ALGPOWER-v2-MIB
AI MIB Summary
Standard SNMP MIB module defining data structures for ALGPOWER-v2-MIB.
59
Objects
Active
Status
3
Dependencies
Imported Objects
Objects
59 total| Object Name |
|---|
algcom OBJECT IDENTIFIER .1.3.6.1.4.1.49136 |
RFC1213-MIB Unknown .1.3.6.1.4.1.49136 |
upsObjects OBJECT IDENTIFIER .1.3.6.1.4.1.49136.1 |
output OBJECT IDENTIFIER .1.3.6.1.4.1.49136.1.1 |
outputVoltageNumeric value of instantaneous output voltage from
the source in tenths of a volt. To get the value
actual in volt should be divided by 10.
Example:
Read value 241, actual value 24.1V.ro INTEGER .1.3.6.1.4.1.49136.1.1.1 |
outputCurrentNumeric value of current output of converter AC/DC.
Real value reading in milli ampere.
Example:
Read value 1087, Actual value 1.087 milli ampere
or 1.087A.
If the output is '0' the AC/DC is off and the output
for the equipments is provide from batteriesro INTEGER .1.3.6.1.4.1.49136.1.1.2 |
oidNotUsed0OID not used.ro INTEGER .1.3.6.1.4.1.49136.1.1.3 |
oidNotUsed1OID not used.ro INTEGER .1.3.6.1.4.1.49136.1.1.4 |
battery OBJECT IDENTIFIER .1.3.6.1.4.1.49136.1.2 |
batteryVoltageNumeric value of instantaneous voltage of battery bank.
To get the actual value in volt must be divided by 10.
Example:
Read value 240, actual value 24.0V.ro INTEGER .1.3.6.1.4.1.49136.1.2.1 |
batteryCurrentNumeric value of current in Battery bank. Real
value reading in milli ampere.
If the value is negative the Battery bank is provide
energy for the output.
If the value is positive the Battery bank is under
charger
Example:
Read value -2230, Actual value 2,230 ampere and the
battery bank is provide this current.
Read value 3000, Actual value 3.000 milli ampere and
the battery bank is absorve this current.ro INTEGER .1.3.6.1.4.1.49136.1.2.2 |
chargerStatusShow the status of battery charger:
0 - The battery is not connected in DC UPS;
1 - The battery is voltage incompatible with DC UPS;
2 - The DC UPS is in nobreak mode;
3 - The charger of Battery is in Bulk stage;
4 - The charger of Battery is Absorption stage;
5 - The charger of Battery is Float stage;
6 - The Battery will be disconnected in 30s due to
low voltage and the DC-UPS output will be
turned off.
7 - The Battery is under testro INTEGER .1.3.6.1.4.1.49136.1.2.3 |
input OBJECT IDENTIFIER .1.3.6.1.4.1.49136.1.3 |
alarmOnBatteryShows the operation mode of DC-UPS:
0 - The DC-UPS output is provide by AC energy.
1 - The DC-UPS output is provide by Batteryro INTEGER .1.3.6.1.4.1.49136.1.3.1 |
acFailAlarm that alert about AC outages in the last 10
minutes:
0 - DC-UPS in normal operation.
1 - Occur a AC fail in the last 10 minutes.ro INTEGER .1.3.6.1.4.1.49136.1.3.2 |
batteryChargingShow the status of charging Battery:
1 - The battery is on charging.
0 - The battery is on discharging.ro INTEGER .1.3.6.1.4.1.49136.1.3.3 |
batteryDischargingShow the status of discharging Battery:
1 - The battery is on discharging.
0 - The battery is on charging.ro INTEGER .1.3.6.1.4.1.49136.1.3.4 |
overheatAlarm that alert about overtemperature of DC-UPS
1 - The DC-UPS is in condition of overtemperature.
0 - The DC-UPS is in normal condition.ro INTEGER .1.3.6.1.4.1.49136.1.3.5 |
overloadAlarm that alert about overload of DC-UPS
1 - The DC-UPS is in condition of overload.
0 - The DC-UPS is in normal condition.ro INTEGER .1.3.6.1.4.1.49136.1.3.6 |
fanAfailAlarm that alert about fail in internal FAN A
1 - Internal FAN with fail.
0 - Internal FAN okro INTEGER .1.3.6.1.4.1.49136.1.3.7 |
fanBfailAlarm that alert about fail in internal FAN B
1 - Internal FAN with fail.
0 - Internal FAN okro INTEGER .1.3.6.1.4.1.49136.1.3.8 |
oidNotUsed2OID not used.ro INTEGER .1.3.6.1.4.1.49136.1.3.9 |
oidNotUsed3OID not used.ro INTEGER .1.3.6.1.4.1.49136.1.3.10 |
upTimeSystem Up time in hoursro INTEGER .1.3.6.1.4.1.49136.1.3.11 |
temperature OBJECT IDENTIFIER .1.3.6.1.4.1.49136.1.4 |
innerTemperatureShow the internal temperature of power supply.
Uses the unit degree Celsius.
Example
Read value: 25, temperature is 25degC.ro INTEGER .1.3.6.1.4.1.49136.1.4.1 |
outerTemperatureShow the temperature of external sensor (cable that
comes with power supply).
Uses the unit degree Celsius.
Example
Read value: 25, temperature is 25degC.ro INTEGER .1.3.6.1.4.1.49136.1.4.2 |
heatSinkTemperatureShow the temperature of sensor in the heatsink of
power supply use the unit degree Celsius.
