKWhTotalTotal kWh value of an input. This value can not be reset.ro KiloWattHour UNITS "kWh" .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.2 |
sdbDevBranchKWhSubtotalSubtotal kWh value of an input. This value can be reset.ro KiloWattHour UNITS "kWh" .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.3 |
sdbDevBranchPowerFactorPower factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This value is expressed as a percentage between 0% and 100%.ro CentiPercent UNITS "%" .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.4 |
sdbDevBranchActualCurrentActual apparent, RMS current.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.5 |
sdbDevBranchPeakCurrentPeak apparent, RMS current. Highest value since last reset of the alerts.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.6 |
sdbDevBranchActualVoltageThe actual voltage.ro CentiVolt UNITS "V" .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.7 |
sdbDevBranchMinVoltageRMS voltage dip. Lowest value since reset of alerts.ro CentiVolt UNITS "V" .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.8 |
sdbDevBranchPowerVoltAmpereCalculated apparent power.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.9 |
sdbDevBranchPowerWattCalculated real power.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.10 |
sdbDevBranchMaxAmpsMaximum current per input phase. Should last at least sdbDevStPeakDuration ms before triggering an alert.rw CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.11 |
sdbDevBranchCTRatioThe multiplier to use for the input CTs.rw Integer32 .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.12 |
sdbDevBranchNameUser configurable naming of branches.rw DisplayString .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.13 |
sdbDevBranchZeroKWhSubtotalReset input kWh subtotal counter of a single input to zero.rw Enumeration .1.3.6.1.4.1.28402.12.1.1.2.10.1.1.14 |
sdbDevTotals OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.1.2.11 |
sdbDevTotalsTableA table containing information of inputs of devices connected to the databus. SEQUENCE OF SdbDevTotalsEntry .1.3.6.1.4.1.28402.12.1.1.2.11.1 |
sdbDevTotalsEntryInputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevTotalsIndex to identify a particular input of the device identified by sdbDevIdIndex. SdbDevTotalsEntry .1.3.6.1.4.1.28402.12.1.1.2.11.1.1 |
sdbDevTotalsIndexA unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases. Integer32 .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.1 |
sdbDevTotalsKWhTotalTotal kWh value of an input. This value can not be reset.ro KiloWattHour UNITS "kWh" .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.2 |
sdbDevTotalsPowerFactorPower factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This value is expressed as a percentage between 0% and 100%.ro CentiPercent UNITS "%" .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.3 |
sdbDevTotalsActualCurrentActual apparent, RMS current.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.4 |
sdbDevTotalsPeakCurrentPeak apparent, RMS current. Highest value since last reset of the alerts.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.5 |
sdbDevTotalsPowerVoltAmpereCalculated apparent power.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.6 |
sdbDevTotalsPowerWattCalculated real power.ro Integer32 .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.7 |
sdbDevTotalsNeutralCurrentNeutral current of phases.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.8 |
sdbDevTotalsNeutralPeakPeak neutral current of phases.ro CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.9 |
sdbDevTotalsNeutralMaxAmpsMaximum neutral current. Should last at least sdbDevStPeakDuration ms before triggering an alert.rw CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.10 |
sdbDevTotalsResidualMaxAmpsMaximum residual current. Should last at least sdbDevStPeakDuration ms before triggering an alert.rw CentiAmpere UNITS "A" .1.3.6.1.4.1.28402.12.1.1.2.11.1.1.11 |
sdbMIBConformance OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.2 |
sdbMIBCompliances OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.2.1 |
sdbMIBComplianceThe requirements for conformance to the CONTEG-DATABUS-MIB. Unknown .1.3.6.1.4.1.28402.12.1.2.1.1 |
sdbMIBGroups OBJECT IDENTIFIER .1.3.6.1.4.1.28402.12.1.2.2 |
sdbMIBNotificationGroupA collection of notifications. Unknown .1.3.6.1.4.1.28402.12.1.2.2.1 |
sdbMIBDevIdGroupA collection of objects providing identification information about the device. Unknown .1.3.6.1.4.1.28402.12.1.2.2.3 |
sdbMIBDevCfGroupA collection of objects providing configuration information about the device. Unknown .1.3.6.1.4.1.28402.12.1.2.2.4 |
sdbMIBDevSsGroupA collection of objects providing status information about the device. Unknown .1.3.6.1.4.1.28402.12.1.2.2.5 |
sdbMIBDevRsGroupGroups resettable attributes op the device. Unknown .1.3.6.1.4.1.28402.12.1.2.2.6 |
sdbMIBDevStGroupA collection of objects providing the actual settings about the device. Unknown .1.3.6.1.4.1.28402.12.1.2.2.7 |
sdbMIBDevInGroupA collection of objects providing the actual input measurements of the device. Unknown .1.3.6.1.4.1.28402.12.1.2.2.8 |
sdbMIBDevOutGroupA collection of objects providing the actual outlet measurements of the device. Unknown .1.3.6.1.4.1.28402.12.1.2.2.9 |
sdbMIBDevOutMtGroupA collection of objects providing the actual outlet measurements of the device. Unknown .1.3.6.1.4.1.28402.12.1.2.2.10 |
sdbMIBDevOutSwGroupA collection of objects providing the actual outlet measurements of the device. Unknown .1.3.6.1.4.1.28402.12.1.2.2.11 |
sdbMIBDevSensorGroupA collection of objects providing the actual environmental measurements of the device. Unknown .1.3.6.1.4.1.28402.12.1.2.2.12 |
sdbMIBMgmtStatusGroupA collection of objects providing management status information about the databus. Unknown .1.3.6.1.4.1.28402.12.1.2.2.13 |
sdbMIBMgmtControlGroupA collection of objects providing management control information about the databus. Unknown .1.3.6.1.4.1.28402.12.1.2.2.14 |
sdbMIBDevPerformanceGroupA collection of objects providing performance information about the MCU Unknown .1.3.6.1.4.1.28402.12.1.2.2.15 |