Home/Catalog/BESTPOWER-MIB

BESTPOWER-MIB

AI MIB Summary

Standard SNMP MIB module defining data structures for BESTPOWER-MIB.

211
Objects
Active
Status
4
Dependencies

Imported Objects

Objects

211 total
Object Name
bestPower
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947
RFC1213-MIB
Unknown
.1.3.6.1.4.1.2947
upsTrapPowerFailWARNING: Utility power not available.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.1
upsTrapPowerRestoredINFORMATION: Utility power has been restored.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.2
upsTrapUPSOnBatteryWARNING: The UPS has switched to battery backup power.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.3
upsTrapUPSNotOnBatteryINFORMATION: The UPS is not on battery power.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.4
upsTrapLowRuntimeSEVERE: The runtime remaining on battery power is very short, and the UPS will soon shut down.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.5
upsTrapUPSCanRunOnBatteryINFORMATION: The UPS has returned from a low runtime condition.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.6
upsTrapNearLowBatterySEVERE: The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to the load.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.7
upsTrapHighBatteryWARNING: The battery charger voltage on the UPS has reached a value that is too high for safe battery maintenance.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.8
upsTrapBatteryOKINFORMATION: The UPS has returned from a near low or high battery condition.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.9
upsTrapLowBatterySEVERE: The UPS will run for approximately 2 minutes more and then put itself to sleep to prevent a complete discharge of the batteries.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.10
upsTrapCheckBatterySEVERE: The UPS has failed a scheduled or manual battery test.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.11
upsTrapReplaceBatterySEVERE: One or more UPS batteries need to be replaced.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.12
upsTrapCheckInverterSEVERE: The UPS has failed a scheduled or manual inverter test.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.13
upsTrapBatteriesDisconnectedWARNING: The UPS battery voltage is either too low or missing to start up.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.14
upsTrapOutputOverloadWARNING: The output load exceeds the UPS output capacity.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.15
upsTrapUPSNoLongerOverloadedINFORMATION: The UPS has returned from an output overload condition.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.16
upsTrapLowAcOutSEVERE: The output load has exceeded the UPS output capacity, and the UPS has shut down.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.17
upsTrapCircuitBreakerWarningSEVERE: To much load equipment has been connected to the UPS and has has caused excess current draw from the output.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.18
upsTrapCircuitBreakerOKINFORMATION: The UPS has returned from a circuit breaker warning condition.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.19
upsTrapCircuitBreakerShdnSEVERE: The UPS has shut down due to an extended excess of current draw from the output.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.20
upsTrapBypassOnSEVERE: The Bypass is presently engaged on the UPS.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.21
upsTrapUPSOnlineINFORMATION: The UPS has returned from an on bypass condition.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.22
upsTrapSiteWiringFaultSEVERE: The UPS has found a problem in your wall outlet.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.23
upsTrapCheckFanSEVERE: The fan on the UPS has stopped .
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.24
upsTrapHighUPSTempSEVERE: The internal temperature inside the UPS is too hot.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.25
upsTrapTempOKINFORMATION: The UPS has returned from a high ambient temp condition.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.26
upsTrapHighHSTempSEVERE: The Inverter heatsink assembly inside the UPS is too hot .
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.27
upsTrapHSTempOKINFORMATION: The UPS has returned from a high heatsink temp condition.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.28
upsTrapHighXFMRTempSEVERE: The temperature of the main transformer inside the UPS is too hot .
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.29
upsTrapHighPFMTempSEVERE: The temperature of the PFM module inside the UPS is too hot.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.30
upsTrapProbeMissingSEVERE: One or all of the temperature probes has been disconnected on the UPS.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.31
upsTrapProbeReconnectedINFORMATION: The UPS has returned from a probe missing condition.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.32
upsTrapCheckPowerSupplySEVERE: The internal DC supply voltages are attenuated or missing.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.33
upsTrapTapRegulatorFaultSEVERE: The UPS detected a possible failure in the tap changer (open or welded relay, etc.)
