ASETEK-RACKCDU-SMI-V1-MIB-V16
AI MIB Summary
Standard SNMP MIB module defining data structures for ASETEK-RACKCDU-SMI-V1-MIB-V16.
152
Objects
Active
Status
4
Dependencies
Imported Objects
Objects
152 total| Object Name |
|---|
asetek OBJECT IDENTIFIER .1.3.6.1.4.1.39829 |
IMPORTS Unknown .1.3.6.1.4.1.39829 |
rackCDU OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1 |
traps OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.0 |
alarmNotify} TRAP-TYPE .1.3.6.1.4.1.39829.1.0.500 |
warningNotify} TRAP-TYPE .1.3.6.1.4.1.39829.1.0.501 |
facilitySupplyWarningFacility supply temperature warning. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.504 |
facilityReturnWarningFacility return temperature warning. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.505 |
serverSupplyWarningServer supply temperature warning. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.506 |
serverReturnWarningServer return temperature warning. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.507 |
facilityPressureWarningFacility pressure warning. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.508 |
serverPressureWarningServer pressure warning. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.509 |
facilityFlowWarningFacility flow warning. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.512 |
facilitySupplyAlarmFacility supply temperature alarm. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.517 |
facilityReturnAlarmFacility return temperature alarm. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.518 |
serverSupplyAlarmServer supply temperature alarm. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.519 |
serverReturnAlarmServer return temperature alarm. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.520 |
facilityPressureAlarmFacility pressure alarm. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.521 |
serverPressureAlarmServer pressure alarm. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.522 |
leakDetectionAlarmLeak detection alarm. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.523 |
liquidLevelAlarmLow liquid level alarm. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.524 |
facilityFlowAlarmFacility flow alarm. TRAP-TYPE .1.3.6.1.4.1.39829.1.0.525 |
product OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.1 |
nameProduct name.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.39829.1.1.1 |
versionSoftware version.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.39829.1.1.2 |
dateSoftware revision date.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.39829.1.1.3 |
rackNumberRackCDU number.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.39829.1.1.4 |
descriptionRackCDU description.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.39829.1.1.5 |
statusThe overall status of the RackCDU. Status is evaluated based on the
notification settings. If a noticiation has been disabled it will not
be included in the overall status either.ro Enumeration .1.3.6.1.4.1.39829.1.1.6 |
setup OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.2 |
notifyTableTable of settings used to setup notifications. SEQUENCE OF NotifyEntry .1.3.6.1.4.1.39829.1.2.1 |
notifyEntrySingle notify entry containing notification receiver info. NotifyEntry .1.3.6.1.4.1.39829.1.2.1.1 |
notifyReceiverNumberIndex of notification receiver.ro INTEGER .1.3.6.1.4.1.39829.1.2.1.1.1 |
notifyEnabledIndicates if this notify entry is enabled or not.rw Enumeration .1.3.6.1.4.1.39829.1.2.1.1.2 |
notifyReceiverIPAddressNotification receiver IP address.rw IpAddress .1.3.6.1.4.1.39829.1.2.1.1.3 |
notifyCommunityNotification community to be used by agent to send trap.rw DisplayString .1.3.6.1.4.1.39829.1.2.1.1.4 |
measurements OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.3 |
temperatureFacilityInThe temperature of the water going into the RackCDU on the Facility side
(cold).ro INTEGER (-870..999) .1.3.6.1.4.1.39829.1.3.100 |
temperatureFacilityOutThe temperature of the water going out of the RackCDU on the Facility
side (hot).ro INTEGER (-870..999) .1.3.6.1.4.1.39829.1.3.101 |
temperatureServerInThe temperature of the water going into the servers node (cold).ro INTEGER (-870..999) .1.3.6.1.4.1.39829.1.3.102 |
temperatureServerOutThe temperature of the water going out of the servers node (hot).ro INTEGER (-870..999) .1.3.6.1.4.1.39829.1.3.103 |
temperatureAmbientThe temperature of the ambient air close to the RackCDU.roobsolete INTEGER (-870..999) .1.3.6.1.4.1.39829.1.3.104 |
pressureServerThe pressure inside the RackCDU on the server side.ro Gauge .1.3.6.1.4.1.39829.1.3.105 |
pressureFacilityThe pressure inside the RackCDU on the facility side.ro Gauge .1.3.6.1.4.1.39829.1.3.106 |
serverLeakBoolean indication of whether the RackCDU has detected a leak in the
system.ro Enumeration .1.3.6.1.4.1.39829.1.3.107 |
serverLevelBoolean indication of whether the RackCDU has detected a low level of
cooleant.ro Enumeration .1.3.6.1.4.1.39829.1.3.108 |
flowFacilityThe flow of the cooleant on the facility side.ro Gauge .1.3.6.1.4.1.39829.1.3.109 |
heatloadThe heatload of the cooleant on the facility side. Can be averaged from
