Home/Catalog/CCPOWER-MIB

CCPOWER-MIB

Detailed view of the defined objects, syntax rules, and hierarchical paths.

194
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

194 total
Object Name
ccpower
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642
RFC1213-MIB
Unknown
.1.3.6.1.4.1.18642
breakerTrapBreaker has tripped.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.0
fuseTrapFuse has opened.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.1
batteryDisconnectTrapBattery disconnect has operated.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.2
programmableTrapProgrammable alarm has occurred.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.3
highVoltageTrapFloat voltage has exceeded preset value. Return value: High voltage alarm XX.X volts.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.4
lowVoltageTrapFloat voltage is below preset value. Return value: Low voltage alarm XX.X volts.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.5
loadOverCurrentTrapLoad current has exceeded preset value. Return value: Load over current alarm XXXX amps.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.6
batteryFloatCurrentTrapBattery float current has exceeded preset value. Return value: Battery float current alarm XXXX amps.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.7
loadDisconnect1VoltageTrapLoad disconnect 1 voltage has dropped below preset value. Return value: Load disconnect 1 voltage XX.X volts.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.8
loadDisconnect2VoltageTrapLoad disconnect 2 voltage has dropped below preset value. Return value: Load disconnect 2 voltage XX.X volts.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.9
loadDisconnect3VoltageTrapLoad disconnect 3 voltage has dropped below preset value. Return value: Load disconnect 3 voltage XX.X volts.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.10
loadDisconnect1TemperatureTrapLoad disconnect 1 temperature has exceeded preset value. Return value: Load disconnect 1 temperature alarm XX C.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.11
loadDisconnect2TemperatureTrapLoad disconnect 2 temperature has exceeded preset value. Return value: Load disconnect 2 temperature alarm XX C.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.12
loadDisconnect3TemperatureTrapLoad disconnect 3 temperature has exceeded preset value. Return value: Load disconnect 3 temperature alarm XX C.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.13
rectifierFailureTrapRectifier failure. Return value: Rectifier failure.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.14
fanFailureTrapRectifier fan has failed. Return value: Fan failure.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.15
acFailureTrapRectifier has lost AC input power. Return value: AC failure.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.16
majorFailureTrapMultiple failures of AC, rectififers, fans or a programmed alarm. Return value: Multiple AC, fan, rectifier or optional alarm failures has occurred.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.17
batteryResistanceTrapBattery resistance has increased by a programmed percentage. Return value: Battery resistance alarm X.XXXX ohms, XXX %.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.18
batteryTestAbort1TrapBattery failure abort 1 has occured during battery resistance test. Return value: Battery test failure: Abort 1.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.19
batteryTestAbort2TrapBattery failure abort 2 has occured during battery resistance test. Return value: Battery test failure: Abort 2.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.20
batteryTestAbort3TrapBattery failure abort 3 has occured during battery resistance test. Return value: Battery test failure: Abort 3.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.21
breakerTrapClearBreaker alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.100
fuseTrapClearFuse alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.101
batteryDisconnectTrapClearBattery disconnect alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.102
programmableTrapClearProgrammable alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.103
highVoltageTrapClearHigh voltage alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.104
lowVoltageTrapClearLow voltage alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.105
loadOverCurrentTrapClearLoad over current alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.106
batteryFloatCurrentTrapClearBattery float current alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.107
loadDisconnect1VoltageTrapClearLoad disconnect 1 voltage alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.108
loadDisconnect2VoltageTrapClearLoad disconnect 2 voltage alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.109
loadDisconnect3VoltageTrapClearLoad disconnect 3 voltage alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.110
loadDisconnect1TemperatureTrapClearLoad disconnect 1 temperature alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.111
loadDisconnect2TemperatureTrapClearLoad disconnect 2 temperature alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.112
loadDisconnect3TemperatureTrapClearLoad disconnect 3 temperature alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.113
rectifierFailureTrapClearRectififer failure alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.114
fanFailureTrapClearFan failure alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.115
acFailureTrapClearAC failure alarm been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.116
majorFailureTrapClearMajor failure alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.117
batteryResistanceTrapClearBattery resistance alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.118
batteryTestAbort1TrapClearBattery test abort 1 alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.119
batteryTestAbort2TrapClearBattery test abort 2 alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.120
batteryTestAbort3TrapClearBattery test abort 3 alarm has been cleared.
