Home/Catalog/ATEN-PE-CFG

ATEN-PE-CFG

AI MIB Summary

The ATEN-PE-CFG MIB module facilitates the remote configuration and monitoring of ATEN Power Equipment (PE) devices, specifically managing power distribution unit settings, outlet states, and environmental sensor data via SNMP.

ATEN PE MIB
Main OID:
aten.1.3.6.1.4.1.21317
361
Objects
Active
Status
7
Dependencies

Imported Objects

Objects

361 total
Object Name
atenATEN PE MIB
MODULE-IDENTITY
.1.3.6.1.4.1.21317
RFC1213-MIBATEN PE MIB
Unknown
.1.3.6.1.4.1.21317
atenProducts
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1
overip
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3
poweroverip
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2
pe
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2
userManagement
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.1
usrListTableA list of user. The number of user is given by the value of usrcfgNumber.
SEQUENCE OF UsrListEntry
.1.3.6.1.4.1.21317.1.3.2.2.1.1
usrListEntryStatus and parameter values for a pe8208 user.
UsrListEntry
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1
usrIndexThe value of usrIndex for the user. We have 1 administrator and 8 users. The index 9 will be the administrator.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.1
usrTypeThe user's type.ro
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.2
usrNameA textual string containing name of the user. string length: 1~16rw
DisplayString
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.3
usrPasswordA textual string containing password of the user. string length: 1~16rw
DisplayString
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.4
usrPort1AuthDisplay or set this user's outlet 1 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.5
usrPort2AuthDisplay or set this user's outlet 2 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.6
usrPort3AuthDisplay or set this user's outlet 3 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.7
usrPort4AuthDisplay or set this user's outlet 4 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.8
usrPort5AuthDisplay or set this user's outlet 5 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.9
usrPort6AuthDispaly or set this user's outlet 6 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.10
usrPort7AuthDisplay or set this user's outlet 7 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.11
usrPort8AuthDisplay or set this user's outlet 8 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.12
usrPort9AuthDisplay or set this user's outlet 9 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.13
usrPort10AuthDisplay or set this user's outlet 10 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.14
usrPort11AuthDisplay or set this user's outlet 11 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.15
usrPort12AuthDisplay or set this user's outlet 12 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.16
usrPort13AuthDisplay or set this user's outlet 13 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.17
usrPort14AuthDisplay or set this user's outlet 14 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.18
usrPort15AuthDisplay or set this user's outlet 15 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.19
usrPort16AuthDisplay or set this user's outlet 16 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.20
usrPort17AuthDisplay or set this user's outlet 17 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.21
usrPort18AuthDisplay or set this user's outlet 18 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.22
usrPort19AuthDisplay or set this user's outlet 19 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.23
usrPort20AuthDisplay or set this user's outlet 20 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.24
usrPort21AuthDisplay or set this user's outlet 21 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.25
usrPort22AuthDisplay or set this user's outlet 22 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.26
usrPort23AuthDisplay or set this user's outlet 23 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.27
usrPort24AuthDisplay or set this user's outlet 24 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.28
usrPort25AuthDisplay or set this user's outlet 25 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.29
usrPort26AuthDisplay or set this user's outlet 26 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.30
usrPort27AuthDisplay or set this user's outlet 27 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.31
usrPort28AuthDisplay or set this user's outlet 28 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.32
usrPort29AuthDisplay or set this user's outlet 29 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.33
usrPort30AuthDisplay or set this user's outlet 30 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.34
usrPort31AuthDisplay or set this user's outlet 31 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.35
usrPort32AuthDisplay or set this user's outlet 32 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.36
usrPort33AuthDisplay or set this user's outlet 33 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.37
usrPort34AuthDisplay or set this user's outlet 34 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.38
usrPort35AuthDisplay or set this user's outlet 35 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.39
usrPort36AuthDisplay or set this user's outlet 36 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.40
usrPort37AuthDisplay or set this user's outlet 37 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.41
usrPort38AuthDisplay or set this user's outlet 38 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.42
usrPort39AuthDisplay or set this user's outlet 39 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.43
usrPort40AuthDisplay or set this user's outlet 40 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.44
usrPort41AuthDisplay or set this user's outlet 41 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.45
usrPort42AuthDisplay or set this user's outlet 42 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.46
usrEnableDisplay or set this user is enable or notrw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.47
control
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.2
device
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.2.1
modelNameIndicate PE device model name.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.1
deviceNameThe name of PE device. string length: 1~39 NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.2
deviceValueTableDevice value table. This table displays device's current, voltage, power and power dissipation.
SEQUENCE OF DeviceValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3
deviceValueEntrySingle deviceValue entry containing device info.
DeviceValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1
deviceValueIndexIndex of deviceValue.ro
INTEGER (1)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.1
deviceCurrentDevice electric current value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.2
deviceVoltageDevice voltage value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.3
devicePowerDevice power value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.4
devicePowerDissipationDevice power dissipation value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.5
inputMaxVoltageDevice input Voltage value. unit:(V) If the device does not support this OID, we show value 0.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.6
inputMaxCurrentDevice input Current value. unit:(A) If the device does not support this OID, we show value 0.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.7
powerCapacityDevice power Capacity value.unit:(VA) If the device does not support this OID, we show value 0.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.8
devicePowerFactorDevice power Factor value. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.9
sensorValueTableDevice's sensor value table. This table displays sensor's temperature, humidity and pressure.
SEQUENCE OF SensorValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.4
sensorValueEntrySingle device's sensor value entry containing device info.
SensorValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1
sensorValueIndexIndex of sensor number.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.1
sensorTemperatureSensor's Temperature value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.2
sensorHumiditySensor's Humidity value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.3
sensorPressureSensor's Pressure value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.4
sensorPropertySensor's Property.ro
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.5
deviceOutletStatusTableDevice outlet status value table.
SEQUENCE OF DeviceOutletStatusEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.5
deviceOutletStatusEntrySingle deviceOutletStatus entry containing device info.
DeviceOutletStatusEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1
deviceOutletStatusIndexIndex of deviceOutletStatusro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1.1
displayOutletStatusDisplay outlet status.ro
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1.2
deviceConfigTableDevice configuration table
SEQUENCE OF DeviceConfigEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6
deviceConfigEntrySingle deviceConfig entry containing device info.
DeviceConfigEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1
deviceConfigIndexIndex of deviceConfigro
INTEGER (1)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.1
deviceMinCurMTDisplay or set device minimum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320. NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.2
deviceMaxCurMTDisplay or set device maximum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.3
deviceMinVolMTDisplay or set device minimum voltage measurement threshold. Exapmple: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (900..2600 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.4
deviceMaxVolMTDisplay or set device maximum voltage measurement threshold. Example: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (900..2600 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.5
deviceMinPMTDisplay or set device minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (0..99999 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.6
deviceMaxPMTDisplay or set device maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (0..99999 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.7
deviceMaxPDMTDisplay or set device maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (0..999990 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.8
deviceSensorTresholdTableDevice environment value table
SEQUENCE OF DeviceSensorTresholdEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7
deviceSensorTresholdEntryDevice's sensor Environment entry containing sensor info.
DeviceSensorTresholdEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1
deviceSensorTresholdIndexIndex of sensor numberro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.1
sensorMinTempMTDisplay or set sensor minimum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (-200..600 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.2
sensorMaxTempMTDisplay or set sensor maximum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (-200..600 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.3
sensorMinHumMTDisplay or set sensor minimum humidity measurement threshold. Example: range 15.0 ~ 95.0 represents 150~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (150..950 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.4
sensorMaxHumMTDisplay or set sensor maximum humidity measurement threshold. Example: range 15.0 ~ 95.0 represents 150~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (150..950 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.5
sensorMinPressMTDisplay or set sensor minimum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (-2500..2500 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.6
sensorMaxPressMTDisplay or set sensor maximum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (-2500..2500 | -3000)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.7
deviceOutletControlThis function is used for all outlet ports control. Set off(1) to turn off for all outlet ports. Set on(2) to turn on for all outlet ports. Get this object always return nostatus(3), because there is no device status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.8
deviceOutletRebootThis function is used for all outlet ports to reboot. Only when outlet status is ON can do outlet reboot action to all ports. Set yes(2) to reboot all outlet ports. Get this object always return no(1).rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.9
switchableOutlet is switchable or not.ro
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.10
perportreadingOutlet is per-port reading or not.ro
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.11
sensornumberSensor number.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.12
outletnumberOutlet number.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.13
banknumberBank number.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.14
doorSensor
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.16
doorSensorStatusDisplay door sensor status. close(0) represents door close. open(1) represents door open. not-attached(2) represents door sensor don't attach to device.ro
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.16.1
doorSensorTypeDoor Sensor Type Selectionrw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.16.2
pop
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.17
enablePOPmodeEnable/Disable POP mode.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.17.1
popThreshold(-1)means default value same as Bank Max Current 16 A. Example: range 0.0~32.0 represents 0~320 You can define the POP threshold or set as default(-1) value.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.17.2
enableOutletPOPmodeEnable/Disable Outlet POP mode.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.17.3
enableLIFOPOPmodeEnable/Disable LIFO POP mode.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.17.4
enablePriorityPOPmodeEnable/Disable Priority POP mode.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.17.5
cap
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.18
enableCAPmodeEnable/Disable CAP mode.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.18.1
outletCAPTableOutlet CAP table
SEQUENCE OF OutletCAPEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2
outletCAPEntryOutlet CAP entry containing CAP info.
OutletCAPEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1
outletCAPIndexIndex of outlet's CAP configurationro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1.1
outletCAPPriorityDisplay or set the CAP Priority of outlet. Priority 0 means this outlet does not support this OID.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1.2
outletInitModechoose outlet init mode you want.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.1.19
deviceIntegerValueTableDevice value table. This table displays device's current, voltage, power and power dissipation.
SEQUENCE OF DeviceIntegerValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99
deviceIntegerValueEntrySingle deviceValue entry containing device info.
DeviceIntegerValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1
deviceIntegerValueIndexIndex of deviceValue.ro
INTEGER (1)
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.1
deviceIntegerCurrentDevice electric current value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.2
deviceIntegerVoltageDevice voltage value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.3
deviceIntegerPowerDevice power value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.4
deviceIntegerPowerDissipationDevice power dissipation value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.5
sensorIntegerValueTableDevice's sensor value table. This table displays sensor's temperature, humidity and pressure.
SEQUENCE OF SensorIntegerValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100
sensorIntegerValueEntrySingle device's sensor value entry containing device info.
SensorIntegerValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1
sensorIntegerValueIndexIndex of sensor number.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.1
sensorIntegerTemperatureSensor's Temperature value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.2
sensorIntegerHumiditySensor's Humidity value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.3
sensorIntegerPressureSensor's Pressure value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.4
outlet
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.2.2
outletValueTableDisplay total outlet value table
SEQUENCE OF OutletValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1
outletValueEntrySingle outletValue entry containing outlet info.
OutletValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1
outletValueIndexIndex of outlet numberro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.1
outletCurrentOutlet electric current value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.2
outletVoltageOutlet voltage value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.3
outletPowerOutlet power value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.4
outletPowerDissipationOutlet power dissipation value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.5
outletMaxCurrentOutlet Max Current value. unit: (A). If the device does not support this OID, we show value 0.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.6
outletPowerFactorOutlet Power Factor value. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.7
outlet1StatusDisplay and control outlet 1 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.2
outlet2StatusDisplay and control outlet 2 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.3
outlet3StatusDisplay and control outlet 3 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.4
outlet4StatusDisplay and control outlet 4 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.5
outlet5StatusDisplay and control outlet 5 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.6
outlet6StatusDisplay and control outlet 6 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.7
outlet7StatusDisplay and control outlet 7 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.8
outlet8StatusDisplay and control outlet 8 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.9
outletConfigTableOutlet configuration table
SEQUENCE OF OutletConfigEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10
outletConfigEntryOutlet Config entry containing outlet info.
OutletConfigEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1
outletConfigIndexIndex of outlet numberro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.1
outletNameDisplay or set the name of outlet. If the device does not support this OID, we show n/a. string length: 0~15 NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.2
outletConfirmationDisplay or set the confirmation of outlet.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.3
outletOnDelayTimeDisplay or set the ON delay time of outlet. When this model does not support the OID, we show value -1.rw
INTEGER (0..999 | -1)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.4
outletOffDelayTimeDisplay or set the OFF delay time of outlet. When this model does not support the OID, we show value -1.rw
INTEGER (0..999 | -1)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.5
outletShutdownMethodDisplay or set the shutdown mehtod of outlet.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.6
outletMACDisplay or set the MAC address of ShutdownMethod. If the device does not support this OID, we show n/a. string length: 12rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.7
outletMinCurMTDisplay or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.8
outletMaxCurMTDisplay or set the outlet maximum electric current measurment threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.9
outletMinVolMTDisplay or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (900..2600 | -3000 | -2000000)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.10
outletMaxVolMTDisplay or set the outlet maximum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (900..2600 | -3000 | -2000000)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.11
outletMinPMTDisplay or set the outlet minimum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (0..99999 | -3000 | -2000000)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.12
outletMaxPMTDisplay or set the outlet maximum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (0..99999 | -3000 | -2000000)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.13
outletMaxPDMTDisplay or set the outlet maximum power dissipation measurment threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (0..999990 | -3000 | -2000000)
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.14
outlet9StatusDisplay and control outlet 9 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.11
outlet10StatusDisplay and control outlet 10 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.12
outlet11StatusDisplay and control outlet 11 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.13
outlet12StatusDisplay and control outlet 12 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.14
outlet13StatusDisplay and control outlet 13 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.15
outlet14StatusDisplay and control outlet 14 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.16
outlet15StatusDisplay and control outlet 15 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.17
outlet16StatusDisplay and control outlet 16 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.18
outlet17StatusDisplay and control outlet 17 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.19
outlet18StatusDisplay and control outlet 18 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.20
outlet19StatusDisplay and control outlet 19 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.21
outlet20StatusDisplay and control outlet 20 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.22