e.g. 1 to 28800 (24 hours) sec.ro Gauge .1.3.6.1.4.1.39829.1.3.110 |
controllerOutThe controller output.ro Gauge .1.3.6.1.4.1.39829.1.3.111 |
network OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.4 |
ipStoreFlashstore settings to Flash.rw Enumeration .1.3.6.1.4.1.39829.1.4.91 |
modeOfOperationMode of operation of ControlBox, can be agent or master.rw Enumeration .1.3.6.1.4.1.39829.1.4.92 |
ipAddrIP address of ControlBox.rw IpAddress .1.3.6.1.4.1.39829.1.4.93 |
priDNSPrimary DNS address of ControlBox.rw IpAddress .1.3.6.1.4.1.39829.1.4.94 |
secDNSSecondary DNS address of ControlBox.rw IpAddress .1.3.6.1.4.1.39829.1.4.95 |
netMaskNetmask of ControlBox.rw IpAddress .1.3.6.1.4.1.39829.1.4.96 |
gatewayGateway of ControlBox.rw IpAddress .1.3.6.1.4.1.39829.1.4.97 |
ipSrcIP address source of ControlBox, eg. static or dhcp.rw Enumeration .1.3.6.1.4.1.39829.1.4.98 |
ipRebootIP address reboot.rw Enumeration .1.3.6.1.4.1.39829.1.4.99 |
controller OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.5 |
gainProportionalProportional gain in PID controller.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.39829.1.5.80 |
gainIntegralIntegral gain in PID controller.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.39829.1.5.81 |
gainDifferentialDifferential gain in PID controller.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.39829.1.5.82 |
deltaOutMaxMaximum delta output from controller.rw Gauge .1.3.6.1.4.1.39829.1.5.83 |
limitPwmMaxMaximum PWM output.rw Gauge .1.3.6.1.4.1.39829.1.5.84 |
limitPwmMinMinimum PWM output.rw Gauge .1.3.6.1.4.1.39829.1.5.85 |
setpointFacilityOutSetpoint for Facility Out Temperature.rw INTEGER .1.3.6.1.4.1.39829.1.5.86 |
controllerOutAlphaController Out Alpha - damping factor of output.rw DisplayString (SNMPv2-TC) .1.3.6.1.4.1.39829.1.5.87 |
units OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.6 |
fluidHeatCapacityHeat Capacity of the liquid coolant utilized in the facility loop.rw INTEGER .1.3.6.1.4.1.39829.1.6.70 |
heatAverageFactorThe time frame of which the heat load is averaged. A short time frame
make the heat load sensative to small changes is temperature and flow
which results in a highly fluctuating value. A long time frame
stabilizes the value, but also results in a long response time.rw Gauge .1.3.6.1.4.1.39829.1.6.71 |
harnessVersionMust be set to the harness version utilized by the RackCDU. The harness
version may affect the functionality of the RackCDU and it it therefor
important that the versions is matched.rw Gauge .1.3.6.1.4.1.39829.1.6.72 |
notifications OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.7 |
snmpTrapsAlarmEnableEnable SNMP Alarm traps.rw Enumeration .1.3.6.1.4.1.39829.1.7.150 |
snmpTrapsWarningEnableEnable SNMP Warning traps.rw Enumeration .1.3.6.1.4.1.39829.1.7.151 |
smtpTrapsAlarmEnableEnable SMTP Alarm traps.rw Enumeration .1.3.6.1.4.1.39829.1.7.152 |
smtpTrapsWarningEnableEnable SMTP Warning traps.rw Enumeration .1.3.6.1.4.1.39829.1.7.153 |
warningMinFiSet Facility In Min Warning level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.154 |
warningMinEnableFiEnable Facility In Min Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.155 |
warningMaxFiSet Facility In Max Warning level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.156 |
warningMaxEnableFiEnable Facility In Max Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.157 |
alarmMinFiSet Facility In Min Alarm level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.158 |
alarmMinEnableFiEnable Facility In Min Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.159 |
alarmMaxFiSet Facility In Max Alarm level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.160 |
alarmMaxEnableFiEnable Facility In Max Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.161 |
warningMinFoSet Facility Out Min Warning level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.162 |
warningMinEnableFoEnable Facility Out Min Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.163 |
warningMaxFoSet Facility Out Max Warning level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.164 |
warningMaxEnableFoEnable Facility Out Max Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.165 |
alarmMinFoSet Facility Out Min alarm level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.166 |
alarmMinEnableFoEnable Facility Out Min alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.167 |
alarmMaxFoSet Facility Out Max Alarm level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.168 |
alarmMaxEnableFoEnable Facility Out Max Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.169 |
warningMinSiSet Server In Min Warning level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.170 |
warningMinEnableSiEnable Server In Min Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.171 |
warningMaxSiSet Server In Max Warning level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.172 |
warningMaxEnableSiEnable Server In Max Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.173 |
alarmMinSiSet Server In Min Alarm level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.174 |
alarmMinEnableSiEnable Server In Min Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.175 |