TRAP-TYPE
.1.3.6.1.4.1.18642.0.121
dcSystem
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1
readWriteObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.1
settings
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.1.1
floatVoltageRectifier DC Output Voltage. Return value is XXX representing XX.X volts.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.1
overloadCurrentCurrent which when exceeded will cause an alarm. Return value is XXXX representing XXXX amps.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.2
highVoltageAlarmVoltage which when exceeded will cause an alarm. Return value is XXX representing XX.X volts.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.3
lowVoltageAlarmVoltage which when exceeded will cause an alarm. Return value is XXX representing XX.X volts.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.4
disconnect1VoltageVoltage which when exceeded will cause a specific load to disconnect. Return value is XXX representing XX.X volts.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.5
disconnect1TemperatureTemperature which when exceeded will cause a specific load to disconnect. Return value is XX representing XX C.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.6
disconnect1LoadShedSundayOffTime on Sunday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.7
disconnect1LoadShedMondayOffTime on Monday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.8
disconnect1LoadShedTuesdayOffTime on Tuesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.9
disconnect1LoadShedWednesdayOffTime on Wednesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.10
disconnect1LoadShedThursdayOffTime on Thursday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.11
disconnect1LoadShedFridayOffTime on Friday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.12
disconnect1LoadShedSaturdayOffTime on Saturday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.13
disconnect2VoltageVoltage which when exceeded will cause a specific load to disconnect. Return value is XXX representing XX.X volts.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.14
disconnect2TemperatureTemperature which when exceeded will cause a specific load to disconnect. Return value is XX representing XX C.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.15
disconnect2LoadShedSundayOffTime on Sunday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.16
disconnect2LoadShedMondayOffTime on Monday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.17
disconnect2LoadShedTuesdayOffTime on Tuesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.18
disconnect2LoadShedWednesdayOffTime on Wednesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.19
disconnect2LoadShedThursdayOffTime on Thursday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.20
disconnect2LoadShedFridayOffTime on Friday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.21
disconnect2LoadShedSaturdayOffTime on Saturday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.22
disconnect3VoltageVoltage which when exceeded will cause a specific load to disconnect. Return value is XXX representing XX.X volts.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.23
disconnect3TemperatureTemperature which when exceeded will cause a specific load to disconnect. Return value is XX representing XX C.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.24
disconnect3LoadShedSundayOffTime on Sunday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.25
disconnect3LoadShedMondayOffTime on Monday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.26
disconnect3LoadShedTuesdayOffTime on Tuesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.27
disconnect3LoadShedWednesdayOffTime on Wednesday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.28
disconnect3LoadShedThursdayOffTime on Thursday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.29
disconnect3LoadShedFridayOffTime on Friday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.30
disconnect3LoadShedSaturdayOffTime on Saturday which when reached will cause a specific load to disconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.31
reconnect1VoltageVoltage which when reached will cause a specific load to reconnect. Return value is XXX representing XX.X volts.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.32
reconnect1LoadShedSundayOnTime which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.33
reconnect1LoadShedMondayOnTime on Monday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.34
reconnect1LoadShedTuesdayOnTime on Tuesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.35
reconnect1LoadShedWednesdayOnTime on Wednesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.36
reconnect1LoadShedThursdayOnTime on Thursday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.37
reconnect1LoadShedFridayOnTime on Friday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.38
reconnect1LoadShedSaturdayOnTime on Saturday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.39
reconnect2VoltageVoltage which when reached will cause a specific load to reconnect. Return value is XXX representing XX.X volts.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.40
reconnect2LoadShedSundayOnTime on Sunday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.41
reconnect2LoadShedMondayOnTime on Monday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.42
reconnect2LoadShedTuesdayOnTime on Tuesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.43
reconnect2LoadShedWednesdayOnTime on Wednesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.44
reconnect2LoadShedThursdayOnTime on Thursday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.45
reconnect2LoadShedFridayOnTime on Friday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.46
reconnect2LoadShedSaturdayOnTime on Saturday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.47
reconnect3VoltageVoltage which when reached will cause a specific load to reconnect. Return value is XXX representing XX.X volts.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.48
reconnect3LoadShedSundayOnTime on Sunday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.49
reconnect3LoadShedMondayOnTime on Monday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.50