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.34
upsTrapRelayFailureSEVERE: There is a hardware problem inside the UPS.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.35
upsTrapCheckFuseSEVERE: The failure of one or more fuses has been detected.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.36
upsTrapCheckMOVSEVERE: One or more MOVs have failed due to a voltage surge.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.37
upsTrapMemoryErrorSEVERE: The UPS has lost the programmed settings in the memory of the logic board.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.38
upsTrapCallServiceSEVERE: A hardware malfunction has occurred inside the UPS. Please consult a factory authorized service representative for assistance.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.39
upsTrapManualAlarmBeeperTestInitiatedINFORMATION: A manual test of the alarm beeper is being performed on the UPS.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.40
upsTrapManualAlarmBeeperTestAbortedINFORMATION: The test of UPS has completed.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.41
upsTrapScheduledTestInProgressINFORMATION: A test is in progress.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.42
upsTrapScheduledTestFailedSEVERE: The last test performed failed.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.43
upsTrapCommunicationLostSEVERE: Communication to the UPS has been lost. Steps to reestablish communication are in progress.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.44
upsTrapCommunicationRestoredINFORMATION: Communication with the UPS has been restored.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.45
upsTrapUPSGoingDownWARNING: The ups has been given shutdown command by the management station.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.46
upsTrapUPSTurnedOffINFORMATION: The ups has been turned off by the management station.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.47
upsTrapUPSSleepingINFORMATION: The UPS has entered in 'sleep' mode. Power to the load has been cut off.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.48
upsTrapUPSWokeUpINFORMATION: The UPS woke up from 'sleep' mode. Power to the load has been restored.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.49
upsTrapUPSRebootedINFORMATION: The UPS is rebooted.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.50
upsTrapEmergencyPowerOFFSEVERE: The Emergency Power OFF feature has been activiated at the RS-232 port on the UPS.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.51
upsTrapHistLogWarnWARNING: The ups history log buffer is almost full.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.52
upsTrapEventLogWarnWARNING: The ups event log buffer is almost full.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.53
upsTrapUPSFailSEVERE: A critical fault has been detected inside the UPS. Power to the load has been shut off.
TRAP-TYPE
.1.3.6.1.4.1.2947.1.0.54
upsIdent
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.1
upsIdentUpsNameAn ID string identifying the Family of UPS.ro
DisplayString
.1.3.6.1.4.1.2947.1.1.1
upsIdentModelThe UPS model name (example: 'FE500VA').ro
DisplayString
.1.3.6.1.4.1.2947.1.1.2
upsIdentVARatingThe capacity rating of the UPS expressed in VoltAmperes(VA).ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.2947.1.1.3
upsIdentUpsTypeType of UPS.ro
Enumeration
.1.3.6.1.4.1.2947.1.1.4
upsIdentUpsSerialNumberA unique identification number provided by the factory.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.2947.1.1.5
upsIdentUpsIdentificationA string entered by the administrator to provide a unique name for the UPS.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.2947.1.1.6
upsIdentFirmwareRevisionThe firmware revision of the UPS.ro
DisplayString
.1.3.6.1.4.1.2947.1.1.7
upsIdentDateOfManufactureThe date when the UPS was manufactured in mm/dd/yyyy format.rw
DisplayString
.1.3.6.1.4.1.2947.1.1.8
upsBattery
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.2
upsBatteryStatusThe status of the inverter .ro
Enumeration
.1.3.6.1.4.1.2947.1.2.1
upsBatteryTimeOnBatteryThe elapsed time in seconds since the UPS has switched to battery power.ro
INTEGER
.1.3.6.1.4.1.2947.1.2.2
upsBatteryRuntimeRemainingThe remaining time in minutes that the UPS will be able to run on battery power.ro
INTEGER
.1.3.6.1.4.1.2947.1.2.3
upsBatteryVoltageThe UPS battery voltage expressed in 1/10 VDC.ro
INTEGER
.1.3.6.1.4.1.2947.1.2.4
upsBatteryCurrentThe battery current expressed in 1/10 ADC.ro
INTEGER
.1.3.6.1.4.1.2947.1.2.5
upsBatteryTemperatureThe internal UPS temperature expressed in 1/10 degree C.ro
INTEGER
.1.3.6.1.4.1.2947.1.2.6
upsBatteryLastReplaceDateThe date when the UPS system's batteries were last replaced in mm/dd/yyyy format. When the UPS batteries are replaced, this value should be reset by the administrator.rw
DisplayString
.1.3.6.1.4.1.2947.1.2.7
upsInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.3
upsInputPhaseThe AC input phase.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.1
upsInputFrequencyThe utility line frequency in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.2
upsInputVoltageThe utility line voltage in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.3
upsInputCurrentThe utility line current in 1/10 Ampere AC.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.4