outlet21StatusDisplay and control outlet 21 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.23
outlet22StatusDisplay and control outlet 22 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.24
outlet23StatusDisplay and control outlet 23 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.25
outlet24StatusDisplay and control outlet 24 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.26
outlet25StatusDisplay and control outlet 25 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.27
outlet26StatusDisplay and control outlet 26 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.28
outlet27StatusDisplay and control outlet 27 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.29
outlet28StatusDisplay and control outlet 28 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.30
outlet29StatusDisplay and control outlet 29 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.31
outlet30StatusDisplay and control outlet 30 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.32
outlet31StatusDisplay and control outlet 31 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.33
outlet32StatusDisplay and control outlet 32 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.34
outlet33StatusDisplay and control outlet 33 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.35
outlet34StatusDisplay and control outlet 34 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.36
outlet35StatusDisplay and control outlet 35 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.37
outlet36StatusDisplay and control outlet 36 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.38
outlet37StatusDisplay and control outlet 37 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.39
outlet38StatusDisplay and control outlet 38 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.40
outlet39StatusDisplay and control outlet 39 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.41
outlet40StatusDisplay and control outlet 40 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.42
outlet41StatusDisplay and control outlet 41 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.43
outlet42StatusDisplay and control outlet 42 status. Can't set pending status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.44
outletSwitchableTable
SEQUENCE OF OutletSwitchableEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.2.70
outletSwitchableEntry
OutletSwitchableEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1
outletSwitchableIndexIndex of outlet number.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1.1
outletSwitchablero
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1.2
outletIntegerValueTableDisplay total outlet value table
SEQUENCE OF OutletIntegerValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99
outletIntegerValueEntrySingle outletValue entry containing outlet info.
OutletIntegerValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1
outletIntegerValueIndexIndex of outlet number.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.1
outletIntegerCurrentOutlet electric current value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.2
outletIntegerVoltageOutlet voltage value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.3
outletIntegerPowerOutlet power value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.4
outletIntegerPowerDissipationOutlet power dissipation value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.5
bank
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.2.3
breakerStatusTableDisplay total bank value table
SEQUENCE OF BreakerStatusEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.3.1
breakerStatusEntrySingle bankValue entry containing bank info.
BreakerStatusEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1
breakerStatusIndexIndex of breaker number.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1.1
breakerStatusBreaker status.ro
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1.2
bankValueTableDisplay total bank value table
SEQUENCE OF BankValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2
bankValueEntrySingle bankValue entry containing bank info.
BankValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1
bankValueIndexIndex of bank numberro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.1
bankCurrentBank electric current value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.2
bankVoltageBank voltage value. We put this OID to write access type for user to set the reference voltage on EC1000 model. And the setting should be the numbers. You can set 0 to clear the setting. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.3
bankPowerBank power value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.4
bankPowerDissipationBank power dissipation value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.5
bankMaxCurrentThe Bank Max Current value. unit: (A) EC1000:0A~320Aro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.6
bankAttachStatusThe status of Energy sensor Bank attached status.ro
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.7
bankPowerFactorBank Power Factor value. If the device does not support this OID, it returns: not-support.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.8
bankConfigTableBank configuration table
SEQUENCE OF BankConfigEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3
bankConfigEntryBank Config entry containing Bank info.
BankConfigEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1
bankConfigIndexIndex of bank numberro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.1
bankNameDisplay or set the name of bank. When this model does not support the OID, we show n/a. string length: 0~15 NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.2
bankMinCurMTDisplay or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.3
bankMaxCurMTDisplay or set the outlet maximum electric current measurment threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.4
bankMinVolMTDisplay or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (900..2600 | -3000 | -2000000)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.5
bankMaxVolMTDisplay or set the outlet maximum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (900..2600 | -3000 | -2000000)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.6
bankMinPMTDisplay or set the outlet minimum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (0..99999| -3000 | -2000000)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.7
bankMaxPMTDisplay or set the outlet maximum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (0..99999 | -3000 | -2000000)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.8
bankMaxPDMTDisplay or set the outlet maximum power dissipation measurment threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.rw
INTEGER (0..999990 | -3000 | -2000000)
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.9
bankControlTableBank Control table
SEQUENCE OF BankControlEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.3.4
bankControlEntryBank control entry.
BankControlEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1
bankControlIndexIndex of bank numberro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1.1
bankControlStatusThis function is used for outlet control of bank. Set off(1) to turn off for outlet control of bank. Set on(2) to turn on for all outlet control of bank. Set reboot(3) to turn on for outlet control of bank. Get this object always return nostatus(3), because there is no bank status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1.2
bankIntegerValueTableDisplay total bank value table
SEQUENCE OF BankIntegerValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99
bankIntegerValueEntrySingle bankValue entry containing bank info.