reconnect3LoadShedTuesdayOnTime on Tuesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.51
reconnect3LoadShedWednesdayOnTime on Wednesday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.52
reconnect3LoadShedThursdayOnTime on Thursday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.53
reconnect3LoadShedFridayOnTime on Friday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.54
reconnect3LoadShedSaturdayOnTime on Saturday which when reached will cause a specific load to reconnect. Return value is XX:XX representing HH:MM.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.1.1.55
equalizeTimeNumber of hours the equalize voltage is to be applied. Return value is XXX representing XX.X hours.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.56
equalizeVoltageEqualize voltage to be applied. Return value is XXX representing XX.X volts.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.57
batteryResistancePercentChangeResistance percentange change that when reached will cause an alarm. Return value is XXX representing XXX %.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.58
batteryResistanceTestIntervalBattery resistance test interval. Return value is XX representing XX weeks.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.59
loadShedTimeControlLoad shed time control enabled/disabled status. Return value: 1 = time control enabled, 2 = time control disabled.rw
Enumeration
.1.3.6.1.4.1.18642.1.1.1.60
batteryFloatCurrentBattery float current. Return value is XXX representing XXX amps.rw
INTEGER
.1.3.6.1.4.1.18642.1.1.1.61
readOnlyObjects
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.2
rectifiers
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.2.1
rectifierFloatVoltageRectifier float voltage. Return value is XXX representing XX.X volts. Valid ranges are 24.0 to 57.0 volts.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.1.1
rectifierLoadCurrentRectifier DC load current. Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 5000 amps.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.1.2
batteries
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.2.2
batteryCurrentBattery current. Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 1000 amps.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.2.1
batteryTemperatureBattery temperature. Return value is XX representing XX C. Valid ranges are -40 to 99 C.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.2.2
batteryResistanceReferenceInitial battery resistance. Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.2.3
batteryResistanceReadingLast battery resistance reading. Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.2.4
batteryResistanceChangePercent change from last battery resistance reading. Return value is XXX representing XXX %. Valid ranges are 001 to 999 %.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.2.5
batteryCycles1Number of discharge/recharge cycles less than 1 minute. Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.2.6
batteryCycles1to5Number of discharge/recharge cycles from 1 to 5 minutes. Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.2.7
batteryCycles5to15Number of discharge/recharge cycles from 5 to 15 minutes. Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.2.8
batteryCycles15Number of discharge/recharge cycles greater than 15 minutes. Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.2.9
batteryCycles15LastCycleDateLast cycle date of batteryCycles15. Return value is MM-DD-YY, HH-MM.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.2.10
batteryCycles15LastDurationDuration of batteryCycles15 last cycle. Return value is XXXX representing XXXX minutes.ro
INTEGER
.1.3.6.1.4.1.18642.1.2.2.11
batteryTestFaultBattery failure has occured during battery restistance test. Return value: 1 = Abort 1, 2 = Abort 2, 3 = Abort 3, 4 = None.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.2.12
factorySettings
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.2.3
floatVoltagePresetsFloat voltage factory setting range. Return value is XX.X volts min, XX.X volts max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.1
highVoltageAlarmPresetsHigh voltage alarm factory setting range. Return value is XX.X volts min, XX.X volts max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.2
lowVoltageAlarmPresetsLow voltage alarm factory setting range. Return value is XX.X volts min, XX.X volts max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.3
disconnect1VoltagePresetsDisconnect voltage 1 factory setting range. Return value is XX.X volts min, XX.X volts max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.4
disconnect1TemperaturePresetDisconnect temperature 1 factory setting. Return value is XX C.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.5
disconnect1LoadShedSundayPresetsDisconnect 1 load shed Sunday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.6
disconnect1LoadShedMondayPresetsDisconnect 1 load shed Monday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.7
disconnect1LoadShedTuesdayPresetsDisconnect 1 load shed Tuesday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.8
disconnect1LoadShedWednesdayPresetsDisconnect 1 load shed Wednesday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.9
disconnect1LoadShedThursdayPresetsDisconnect 1 load shed Thursday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.10
disconnect1LoadShedFridayPresetsDisconnect 1 load shed Friday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.11
disconnect1LoadShedSaturdayPresetsDisconnect 1 load shed Saturday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.12
reconnectVoltage1PresetsReconnect voltage 1 factory setting range. Return value is XX.X volts min, XX.X volts max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.13
disconnect2VoltagePresetsDisconnect voltage 2 factory setting range. Return value is XX.X volts min, XX.X volts max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.14
disconnect2TemperaturePresetDisconnect temperature 2 factory setting. Return value is XX C.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.15
disconnect2LoadShedSundayPresetsDisconnect 2 load shed Sunday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.16
