BATM-DRY-CONTACTS-MIB
AI MIB Summary
The BATM-DRY-CONTACTS-MIB defines managed objects and notifications for monitoring the state of external dry-contact alarm inputs on network hardware. It enables the polling of contact closure status and the generation of SNMP traps to alert management systems when physical alarm sensors trigger.
Initial version. This MIB provides external-alarm management and notifications
Main OID:
batmDryContactsMIB.1.3.6.1.4.1.738.1.5.112
15
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
15 total| Object Name |
|---|
batmDryContactsMIBInitial version. This MIB provides external-alarm management and notifications MODULE-IDENTITY .1.3.6.1.4.1.738.1.5.112 |
dryContactsObjects OBJECT IDENTIFIER .1.3.6.1.4.1.738.1.5.112.1 |
inputsCfgTableA table containing inputs configuration and statuses SEQUENCE OF InputsCfgEntry .1.3.6.1.4.1.738.1.5.112.1.1 |
inputsCfgEntry InputsCfgEntry .1.3.6.1.4.1.738.1.5.112.1.1.1 |
extAlarmIDExternal alarm index uniquely identifies this row.
An integer with supported range of values 1-4. Index. Not-accessiblero INTEGER .1.3.6.1.4.1.738.1.5.112.1.1.1.1 |
nameName of alarm. An OCTET-STRING with max. 16 OCTETS.
Default value null string. Read-writerw OCTET STRING .1.3.6.1.4.1.738.1.5.112.1.1.1.2 |
descriptionAlarm description. An OCTET-STRING with max. 64 OCTETS.
Default value null string. Read-writerw OCTET STRING .1.3.6.1.4.1.738.1.5.112.1.1.1.3 |
enableStatusSenging alarms status. An enumeration with two values: enabled(1), disabled(2).
Default value is disabled(2). Read-writerw Enumeration .1.3.6.1.4.1.738.1.5.112.1.1.1.4 |
alarmStatusAlarm status. An enumeration with two values: no-alarm(1), alarm(2).
Default value is no-alarm(1). Read-only.ro Enumeration .1.3.6.1.4.1.738.1.5.112.1.1.1.5 |
alarmSeverityConfigured alarm severity. An enumeration with 4 values:
info(1), minor(2), major(3) and critical(4).
Default value is info(1). Read-writerw Enumeration .1.3.6.1.4.1.738.1.5.112.1.1.1.6 |
polarityConfigured polarity.
An enumeration with 2 values: normally-opened(1), normally-closed(2).
Default value is normally-opened(1). Read-writerw Enumeration .1.3.6.1.4.1.738.1.5.112.1.1.1.7 |
lastChangeThe value of sysUpTime at the time of the last operational status change.
TimeTicks. Read-onlyro TimeTicks (SNMPv2-SMI) .1.3.6.1.4.1.738.1.5.112.1.1.1.8 |
dryContactsNotifications OBJECT IDENTIFIER .1.3.6.1.4.1.738.1.5.112.2 |
inputStateChanged OBJECT IDENTIFIER .1.3.6.1.4.1.738.1.5.112.2.1 |
inputStateChangedTrapSend notification when operational status of the input changes NOTIFICATION-TYPE .1.3.6.1.4.1.738.1.5.112.2.1.1 |