BankIntegerValueEntry
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1
bankIntegerValueIndexIndex of bank number.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.1
bankIntegerCurrentBank electric current value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.2
bankIntegerVoltageBank voltage value. This value indicates that 1,000 times. We put this OID to write access type for user to set the reference voltage on EC1000 model. And the setting should be the numbers. You can set 0 to clear the setting. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.3
bankIntegerPowerBank power value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.4
bankIntegerPowerDissipationBank power dissipation value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.5
deviceManagement
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3
config
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4
deviceMACDisplay device MAC address.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.4.1
deviceIPv4Display device IP address.ro
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.4.2
deviceFWversionDisplay device FW version.ro
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.4.3
dashBoard
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.4
dashboardRowDisplay or set device's dashboard row number.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.4.1
dashboardColumnDisplay or set device's dashboard column number.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.4.2
dashboardRackNameDisplay or set device's dashboard rack name. string length: 1~32 NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.4.4.3
servicePorts
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.5
httpPortDisplay or set the HTTP port of PE device.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.5.1
httpsPortDisplay or set the HTTPs port of PE device.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.5.2
httpsOnlyEnableEnable to use Webpage HTTPs only or disable to use Webpage HTTP/HTTPsrw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.5.3
ipv4config
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.6
staticIPEnabledDisplay or set IPv4 address automatically or notrw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.6.1
fixedIPv4Display or set fixed IPv4 addressrw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.4.6.2
subnetMaskDisplay or set subnet mask addressrw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.4.6.3
gatewayDisplay or set gateway addressrw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.4.6.4
staticDNSEnabledDisplay or set DNS address automatically or notrw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.6.5
dnsPreferIPv4Display or set prefer DNS addressrw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.4.6.6
dnsAlternateIPv4Display or set alternate DNS addressrw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.4.6.7
eventNotification
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7
devicesnmp
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1
trapEnabledIndicates if this trap entry is enabled or not. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.1
trapVersionChoose SNMP Trap version to send trap. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.2
snmpTrapTablePE SNMP agent trap setup table. If users want to use trap, they must set enable trap, ip and community first.
SEQUENCE OF SnmpTrapEntry
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3
snmpTrapEntrySingle trap entry containing trap receiver info.
SnmpTrapEntry
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1
trapReceiverNumberIndex of trap receiverro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.1
trapReceiverIPAddressTrap receiver IP addressrw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.2
trapPortNMS trap port to be used by agent to send traprw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.3
trapCommunityIf use SNMPv1/v2c to receive trap should set this Community string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL.rw
DisplayString
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.4
trapUsernameIf use SNMPv3 to receive trap should set this string. NOTE: Input string as /empty to set this object to NULL. MAX string length: 20rw
DisplayString
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.5
trapAuthpasswordIf use SNMPv3 to receive trap should set this string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL.rw
DisplayString
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.6
trapPrivpasswordIf use SNMPv3 to receive trap should set this string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL.rw
DisplayString
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.7
syslog
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2
sysLogServerEnabledDisplay or set syslog server address automatically or notrw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.1
sysLogServerIPv4Display or set syslog server addressrw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.2
sysLogServerPortDisplay or set syslog server portrw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.3