upsInputPowerThe utility line power in 1/10 Watts.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.5
upsInputPhase2
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.3.6
upsInputP2The AC input phase.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.6.1
upsInputFrequency2The utility line frequency in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.6.2
upsInputVoltage2The utility line voltage in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.6.3
upsInputCurrent2The utility line current in 1/10 Ampere AC.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.6.4
upsInputPower2The utility line power in 1/10 Watts.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.6.5
upsInputPhase3
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.3.7
upsInputP3The AC input phase.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.7.1
upsInputFrequency3The utility line frequency in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.7.2
upsInputVoltage3The utility line voltage in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.7.3
upsInputCurrent3The utility line current in 1/10 Ampere AC.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.7.4
upsInputPower3The utility line power in 1/10 Watts.ro
INTEGER
.1.3.6.1.4.1.2947.1.3.7.5
upsOutput
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.4
upsOutputStatusThe current state of the UPS. If the UPS is unable to determine its state, this variable is set to unknown(1).ro
Enumeration
.1.3.6.1.4.1.2947.1.4.1
upsOutputPhaseThe output phase.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.2
upsOutputFrequencyThe output frequency of the UPS expressed in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.3
upsOutputVoltageThe output voltage of the UPS expressed in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.4
upsOutputCurrentThe output current of the UPS expressed in 1/10 AC Amperes.ro
NonNegativeInteger
.1.3.6.1.4.1.2947.1.4.5
upsOutputTruePowerThe true output power of the UPS expressed in 1/10 Watts.ro
NonNegativeInteger
.1.3.6.1.4.1.2947.1.4.6
upsOutputApparentPowerThe apparent output power of the UPS expressed in 1/10 VoltAmperes(VA).ro
NonNegativeInteger
.1.3.6.1.4.1.2947.1.4.7
upsOutputPowerFactorThe output powerfactor of the UPS expressed in +/- 1/10 units deviating from 1.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.8
upsOutputPercentLoadThe percentage of the total UPS power capacity being used expressed in % of 100.ro
INTEGER -- UNITS percent
.1.3.6.1.4.1.2947.1.4.9
upsOutputPhase2
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.4.10
upsOutputP2The output phase.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.10.1
upsOutputFrequency2The output frequency of the UPS expressed in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.10.2
upsOutputVoltage2The output voltage of the UPS expressed in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.10.3
upsOutputCurrent2The output current of the UPS expressed in 1/10 AC Amperes.ro
NonNegativeInteger
.1.3.6.1.4.1.2947.1.4.10.4
upsOutputTruePower2The true output power of the UPS expressed in 1/10 Watts.ro
NonNegativeInteger
.1.3.6.1.4.1.2947.1.4.10.5
upsOutputApparentPower2The apparent output power of the UPS expressed in 1/10 VoltAmperes(VA).ro
NonNegativeInteger
.1.3.6.1.4.1.2947.1.4.10.6
upsOutputPowerFactor2The output powerfactor of the UPS expressed in +\- 1/10 units deviating from 1.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.10.7
upsOutputPhase3
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.4.11
upsOutputP3The output phase.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.11.1
upsOutputFrequency3The output frequency of the UPS expressed in 1/10 Hz.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.11.2
upsOutputVoltage3The output voltage of the UPS expressed in 1/10 VAC.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.11.3
upsOutputCurrent3The output current of the UPS expressed in 1/10 AC Amperes.ro
NonNegativeInteger
.1.3.6.1.4.1.2947.1.4.11.4
upsOutputTruePower3The true output power of the UPS expressed in 1/10 Watts.ro
NonNegativeInteger
.1.3.6.1.4.1.2947.1.4.11.5
upsOutputApparentPower3The apparent output power of the UPS expressed in 1/10 VoltAmperes = (VA).ro
NonNegativeInteger
.1.3.6.1.4.1.2947.1.4.11.6
upsOutputPowerFactor3The output powerfactor of the UPS expressed in +/- 1/10 units deviating from 1.ro
INTEGER
.1.3.6.1.4.1.2947.1.4.11.7
upsConfig
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.5
upsConfigLowRuntimeSetpointThis setpoint controls when the UPS will initiate a Low Runtime Alarm.rw
INTEGER
.1.3.6.1.4.1.2947.1.5.1
upsConfigDelayBeforeRestartThe delay in seconds after utility line power returns before the UPS will turn on. This value is used in conjunction with TurnUPSOff, RebootUPS, and the Scheduled Shutdown objects.rw
INTEGER
.1.3.6.1.4.1.2947.1.5.2
upsConfigDelayBeforeShutdownThe delay in seconds that the UPS waits before executing an off command upon request of an external device.rw
INTEGER
.1.3.6.1.4.1.2947.1.5.3
upsConfigTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.5.4
upsConfigTestLevelThis is the level of the System Test.rw
Enumeration
.1.3.6.1.4.1.2947.1.5.4.1
upsConfigDaysBetweenTestsThe number of days between Tests.rw
INTEGER
.1.3.6.1.4.1.2947.1.5.4.3
upsConfigBatteryTestDurationThe number of seconds the UPS must run on battery power during a battery test.rw
INTEGER
.1.3.6.1.4.1.2947.1.5.4.4
upsConfigScheduleTableThe table to schedule shutting down the ups.