Example
Read value: 25, temperature is 25degC.ro INTEGER .1.3.6.1.4.1.49136.1.4.3 |
watchdog OBJECT IDENTIFIER .1.3.6.1.4.1.49136.1.5 |
watchdogPing1Alarm indicating the action of watchdog 1
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 1 acted on the output the last 10
minutes.
0 - The Watchdog 1 has not acted in the last 10
minutes.ro INTEGER .1.3.6.1.4.1.49136.1.5.1 |
watchdogPing2Alarm indicating the action of watchdog 2
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 2 acted on the output the last 10
minutes.
0 - The Watchdog 2 has not acted in the last 10
minutes.ro INTEGER .1.3.6.1.4.1.49136.1.5.2 |
watchdogPing3Alarm indicating the action of watchdog 3
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 3 acted on the output the last 10
minutes.
0 - The Watchdog 3 has not acted in the last 10
minutes.ro INTEGER .1.3.6.1.4.1.49136.1.5.3 |
watchdogPing4Alarm indicating the action of watchdog 4
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 4 acted on the output the last 10
minutes.
0 - The Watchdog 4 has not acted in the last 10
minutes.ro INTEGER .1.3.6.1.4.1.49136.1.5.4 |
watchdogPing5Alarm indicating the action of watchdog 5
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 5 acted on the output the last 10
minutes.
0 - The Watchdog 5 has not acted in the last 10
minutes.ro INTEGER .1.3.6.1.4.1.49136.1.5.5 |
watchdogPing6Alarm indicating the action of watchdog 6
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 6 acted on the output the last 10
minutes.
0 - The Watchdog 6 has not acted in the last 10
minutes.ro INTEGER .1.3.6.1.4.1.49136.1.5.6 |
watchdogPing7Alarm indicating the action of watchdog 7
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 7 acted on the output the last 10
minutes.
0 - The Watchdog 7 has not acted in the last 10
minutes.ro INTEGER .1.3.6.1.4.1.49136.1.5.7 |
watchdogPing8Alarm indicating the action of watchdog 8
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 8 acted on the output the last 10
minutes.
0 - The Watchdog 8 has not acted in the last 10
minutes.ro INTEGER .1.3.6.1.4.1.49136.1.5.8 |
watchdogPing9Alarm indicating the action of watchdog 9
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 9 acted on the output the last 10
minutes.
0 - The Watchdog 9 has not acted in the last 10
minutes.ro INTEGER .1.3.6.1.4.1.49136.1.5.9 |
watchdogPing10Alarm indicating the action of watchdog 10
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 10 acted on the output the last 10
minutes.
0 - The Watchdog 10 has not acted in the last 10
minutes.ro INTEGER .1.3.6.1.4.1.49136.1.5.10 |
supply OBJECT IDENTIFIER .1.3.6.1.4.1.49136.1.6 |
supplyVoltageThe supply AC voltage decivolt [dV]
Numeric value of instantaneous input voltage.
An optional sensor is required to read this value.
To get the actual value in volt it should be
divided by 10.
Example:
Read value 2410, actual value 241 Vac.ro INTEGER .1.3.6.1.4.1.49136.1.6.1 |
installation OBJECT IDENTIFIER .1.3.6.1.4.1.49136.1.7 |
popNamePoP namero DisplayString .1.3.6.1.4.1.49136.1.7.1 |
facilityAddrFacility addressro DisplayString .1.3.6.1.4.1.49136.1.7.2 |
facilityCityFacility cityro DisplayString .1.3.6.1.4.1.49136.1.7.3 |
instDateInstallation datero DisplayString .1.3.6.1.4.1.49136.1.7.4 |
batCapacityBattery capacityro INTEGER .1.3.6.1.4.1.49136.1.7.5 |
batBrandBattery brandro DisplayString .1.3.6.1.4.1.49136.1.7.6 |
batInstDateBattery installation datero DisplayString .1.3.6.1.4.1.49136.1.7.7 |
respPersResponsible personro DisplayString .1.3.6.1.4.1.49136.1.7.8 |
bat-tst OBJECT IDENTIFIER .1.3.6.1.4.1.49136.1.8 |
btst-dateBattery test execution date (dd/mm/yyyy)ro DisplayString .1.3.6.1.4.1.49136.1.8.1 |
btst-statusBattery test status
0 - NEVER DONE
1 - Passed
2 - Running
3 - Aborted
4 - Failedro INTEGER .1.3.6.1.4.1.49136.1.8.2 |
btst-durationProgrammed test duration in minutes
* 999 - Perform the test until battery is fully dischargedro INTEGER .1.3.6.1.4.1.49136.1.8.3 |
btst-elapsedElapsed time in current\last battery testro INTEGER .1.3.6.1.4.1.49136.1.8.4 |
btst-volt-iThe battery initial voltage [dV]
Numeric value of battery voltage when starting the battery test.
Example:
Read value 241, actual value 24.1 V.ro INTEGER .1.3.6.1.4.1.49136.1.8.5 |
btst-amp-iThe battery initial cuurent [mA]
Numeric value of battery current when starting the battery test.
Example:
Read value 1522, actual value 1.55 A.ro INTEGER .1.3.6.1.4.1.49136.1.8.6 |
btst-volt-fThe battery final voltage [dV]
Numeric value of battery voltage when the battery test is done.
Example:
Read value 225, actual value 22.5 V.ro INTEGER .1.3.6.1.4.1.49136.1.8.7 |
btst-amp-fThe battery initial cuurent [mA]
Numeric value of battery current when the battery test is done.
Example:
Read value 1485, actual value 1.48 A.ro INTEGER .1.3.6.1.4.1.49136.1.8.8 |