smtp
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3
smtpServerEnabledDisplay or set SMTP server enable status.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.1
smtpServerNameDisplay or set a SMTP server name. NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.2
smtpAuthEnabledDisplay or set authentication of SMTP server.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.3
smtpAccountNameDisplay or set a user's name of SMTP server. NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.4
smtpAccountPwdDisplay or set a user's password of SMTP server. NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.5
smtpMailFromDisplay or set a mail of SMTP server. NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.6
smtpMailToDisplay or set a mail of SMTP server. NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.7
configurationNotification
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9
configurationNotifyEnabledrw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9.1
configurationNotifyTrapMSG
NOTIFICATION-TYPE
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9.2
dateTime
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8
timeZone
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1
timeZoneSettingDisplay or set the time zone of PE device. (0) [GMT-12:00] Eniwetok Kwajalein (1) [GMT-11:00] Midway Island Samoa (2) [GMT-10:00] Hawaii (3) [GMT-09:00] Alaska (4) [GMT-08:00] Pacific Time (US & Canada); Tijuana (5) [GMT-07:00] Mountain Time (US & Canada) (6) [GMT-07:00] Arizona (7) [GMT-06:00] Central Time (US & Canada) (8) [GMT-06:00] Mexico City (9) [GMT-06:00] Saskatchewan (10)[GMT-06:00] Central America (11)[GMT-05:00] Eastern Time (US & Canada) (12)[GMT-05:00] Indiana (East) (13)[GMT-05:00] Bogota Lima Quito (14)[GMT-04:00] Atlantic Time (Canada) (15)[GMT-04:00] Caracas La Paz (16)[GMT-04:00] Santiago (17)[GMT-03:30] Newfoundland (18)[GMT-03:00] Buenos Aires Georgetown (19)[GMT-03:00] Brasilia (20)[GMT-03:00] Greenland (21)[GMT-02:00] Mid-Atlantic (22)[GMT-01:00] Azores (23)[GMT-01:00] Cape Verde Is (24)[GMT] Casablanca Monrovia (25)[GMT] Greenwich Mean Time: Dublin Edinburgh Lisbon London (26)[GMT+01:00] Amsterdam Copenhagen Madrid Paris Vilnius (27)[GMT+01:00] West Central Africa (28)[GMT+01:00] Belgrade Sarajevo Skopje Sofija Zagreb (29)[GMT+01:00] Bratislava Budapest Ljubljana Prague Warsaw (30)[GMT+01:00] Brussels Berlin Bern Rome Stockholm Vienna (31)[GMT+02:00] Cairo (32)[GMT+02:00] Harare Pretoria (33)[GMT+02:00] Jerusalem (34)[GMT+02:00] Bucharest (35)[GMT+02:00] Helsinki Riga Tallinn (36)[GMT+02:00] Athens Istanbul Minsk (37)[GMT+03:00] Kuwait Riyadh (38)[GMT+03:00] Nairobi (39)[GMT+03:00] Baghdad (40)[GMT+03:00] Moscow St. Petersburg Volgograd (41)[GMT+03:30] Tehran (42)[GMT+04:00] Abu Dhabi Muscat (43)[GMT+04:00] Baku Tbilisi Yerevan (44)[GMT+04:30] Kabul (45)[GMT+05:00] Islamabad Karachi Tashkent (46)[GMT+05:00] Ekaterinburg (47)[GMT+05:30] Calcutta Chennai Mumbai New Delhi (48)[GMT+05:45] Kathmandu (49)[GMT+06:00] Astana Dhaka (50)[GMT+06:00] Sri Jayawardenepura (51)[GMT+06:00] Almaty Novosibirsk (52)[GMT+06:30] Rangoon (53)[GMT+07:00] Bangkok Hanoi Jakarta (54)[GMT+07:00] Krasnoyarsk (55)[GMT+08:00] Beijing Chongqing Hong Kong Urumqi (56)[GMT+08:00] Perth (57)[GMT+08:00] Kuala Lumpur Singapore (58)[GMT+08:00] Taipei (59)[GMT+08:00] Irkutsk Ulaan Bataar (60)[GMT+09:00] Osaka Sapporo Tokyo (61)[GMT+09:00] Seoul (62)[GMT+09:00] Yakutsk (63)[GMT+09:30] Darwin (64)[GMT+09:30] Adelaide (65)[GMT+10:00] Canberra Melbourne Sydney (66)[GMT+10:00] Brisbane (67)[GMT+10:00] Guam Port Moresby (68)[GMT+10:00] Hobart (69)[GMT+10:00] Vladivostok (70)[GMT+11:00] Magadan Solomon Is New Caledonia (71)[GMT+12:00] Fiji Kamchatka Marshall Is. (72)[GMT+12:00] Auckland Wellington (73)[GMT+13:00] Nuku'alofarw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1.1
dstEnabledDisplay or set daylight savings time .rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1.2
manualInput
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2
dateSettingDisplay or set date in a manual way.(This is Greenwich Mean Time, GMT) string length: 10 This value format must match the following form: YYYY-MM-DD ex. 2011-01-01 Note: range of year: 2000-2099 range of month: 01-12 range of day: 01-31rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2.1
timeSettingDisplay or set time in a manual way.(This is Greenwich Mean Time, GMT) string length: 8 This value format must match the following form: HH:MM:SS ex. 02:02:02 Note: range of hour: 00-24 range of minute: 00-60 range of second: 00-60rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2.2
networkTime
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3
autoAdjustEnabledDisplay or set date time useing auto adjustment way.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.1