SEQUENCE OF UpsConfigScheduleEntry
.1.3.6.1.4.1.2947.1.5.5
upsConfigScheduleEntryThe entries for each day.
UpsConfigScheduleEntry
.1.3.6.1.4.1.2947.1.5.5.1
upsConfigScheduleIndexThe index of scheduled events.ro
INTEGER
.1.3.6.1.4.1.2947.1.5.5.1.1
upsConfigScheduleShutdownDayThe weekday on which the UPS should shut down.rw
Enumeration
.1.3.6.1.4.1.2947.1.5.5.1.2
upsConfigScheduleShutdownTimeThe time that the process of shutting down the UPS will be initiatedrw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.2947.1.5.5.1.3
upsConfigScheduleRestartDayThe weekday on which the UPS should restartrw
Enumeration
.1.3.6.1.4.1.2947.1.5.5.1.4
upsConfigScheduleRestartTimeThe time the UPS will restart in hh:mm:ss format.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.2947.1.5.5.1.5
bestLinkHistoryLogFrequencyThe frequency of updating the history log in minutes.rw
INTEGER
.1.3.6.1.4.1.2947.1.5.8.1
bestLinkRefreshFrequencyThe frequency of saving configuration,history and event log data in non-volatile memory. If the value is set to 0, then saving data is disabled.rw
INTEGER
.1.3.6.1.4.1.2947.1.5.8.2
bestLinkNetIdThe IP address of the device. Setting this parameter causes BestLink to reboot.rw
IpAddress
.1.3.6.1.4.1.2947.1.5.8.3
bestLinkGatewayThe gateway address for the network BestLink is connected to.rw
IpAddress
.1.3.6.1.4.1.2947.1.5.8.4
bestLinkNetMaskThe net mask of the device.rw
IpAddress
.1.3.6.1.4.1.2947.1.5.8.5
bestLinkSysDateThe system date of the device. The date is in mm/dd/yyyy format. The range of system date is from 1/1/1980 to 12/31/2037.rw
DisplayString
.1.3.6.1.4.1.2947.1.5.8.6
bestLinkSysTimeThe system time of the device. The time is in hh:mm:ss format.rw
DisplayString
.1.3.6.1.4.1.2947.1.5.8.7
bestLinkTftpFileNameThe tftp file name that contains the software upgrade image.rw
DisplayString
.1.3.6.1.4.1.2947.1.5.8.8
bestLinkTftpHostThe tftp host IP address from where to get the image.rw
IpAddress
.1.3.6.1.4.1.2947.1.5.8.9
bestLinkFlashEEPROMSaves the history log, eventlog, and configuration data to non-volatile memory.rw
Enumeration
.1.3.6.1.4.1.2947.1.5.8.10
bestLinkPrimaryTimeServerThe primary time server is responsible for sending the correct time to the UPS.rw
IpAddress
.1.3.6.1.4.1.2947.1.5.8.11
bestLinkSecondaryTimeServerThe secondary time server responsible for sending the correct time to the UPS.rw
IpAddress
.1.3.6.1.4.1.2947.1.5.8.12
bestLinkSoftwareVersionThe version of BestLink software.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.2947.1.5.8.13
upsConfigTrapsReceivers
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.5.9
upsConfigTrapsReceiversTableA list of managers to send traps to.