alarmMaxSiSet Server In Max Alarm level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.176 |
alarmMaxEnableSiEnable Server In Max Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.177 |
warningMinSoSet Server Out Min Warning level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.178 |
warningMinEnableSoEnable Server Out Min Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.179 |
warningMaxSoSet Server Out Max Warning level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.180 |
warningMaxEnableSoEnable Server Out Max Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.181 |
alarmMinSoSet Server Out Min Alarm level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.182 |
alarmMinEnableSoEnable Server Out Min Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.183 |
alarmMaxSoSet Server Out Max Alarm level.rw INTEGER (-75..75) .1.3.6.1.4.1.39829.1.7.184 |
alarmMaxEnableSoEnable Server Out Max Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.185 |
warningMinFlowSet Flow Min Warning level.rw INTEGER .1.3.6.1.4.1.39829.1.7.186 |
warningMinEnableFlowEnable Flow Min Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.187 |
warningMaxFlowSet Flow Max Warning level.rw INTEGER .1.3.6.1.4.1.39829.1.7.188 |
warningMaxEnableFlowEnable Flow Max Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.189 |
alarmMinFlowSet Flow Min Alarm level.rw INTEGER .1.3.6.1.4.1.39829.1.7.190 |
alarmMinEnableFlowEnable Flow Min Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.191 |
alarmMaxFlowSet Flow Max Alarm level.rw INTEGER .1.3.6.1.4.1.39829.1.7.192 |
alarmMaxEnableFlowEnable Flow Max Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.193 |
warningMinPressureServerSet Server Pressure Min Warning level.rw INTEGER .1.3.6.1.4.1.39829.1.7.194 |
warningMinEnablePressureServerEnable Server Pressure Min Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.195 |
warningMaxPressureServerSet Server Pressure Max Warning level.rw INTEGER .1.3.6.1.4.1.39829.1.7.196 |
warningMaxEnablePressureServerEnable Server Pressure Max Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.197 |
alarmMinPressureServerSet Server Pressure Min Alarm level.rw INTEGER .1.3.6.1.4.1.39829.1.7.198 |
alarmMinEnablePressureServerEnable Server Pressure Min Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.199 |
alarmMaxPressureServerSet Server Pressure Max Alarm level.rw INTEGER .1.3.6.1.4.1.39829.1.7.200 |
alarmMaxEnablePressureServerEnable Server Pressure Max Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.201 |
warningMinPressureFacilitySet Facility Pressure Min Warning level.rw INTEGER .1.3.6.1.4.1.39829.1.7.202 |
warningMinEnablePressureFacilityEnable Facility Pressure Min Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.203 |
warningMaxPressureFacilitySet Facility Pressure Max Warning level.rw INTEGER .1.3.6.1.4.1.39829.1.7.204 |
warningMaxEnablePressureFacilityEnable Facility Pressure Max Warning level.rw Enumeration .1.3.6.1.4.1.39829.1.7.205 |
alarmMinPressureFacilitySet Facility Pressure Min Alarm level.rw INTEGER .1.3.6.1.4.1.39829.1.7.206 |
alarmMinEnablePressureFacilityEnable Facility Pressure Min Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.207 |
alarmMaxPressureFacilitySet Facility Pressure Max Alarm level.rw INTEGER .1.3.6.1.4.1.39829.1.7.208 |
alarmMaxEnablePressureFacilityEnable Facility Pressure Max Alarm level.rw Enumeration .1.3.6.1.4.1.39829.1.7.209 |
alarmEnableLeakEnable leak detection.rw Enumeration .1.3.6.1.4.1.39829.1.7.210 |
alarmEnableLevelEnable low liquid level.rw Enumeration .1.3.6.1.4.1.39829.1.7.211 |
conformance OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8 |
cduProdGroup OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.1 |
cduSetupGroup OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.2 |
cduMeasGroup OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.3 |
cduMeasGroupRev2 OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.4 |
cduNetGroup OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.5 |
cduCntlGroup OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.6 |
cduUnitGroup OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.7 |
cduNotifyGroup OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.8 |
cduTrapGroup OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.9 |
cduCompliances OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.10 |
cduEventGroup OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.11 |
cduTrapGroupRev2 OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.12 |
cduCompliancesRev2 OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.8.13 |
eventDescriptors OBJECT IDENTIFIER .1.3.6.1.4.1.39829.1.9 |
eventDescriptionText which provide the user with a corrective action in case of a
warning or alarm trap.
IMPORTANT: Must only be used in traps! Any other use of this object is
invalid.ro DisplayString (SNMPv2-TC) .1.3.6.1.4.1.39829.1.9.1 |
eventValueEvent value placeholder sent with generic traps where the unit of the
value can be different.
IMPORTANT: Must only be used in traps! Any other use of this object is
invalidro INTEGER .1.3.6.1.4.1.39829.1.9.2 |