preferNTPDisplay or set prefer NTP server. AU | ntp1.cs.mu.OZ.AU(0), AU | ntp0.cs.mu.OZ.AU(1), BE | ntp2.oma.be(2), BE | ntp1.oma.be(3), BR | ntps1.pads.ufrj.br(4), CH | swisstime.ethz.ch(5), CL | ntp.shoa.cl(6), CZ | ntp.nic.cz(7), DE | ntp.stairweb.de(8), DE | ntps1-0.cs.tu-berlin.de(9), DE | ptbtime1.ptb.de(10), DE | ntp1.fau.de(11), DE | ptbtime2.ptb.de(12), DE | time1.one4vision.de(13), DE | rustime01.rus.uni-stuttgart.de(14), DE | ntp.probe-networks.de(15), DE | ntp2.fau.de(16), ES | hora.roa.es(17), HK | stdtime.gov.hk(18), IE | ntp-galway.hea.net(19), IT | ntp1.inrim.it(20), IT | ntp2.inrim.it(21), JP | clock.tl.fukuoka-u.ac.jp(22), JP | ntp.nict.jp(23), JP | clock.nc.fukuoka-u.ac.jp(24), KR | ntp.xbsd.kr(25), MX | cronos.cenam.mx(26), NL | ntp0.nl.uu.net(27), NL | ntp1.nl.uu.net(28), NL | ntp.remco.org(29), NL | ntp0.nl.net(30), PL | vega.cbk.poznan.pl(31), PL | ntp.ntp-servers.com(32), RO | ntp3.usv.ro(33), RO | ntp2.usv.ro(34), RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35), RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36), SE | ntp1.mmo.netnod.se(37), SE | ntp1.sth.netnod.se(38), SE | ntp2.mmo.netnod.se(39), SE | ntp2.sth.netnod.se(40), SE | time2.stupi.se(41), SE | ntp1.sp.se(42), SE | timehost.lysator.liu.se(43), SI | ntp.mostovna.com(44), US CA | timekeeper.isi.edu(45), US CA | clock.sjc.he.net(46), US CA | nist1.symmetricom.com(47), US CA | clock.via.net(48), US CA | nist1.aol-ca.truetime.com(49), US CA | clock.isc.org(50), US CA | clepsydra.dec.com(51), US CA | gps.layer42.net(52), US CA | time.no-such-agency.net(53), US CA | nist1-sj.WiTime.net(54), US CA | clock.fmt.he.net(55), US CO | time-b.timefreq.bldrdoc.gov(56), US CO | time-a.timefreq.bldrdoc.gov(57), US CO | utcnist.colorado.edu(58), US CO | time-c.timefreq.bldrdoc.gov(59), US DE | rackety.udel.edu(60), US DE | mizbeaver.udel.edu(61), US GA | nist1.columbiacountyga.gov(62), US IL | ntp.your.org(63), US MA | bonehed.lcs.mit.edu(64), US MA | time.keneli.org(65), US MA | ntp0.broad.mit.edu(66), US MD | time-a.nist.gov(67), US MD | time-b.nist.gov(68), US MI | nist.netservicesgroup.com(69), US NY | nist1-ny.WiTime.net(70), US NY | clock.nyc.he.net(71), US UT | time.xmission.com(72), US VA | nist1-dc.WiTime.net(73), US VA | nist1.aol-va.truetime.com(74), US WA | time-nw.nist.gov(75), FR | utp.univ-lyon1.fr(76), FR | ntp-sop.inria.fr(77), FR | ntp.tuxfamily.net(78), UK | bear.zoo.bt.co.uk(79)rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.2
preferServerIPenableEnable or disable prefer custom server IP.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.3
preferNTPIpDisplay or set prefer NTP server IP.rw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.4
alternateNtpEnabledDisplay or set date time using alternate NTP server.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.5
alternateNtpDisplay or set alternative NTP server. AU | ntp1.cs.mu.OZ.AU(0), AU | ntp0.cs.mu.OZ.AU(1), BE | ntp2.oma.be(2), BE | ntp1.oma.be(3), BR | ntps1.pads.ufrj.br(4), CH | swisstime.ethz.ch(5), CL | ntp.shoa.cl(6), CZ | ntp.nic.cz(7), DE | ntp.stairweb.de(8), DE | ntps1-0.cs.tu-berlin.de(9), DE | ptbtime1.ptb.de(10), DE | ntp1.fau.de(11), DE | ptbtime2.ptb.de(12), DE | time1.one4vision.de(13), DE | rustime01.rus.uni-stuttgart.de(14), DE | ntp.probe-networks.de(15), DE | ntp2.fau.de(16), ES | hora.roa.es(17), HK | stdtime.gov.hk(18), IE | ntp-galway.hea.net(19), IT | ntp1.inrim.it(20), IT | ntp2.inrim.it(21), JP | clock.tl.fukuoka-u.ac.jp(22), JP | ntp.nict.jp(23), JP | clock.nc.fukuoka-u.ac.jp(24), KR | ntp.xbsd.kr(25), MX | cronos.cenam.mx(26), NL | ntp0.nl.uu.net(27), NL | ntp1.nl.uu.net(28), NL | ntp.remco.org(29), NL | ntp0.nl.net(30), PL | vega.cbk.poznan.pl(31), PL | ntp.ntp-servers.com(32), RO | ntp3.usv.ro(33), RO | ntp2.usv.ro(34), RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35), RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36), SE | ntp1.mmo.netnod.se(37), SE | ntp1.sth.netnod.se(38), SE | ntp2.mmo.netnod.se(39), SE | ntp2.sth.netnod.se(40), SE | time2.stupi.se(41), SE | ntp1.sp.se(42), SE | timehost.lysator.liu.se(43), SI | ntp.mostovna.com(44), US CA | timekeeper.isi.edu(45), US CA | clock.sjc.he.net(46), US CA | nist1.symmetricom.com(47), US CA | clock.via.net(48), US CA | nist1.aol-ca.truetime.com(49), US CA | clock.isc.org(50), US CA | clepsydra.dec.com(51), US CA | gps.layer42.net(52), US CA | time.no-such-agency.net(53), US CA | nist1-sj.WiTime.net(54), US CA | clock.fmt.he.net(55), US CO | time-b.timefreq.bldrdoc.gov(56), US CO | time-a.timefreq.bldrdoc.gov(57), US CO | utcnist.colorado.edu(58), US CO | time-c.timefreq.bldrdoc.gov(59), US DE | rackety.udel.edu(60), US DE | mizbeaver.udel.edu(61), US GA | nist1.columbiacountyga.gov(62), US IL | ntp.your.org(63), US MA | bonehed.lcs.mit.edu(64), US MA | time.keneli.org(65), US MA | ntp0.broad.mit.edu(66), US MD | time-a.nist.gov(67), US MD | time-b.nist.gov(68), US MI | nist.netservicesgroup.com(69), US NY | nist1-ny.WiTime.net(70), US NY | clock.nyc.he.net(71), US UT | time.xmission.com(72), US VA | nist1-dc.WiTime.net(73), US VA | nist1.aol-va.truetime.com(74), US WA | time-nw.nist.gov(75), FR | utp.univ-lyon1.fr(76), FR | ntp-sop.inria.fr(77), FR | ntp.tuxfamily.net(78), UK | bear.zoo.bt.co.uk(79)rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.6
alternateServerIPenableEnable or disable alternate custom server IP.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.7