SEQUENCE OF UpsConfigTrapsReceiversEntry
.1.3.6.1.4.1.2947.1.5.9.1
upsConfigTrapsReceiversEntryThe managers to send traps to.
UpsConfigTrapsReceiversEntry
.1.3.6.1.4.1.2947.1.5.9.1.1
trapsIndexThe index to a trap receiver entry.ro
INTEGER
.1.3.6.1.4.1.2947.1.5.9.1.1.1
trapsReceiverAddrThe IP address of the manager to send a trap to.rw
IpAddress
.1.3.6.1.4.1.2947.1.5.9.1.1.2
receiverCommunityStringThe community name to use in the trap when sent to the manager.rw
DisplayString
.1.3.6.1.4.1.2947.1.5.9.1.1.3
severityLevelThe severity threshold of traps to send to the manager. Traps are labeled by severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager.rw
Enumeration
.1.3.6.1.4.1.2947.1.5.9.1.1.4
receiverAcceptAn entry will become active if yes, otherwise it will be disabled.rw
Enumeration
.1.3.6.1.4.1.2947.1.5.9.1.1.5
upsConfigRegisteredShutdownClients
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.5.10
upsRegisteredShutdownClientsTableA list of registered shutdown client table entries. The table contains zero, one, or many rows at any moment, depending upon the number of Netwatch clients registered with BestLink
SEQUENCE OF UpsRegisteredShutdownClientsEntry
.1.3.6.1.4.1.2947.1.5.10.1
upsRegisteredShutdownClientsEntryAn entry containing information applicable to a particular registered shutdown client.
UpsRegisteredShutdownClientsEntry
.1.3.6.1.4.1.2947.1.5.10.1.1
upsRegisteredShutdownClientsIndexAn index of alarm entries in the RegisteredShutdownClientsTable.ro
PositiveInteger
.1.3.6.1.4.1.2947.1.5.10.1.1.1
upsRegisteredShutdownClientsIPAddressThe IP Address of the registered shutdown clientro
IpAddress
.1.3.6.1.4.1.2947.1.5.10.1.1.2
upsRegisteredShutdownClientsTotalNumberOfThe total number of registered shutdown clients.ro
INTEGER
.1.3.6.1.4.1.2947.1.5.10.2
upsControl
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.6
upsControlTurnOffUPSSetting this variable to UpsOff(2) causes the UPS to shut off. When the UPS is in the off state, the UPS will remain off until the ON/OFF switch is manually toggled. Setting this variable to cancelUpsOff(1) allows for a method to cancel the upsOff(2) command to the UPS that is still pending, or will make an attempt to restart a UPS that has been shutdown, provided that BestLink is powered by some other means. Setting this variable to rebootUps(3) causes the UPS to shut off and turn back on. Setting this variable to cancelrebootUps(4) allows for a method to cancel the rebootUps(3) command to the UPS that is still pending, or will make an attempt to restart a UPS that has been shutdown, provided that BestLink is powered by some other means.rw
Enumeration
.1.3.6.1.4.1.2947.1.6.1
upsControlActivateUpsSchedulingSetting this variable to On(2) causes the UPS to activate the scheduling parameters that have been previously configured within the upsConfigDailyShutdownScheduleTable and the upsConfigWeeklyShutdownScheduleTable. Setting this variable to Off(1) suspends all currently configured schedules.rw
Enumeration
.1.3.6.1.4.1.2947.1.6.4
upsTest
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.7
upsManualTestsSetting this variable to any value other than (1) causes the UPS to perform a manual test or abort a particular test in progress.rw
Enumeration
.1.3.6.1.4.1.2947.1.7.1
upsAlarm
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.8
upsAlarmsPresentThe present number of active alarm conditions.ro
Gauge
.1.3.6.1.4.1.2947.1.8.1
upsLastKnownAlarmA unique identifier for an alarm condition. This value must remain constant. Value 'noAlarm(37)' will be returned if no Alarm has occured till the point of GET operation.ro
Enumeration
.1.3.6.1.4.1.2947.1.8.2
upsAlarmTableA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmIndex equal to 1, and increments the value of upsAlarmIndex each time a new row is created.
SEQUENCE OF UpsAlarmEntry
.1.3.6.1.4.1.2947.1.8.3
upsAlarmEntryAn entry containing information applicable to a particular alarm.