disconnect2LoadShedMondayPresetsDisconnect 2 load shed Monday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.17
disconnect2LoadShedTuesdayPresetsDisconnect 2 load shed Tuesday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.18
disconnect2LoadShedWednesdayPresetsDisconnect 2 load shed Wednesday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.19
disconnect2LoadShedThursdayPresetsDisconnect 2 load shed Thursday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.20
disconnect2LoadShedFridayPresetsDisconnect 2 load shed Friday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.21
disconnect2LoadShedSaturdayPresetsDisconnect 2 load shed Saturday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.22
reconnect2VoltagePresetsReconnect voltage 2 factory setting range. Return value is XX.X volts min, XX.X volts max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.23
disconnect3VoltagePresetsDisconnect voltage 3 factory setting range. Return value is XX.X volts min, XX.X volts max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.24
disconnect3TemperaturePresetDisconnect temperature 3 factory setting. Return value is XX C.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.25
disconnect3LoadShedSundayPresetsDisconnect 3 load shed Sunday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.26
disconnect3LoadShedMondayPresetsDisconnect 3 load shed Monday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.27
disconnect3LoadShedTuesdayPresetsDisconnect 3 load shed Tuesday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.28
disconnect3LoadShedWednesdayPresetsDisconnect 3 load shed Wednesday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.29
disconnect3LoadShedThursdayPresetsDisconnect 3 load shed Thursday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.30
disconnect3LoadShedFridayPresetsDisconnect 3 load shed Friday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.31
disconnect3LoadShedSaturdayPresetsDisconnect 3 load shed Saturday time settings. Return value is XX:Xx off, XX:XX on.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.32
reconnect3VoltagePresetsReconnect voltage 3 factory setting range. Return value is XX.X volts min, XX.X volts max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.33
overloadCurrentPresetsOverload current factory setting range. Return value is XXXX amps min, XXXX amps max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.34
maximumCurrentPresetMaximum current factory setting. Return value is XXXX amps.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.35
batteryFloatCurrentPresetsBattery float current factory settings. Return value is XXX amps min, XXX amps max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.36
equalizeTimePresetsEqualize time factory setting range. Return value is 00.0 hours min, XX.X hours max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.37
equalizeVoltagePresetsEqualize voltage factory setting range. Return value is XX.X volts min, XX.X volts max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.38
batteryResistancePresetsBattery resistance percent change factory setting range. Return value is XXX % min, XXX % max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.39
batteryTestIntervalPresetsBattery resistance test interval factory setting range. Return value is XX weeks min, XX weeks max.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.18642.1.2.3.40
alarmStatus
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.2.4
highVoltageAlarmStatusHigh voltage alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.1
lowVoltageAlarmStatusLow voltage alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.2
overloadAlarmStatusOverload alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.3
breakerAlarmStatusBreaker alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.4
acFailureAlarmStatusAC failure alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.5
fanFailureAlarmStatusFan failure alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.6
rectifierFailureAlarmStatusRectifier failure alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.7
majorAlarmStatusMajor alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.8
lowVoltageDisconnect1TemperatureAlarmStatusLow voltage disconnect 1 high temperature alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.9
lowVoltageDisconnect2TemperatureAlarmStatusLow voltage disconnect 2 high temperature alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.10
lowVoltageDisconnect3TemperatureAlarmStatusLow voltage disconnect 3 high temperature alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.11
lowVoltageDisconnect1VoltageAlarmStatusLow voltage disconnect 1 low voltage alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.12
lowVoltageDisconnect2VoltageAlarmStatusLow voltage disconnect 2 low voltage alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.13
lowVoltageDisconnect3VoltageAlarmStatusLow voltage disconnect 3 low voltage alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.14
batteryResistanceAlarmStatusBattery resistance alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.15
batteryCurrentAlarmStatusBattery resistance alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.16
batteryTestAbortCondition1AlarmStatusBattery test abort condition 1 alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.17
batteryTestAbortCondition2AlarmStatusBattery test abort condition 2 alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.18
batteryTestAbortCondition3AlarmStatusBattery test abort condition 3 alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.19
batteryDisconnectAlarmStatusBattery disconnect alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.20
fuseAlarmStatusFuse alarm status. Return value 1 = alarm inactive, 2 = alarm active.ro
Enumeration
.1.3.6.1.4.1.18642.1.2.4.21
digitalSensorAlarms
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.2.5
systemAlarms
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.2.6
digitalSensorAlarmClears
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.2.7
systemAlarmClears
OBJECT IDENTIFIER
.1.3.6.1.4.1.18642.1.2.8
CCPOWER-MIB - SNMP MIB Reference | MIBs Explorer