alternateNtpIpDisplay or set alternative NTP server IP.rw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.8
adjustTimeEveryDaysDisplay or set frequency of adjustment in days.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.9
devicesecurity
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.5
loginFailures
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.1
loginAllowTimesDisplay or set time of login faliure.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.1.1
loginTimeOutDisplay or set login time out.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.1.2
workingMode
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.2
icmpEnabledDisplay or set status of ICMP.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.5.2.1
accountPolicy
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.3
minUserNameLenDisplay or set minimum length of user name.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.3.1
minUserPwdLenDisplay or set minimum length of user password.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.3.2
upperCaseEnabledDisplay or set one upper case rule in user password.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.5.3.3
lowerCaseEnabledDisplay or set one lower case rule in user password.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.5.3.4
numberEnabledDisplay or set one number rule in user password.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.5.3.5
disableDuplicateLoginDisplay or set status of disabled duplicate login rule.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.5.3.6
loginRestriction
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4
loginStringDisplay or set a login string. string length: 0~32 NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.1
ipFilter
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2
ipFilterEnabledDisplay or set status of ip filter.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.1
ipFilterRuleDisplay or set status of ip filter rule.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.2
ipFilterTableA list of restricted ip.
SEQUENCE OF IpFilterEntry
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3
ipFilterEntryStatus and parameter values for a PE's restricted IP.
IpFilterEntry
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1
ipFilterIndexThe value of index for the ip filter.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.1
ipFilterFromA set of restricted ip. ex. 192.168.0.1 Note: Users must follow in order to set the ip address. Note: To clear the settings to set the ip 0.0.0.0rw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.2
ipFilterToA set of restricted ip. ex. 192.168.0.255 Note: Users must follow in order to set the ip address. Note: To clear the settings to set the ip 0.0.0.0rw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.3
macFilter
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3
macFilterEnabledDisplay or set status of mac filter.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.1
macFilterRuleDisplay or set status of mac filter rule.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.2
macFilterTableA list of restricted mac.
SEQUENCE OF MacFilterEntry
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3
macFilterEntryStatus and parameter values for a PE's restricted MAC.
MacFilterEntry
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1
macFilterIndexThe value of index for the mac filter.ro
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1.1
macFilterSetA set of restricted mac. string length: 12 ex. 004854655511 Note: Users must follow in order to set the MAC address. Note: To clear the settings to set the MAC 000000000000rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1.2
authentication
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.5
radius
OBJECT IDENTIFIER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1
radiusEnabledDisplay or set status of RADIUS server.rw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.1
preferRadiusIpDisplay or set prefer RADIUS server IP.rw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.2
preferRadiusPortDisplay or set prefer RADIUS server port.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.3
alternateRadiusIpDisplay or set alternative RADIUS server IP.rw
IpAddress
.1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.4
alternateRadiusPortDisplay or set alternative RADIUS server port.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.5
radiusTimeOutDisplay or set time out of authentication using RADIUS server. The unit is sec.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.6
radiusRetryDisplay or set retry times of authentication using RADIUS server.rw
INTEGER
.1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.7
radiusSecretDisplay or set shared secret of RADIUS server. string length: 6~15 At least 6 characters. NOTE: Input string as /empty to set this object to NULL.rw
DisplayString (SNMPv2-TC)
.1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.8
customTrapMSGDisplay custom trap message.
NOTIFICATION-TYPE
.1.3.6.1.4.1.21317.1.3.2.2.5
rebootDeviceReboot PE Devicerw
Enumeration
.1.3.6.1.4.1.21317.1.3.2.2.6