UpsAlarmEntry
.1.3.6.1.4.1.2947.1.8.3.1
upsAlarmIndexAn index of alarm entries in the alarm log.ro
PositiveInteger
.1.3.6.1.4.1.2947.1.8.3.1.1
upsAlarmNameA unique identifier for an alarm condition. This value must remain constant.ro
Enumeration
.1.3.6.1.4.1.2947.1.8.3.1.2
upsAlarmTimeThe time that the alarm occurred in hh:mm:ss format.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.2947.1.8.3.1.3
upsWellKnownAlarms
OBJECT IDENTIFIER
.1.3.6.1.4.1.2947.1.8.4
upsAlarmOnBatteryThe UPS is drawing power from the batteries.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.1
upsAlarmLowRuntimeThe remaining battery runtime is less than or equal to the upsConfigLowRuntimeSetpoint.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.2
upsAlarmNearLowBatteryThe battery voltage on the UPS has reached a value where the inverter will not be able to function very much longer.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.3
upsAlarmLowBatteryThe battery voltage on the UPS has reached a value where the inverter has stopped providing output power to the connected load equipment. The UPS has shutdown to protect the batteries from complete discharge.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.4
upsAlarmHighBatteryThe battery charger voltage on the UPS has reached a value that is too high for safe battery maintenance.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.5
upsAlarmCheckBatteryThe periodic battery test has failed. A manual test of the batteries needs to be performed to determine which battery\batteries need replaced.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.6
upsAlarmReplaceBatteryOne or more batteries have been determined to require replacement. Compatibility: Fortress IIro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.7
upsAlarmCheckInverterThe inverter has failed the automatic system test.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.8
upsAlarmBatteriesDisconnectedThe UPS has detected that the DC voltage needed to start up is too low or missing.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.9
upsAlarmOutputOverloadThe output load exceeds the UPS output capacity.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.10
upsAlarmLowAcOutThe output load has exceeded the UPS output capacity, and the UPS has shut down.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.11
upsAlarmCircuitBreakerWarningTo much load equipment has been connected to the UPS and has has caused excess current draw from the output.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.12
upsAlarmCircuitBreakerShdnThe UPS has shut down due to an extended excess of current draw from the output.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.13
upsAlarmBypassOnThe Bypass is presently engaged on the UPS.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.14
upsAlarmAutoBypassThe UPS has gone into the Auto Bypass mode to redirect power around the UPS circuitry.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.15
upsAlarmSiteWiringFaultThe UPS has found a problem in your wall outlet.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.16
upsAlarmCheckFanThe fan on the UPS has stoppedro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.17
upsAlarmHighAmbTempThe internal temperature inside the UPS is too hot.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.18
upsAlarmHighHSTempThe Inverter heatsink assembly inside the UPS is to hot .ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.19
upsAlarmHighXFMRTempThe temperature of the main transformer inside the UPS is too hot .ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.20
upsAlarmHighPFMTempThe temperature of the PFM module inside the UPS is too hot .ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.21
upsAlarmProbeMissingOne or all of the sense probes has been disconnected on the UPS.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.22
upsAlarmCheckPowerSupplyThe internal DC supply voltages are attenuated or missing.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.23
upsAlarmTapRegulatorThe UPS detected a possible failure in the tap changer (open or welded relay, etc.)ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.24
upsAlarmRelayFailureThere is a hardware problem inside the UPS.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.25
upsAlarmCheckFuseThe failure of one or more fuses has been detected.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.26
upsAlarmCheckMOVOne or more MOVs have failed due to a voltage surge.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.27
upsAlarmMemoryErrorThe UPS has lost the programmed settings in the memory of the logic board.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.28
upsAlarmCallServiceA hardware malfunction has occurred inside the UPS. Please consult a factory authorized service representative for assistance.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.29
upsAlarmupsFailedA general fault in the UPS has been detected.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.30
upsAlarmUserTestA user test of the alarm beeper is in progress.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.31
upsAlarmTestInProgressA test is in progress.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.32
upsAlarmDiagnosticTestFailedThe result of the last diagnostic test indicates a failure.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.33
upsAlarmEPOThe Emergency Power OFF feature has been activiated at the RS-232 port on the UPS.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.34
upsAlarmUpsOffThe output of the UPS is in the off state.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.35
upsAlarmCommunicationsLostA problem has been encountered in the communications between the agent and the UPS.ro
INTEGER
.1.3.6.1.4.1.2947.1.8.4.36